Carrier 50TFQ008-012 User Manual

0 (0)

50TFQ008-012 Single-Package Rooftop Heat Pump Units

Installation, Start-Up and

Service Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . .1

INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-43

Step 1— Provide Unit Support. . . . . . . . . . . . . . . . . . . . . . .1

ROOF CURB

SLAB MOUNT

ALTERNATE UNIT SUPPORT

Step 2 — Field Fabricate Ductwork . . . . . . . . . . . . . . . . . .

3

Step 3

— Install Condensate Drain Line

 

and External Trap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

Step 4

— Rig and Place Unit. . . . . . . . . . . . . . . . . . . . . . . . .

3

• POSITIONING

 

Step 5

— Make Electrical Connections . . . . . . . . . . . . . .

7

FIELD POWER SUPPLY

FIELD CONTROL WIRING

DEFROST BOARD

HEAT ANTICIPATOR SETTINGS

Step 6 — Adjust Factory-Installed Options . . . . . . . . .12

DISCONNECT SWITCH

CONVENIENCE OUTLET

NOVAR CONTROLS

MANUAL OUTDOOR-AIR DAMPER

PREMIERLINK™ CONTROL

OPTIONAL ECONOMI$ER IV AND ECONOMI$ER2

ECONOMI$ER IV STANDARD SENSORS

ECONOMI$ER IV CONTROL MODES

Step 7 — Adjust Indoor-Fan Speed . . . . . . . . . . . . . . . . .25

PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44 START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44-47 SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47-49 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49-53 INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54 START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.

Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.

Before performing service or maintenance operations on unit, turn off main power switch to unit and install lockout tag. Ensure voltage listed on unit data plate agrees with electrical supply provided for the unit. Electrical shock could cause personal injury.

INSTALLATION

Unit is shipped in the vertical configuration. To convert to horizontal configuration, remove side duct opening covers. Using the same screws, install covers on vertical duct openings with the insulation-side down. Seals around duct openings must be tight.

Step 1 — Provide Unit Support

ROOF CURB — Assemble and install the accessory roof curb in accordance with instructions shipped with the curb. See Fig. 1. Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb. If electric or control power will be routed through the basepan, use the proper accessory kit listed in Fig. 1, available from your local distributor. Attach the accessory thru-the-bottom service connections to the basepan in accordance with the accessory installation instructions. Connections must be installed before the unit is set on the roof curb.

IMPORTANT: The gasketing of the unit to the roof curb is critical for a water-tight seal. Install gasket supplied with the roof curb as shown in Fig. 1. Improperly applied gasket can also result in air leaks and poor unit performance.

The roof curb should be level. Unit leveling tolerances are shown in Fig. 2. This is necessary for the unit drain to function properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

1

4

Catalog No. 04-53500019-01

Printed in U.S.A.

Form 50TFQ-9SI

Pg 1

9-05

Replaces: 50TFQ-7SI

Tab

5a

5a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 1 — Roof Curb Details

2

MAXIMUM ALLOWABLE

DIFFERENCE (in.)

A-B

B-C

A-C

0.5

1.0

1.0

Fig. 2 — Unit Leveling Tolerances

SLAB MOUNT (Horizontal Units Only) — Provide a level concrete slab that extends a minimum of 6 in. beyond the unit cabinet on all sides. Install a gravel apron in front of the outdoor coil air inlet to prevent grass and foliage from obstructing airflow.

NOTE: Horizontal units may be installed on a roof curb if required.

ALTERNATE UNIT SUPPORT — When the curb or adapter cannot be used, support unit with sleeper rails using unit curb or adapter support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.

Step 2 — Field Fabricate Ductwork — On vertical discharge units, secure all ducts to the roof curb and building structure. Do not connect ductwork to the unit. For horizontal applications, field-supplied flanges should be attached to horizontal discharge openings and all ductwork attached to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.

Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.

If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.

A minimum clearance is not required around ductwork. Cabinet return-air static pressure (a negative condition) should not exceed 0.35 in. wg with economizer, or 0.45 in. wg without economizer.

Step 3 — Install Condensate Drain Line and External Trap — Condensate drain connections are located at the bottom and end of the unit. Unit discharge connections do not determine the use of drain connections; either drain connection can be used in vertical or horizontal applications.

When using the standard end drain connection, make sure the plug in the alternate bottom connection is tight before installing the unit.

To use the bottom drain connection for a roof curb installation, relocate the factory-installed plug from the bottom connection to the end connection. The center drain plug looks like a star connection, but can be removed with a 1/2-in. socket drive extension. See Fig. 3. The piping for the condensate drain and external trap can be completed after the unit is in place.

All units must have an external trap for condensate drainage. Install a trap at least 4-in. deep and protect against freezeup. If drain line is installed downstream from the external trap,

pitch the line away from the unit at 1/4-in. per ft of run. Do not use a pipe size smaller than the unit connection. See Fig. 4.

Step 4 — Rig and Place Unit — Inspect the unit for transportation damage. File any claim with the transportation agency. Keep the unit upright and do not drop it. Spreader bars are not required if top crating is left on the unit. Rollers may be used to move the unit across a roof. Level by using the unit frame as a reference. See Table 1 and Fig. 5 for additional information. Operating weight is shown in Table 1 and Fig. 5.

Lifting holes are provided in the base rails as shown in Fig. 5 and 6. Refer to rigging instructions on the unit.

POSITIONING — Maintain clearance around and above the unit to provide proper airflow and service access. See Fig. 6.

Position the unit on the roof curb so that the following clearances are maintained: 1/4-in. clearance between the roof curb and base rails on each side and in front of the unit; 35/16-in. clearance between the roof curb and the outdoor fan end of the unit (see Fig. 1, section C-C).

Do not install the unit indoors. Do not locate the unit air inlet near exhaust vents or other sources of contaminated air.

Although the unit is weatherproof, guard against water from higher level runoff and overhangs.

After the unit is in position, remove the polyethylene shipping wrapper and rigging skid.

HORIZONTAL

DRAIN PLUG

DRAIN OUTLET

 

NOTE: Drain plug is shown in factory-installed position.

Fig. 3 — Condensate Drain Pan (Side View)

NOTE: Trap should be deep enough to offset maximum unit static difference. A 4-in. trap is recommended.

Fig. 4 — Condensate Drain Piping Details

3

NOTES:

1. Dimension in ( ) is in millimeters.

2.Hook rigging shackles through holes in base rail, as shown in detail A.Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.

3.Unit weights do not include economizer. See Table 1 for economizer weights.

All panels must be in place when rigging. Unit is not designed for handling by a fork truck. Damage to unit may result.

50TFQ

WEIGHT

 

A

 

B

 

C

Lb

Kg

in.

mm

in.

mm

in.

 

mm

 

 

008

940

426

77.42

1966.5

41.5

1054

42.12

 

1070

009

965

438

77.42

1966.5

41.5

1054

42.12

 

1070

012

1015

460

77.42

1966.5

41.5

1054

42.12

 

1070

Fig. 5 — Rigging Details

4

Table 1 — Physical Data

UNIT SIZE 50TFQ

 

008

 

 

009

 

 

012

NOMINAL CAPACITY (tons)

 

71/2

 

 

81/2

 

 

10

OPERATING WEIGHT (lb)

 

 

 

 

 

 

 

 

 

Unit

 

940

 

 

965

 

 

1015

Economizer

 

 

 

 

 

 

 

 

 

EconoMi$er IV

 

75

 

 

75

 

 

75

Roof Curb*

 

143

 

 

143

 

 

143

COMPRESSOR (Hermetic)

 

 

Reciprocating

 

 

Scroll

Quantity

 

2

 

 

2

 

 

2

 

 

Oil (oz)

 

45 ea

 

 

54 ea

 

 

54 ea

REFRIGERANT TYPE

 

 

 

 

R-22

 

 

 

Operating Charge (lb-oz)

 

 

 

 

 

 

 

 

 

Circuit 1

 

5-14

 

 

8- 6

 

 

7-14

 

 

 

Circuit 2

 

5-13

 

 

8-13

 

 

8- 3

OUTDOOR COIL

 

Enhanced Copper Tubes, Aluminum Lanced Fins, Acutrol™ Feed Device

Rows...Fins/in.

