Installation Instructions 818954-01
Level Electrodes NRG 16-50, NRG 17-50, NRG 19-50, NRG 111-50
English
1
2
Contents
Page
Application
Usage for the intended purpose ..............................................................................................................4
Function .................................................................................................................................................4
Directives and Standards
Pressure Equipment Directive (PED) 97/23/EC ........................................................................................
Functional Safety acc. to IEC 61508 ........................................................................................................
VdTÜV Bulletin "Wasserstand 100" (= Water Level 100) ..........................................................................
ATEX (Atmosphère Explosible) ................................................................................................................. 5
Technical Data
NRG 16-50, NRG 17-50, NRG 19-50, NRG 111-50 ..................................................................................
Corrosion resistance ............................................................................................................................... 7
Sizing .....................................................................................................................................................7
Name plate / marking .............................................................................................................................8
Dimensions NRG 16-50, NRG 17-50, NRG 19-50 ....................................................................................
Dimensions NRG 111-50 ......................................................................................................................10
Functional Elements
NRG 16-50, NRG 17-50, NRG 19-50 ..................................................................................................... 11
NRG 16-50, NRG 17-50, NRG 19-50, NRG 111-50 four-pole connector ............................................11,12
NRG 16-50F, NRG 17-50F, NRG 19-50F, NRG 111-50F aluminium terminal box ..................................... 13
Key .......................................................................................................................................................14
Important Notes
Safety note ...........................................................................................................................................15
Scope of supply .................................................................................................................................... 15
Installation
5 5 5
6
9
NRG 16-50, NRG 17-50, NRG 19-50, NRG 111-50, step 1 ..................................................................... 16
NRG 16-50, NRG 17-50, NRG 19-50, NRG 111-50, step 2 ..................................................................... 16
NRG 16-50F, NRG 17-50F, NRG 19-50F, additional information ..............................................................16
Tools .....................................................................................................................................................17
Examples of installation
NRG 16-50, NRG 17-50, NRG 19-50 ..................................................................................................... 18
NRG 111-50 .........................................................................................................................................19
Key .......................................................................................................................................................20
Contents – continued –
Page
Electrical Connection
Connection of level electrode ................................................................................................................ 21
NRG 16-50, NRG 17-50, NRG 19-50, NRG 111-50, with four-pole connector .........................................
NRG 16-50F, NRG 17-50F, NRG 19-50F, NRG 111-50F, with aluminium terminal box .............................
Wiring diagram ..................................................................................................................................... 22
Key .......................................................................................................................................................23
Tools .....................................................................................................................................................23
Commissioning, fault indication and remedy
NRG 16-50, NRG 17-50, NRG 19-50, NRG 111-50 ................................................................................23
Decommissioning
Disposal................................................................................................................................................23
21 21
3
4
Application
Usage for the intended purpose
The level electrodes NRG 16-50, NRG 17-50, NRG 19-50 and NRG 111-50 are used in conjunction with level switch NRS 1-50 as water level limiters for steam boiler plants and (pressurised) hot water installations. Water level limiters switch off the heating when the water level falls below the set minimum level (low water).
Function
When the water level falls below the low level, the level electrode is exposed and a low level alarm is triggered in the level switch NRS 1-50. This switchpoint “Low water level (LW)” is determined by the length of the electrode tip.
The self-monitoring function ensures that an alarm will also be triggered if the electrode insulation is contaminated or has developed a leak or if there is a malfunction in the electrical connection.
The level electrode is installed inside steam boilers, vessels or inlet lines of hot-water systems. The protective tube mounted on site (see section Examples of Installation (pages 18, 19) ensures correct functioning.
One level electrode NRG 1...-50 can be installed together with one GESTRA level electrode, one level switch or transmitter for water level control and high level alarm in one single protection tube or level pot.
If the level electrode is installed in an isolatable level pot outside the boiler, make sure that the connecting lines are rinsed regularly. In addition, the logic unit SRL is required to monitor the purging times and the purging sequence.
If the connecting lines for steam ≥ 40 mm and water ≥ 100mm, the installation is considered to be internal. In this case the rinsing processes do not have to be monitored.
Directives and Standards
Pressure Equipment Directive (PED) 97/23/EC
Water level limiters are safety accessories as defined in the Pressure Equipment Directive (PED). The level electrode NRG 1...-50 in conjunction with level switch NRS 1-50 is EC type approved according to EN 12952/EN 12953. These Directives state, among other things, the requirements made on limiting systems and equipment for steam boiler plants and (pressurised) hot-water installations.
Functional Safety acc. to IEC 61508
The level electrodes NRG 1...-50 / NRG 16-36 are certified acc. to IEC 61508 only if used in combination with level switch NRS 1-50. This standard describes the functional safety of safety-related electrical/electronic/programmable electronic systems.
