Carrier 58GS User Manual

4 (2)
Carrier 58GS User Manual

Gas-Fired Forced-Air Furnace

with Electronic Ignition

INSTALLATION

Before installing the furnace, refer to “Pro­ cedures for Gas-Fired Furnaces” (packaged with the equipment) for information concerning com­ bustion, venting, piping, and other standard instal­ lation practices. Further reference is made to the current edition of the American National Standard Z223.1 National Fuel Gas Code.

Each furnace is shipped from the factory com­ pletely assembled with multispeed direct-drive blower and wired ready for indoor heating installa­ tion. All sizes feature a printed-circuit board control center with easy-to-read low-voltage terminal strip to ensure proper connections. The control center also provides easy connections for line-voltage air cleaners.

CAUTK)?i : Do not iosiaB famace in a corrosive or contasninated atmospheres Miakesnre that ail local ordinances for combnstion and oircalating air supply axe observed.

Table 1 — Clearances (in inches)

SIZES

050 & 075

100 thru 175

Sides

f

. .

Single Wall Vent

 

Type B — Double Wall Vent

0

1

Back

0

0

Top of Plenum

1

1

Vent Connector

6

6

Single Wall

Type B — Double Wall

_____

______1 _

Front____________ ____________

“e

6

Combustion Air

Service

30

30

 

 

 

Installation comprises the following:

 

Inspection ....................................................................

 

*

Location, Ventilation and Air

 

for Combustion........................................................

 

*

Gas Piping....................................................................

 

*

Venting.........................................................................

 

*

Electrical ...................................................................

 

1

Filter.............................................................................

 

7

Start-Up, Adjustment, and Safety Check...............

8

Service.......................................................................

11

*To perform these installation

steps, refer tothe appropriate

 

sections of “Procedures

forGas-FiredFurnaces” booklet

 

packaged with this unit.

 

 

The design of the upflow gas-fired furnaces is A.G.A. certified for installation on combustible flooring in alcoves, basements, closets, or utility rooms.

For accessory installation details, i.e., automatic vent damper, humidifier, electronic air cleaner, etc., refer to applicable installation literature.

Electrical Connections

LINE VOLTAGE WIRING

IMPORTANT: Before proceeding with the elec­ trical connections, make certain that voltage, frequency, and phase correspond to that specified on the unit rating plate. Also, check to be sure that the service provided by the utility is sufficient to handle the additional load imposed by this equip­ ment. Refer to the unit rating plate for equipment electrical requirements.

K0'S(4)

RETURN AIR OPENING (SIDE) (FIELD CUT EITHER SIDE) BEND FLANGES UP 90'

*B0TT0M OPENING

ISsjlj SERVICE CLEARANCE C> AIRFLOW

Certified dimension drawings available on request

Fig. 1 — Dimensions

© Carrier Corporation 1978

Form 58GS-2SI

Table 2 — Dimensions апЭ Physical Data

MODEL NO 58GS

 

 

050

 

 

075

 

 

100

 

SERIES

 

100

2P0

300

100

200

300

100

200

300

DIMENSIONS* (in.)

 

 

 

 

 

 

 

 

 

 

Width

A

14-3/16

14-3/16

14-3/16

14-3/16

14-3/16

14-3/16

17-1/2

17-1/2

21

Depth

В

28-1/2

28-1/2

28-1/2

28-1/2

28-1/2

28-1/2

28-1/2

28-1/2

28-1/2

Height!

 

 

 

 

 

 

 

 

 

 

Casing Only

c

46-3/16

46-3/16

46-3/16

46-3/16

46-3/16

46-3/16

46-3/16

46-3/16

46-3/16

Air Openings

 

 

 

 

 

 

 

 

 

 

Supply

D

12-9/16

12-9/16

12-9/16

12-9/16

12-9/16

12-9/16

15-7/8

15-7/8

19-3/8

Side Return (E x 23-1 /4)

E

14-1/2

14-1/2

14-1/2

14-1/2

14-1/2

14-1/2

14-1/2

14-1/2

14-1/2

From Opening to Floor

F

2-3/4

2-3/4

2-3/4

2-3/4

2-3/4

2-3/4

2-3/4

2-3/4

2-3/4

Bottom Return

G

11-11/16

11-11/16

11-1 1/16

11-11/16

11-1 1/16

11-11/16

15

15

18-1/2

Flue (Equiv Round Pipe Dia.)