 

1...17

 

 

2...17

 

 

2...17

 

 

 

Total Face Area (sq ft)

 

20.50

 

 

18.00

 

 

18.30

OUTDOOR FAN

 

 

 

 

Propeller Type

 

 

 

Nominal Cfm

 

6500

 

 

6500

 

 

6500

 

 

 

Quantity...Diameter (in.)

 

2...22

 

 

2...22

 

 

2...22

Motor Hp...Rpm

 

1/4...1100

 

 

1/4...1100

 

 

1/4...1100

Watts Input (Total)

 

500

 

 

500

 

 

500

INDOOR COIL

 

Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol Feed Device

Rows...Fins/in.

 

3...15

 

 

3...15

 

 

3...15

 

 

 

Total Face Area (sq ft)

 

8.0

 

 

8.0

 

 

11.1

INDOOR FAN

 

 

 

 

Centrifugal Type

 

 

 

Quantity...Size (in.)

Std

1...15 x 15

 

 

1...15 x 15

 

 

1...15 x 15

 

 

 

 

Alt

1...15 x 15

 

 

 

 

1...15 x 15

 

High-Static

1...15 x 15

 

 

1...15 x 15

 

 

1...15 x 15

Type Drive

Std

Belt

 

 

Belt

 

 

Belt

 

Alt

Belt

 

 

 

 

Belt

Nominal Cfm

High-Static

Belt

 

 

Belt

 

 

Belt

 

3000

 

 

3600

 

 

4000

Maximum Continuous Bhp

Std

2.40

 

 

2.40

 

 

2.40

 

Alt

2.40

 

 

 

2.90

 

High-Static

3.70

 

 

3.70

 

 

5.25

Motor Frame Size

Std

56

 

 

56

 

 

56

 

Alt

56

 

 

 

56

 

High-Static

56

 

 

56

 

 

56

Nominal Rpm

Std

 

 

 

 

 

Alt

 

 

 

 

 

High-Static

1725

 

 

1725

 

 

1725

Fan Rpm Range

Std

590840

 

 

685935

 

 

685935

 

Alt

685935

 

 

 

835-1085

Motor Bearing Type

High-Static

860-1080

 

 

860-1080

 

 

830-1130

 

Ball

 

 

Ball

 

 

Ball

Maximum Allowable Rpm

 

2100

 

 

2100

 

 

2100

Motor Pulley Pitch Diameter Min/Max (in.)

Std

2.4/3.4

 

 

2.8/3.8

 

 

2.8/3.8

 

Alt

2.8/3.8

 

 

 

3.4/4.4

 

High-Static

4.0/5.0

 

 

4.0/5.0

 

 

2.8/3.8

Nominal Motor Shaft Diameter (in.)

Std

5/8

 

 

5/8

 

 

5/8

 

Alt

5/8

 

 

 

7/8

Fan Pulley Pitch Diameter (in.)

High-Static

7/8

 

 

7/8

 

 

7/8

Std

7.0

 

 

7.0

 

 

7.0

 

Alt

7.0

 

 

 

7.0

 

High-Static

8.0

 

 

8.0

 

 

5.8

Belt, Quantity...Type...Length (in.)

Std

1...A...53

 

 

1...A...48

 

 

1...A...49

 

Alt

1...A...49

 

 

 

 

1...A...51

 

High-Static

1...A...65

 

 

1...A...53

 

 

1...BX...48

Pulley Center Line Distance (in.)

Std

16.75-19.25

 

 

16.75-19.25

 

 

15.85-17.50

 

Alt

16.75-19.25

 

 

 

15.85-17.50

 

High-Static

16.75-19.25

 

 

16.75-19.25

 

 

15.85-17.50

Speed Change per Full Turn of

Std

50

 

 

50

 

 

50

Moveable Pulley Flange (rpm)

Alt

50

 

 

 

50

 

High-Static

60

 

 

60

 

 

60

Moveable Pulley Maximum Full Turns

Std

5

 

 

5

 

 

5

From Closed Position

Alt

5

 

 

 

5

 

High-Static

5

 

 

5

 

 

6

Factory Setting

Std

5

 

 

5

 

 

5

 

Alt

5

 

 

 

5

 

High-Static

5

 

 

5

 

 

5

Factory Speed Setting (rpm)

Std

590

 

 

685

 

 

685

 

Alt

685

 

 

 

835

Fan Shaft Diameter at Pulley (in.)

High-Static

860

 

 

880

 

 

887

 

1

 

 

1

 

 

1

HIGH-PRESSURE SWITCH (psig)

 

 

 

 

 

 

 

 

 

Standard Compressor Internal Relief (Differential)

 

 

450 ± 50

 

 

 

 

Cutout

 

 

428

 

 

 

 

Reset (Auto.)

 

 

320

 

 

 

 

LOSS-OF-CHARGE (LOW-PRESSURE) SWITCH (psig)

 

 

 

 

 

 

 

 

 

Cutout

 

 

7 ± 3

 

 

 

 

Reset (Auto.)

 

 

22 ± 5

 

 

 

 

FREEZE PROTECTION THERMOSTAT (F)

 

 

 

 

 

 

 

 

 

Opens

 

 

30 ± 5

 

 

 

 

Closes

 

 

45 ± 5

 

 

 

 

OUTDOOR-AIR INLET SCREENS

 

 

 

 

Cleanable.

 

 

 

 

 

Screen quantity and size vary based on options selected.

RETURN-AIR FILTERS

 

 

 

 

Throwaway

 

 

 

Quantity...Size (in.)

 

4...16 x 20 x 2

 

 

4...16 x 20 x 2

 

 

 

4...20 x 20 x 2

 

 

 

 

 

 

LEGEND

 

*Weight of 14-in. roof curb.

 

 

 

Bhp — Brake Horsepower

 

 

 

 

 

 

 

 

 

5

Carrier 50TFQ008-012 User Manual

6

Fig. 6 — Base Unit Dimensions

Step 5 — Make Electrical Connections

Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code) ANSI (American National Standards Institute)/ NFPA (National Fire Protection Association) 70 latest year and local electrical codes. Failure to follow this warning could result in the installer being liable for personal injury of others.

FIELD POWER SUPPLY — All units except 208/230-v units are factory-wired for the voltage shown on the unit nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the transformer must be rewired by disconnecting the black wire from the 230-v 1/4-in. male spade terminal on the transformer and connecting it to the 208-v 1/4-in. male spade terminal from the transformer.

Refer to the unit label diagram for additional information. Pigtails are provided for field wire connections. Use factorysupplied splices or a UL (Underwriters’ Laboratories) approved copper/aluminum connector.

When installing units, provide a disconnect per the NEC.

All field wiring must comply with the NEC and local requirements. In Canada, electrical connections must be made in accordance with CSA (Canadian Standards Association) C22.1 Canadian Electrical Code Part One.

Install field wiring as follows:

1.Install conduit through the side panel openings. For units without electric heat, install conduit between the disconnect and control box.

2.Install power lines to terminal connections as shown in Fig. 7.

3.For units with electric heat, refer to Table 2 and Accessory Installation Instructions.

During operation, voltage to compressor terminals must be within range indicated on unit nameplate (see Tables 3A and 3B). On 3-phase units, voltages between phases must be balanced within 2%, and the current within 10%. Use the formula shown in Tables 3A and 3B, Note 2 on page 11 to determine the percentage of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty.

208/230-3-60

 

575-3-60

460-3-60

 

 

 

 

LEGEND

C

Contactor

COMP —

Compressor

IFC

Indoor-Fan Contactor

NEC

National Electrical Code

TB

Terminal Block

 

 

Field Wiring

 

 

Factory Wiring

 

 

Splice Connection

 

 

(Factory-Supplied)

Fig. 7 — Power Wiring Connections

7

Table 2 — Electric Heating Capacities

50TFQ

UNIT VOLTAGE

ACCESSORY

ELECTRIC HEATER

SINGLE POINT BOX

PART NUMBER

PACKAGE NO.