The equipment combination NRG 1...-50 or NRG 16-36 + NRS 1-50 corresponds to a type B subsystem with Safety Integrity Level (SIL) 3.
VdTÜV Bulletin “Wasserstand 100” (= Water Level 100)
The level electrodes NRG 1-50, NRG 1...-11 and NRG 16-36 in conjunction with the level switch NRS 1-50 are type approved according to the VdTÜV Bulletin “Water Level 100”.
The VdTÜV Bulletin “Wasserstand (=Water Level) 100” specifies the requirements made on water level control and limiting equipment for boilers.
ATEX (Atmosphère Explosible)
The level electrodes NRG 1...-50, NRG 1...-11 and NRG 16-36 are simple items of electrical equipment as specified in EN 60079-11 section 5.7. According to the European Directive 94/9/EC the equipment must be equipped with approved Zener barriers if used in potentially explosive areas. Applicable in Ex zones 1, 2 (1999/92/EC). The equipment does not bear an Ex marking. The suitability of the Zener barriers is certified in a separate document.
Note that the requirements of the IEC 61508 are not met if the NRG 1...-50, NRG 1...-11, NRG 16-36 + Zener barriers + NRS 1-50 are interconnected!
5
6
Technical Data
NRG 16-50, NRG 17-50, NRG 19-50, NRG 111-50
Service pressure
NRG 16-50: PN 40, 32 bar at 238 °C NRG 17-50: PN 63, 60 bar at 275 °C NRG 19-50: PN 160, 100 bar at 311 °C NRG 111-50: PN 320, 183 bar at 357 °C
Mechanial connection
Screwed ¾" to EN ISO 228-1 (NRG 16-50, NRG 17-50, NRG 19-50) Screwed 1" to EN ISO 228-1 (NRG 111-50)
Materials
Sheath: 1.4301, X5 CrNi18-10 Screw-in body: 1.4571, X6CrNiMoTi17-12-2 (NRG 16-50, NRG 17-50, NRG 19-50) Screw-in body: 1.4529, X1NiCrMoCuN25-20-7 (NRG 111-50) Measuring electrode: 1.4571, X6CrNiMoTi17-12-2 (NRG 16-50, NRG 17-50, NRG 19-50) Measuring electrode: 1.4122, X39CrMo17-1 (NRG 111-50) Electrode tip: 1.4401, X5CrNiMo17-12-2 Electrode insulation: Gylon
®
(NRG 16-50, NRG 17-50, NRG 19-50) Electrode insulation: Special ceramic (NRG 111-50) NRG 1...-50: Four-pole connector: polyamid (PA) NRG 1...-50F: Terminal box 3.2161 G AlSi8Cu3
Lengths supplied
500 mm, 1000 mm, 1500 mm, 2000 mm, 2500 mm, 3000 mm ph value
Max. admissible: 10 (NRG 111-50)
Electrical connection
NRG 1...-50:
Four-pole connector, cable glands M 16
NRG 1...-50F: Terminal box made from aluminium, cable gland M 20
Protection
IP 65 to EN 60529
Max. admissible ambient temperature
70°C
Weight
Approx. 1.2 kg (without extension) (NRG 16-50, NRG 17-50, NRG 19-50) Approx. 2.1 kg (without extension) (NRG 16-50F, NRG 17-50F, NRG 19-50F) Approx. 1.8 kg (without extension) (NRG 111-50) Approx. 2.7 kg (without extension) (NRG 111-50F)
Approvals
EC Prototype approval PED Pressure Equipment Directive 97/23/EC, EN 12952-11, EN 12953-09: Requirements made on limiting equipment for boilers.
Functional Safety SIL 3 IEC 61508: Functional safety of safety-related electrical/electronic/programmable electronic systems
TÜV type approval VdTÜV Bulletin “Wasserstand 100” (= Water Level 100): Requirements made on water level limiting & control equipment.
Type approval no. TÜV · SWB / SHWS · XX-XXX (see name plate)
Gylon® is a registered trademark of Garlock Sealing Technologies, Palmyra NY, USA
Technical Data – continued –
Corrosion resistance
If the equipment is used for the intended purpose, its safety is not impaired by corrosion.
Sizing
The body is not designed for pulsating loads. Welds and flanges are designed to withstand dynamic loading (bending and alternative stress). The dimensional allowances and anti-corrosive additives reflect the latest state of the technical art.
7
8
Technical Data – continued –
Name plate / marking
Equipment designation Safety note
Disposal note Pressure rating, thread type,
material number, type approval number CE marking
Fig. 1
Manufacturer
Serial number
Safety note
Equipment designation Pressure rating, thread type, material
number
Pressure/temperature rating
CE Marking, type approval
Fig. 2
Disposal note
Manufacturer
Serial number
Fig. 3