J

4

4

4

4

4

4

5

5

5

FILTERt

 

 

 

 

 

 

 

 

 

 

Size X 27-3/4 (in.)

 

12-9/16

12-9/16

12-9/16

12-9/16

12-9/16

12-9/16

15-7/8

15-7/8

19-3/8

RATINGS** (Natural Gas)

 

 

 

 

 

 

 

 

 

 

Input (1000 Btuh)

 

50

50

50

75

75

75

100

100

100

Bonnet Cap (1000 Btuh)

 

40

40

40

60

60

60

80

80

80

Temp Rise!! (F)

 

40-70

40-70

35-65

55-85

55-85

45-75

65-95

60-90

45-75

Minimum Air for Heating

 

 

 

_

 

 

 

 

 

 

ESP (in. wg)

 

0 12

__

0.12

 

 

0.15

 

 

Cfm

 

673

673

740

793

793

925

925

987

1234

Max Air Cfm (g) 0 5 in. wg ESP

 

815

1170

800

1150

 

1155

1610

DD Blower Wheel (nom. size — in.)

 

9x6

9x6

10x6

9x6

9x6

10x6

9x7

10x7

10x8

HP-Type

 

1/IOSh P

1/6Sh P

1/3Sh.P

1/10Sh.P

1/6Sh.P

l/3Sh.P

1/6Sh.P

1/3Sh.P

1/2PSC

BURNERS(No)

 

2

2

2

3

3

3

4

4

4

APPROX SHIP WT(lb)

 

105

105

105

122

122

125

160

160

175

ELECTRICAL(S)

 

 

 

 

 

 

 

 

 

 

Unit Voltage (60-Hz)

 

115

115

115

115

115

115

115

115

115

Transformer (120-V/24-V)

 

20 va

40 va

40 va

20 va

40 va

40 va

20 va

40 va

40 va

A/C Blower Relay Rating

 

None

138

138

None

138

138

None

13 8

13 8

@ 120 V (amps)

 

 

 

 

 

 

 

 

 

 

 

Motor Full Load Amps

 

5

6

99

5

6

9 9

5 5

9 9

8 5

 

 

 

 

 

 

 

 

 

 

 

MODEL NO. 58GS

 

 

125

 

 

150

 

 

 

175

 

SERIES

100

200

 

300

400

100

200

 

300

300

 

DIMENSIONS* (in.)

 

 

 

 

 

 

 

 

 

 

 

 

Width A

21

21

 

21

24-1/2

24-1/2

24-1/2

24-1/2

31-1/2

 

Depth B

28-1/2

28-1/2

 

28-1/2

28-1/2

28-1/2

28-1/2

28-1/2

28-1/2

 

Height!

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Casing Only C

46-3/16

46-3/16

 

46-3/16

46-3/16

46-3/16

46-3/16

46-3/16

46-3/16

 

Air Openings

 

 

 

 

 

 

 

 

 

 

 

 

Supply D

19-3/8

19-3/8

 

19-3/8

22-7/8

22-7/8

22-7/8

22-7/8

29-7/8

 

Side Return (Ex 23-1/4) E

14-1/2

14-1/2

 

14-1/2

14-1/2

14-1/2

14-1/2

14-1/2

14-1/2

 

From Opening to Floor F

2-3/4

2-3/4

 

2-3/4

2-3/4

2-3/4

2-3/4

2-1/16

2-1/16

 

Bottom Return G

18-1/2

18-1/2

 

18-1/2

22

22

22

 

22

29

 

Flue (Equiv Round Pipe Dia ) J

5

5

 

5

5

6

6

 

6

7

 

FILTERt

 

 

 

 

 

 

 

 

 

 

 

 

Size X 27-3/4 (in.)