UNIT SIZE

(60 Hz)

 

kW

 

CRHEATER---A00

CRSINGLE---A00

 

 

 

 

 

 

7.8/

9.6/10.4

017

007

 

208/230/240

12.0/14.7/16.0

010

007

 

18.6/22.8/24.8

011

009

 

(3 phase)

 

24.0/29.4/32.0

012

009

 

 

 

 

31.8/39.0/42.4*

012 and 017

013

008, 009

 

12.8/13.9

016

006

460/480

15.2/16.5

013

006

 

 

25.6/27.8

014

008

 

(3 phase)

 

30.4/33.0

015

008

 

 

 

 

38.4/41.7*

014 and 016

010

 

575

 

17.0

018

006

 

(3 phase)

 

34.0

019

006†

 

 

7.8/

9.6/10.4

017

012

 

208/230/240

12.0/14.7/16.0

010

012

 

24.0/29.4/32.0

012

015

 

(3 phase)

 

31.8/39.0/42.4*

012 and 017

017

 

 

 

 

37.6/46.2/50.0*

010 and 012

017

012

 

15.2/16.5

013

011

460/480

25.6/27.8

014

014

 

30.4/33.0

015

014

 

(3 phase)

 

38.4/41.7*

014 and 016

016

 

 

 

 

45.9/50.0*

013 and 015

016

 

575

 

17.0

018

011

 

 

34.0

019

014

 

(3 phase)

 

 

 

51.0*

018 and 019

016

 

 

 

*Two heater packages required to provide kW indicated.

†Use CRSINGLE008A00 for units with an electrical convenience outlet.

NOTES:

1.The rated heater voltage is 240, 480, and 575 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly.

2.To determine heater kW at voltages other than those shown in table, use the following formula:

Heater kW new = Heater kW rated x (unit power distribution voltage/rated heater voltage)2

As an example:

For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v kW new = 16 kW (215/240)2

kW new = 12.8 kW (rating at 215 v)

Table 3A — Electrical Data (Units Without Electrical Convenience Outlet)

 

 

 

VOLTAGE

COMPRESSOR

 

 

ELECTRIC HEAT*

POWER SUPPLY

DISCONNECT

50TFQ

NOMINAL

IFM

RANGE

(each)

OFM

IFM

 

SIZE†

 

 

 

 

 

 

 

 

UNIT SIZE

V-PH-Hz

TYPE

Min

Max

RLA

LRA

FLA

FLA

Nominal

FLA

MCA

MOCP

FLA

LRA

 

 

 

 

 

kW**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38.8/ 38.8

40/ 40††

41/ 41

229/229

 

 

 

 

 

 

 

 

 

7.8/10.4

21.7/ 25.0

65.9/

70.0

70/

70

66/

69

251/254

 

 

STD

187

254

13.4

91.0

1.4

5.8

12.0/16.0

33.3/ 38.5

80.4/

86.9

90/

90

79/

85

262/268***

 

 

18.6/24.8

51.6/

59.7

103.3/113.4

110/125

100/109

281/289***

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24.0/32.0

66.6/

77.0

122.0/135.0

125/150

117/129

296/306***

 

208/230-3-60

 

 

 

 

 

 

 

31.8/42.4

88.3/102.0

149.1/166.3

150/175

142/158

317/331***

 

 

 

 

 

 

 

 

43.6/ 43.6

45/ 45††

46/ 46

273/273

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.8/10.4

21.7/

25.0

70.7/

74.8

80/

80

71/

75

294/298

 

 

HIGH-STATIC

187

254

13.4

91.0

1.4

10.6

12.0/16.0

33.3/

38.5

85.2/

91.7

90/100

85/

91

306/311***

 

 

18.6/24.8

51.6/

59.7

108.1/118.2

110/125

106/115

324/332***

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24.0/32.0

66.6/

77.0

126.8/139.8

150/150

123/135

339/350***

 

 

 

 

 

 

 

 

 

31.8/42.4

88.3/102.0

153.9/171.1

175/175

148/164

361/375***

 

 

 

 

 

 

 

 

 

19.1

20††

20

 

108

 

 

 

 

 

 

 

 

 

13.9

16.7

40.0

40††

39

 

124

008

 

STD

414

508

6.7

42.0

0.7

2.6

16.5

19.8

43.8

45††

43

 

128

(71/2 Tons)

 

27.8

33.4

60.8

70

58

 

141

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33.0

39.7

68.7

70

66

 

147

 

460-3-60

 

 

 

 

 

 

 

41.7

50.2

81.8

90

78

 

158

 

 

 

 

 

 

 

 

21.3

25††

23

 

130

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13.9

16.7

42.2

45††

42

 

146

 

 

HIGH-STATIC

414

508

6.7

42.0

0.7

4.8

16.5

19.8

46.0

50††

45

 

149

 

 

27.8

33.4

63.0

70

61

 

163

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33.0

39.7

70.9

80

68

 

169

 

 

 

 

 

 

 

 

 

41.7

50.2

84.0

90

80

 

180***

 

 

 

 

 

 

 

 

 

15.4

20††

16

 

97

 

 

STD

 

 

 

 

 

2.6

17.0

17.1

36.7

40††

36

 

114

 

575-3-60

 

518

632

5.4

39.0

0.7

 

34.0

34.1

58.0

60††

55

 

131

 

 

 

17.1

20††

18

 

114

 

 

 

 

 

 

 

 

 

 

 

 

HIGH-STATIC

 

 

 

 

 

4.8

17.0

17.1

38.5

40††

38

 

132

 

 

 

 

 

 

 

 

 

34.0

34.1

59.7

60††

57

 

149

NOTE: Legend and Notes for Electrical Data are on page 11.

8

Table 3A — Electrical Data (Units Without Electrical Convenience Outlet) (cont)

 

 

 

VOLTAGE

COMPRESSOR

 

 

ELECTRIC HEAT*

POWER SUPPLY

 

DISCONNECT

50TFQ

NOMINAL

IFM

RANGE

 

(each)

OFM

IFM

 

 

SIZE†

 

 

 

 

 

 

 

 

 

 

UNIT SIZE

V-PH-Hz

TYPE

Min

Max

RLA

 

LRA

FLA

FLA

Nominal

FLA

MCA

MOCP

FLA

LRA

 

 

 

 

 

 

kW**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

44.6/ 44.6

45/ 45††

47/ 47

321/321

 

 

 

 

 

 

 

 

 

 

7.8/10.4

21.7/

25.0

71.7/

75.9

80/

80

72/

75

343/346

 

 

STD

187

254

16.0

 

137.0

1.4

5.8

12.0/16.0

33.3/

38.5

86.2/

92.7

90/100

85/

91

354/360***

 

 

 

18.6/24.8

51.6/

59.7

109.1/119.2

110/125

106/115

373/381***

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24.0/32.0

66.6/

77.0

127.9/140.9

150/150

123/135

388/398***

 

208/230-3-60

 

 

 

 

 

 

 

 

31.8/42.4

88.3/102.0

155.0/172.1

175/175

148/164

409/428***

 

 

 

 

 

 

 

 

 

49.4/ 49.4

50/ 50††

52/ 52

365/365

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.8/10.4

21.7/

25.0

76.5/

80.7

80/

90

77/

81

386/390***

 

 

HIGH-STATIC

187

254

16.0

 

137.0

1.4

10.6

12.0/16.0

33.3/

38.5

91.0/

97.5

100/100

91/

96

398/403***

 

 

 

18.6/24.8

51.6/

59.7

113.9/124.0

125/125

112/121

416/424***

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24.0/32.0

66.6/

77.0

132.7/145.7

150/150

129/141

431/442***

 

 

 

 

 

 

 

 

 

 

31.8/42.4

88.3/102.0

159.8/176.9

175/200

154/170

453/467***

 

 

 

 

 

 

 

 

 

 

22.7

25††

24

 

162

 

 

 

 

 

 

 

 

 

 

13.9

16.7

43.6

45††

43

 

178

009

 

STD

414

508

8.3

 

69.0

0.7

2.6

16.5

19.8

47.4

50††

46

 

182

(81/2 Tons)

 

 

27.8

33.4

64.4

70

 

62

 

195

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33.0

39.7

72.3

80

 

69

 

201

 

460-3-60

 

 

 

 

 

 

 

 

41.7

50.2

85.4

90

 

81

 

212***

 

 

 

 

 

 

 

 

 

24.9

25††

26

 

184

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13.9

16.7

45.8

50††

45

 

200

 

 

HIGH-STATIC

414

508

8.3

 

69.0

0.7

4.8

16.5

19.8

49.6

50††

49

 

203

 

 

 

27.8

33.4

66.6

70

 

65

 

217

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33.0

39.7

74.5

80

 

72

 

223

 

 

 

 

 

 

 

 

 

 

41.7

50.2

87.6

90

 

84

 

234***

 

 

 

 

 

 

 

 

 

 

17.6

20††

18

 

135

 

 

STD

 

 

 

 

 

 

2.6

17.0

17.1

39.0

40††

38

 

152

 

575-3-60

 

518

632

6.4

 

58.0

0.7

 

34.0

34.1

60.2

70††

58

 

169

 

 

 

 

19.4

20††

20

 

152

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH-STATIC

 

 

 

 

 

 

4.8

17.0

17.1

40.7

45††

40

 

170

 

 

 

 

 

 

 

 

 

 

34.0

34.1

62.0

70

 

60

 

187

 

 

 

 

 

 

 

 

 

 

47.3/ 47.3

50/ 50††

49/ 49

295/295

 

 

 

 

 

 

 

 

 

 

7.8/10.4

21.7/

25.0

74.4/

78.6

80/

80

74/

78

317/320

 

 

STD

187

254

17.2

 

124.0

1.4

5.8

12.0/16.0

33.3/

38.5

88.9/

95.4

90/100

88/

94

328/334***

 

 

 

24.0/32.0

66.6/

77.0

130.6/143.6

150/150

126/138

362/372***

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31.8/42.4

88.3/102.0

157.7/174.8

175/175

151/167

383/397***

 

 

 

 

 

 

 

 

 

 

37.6/50.0

104.4/120.3

177.8/167.6

200/175

170/188

399/415***

 

 

 

 

 

 

 

 

 

 

49.0/ 49.0

50/ 50††

51/ 51

314/314

 

 

 

 

 

 

 

 

 

 

7.8/10.4

21.7/

25.0

76.1/

80.8

80/

90

76/

80

336/389***

 

208/230-3-60

ALT

187

254

17.2

 

124.0

1.4

7.5

12.0/16.0

33.3/

38.5

90.6/

97.1

100/100

90/

96

347/353***

 

 

24.0/32.0

66.6/

77.0

132.3/145.3

150/150

128/140

381/391***

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31.8/42.4

88.3/102.0

159.4/176.5

175/200

153/169

402/416***

 

 

 

 

 

 

 

 

 

 

37.6/50.0

104.4/120.3

179.5/169.3

200/200

171/190

418/434***

 

 

 

 

 

 

 

 

 

 

56.5/ 56.5

60/ 60††

60/ 60

362/362

 

 

 

 

 

 

 

 

 

 

7.8/10.4

21.7/

25.0

83.6/

87.8

90/

90

85/

89

384/387***

 

 

HIGH-STATIC

187

254

17.2

 

124.0

1.4

15.0

12.0/16.0

33.3/

38.5

98.1/104.6

100/110

98/104

395/401***

 

 

 

24.0/32.0

66.6/

77.0

139.8/152.8

150/175

137/149

429/439***

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31.8/42.4

88.3/102.0

166.9/184.0

175/200

162/177

450/464***

 

 

 

 

 

 

 

 

 

 

37.6/50.0

104.4/120.3

187.0/176.8

200/200

180/198

466/482***

 

 

 

 

 

 

 

 

 

 

23.4

25††

24

 

143

 

 

 

 

 

 

 

 

 

 

16.5

19.8

48.1

50††

47

 

163

 

 

STD

414

508

8.6

 

59.6

0.7

2.6

27.8

33.4

65.1

70

 

63

 

176

 

 

 

33.0

39.7

73.0

80

 

70

 

183

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41.7

50.2

86.1

90

 

82

 

193***

012

 

 

 

 

 

 

 

 

 

50.0

60.1

83.5

90

 

93

 

203***

(10 Tons)

 

 

 

 

 

 

 

 

 

24.2

25††

25

 

182

 

 

 

 

 

 

 

 

 

 

16.5

19.8

48.9

50††

48

 

202

 

460-3-60

ALT

414

508

8.6

 

59.6

0.7

3.4

27.8

33.4

65.9

70

 

64

 

216

 

 

33.0

39.7

73.8

80

 

71

 

222

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41.7

50.2

86.9

90

 

83

 

233***

 

 

 

 

 

 

 

 

 

 

50.0

60.1

84.3

90

 

94

 

243***

 

 

 

 

 

 

 

 

 

 

28.2

30††

30

 

176

 

 

 

 

 

 

 

 

 

 

16.5

19.8

52.9

60††

53

 

196

 

 

HIGH-STATIC

414

508

8.6

 

59.6

0.7

7.4

27.8

33.4

69.9

70

 

68

 

210

 

 

 

33.0

39.7

77.8

80

 

76

 

216

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41.7

50.2

90.9

100

 

88

 

227***

 

 

 

 

 

 

 

 

 

 

50.0

60.1

88.3

100

 

99

 

237***

 

 

 

 

 

 

 

 

 

 

18.7

20††

20

 

118

 

 

STD

518

632

6.9

 

49.4

0.7

2.6

17.0

17.1

40.1

45††

39

 

135

 

 

 

34.0

34.1

61.4

70

 

59

 

152

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51.0

51.2

69.9

70

 

78

 

169

 

 

 

 

 

 

 

 

 

 

19.4

20††

20

 

149

 

575-3-60

ALT

518

632

6.9

 

49.4

0.7

3.4

17.0

17.1

40.7

45††

40

 

166

 

 

34.0

34.1

62.0

70

 

60

 

183

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51.0

51.2

70.6

80

 

79

 

201***

 

 

 

 

 

 

 

 

 

 

22.6

25††

24

 

145

 

 

HIGH-STATIC

518

632

6.9

 

49.4

0.7

7.4

17.0

17.1

43.9

45††

44

 

162

 

 

 

34.0

34.1

65.2

70

 

63

 

179

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51.0

51.2

73.8

80

 

83

 

196***

NOTE: Legend and Notes for Electrical Data are on page 11.

9

Table 3B — Electrical Data (Units With Electrical Convenience Outlet)

 

 

 

VOLTAGE

COMPRESSOR

 

 

ELECTRIC

 

POWER SUPPLY

DISCONNECT

50TFQ

NOMINAL

IFM

RANGE

(each)

OFM

IFM

HEAT*

 

 

SIZE†

 

 

 

 

 

 

UNIT SIZE

V-PH-Hz

TYPE

Min

Max

RLA

LRA

FLA

FLA

Nominal

FLA

MCA

MOCP

FLA

LRA

 

 

 

 

 

kW**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

43.6/ 43.6

45/ 45††

46/ 46

234/234

 

 

 

 

 

 

 

 

 

7.8/10.4

21.7/

25.0

70.7/

74.8

80/

80

71/

75

256/259

 

 

STD

187

254

13.4

91.0

1.4

5.8

12.0/16.0

33.3/

38.5

85.2/

91.7

90/100

85/

91

267/272***

 

 

18.6/24.8

51.6/

59.7

108.1/118.2

110/125

106/115

285/294***

 

 

 

 

 

 

 

 

 

24.0/32.0

66.6/

77.0

126.8/139.8

150/150

123/135

300/311***

 

208/230-3-60

 

 

 

 

 

 

 

31.8/42.4

88.3/102.0

153.9/171.1

175/175

148/164

322/336***

 

 

 

 

 

 

 

 

48.4/ 48.4

50/ 50††

52/ 52

277/277

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.8/10.4

21.7/

25.0

75.5/

79.6

80/

80

77/

81

299/302***

 