19-3/8

19-3/8

 

19-3/8

22-7/8

22-7/8

22-7/8

22-7/8

29-7/8

 

RATINGS** (Natural Gas)

 

 

 

 

 

 

 

 

 

 

 

 

Input (1000 Btuh)

125

125

 

125

125

150

150

 

150

175

 

Bonnet Cap (1000 Btuh)

100

100

 

100

100

120

120

 

120

140

 

Temp Riseft (F)

70-100

65-95

 

60-90

45-75

65-95

65-95

45-75

60-90

 

Minimum Air for Heating

 

 

 

 

-

 

 

 

 

 

 

 

ESP (in wg)

0 20

 

0 20

 

 

Cfm

1089

1157

 

1234

1543

1388

1388

 

1851

1450

 

Max Air Cf/n (g) 0.5 in wg ESP

-

1230

 

1550

2110

1600

 

2110

1980

 

DD Blower Wheel (nom size — in )

9x8

10x8

 

10x8

(2)10x6

10x10

10x10

(2)10x6

(2)10x6

HP-Type

1/5 Sh P

1/3Sh P

 

1/2 PSC

1/2PSC

1/3Sh P

1/2 PSC

1/2 PSC

1/2 PSC

BURNERS(No)

5

5

 

5

5

6

6

 

6

7

 

APPROX SHIP WT(lb)

190

190

 

190

200

205

220

 

230

250

 

ELECTRICAL(S)

 

 

 

 

 

 

 

 

 

 

 

 

Unit Voltage (60-Hz)

115

115

 

115

115

115

115

 

115

115

 

Transformer (120-V/24-V)

20 va

40 va

 

40 va

40 va

20 va

40 va

40 va

 

40 va

A/C Blower Relay Rating

None

13 8

 

13 8

13 8

None

138

 

13 8

13 8

 

@ 120 V (amps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor Full Load Amps

8

9

 

9

8 5

9 5

9 5

-

85

85

 

 

 

 

 

 

 

 

 

 

 

 

 

ESP — External Static Pressure

DD — Direct Drive

PSC — Permanent Split Capacitor

Sh P — Shaded Pole

*See certified prints for complete dimensional specifications

tSee Furnace-Coil-Plenum-Adapter Combinations table in Product Data Digest Refer to 28 Series literaturefor plenum dimensions

iDuralast permanent cleanable filters See manufacturer's recommenda­ tions for cleaning

**Ratings shown are for elevations up to 2000 ft above sea level For elevations above 2000 ft, deduct 4% of input ca­ pacity for each 1000 ft above sea level ttDo not exceed temperature rise speci­ fied on furnace nameplate Air tem­ perature rise may be calculated using

the following formula:

bonnet capacity

0 24 X specific wt of air x 60 xcfm

bonnet capacity

1 08 X cfm

NOTE: Refer to Application Data litera­ ture for complete fan performance curves

CAOTiON, Air <^.vwy iSOO

i>3ce be or e combioatKi» of one side ano bottom^ of boisam on^y for reiurti a>r.

CAUTION: Use copper or copper-dad aluiainum conductors only. Use a separate branch electrical circuit for this furnace. A disconnect­ ing means must be located within sight of, and readily accessible to, the furnace.

See Fig. 2 for wiring diagram showing the proper field highand low-voltage wiring. Make all elec­ trical connections in accordance with the National Electrical Code and any local codes or ordinances that might apply.

WARNING: The unit cabinet m.ust have an uninterrupted or unbroken electrical ground to minimize personal injury if an electrical fanlt should occur. This may consist of electrical wire or approved conduit when installed in accordance with e.Kisting electrical codes.

LOW-VOLTAGE WIRING — Make field lowvoltage connections at the low-voltage terminal strip. See Fig. 2.

Set the thermostat heat anticipator at the settings indicated below. If additional controls are connected in the thermostat circuit, their amp draw must be added to this setting. Failure to make the setting will result in improper operation of the thermostat.

58GS050 thru 150 sizes with

 

BDP 646AW gas valve.

 

Heat/Cool or Heat only models................

0.55 amp

exposed to cold air infiltration, drafts from win­ dows, doors, or other openings leading to the out­ side, or exposure to air currents from warm or cold air registers; or to exposure where the natural circu­ lation of the air is cut off — such as behind doors, above or below mantels, shelves, etc.

The thermostat should not be exposed to heat from nearby fireplaces, radios, televisions, lamps, or rays from the sun. Nor should the thermostat be mounted on a wall containing pipes or warm air ducts, or a flue or vent that could affect its operation and prevent it from properly controlling the room temperature. Any hole in the plaster or panel thru which the wires pass from the thermostat should be adequately sealed with suit­ able material to prevent drafts from affecting the thermostat.