 

HIGH-STATIC

187

254

13.4

91.0

1.4

10.6

12.0/16.0

33.3/

38.5

90.0/

96.5

90/100

90/

96

311/316***

 

 

18.6/24.8

51.6/

59.7

112.9/123.0

125/125

111/120

329/337***

 

 

 

 

 

 

 

 

 

24.0/32.0

66.6/

77.0

131.6/144.6

150/150

128/140

344/354***

 

 

 

 

 

 

 

 

 

31.8/42.4

88.3/102.0

158.7/175.9

175/200

153/169

366/379***

 

 

 

 

 

 

 

 

 

21.3

25††

23

 

110

 

 

 

 

 

 

 

 

 

13.9

16.7

42.1

45††

42

 

127

008

 

STD

414

508

6.7

42.0

0.7

2.6

16.5

19.8

46.0

50††

45

 

130

(71/2 Tons)

 

27.8

33.4

63.0

70

61

 

143

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33.0

39.7

70.9

80

68

 

150

 

460-3-60

 

 

 

 

 

 

 

41.7

50.2

84.0

90

80

 

160***

 

 

 

 

 

 

 

 

23.5

25††

25

 

132

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13.9

16.7

44.3

45††

44

 

148

 

 

HIGH-STATIC

414

508

6.7

42.0

0.7

4.8

16.5

19.8

48.2

50††

48

 

151

 

 

27.8

33.4

65.2

70

63

 

165

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33.0

39.7

73.1

80

71

 

171

 

 

 

 

 

 

 

 

 

41.7

50.2

86.2

90

83

 

182***

 

 

 

 

 

 

 

 

 

17.1

20††

18

 

99

 

 

STD

518

632

5.4

39.0

0.7

2.6

17.0

17.1

38.5

40††

38

 

116

 

575-3-60

 

 

 

 

 

 

 

34.0

34.1

59.7

60††

57

 

133

 

 

 

 

 

 

 

 

18.9

20††

20

 

116

 

 

 

 

 

 

 

 

 

 

 

 

HIGH-STATIC

518

632

5.4

39.0

0.7

4.8

17.0

17.1

40.2

45††

40

 

133

 

 

 

 

 

 

 

 

 

34.0

34.1

61.5

70

59

 

150

 

 

 

 

 

 

 

 

 

49.4/ 49.4

50/ 50††

52/ 52

326/326

 

 

 

 

 

 

 

 

 

7.8/10.4

21.7/

25.0

76.5/

80.7

80/

90

77/

81

348/351

 

 

STD

187

254

16.0

137.0

1.4

5.8

12.0/16.0

33.3/

38.5

91.0/

97.5

100/100

91/

96

359/364

 

 

18.6/24.8

51.6/

59.7

113.9/124.0

125/125

112/121

377/386

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24.0/32.0

66.6/

77.0

132.7/145.7

150/150

129/141

392/403

 

208/230-3-60

 

 

 

 

 

 

 

31.8/42.4

88.3/102.0

154.8/176.9

175/200

154/170

414/428

 

 

 

 

 

 

 

 

54.2/ 54.2

60/ 60††

58/ 58

369/369

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.8/10.4

21.7/

25.0

81.3/

85.5

90/

90

83/

86

391/394***

 

 

HIGH-STATIC

187

254

16.0

137.0

1.4

10.6

12.0/16.0

33.3/

38.5

95.8/102.3

100/110

96/102

403/408***

 

 

18.6/24.8

51.6/

59.7

118.7/128.8

125/150

117/126

421/429***

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24.0/32.0

66.6/

77.0

137.5/150.5

150/175

134/146

436/446***

 

 

 

 

 

 

 

 

 

31.8/42.4

88.3/102.0

164.6/181.7

175/200

159/175

458/471***

 

 

 

 

 

 

 

 

 

24.9

25††

26

 

164

 

 

 

 

 

 

 

 

 

13.9

16.7

45.7

50††

45

 

181

009

 

STD

414

508

8.3

69.0

0.7

2.6

16.5

19.8

49.6

50††

49

 

184

(81/2 Tons)

 

27.8

33.4

66.6

70

 

65

 

197

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33.0

39.7

74.5

80

 

72

 

204

 

460-3-60

 

 

 

 

 

 

 

41.7

50.2

87.6

90

 

84

 

214***

 

 

 

 

 

 

 

 

27.1

30††

29

 

186

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13.9

16.7

47.9

50††

48

 

202

 

 

HIGH-STATIC

414

508

8.3

69.0

0.7

4.8

16.5

19.8

51.8

60††

51

 

205

 

 

27.8

33.4

68.8

70

 

67

 

219

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33.0

39.7

76.7

80

 

74

 

225

 

 

 

 

 

 

 

 

 

41.7

50.2

89.8

90

 

86

 

236***

 

 

 

 

 

 

 

 

 

19.3

20††

20

 

137

 

 

STD

518

632

6.4

58.0

0.7

2.6

17.0

17.1

40.7

45††

40

 

154

 

575-3-60

 

 

 

 

 

 

 

34.0

34.1

62.0

70

 

60

 

171

 

 

 

 

 

 

 

 

21.1

25††

22

 

154

 

 

 

 

 

 

 

 

 

 

 

 

HIGH-STATIC

518

632

6.4

58.0

0.7

4.8

17.0

17.1

42.5

45††

42

 

171

 

 

 

 

 

 

 

 

 

34.0

34.1

63.7

70

 

62

 

188

NOTE: Legend and Notes for Electrical Data are on page 11.

10

Table 3B — Electrical Data (Units With Electrical Convenience Outlet) (cont)

 

 

 

VOLTAGE

COMPRESSOR

 

 

ELECTRIC

 

POWER SUPPLY

 

DISCONNECT

50TFQ

NOMINAL

IFM

RANGE

 

(each)

OFM

IFM

 

HEAT*

 

 

 

SIZE†

 

 

 

 

 

 

 

 

 

UNIT SIZE

V-PH-Hz

TYPE

Min

Max

RLA

 

LRA

FLA

FLA

Nominal

 

FLA

MCA

MOCP

FLA

 

LRA

 

 

 

 

 

 

kW**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

52.1/ 52.1

60/ 60††

55/ 55

 

300/300

 

 

 

 

 

 

 

 

 

 

7.8/10.4

 

21.7/

25.0

79.2/

83.4

80/

90

80/

84

 

322/325***

 

 

STD

187

254

17.2

 

124.0

1.4

5.8

12.0/16.0

 

33.3/

38.5

93.7/100.2

100/110

93/

99

 

333/338***

 

 

 

24.0/32.0

 

66.6/

77.0

135.4/148.4

150/150

132/144

 

366/377***

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31.8/42.4

 

88.3/102.0

162.5/179.6

175/200

157/172

 

388/402***

 

 

 

 

 

 

 

 

 

 

37.6/50.0

 

104.4/120.3

182.6/172.4

200/200

175/193

 

404/420***

 

 

 

 

 

 

 

 

 

 

 

 

53.8/ 53.8

60/ 60††

57/ 57

 

319/319

 

 

 

 

 

 

 

 

 

 

7.8/10.4

 

21.7/

25.0

80.9/

85.1

90/

90

82/

86

 

341/344***

 

208/230-3-60

ALT

187

254

17.2

 

124.0

1.4

7.5

12.0/16.0

 

33.3/

38.5

95.4/101.9

100/110

95/101

 

352/357***

 

 

24.0/32.0

 

66.6/

77.0

137.1/150.1

150/175

134/145

 

385/396***

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31.8/42.4

 

88.3/102.0

164.2/181.3

175/200

158/174

 

407/421***

 

 

 

 

 

 

 

 

 

 

37.6/50.0

 

104.4/120.3

184.3/174.1

200/200

177/195

 

423/439***

 

 

 

 

 

 

 

 

 

 

 

 

61.3/ 61.3

70/ 70

66/ 66

 

367/367

 

 

 

 

 

 

 

 

 

 

7.8/10.4

 

21.7/

25.0

88.4/

92.6

90/100

91/

94

 