NOTES FOR LABEL WIRING DIAGRAMS

1

 

Screw terminals for field wiring connections

 

 

 

 

1/4-in quick connect terminals

 

 

 

 

3

L"

If J Heating fan relay contact

is

normally

closed

until

 

r " 1 1 5 vac is applied to furnace

 

 

 

 

4 To

change motor speed, move black or

red

wire to

desired

speed

 

setting

 

 

 

 

5 If any of the original wire as supplied with the appliance must be replaced, it must be replaced with AWM (105 C) wire or its equivalent

6 Motor is thermally overload protected

58GS175 size with Essex 242NS gas valve,

 

Heat/Cool models.......................................

0.65 amp

With addition of automatic vent damper, antici­ pator setting should be 0.12 amp.

The room thermostat should be located where it will be in the natural circulating path of room air. Avoid locations where the thermostat would be

7 Factory speed

selection is

tor average conditions See installa­

tion instructions

for optimum

speed selection Motor may be 3

or 4 speed

 

 

8 Symbols are an electrical representation only

 

 

 

 

©Cp

THERMOSTAT

 

 

 

 

 

 

 

 

 

TERMINALS

 

 

 

 

 

 

FOUR WIRE-

 

 

 

 

 

 

 

 

 

TWO WIRE HEATING ONLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

JL

©-

 

 

CONDENSING

 

 

 

 

 

 

Jl

 

 

 

UNIT

 

 

 

 

 

 

I TWO WIRE

 

 

 

 

 

■=r

 

 

 

 

.Q^JZL

 

 

 

-CHMV

 

 

&

 

 

 

 

 

 

 

 

SINGLE

 

 

 

 

 

 

 

 

———

 

PHASE

LOW-VOLTAGE

 

&-

 

 

 

-Ijj^

 

 

 

 

 

 

 

 

 

 

 

= GN0

 

 

TERMINAL BLOCK

 

 

 

 

 

 

 

 

 

 

Field Low-Voltage Wiring

 

 

NOTE: If any of the

original wire as supplied,

must be replaced,

Field High-Voltage Wiring

 

 

use same type or equivalent wire

 

 

 

 

 

Factory Low-Voltage Wiring

 

 

 

 

 

 

 

 

 

 

 

Fig. 2 — Heating and Cooljng Application Wiring Diagram

lA-TRANSFORMER

115/24

 

 

2 A-RE LAY-HEAT (SPST-NC)

 

 

3D-BLOWER

MOTOR

 

 

 

4A-RUN

CAPACITOR

 

 

 

5F-GAS VALVE

 

 

 

6C1-PRINT

ED CIRCUIT BOARD

 

6F-PILOT

IGNITER

 

 

 

6H-SAFETY

PILOT

(FLAME

SENSING)

 

7H-UMIT

SWITCH

(SPST-NC)

 

 

9G-BLOWER

DOOR SWITCH (SPST-N. O. )

 

IIC-FUSIBLE

UNK

 

 

 

HE-GROUND

LUG

 

 

 

 

•FACTORY

HIGH-VOLTAGE

WIRING

 

-FACTORY LOW-VOLTAGE WIRING

 

— — — —FIELD HIGH-VOLTAGE WIRING

 

Fig. 3 — Label Wiring Diagram; 58GS050-150 Sizes; Heating Only

lA-TRANSFORMER

lls/24

 

 

2A-RELAY - HEAT (SPSP-NC)

 

 

 

2F-RELAY - COOL(DPDT)

 

 

 

 

3D-BLOWER

 

MOTOR

 

 

 

4A-RUN

CAPACITOR

 

 

 

5F-GAS VALVE

 

 

 

 

 

6C1-PRINTED

 

CIRCUIT

BOARD

 

6F-PiLOT

 

IGNITER

 

 

 

6H-SAFETY

 

PILOT

(FLAME

SENSING)

 

7H-UMIT

SWITCH

(SPST-NC)

 

9G-BLOV.ER

DOOR

SWITCH

 

(SPST-N. O.

)

lie

FUSIBLE

UNK

 

 

 

Uh-GROUND LUG

 

 

 

 

 

—----------- FACTORY

 

HIGH-VOLTAGE

WIRING

 

--------FACTORY LOW-VOLTAGE WIRING

 

-— FIE LD HIGHVOLTAGE WIRING

Fig. 4 — Label Wiring Diagram; 58GS050-150 Si2:es; Heat/Cool

5

Loading...
+ 10 hidden pages