389/392***

 

 

HIGH-STATIC

187

254

17.2

 

124.0

1.4

15.0

12.0/16.0

 

33.3/

38.5

102.9/109.4

110/110

104/110

 

400/405***

 

 

 

24.0/32.0

 

66.6/

77.0

144.6/157.6

150/175

142/154

 

433/444***

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31.8/42.4

 

88.3/102.0

171.7/188.8

175/200

167/183

 

455/459***

 

 

 

 

 

 

 

 

 

 

37.6/50.0

 

104.4/120.3

191.8/181.6

200/200

186/204

 

471/487***

 

 

 

 

 

 

 

 

 

 

 

 

25.5

30††

27

 

145

 

 

 

 

 

 

 

 

 

 

16.5

 

19.8

50.3

60††

50

 

165

 

 

STD

414

508

8.6

 

59.6

0.7

2.6

27.8

 

33.4

67.3

70

 

65

 

178

 

 

 

33.0

 

39.7

75.2

80

 

73

 

185

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41.7

 

50.2

88.3

90

 

85

 

195***

012

 

 

 

 

 

 

 

 

 

50.0

 

60.1

85.6

90

 

96

 

205***

(10 Tons)

 

 

 

 

 

 

 

 

 

 

 

26.3

30††

28

 

185

 

 

 

 

 

 

 

 

 

 

16.5

 

19.8

51.1

60††

51

 

204

 

460-3-60

ALT

414

508

8.6

 

59.6

0.7

3.4

27.8

 

33.4

68.1

70

 

66

 

218

 

 

33.0

 

39.7

76.0

80

 

73

 

224

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41.7

 

50.2

89.1

90

 

86

 

235***

 

 

 

 

 

 

 

 

 

 

50.0

 

60.1

86.4

90

 

97

 

245***

 

 

 

 

 

 

 

 

 

 

 

 

30.3

35††

32

 

179

 

 

 

 

 

 

 

 

 

 

16.5

 

19.8

55.1

60††

55

 

198

 

 

HIGH-STATIC

414

508

8.6

 

59.6

0.7

7.4

27.8

 

33.4

72.1

80

 

71

 

212

 

 

 

33.0

 

39.7

80.0

80

 

78

 

218

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41.7

 

50.2

93.1

100

 

90

 

229***

 

 

 

 

 

 

 

 

 

 

50.0

 

60.1

90.4

100

 

102

 

239***

 

 

 

 

 

 

 

 

 

 

 

 

20.5

25††

22

 

120

 

 

STD

518

632

6.9

 

49.4

0.7

2.6

17.0

 

17.1

41.8

45††

41

 

137

 

 

 

34.0

 

34.1

63.1

70

 

61

 

154

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51.0

 

51.2

71.7

80

 

80

 

171***

 

 

 

 

 

 

 

 

 

 

 

 

21.1

25††

22

 

151

 

575-3-60

ALT

518

632

6.9

 

49.4

0.7

3.4

17.0

 

17.1

42.5

45††

42

 

168

 

 

34.0

 

34.1

63.7

70

 

62

 

185

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51.0

 

51.2

72.3

80

 

81

 

202***

 

 

 

 

 

 

 

 

 

 

 

 

24.3

25††

26

 

146

 

 

HIGH-STATIC

518

632

6.9

 

49.4

0.7

7.4

17.0

 

17.1

45.7

50††

46

 

163

 

 

 

34.0

 

34.1

66.9

70

 

65

 

180

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51.0

 

51.2

75.5

80

 

85

 

198***

 

LEGEND

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

NEC

National Electrical Code

OFM

Outdoor Fan Motor

RLA

Rated Load Amps

*Heaters are field installed only.

†Used to determine minimum disconnect size per NEC.

**Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and 575 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly.

††Fuse or HACR circuit breaker.

***Optional disconnect switch is unavailable.

NOTES:

1.In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%.

Use the following formula to determine the percent of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 v

BC = 464 v

AC = 455 v

Average Voltage =

452 + 464 + 455

3

=

1371

3

= 457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

7

457

= 1.53%

 

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

11

FIELD CONTROL WIRING — Install a Carrier-approved accessory thermostat assembly according to the installation instructions included with the accessory. Locate the thermostat assembly on a solid wall in the conditioned space to sense average temperature in accordance with the thermostat installation instructions.

NOTE: If using a Carrier electronic thermostat, set the thermostat configuration for “non-heat pump operation.” This family of products does not require an O terminal to energize the reversing valve.

Route the thermostat cable or equivalent single leads of colored wire from the subbase terminals to the low-voltage connections on the unit (shown in Fig. 8A and 8B) as described in Steps 1 through 4 below.

NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 51 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.

1.If the unit is mounted on the roof curb and the accessory thru-the-curb service plate connection is used, route wire through the connection plate.

2.Pass control wires through the hole provided on the unit (see connection D in Connection Sizes table in Fig. 6).

3.Feed wire through the raceway built into the corner post to the 24-v barrier located on the left side of the control box. See Fig. 9. The raceway provides the UL required clearance between the high-voltage and low-voltage wiring.

4.Connect the thermostat wires to the screw terminals of the low-voltage connector (see Fig. 8A and 8B).

NOTE: If the unit is mounted on a roof curb and electrical power will be run up “thru-the-bottom,” use accessory kit number CRBTMPWR002A01. This kit, available from your local distributor, ensures a watertight seal. Refer to the accessory installation instructions for information on power wiring. Refer to Fig. 6 for drilling holes in basepan.

COOL STAGE 1

Y1/W2

R

 

FAN

G

G

 

HEAT STAGE 1

W/W1

Y1

WIRE

 

 

 

 

CONNECTIONS

COOL STAGE 2

Y/Y2

Y2

TO

 

 

 

 

LOW-VOLTAGE

HEAT STAGE 2

O/W2

W1

SECTION

 

 

 

 

(CONNECTION

24 VAC HOT

R

W2

BOARD)

24 VAC COM

C

C

 

IPD/X

 

N/A

 

 

 

 

 

 

 

 

OUTDOOR AIR

S1

 

 

SENSOR

S2

 

 

THERMOSTAT DIPSWITCH SETTINGS

 

 

ON

 

 

 

OFF

A B

C D

 

 

 

 

 

LEGEND

Field Wiring

NOTE: Underlined letter indicates active thermostat output when configured for A/C operation.

Fig. 8A — Low-Voltage Connections With or Without Economizer or Two-Position Damper

DEFROST BOARD — The defrost board timer cycle is set to 30 minutes. To change the cycle time, turn off power to the unit and install lockout tag. Remove the wire from defrost board connected to the 30 minute quick-connect. See Fig. 10. Connect the wire to the 50 or 90 minute quick-connects on the defrost board, depending on the desired defrost time.

HEAT ANTICIPATOR SETTINGS — For units with electric heat, set heat anticipator settings as shown in Table 4.

Step 6 — Adjust Factory-Installed Options

DISCONNECT SWITCH — The optional disconnect switch is non-fused. The switch can be locked in place for safety purposes.

 

CONTROL

THERMOSTAT CONTROL

CONNECTION

CONNECTION

 

BOARD

 

BOARD

R

24 VAC

R

R

G

RMTOCC

Y1

Y1

 

CMPSAFE

Y2

Y2

Y2

FSD

W1

W1

W1

SFS

W2

W2

 

NOT USED

G

G

C

C

C

C

X

X

X

 

Fig. 8B — Low Voltage Connections

(Units with PremierLink™ Controls)

DISCONNECT

BOARD

DISCONNECT SWITCH (OPTIONAL)

RACEWAY

COMPRESSOR

NO. 2

CONVENIENCE

OUTLET

HOLE IN

END

PANEL

COMPRESSOR NO. 1

Fig. 9 — Typical Field Control Wiring Raceway

12

Table 4 — Heat Anticipator Settings

 

 

 

 

 

 

UNIT VOLTAGE

 

 

 

 

 

 

 

208/230

 

 

460

 

 

 

575

 

 

UNIT

Heater

Configuration

Heater

Configuration

Heater

Configuration

 

 

2-Stage

 

2-Stage

 

2-Stage

 

kW*

1-Stage

kW*

1-Stage

kW*

1-Stage

 

Stage 1

Stage 2

Stage 1

Stage 2

Stage 1

Stage 2

 

10.4, 16.0

0.3

NA

NA

13.9, 16.5

0.3

NA

NA

17.0, 34.0

0.3

NA

NA

50TFQ

24.8, 32.0

0.6

0.3

0.3

27.8, 33.0

 

 

 

 

 

 

 

 

42.4, 50.0

0.9

0.6

0.3

41.7, 50.0

0.6

0.3

0.3

51.0

0.6

0.3

0.3

*kW is based on 240, 480, or 575 v.

CONVENIENCE OUTLET — An optional convenience outlet provides power for rooftop use. For maintenance personnel safety, the convenience outlet power is off when the unit disconnect is off. Adjacent unit outlets may be used for service tools. An optional “Hot Outlet” is available from the factory as a special order item.

NOVAR CONTROLS — Optional Novar controls (ETM 3051) are available for replacement or new construction jobs.

MANUAL OUTDOOR-AIR DAMPER — The outdoor-air hood and screen are attached to the basepan at the bottom of the unit (for shipping).

Assembly:

1.Determine the amount of ventilation required for building. Record the amount for use in Step 8.

2.Remove the filter access panel by raising the panel and swinging it outward. The panel is now disengaged from the track and can be removed. No tools are required to remove the filter access panel. Remove the outdoor-air opening panel. Save the panels and screws. See Fig. 11.

3.Separate the hood and screen from the basepan by removing the screws and brackets securing them. Save all screws and discard the brackets.

4.Replace the outdoor air opening panel.

5.Place the hood on the front of the outdoor air opening panel. See Fig. 12 for hood details. Secure the top of the hood with the 6 screws removed in Step 3. See Fig. 13.

6.Remove and save the 8 screws (4 on each side) from the sides of the manual outdoor-air damper.

7.Align the screw holes on the hood with the screw holes on the side of the manual outdoor-air damper. See Fig. 12 and 13. Secure the hood with the 8 screws from Step 6.

8.Adjust the minimum position setting of the damper blade by adjusting the manual outdoor-air adjustment screws on the front of the damper blade. See Fig. 11. Slide the blade vertically until it is in the appropriate position determined by Fig. 14. Tighten the screws.

9.Remove and save the screws currently on the sides of hood. Insert the screen. Secure the screen to the hood using the screws. See Fig. 13.

10.Replace the filter access panel. Ensure that the filter access panel slides along the tracks and is securely engaged.

Fig. 10 — Defrost Board

FILTER

ACCESS

PANEL

OUTDOOR AIR

OPENING

PANEL

SCREWS (SIDE)

MANUAL OUTDOOR-AIR ADJUSTMENT

SCREWS DAMPER BLADE

Fig. 11 — Damper Panel with Manual

Outdoor-Air Damper Installed

13

Fig. 12 — Outdoor-Air Hood Details

SCREW HOLES (TOP)

HOOD

HOOD SCREEN LOCATION (SCREEN NOT SHOWN)

Fig. 13 — Optional Manual Outdoor-Air

Damper with Hood Attached

Fig. 14 — Outdoor Air Damper Position Setting

PREMIERLINK™ CONTROL — The PremierLink controller is compatible with Carrier Comfort Network® (CCN) devices. This control is designed to allow users the access and ability to change factory-defined settings, thus expanding the function of the standard unit control board. Carrier’s diagnostic standard tier display tools such as Navigator™ module or Scrolling Marquee can be used with the PremierLink controller.

The PremierLink controller (see Fig. 15A and 15B) requires a Carrier electronic thermostat or a CCN connection for time broadcast to initiate its internal timeclock. This is necessary for broadcast of time of day functions (occupied/unoccupied). Refer to Fig. 16. The PremierLink control may be mounted in the control panel or an area below the control panel.

NOTE: PremierLink versions 1.3 and later are shipped in Sensor mode. If used with a thermostat, the PremierLink control must be configured to Thermostat mode.

The PremierLink control includes a supply-air temperature sensor (SAT) and an outdoor-air temperature sensor (OAT) as standard. An indoor-air quality (CO2) sensor can be added as an option. Refer to Table 5 for sensor usage.

Install the Supply Air Temperature (SAT) Sensor — When the unit is supplied with a factory-mounted PremierLink control, the supply-air temperature (SAT) sensor (33ZCSENSAT) is factory-supplied and wired. The wiring is routed from the PremierLink control over the control box, through a grommet, into the fan section, down along the back side of the fan, and along the fan deck over to the supply-air opening.

The SAT probe is wire-tied to the supply-air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re-position the sensor for installation. Re-position the sensor in the flange of the supply-air opening or in the supply air duct (as required by local codes). Drill or punch a 1/2-in. hole in the flange or duct. Use two fieldsupplied, self-drilling screws to secure the sensor probe in a horizontal orientation.

NOTE: The sensor must be mounted in the discharge airstream downstream of the cooling coil and any heating devices. Be sure that the probe tip does not come in contact with any of the unit or heat surfaces.

Outdoor Air Temperature (OAT) Sensor — When the unit is supplied with a factory-mounted PremierLink control, the outdoor-air temperature (OAT) sensor is factory-supplied and wired.

Install the Indoor Air Quality (CO2) Sensor — Mount the optional indoor air quality (CO2) sensor according to manufacturer specifications.

A separate field-supplied transformer must be used to power the CO2 sensor.

Wire the CO2 sensor to the COM and IAQI terminals of J5 on the PremierLink controller. Refer to the PremierLink Installation, Start-up, and Configuration Instructions for detailed wiring and configuration information.

14

Table 5 — PremierLink™ Sensor Usage

APPLICATION

OUTDOOR AIR

RETURN AIR

OUTDOOR AIR

RETURN AIR

TEMPERATURE SENSOR

TEMPERATURE SENSOR

ENTHALPY SENSOR

ENTHALPY SENSOR

 

Dry Bulb

 

 

 

 

Temperature with

 

 

 

 

PremierLink™*

Included —

(PremierLink

HH79NZ017

 

 

 

requires 4-20 mA

 

 

 

 

Actuator)

 

 

 

 

Differential Dry Bulb

 

 

 

 

Temperature with

 

Required —

 

 

PremierLink*

Included —

 

 

33ZCT55SPT

(PremierLink

HH79NZ017

or Equivalent

 

 

requires 4-20 mA

 

 

 

 

 

 

 

Actuator)

 

 

 

 

Single Enthalpy with

 

 

 

 

PremierLink*

Included —

 

Required —

 

(PremierLink

Not Used

HH57AC077

requires 4-20 mA

 

 

 

 

 

 

Actuator)

 

 

 

 

Differential Enthalpy

 

 

 

 

with PremierLink*

Included —

 

Required —

Required —

(PremierLink

Not Used

HH57AC077

HH57AC078

requires 4-20 mA

 

 

 

 

 

Actuator)

 

 

 

 

*PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT and

Outdoor Air Temperature Sensor HH79NZ017 — Included with factory-installed PremierLink control; field-supplied and field-installed with field-installed PremierLink control.

NOTES:

1.CO2 Sensors (Optional):

33ZCSENCO2 — Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.

33ZCASPCO2 — Aspirator box used for duct-mounted CO2 room sensor. 33ZCT55CO2 — Space temperature and CO2 room sensor with override. 33ZCT56CO2 — Space temperature and CO2 room sensor with override and set point.

2.All units include the following Standard Sensors:

Outdoor-Air Sensor — 50HJ540569 — Opens at 67 F, closes at 52 F, not adjustable.

Mixed-Air Sensor — HH97AZ001 — (PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT and Outdoor Air Temperature Sensor HH79NZ017)

Compressor Lockout Sensor — 50HJ540570 — Opens at 35 F, closes at 50 F.

Fig. 15A — PremierLink Controller

15

PREMIERLINK

CONTROL

HINGED

DOOR

PANEL

PREMIERLINK

COVER

Fig. 15B — PremierLink™ Controller (Installed)

 

 

 

 

BLK

 

 

VIO

 

 

 

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

HK50AA039

 

 

 

 

TB - 2

 

 

 

 

 

 

PNK

7

7

PNK

SAT

 

BLU

ANAL

J6

 

 

 

 

 

BLK

 

 

 

 

 

 

 

 

 

1

BLU

BRN

OG

 

 

 

PremierLink

VIO

 

 

VIO

 

 

 

ORN

 

 

 

6

6

 

2

 

PNK

 

 

 

 

OAT

 

 

 

 

BRN

BRN

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

11

11

 

Space Temp./ Set

3

 

RED

-

 

 

 

 

 

 

 

BLK

mA20

J5

 

 

 

 

 

 

 

 

Point Adjustment

BRN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

10

 

 

4

BRN

BLU

IN

 

 

 

 

 

YEL

 

 

 

 

GRN

 

 

 

 

 

 

8

8

 

 

 

 

 

 

 

 

 

 

 

 

 

5

RED

 

 

 

 

 

 

 

BLU

 

 

 

 

YEL

 

 

 

 

 

 

3

3

 

Indoor Air

 

 

WHT

DISCRETE

J4

 

 

 

 

 

2

2

 

6

 

BLU

 

 

 

 

 

 

 

 

 

 

Quality Sensor

BRN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLK

4

4

 

Outdoor Air

7

BLU

PNK

 

 

 

 

J9

J7

 

 

 

 

GRA

 

 

J2

 

 

 

 

 

Quality Sensor

8

ORN

J1

 

 

0-20 mA

PP/MP

RED

1

1

 

Power Exhaust/Energy Recycler

GRA

PWR COMMS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLU

5

5

GRA

 

TB - 3

 

 

 

 

 

 

 

 

 

 

 

 

PNK

 

 

 

 

 

 

 

 

 

 

 

 

BRN

 

 

 

WHT GRA

YEL

 

 

ORN

 

 

 

 

 

 

 

9

9

RMTOCC

1

GRN

 

 

 

 

 

 

 

 

 

GRA

BLK

 

RED

TB - 1

 

WHT

 

 

 

 

 

 

 

 

 

12

12

PNK

 

2

 

 

 

 

 

 

YEL

 

 

 

 

1

R

 

 

 

CMPSAFE

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

 

TR

 

TR1

FSD

3

BLU

 

 

 

 

2

Y1

GRA

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

SFS

4

WHT

 

 

 

 

Y2

 

 

 

 

+

 

 

 

 

 

ORN

 

SR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

2

 

3

 

PNK

 

 

 

 

4

W1

ORN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

GRAY

RED

 

 

 

 

5

W2

 

 

 

 

 

 

 

 

 

 

PNK

 

OUTDOOR AIR

GRAY

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

6

 

 

 

ENTHALPY SENSOR

CCN

WHT

 

 

 

 

G

 

 

 

 

 

Comm.

 

 

 

 

 

 

 

WHT

 

 

 

 

BLK

8

BLK

 

 

 

 

7

C

 

 

Economi$er2

RED

 

 

 

BRN

 

 

 

4 - 20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

8

X

 

+

 

 

 

S

COMMS — Communications

 

 

 

 

RTU Terminal

RETURN AIR

OAT

Outdoor Air Temperature Sensor

 

Board

ENTHALPY

 

PWR

Power

 

 

SENSOR

 

 

 

RED

 

SAT

Supply Air Temperature Sensor

 

 

BRN

 

 

 

 

 

Fig. 16 — Typical PremierLink Controls Wiring

16

J8

Relays

ORN ORN PNK

ORN

RED

Enthalpy Sensors and Control — The enthalpy control (HH57AC077) is supplied as a field-installed accessory to be used with the economizer damper control option. The outdoor air enthalpy sensor is part of the enthalpy control. The separate field-installed accessory return air enthalpy sensor (HH57AC078) is required for differential enthalpy control.

NOTE: The enthalpy control must be set to the “D” setting for differential enthalpy control to work properly.

The enthalpy control receives the indoor and return enthalpy from the outdoor and return air enthalpy sensors and provides a dry contact switch input to the PremierLink™ controller. Locate the controller in place of an existing economizer controller or near the actuator. The mounting plate may not be needed if existing bracket is used.

A closed contact indicates that outside air is preferred to the return air. An open contact indicates that the economizer should remain at minimum position.

Outdoor Air Enthalpy Sensor/Enthalpy Controller (HH57AC077) — To wire the outdoor air enthalpy sensor, perform the following (see Fig. 17 and 18):

NOTE: The outdoor air sensor can be removed from the back of the enthalpy controller and mounted remotely.

1.Use a 4-conductor, 18 or 20 AWG cable to connect the enthalpy control to the PremierLink controller and power transformer.

2.Connect the following 4 wires from the wire harness located in rooftop unit to the enthalpy controller:

a.Connect the BRN wire to the 24 vac terminal (TR1) on enthalpy control and to pin 1 on 12-pin harness.

b.Connect the RED wire to the 24 vac GND terminal (TR) on enthalpy sensor and to pin 4 on 12-pin harness.

c.Connect the GRAY/ORN wire to J4-2 on PremierLink controller and to terminal (3) on enthalpy sensor.

d.Connect the GRAY/RED wire to J4-1 on PremierLink controller and to terminal (2) on enthalpy sensor.

NOTE: If installing in a Carrier rooftop, use the two gray wires provided from the control section to the economizer to connect PremierLink controller to terminals 2 and 3 on enthalpy sensor.

If NOT using Carrier equipment, wires may need to be field supplied and installed.

Return Air Enthalpy Sensor — Mount the return-air enthalpy sensor (HH57AC078) in the return-air duct. The return air sensor is wired to the enthalpy controller (HH57AC077). The outdoor enthalpy changeover set point is set at the controller.

To wire the return air enthalpy sensor, perform the following (see Fig. 17):

1.Use a 2-conductor, 18 or 20 AWG, twisted pair cable to connect the return air enthalpy sensor to the enthalpy controller.

2.At the enthalpy control remove the factory-installed resistor from the (SR) and (+) terminals.

3.Connect the field-supplied RED wire to (+) spade connector on the return air enthalpy sensor and the (SR+) terminal on the enthalpy controller. Connect the BLK wire to (S) spade connector on the return air enthalpy sensor and the (SR) terminal on the enthalpy controller.

ENTHALPY CONTROLLER

RED

 

 

 

 

 

S (OUTDOOR

 

 

 

 

 

 

 

 

 

+

AIR

 

 

 

 

BRN

 

 

 

 

 

A B C

TR

TR1

 

 

BLK

 

 

ENTHALPY

 

 

 

 

 

 

SENSOR)

 

 

 

 

 

 

 

 

 

 

D

SO

+

 

 

 

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

SR

+

 

 

 

 

 

 

 

S (RETURN AIR

 

 

 

 

 

 

 

 

 

 

+

ENTHALPY

 

2

3

 

 

 

 

 

 

 

 

SENSOR)

 

1

 

 

GRAY/ORN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LED

 

 

 

 

 

 

 

 

WIRE HARNESS

 

 

 

 

GRAY/RED

IN UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

1.Remove factory-installed jumper across SR and + before connecting wires from return air sensor.

2.Switches shown in high outdoor air enthalpy state. Terminals 2 and 3 close on low outdoor air enthalpy relative to indoor air enthalpy.

3.Remove sensor mounted on back of control and locate in outdoor airstream.

Fig. 17 — Outdoor and Return Air Sensor Wiring Connections for Differential Enthalpy Control

HH57AC077

ENTHALPY

CONTROL AND

BRACKET OUTDOOR AIR

ENTHALPY

SENSOR

HH57AC078 ENTHALPY

 

SENSOR (USED WITH

 

ENTHALPY CONTROL

C7400A1004

FOR DIFFERENTIAL

ENTHALPY OPERATION)

+

MOUNTING PLATE

Fig. 18 — Differential Enthalpy Control, Sensor and Mounting Plate (33AMKITENT006)

17

Loading...
+ 39 hidden pages