Carrier 58DR User Manual

4 (1)
Carrier 58DR User Manual

HEATING« COOLING

58DP,DR Downflow Gas-Fired Natural-Draft Furnaces

58DP Series 150 and 160

58DR Series 130

Installation, Start-Up and Service Instructions

NOTE: Read the entire instructions before starting the installation.

INTRODUCTION

Before installing the furnace, refer to “Procedures for Natural-Draft Gas-Fired Furnaces” (packaged with the equipment) for information concerning combustion, venting, piping, and other standeird installation practices. Further reference is made to the current edition of the National Fuel Gas Code NFPA No. 54-1988/ANSI Z223.1-1988.

Reference should also be made to the regulations of the serving gas supplier and the local building, heating, plumb­ ing, or other codes in effect in the area in which the installa­ tion is made.

SAFETY CONSIDERATIONS

Installation and servicing of heating equipment can be haz­ ardous due to gas and electrical components. Only trained and qualified personnel should install, repair, or service heating equipment.

Untrained personnel can perform basic meuntenance func­ tions such as cleaning and replacing air filters. AU other operations must be performed by trained service personnel, when working on heating equipment, observe precautions in the literature, tags, and labels attached to or shipped with the unit and other safety precautions that may apply.

Follow all safety codes, including NFPA No. 54/ANSI Z223.1-1988, National Fuel Gas Code. Wear safety glasses and work gloves. Have fire extinguisher available during startup and adjustment procedures and service call.

Recomized safety information: This is the safety-alert sym­ bol A. When you see this symbol on the furnace and in instructions or manueils, be alert to the potential for per­ sonal injury.

Understand the signal word—DANGER, WARNING, or CAUTION. These words are used with the safety-alert sym­ bol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING on the other hand could result in personal injury or death. CAUTION is used to identify unsafe practices, which would result in minor personal injury or product and property damage.

Each furnace is shipped from the factory completely assem­ bled with multispeed direct-drive blower and wired ready for downflow indoor heating installation only. AU sizes feature a printed-circuit board control center with easy-to-read, 24volt terminal strip to ensure proper connections.

Fig. 1—Model 58DP

Table 1—Clearances (In Inches) (From Combustible Materials)

Sizes

050

075 thru 150

Sides—Single-Wall Vent

1

1

Type-B Double-Wall Vent

0

1

Back

0

0

Top of Plenum

1

1

Vent Connector—Single-Wall

6

6

Type-B Double-Wall

1

1

Front—Combustion Air*

6

6

Service

30

30

*The 6-inch front clearance is needed for combustion-air entry and drafthood relief.

»■NOTE: The furnaces covered by these instructions are design-certified for use with the vent damper specified on the furnace rating plate. See instructions packaged with the vent deunper for its installation.

A CAUTION

Application of this furnace should be indoors with spe­ cial attention given to vent sizing and material, gas input rate, air temperature rise, and unit sizing. Improper installation or misapplication of the furnace can require excessive servicing or cause premature com­ ponent failure.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

'' I ^

PC 101 Catalog No. 565-873

Printed in U.S.A. Form 58DP,DR-4Si 5/89 Pg 1

Replaces: 58DP,DR-2SI

Tab I6al8a

 

 

 

8 THERMOSTAT CONN

/

Table 2—Dimensions (In Inches)

 

 

 

Size

A

D

E

Vent

 

 

 

050-BA

14^6

12"/,e

12”/,6

4

 

 

 

075-AA

17^2

15^

16

4

 

5.

^

075-BA

M'k

15%

16

4

1

100-AA

M'b

15%

16

5

 

— -?>•

r'

100-BA

17Ya

15%

16

5

O:A

125-AA

21

19%

19Ya

5

 

 

KNOCKOUT

 

 

 

 

 

 

 

AUX GAS

125-BA

21

19%

19%

5

 

 

INLET

 

 

 

150-BA

2A'k

22%e

23

6

AIRFLOW

A78595

Fig. 2—Dimensional Drawing

Table 3—Ratings and Performance

 

input

Capacity

Temp

Heating

 

Cooling

 

Motor

Approx

Size

Rise

Ext Static

 

 

Ext Static

 

 

HP&

Shipping

Btuh*

Btuht*

Range

Pressure

 

CFM

Pressure

 

CFM

Type

Weight

050-BA

50,000

39,000t

45—75

0.50

 

600

0.5

 

800

73-SP

129

075-AA

75,000

58,000

70—100

0.12

 

630

 

%0-SP

148

075-BA

 

 

45—75

0.50

 

895

0.5

 

1255

%-SP

157

100-AA

100,000

78,000t

70—100

0.20

 

850

 

Vs-SP

163

100-BA

 

 

60—90

0.50

 

960

0.5

 

1630

%-PSC

170

125-AA

125,000

97,000t

70—100

0.20

 

1050

 

%-SP

187

125-AA

 

 

60—90

0.50

 

1195

0.5

 

1620

%-PSC

187

150-BA

150,000

116,000t

55—85 ,

0.50

 

1535

0.5

 

2075

Ya-PSC

227

*The above gas input ratings are certified for eievations to 2000 ft. For elevations above 2000 ft, reduce input 4% for each 1000 ft above sea ievei. tDetermined by U.S. Government tests.

tDeduct 1000 Btuh for Modei58DR.

, '

;

A73382

Fig. 3—Floor Opening for

Concrete Slab

Table 4—Opening Dimensions

Furnace Casing

A

 

B

Width

 

Heat-Only

 

Heat/Cool*

14%s

13%

19=/s

 

197,6

17%

167,6

19%

 

. 197,6

21

19%

19%

 

197,6

24%

237,6

19%

 

197,6

♦These dimensions appiy when a Model 28RC or RD Evaporator Coil cas­ ing is to be installed.

This furnace is designed for a minimum continuous return air temperature of 60 degrees F DB or an intermittent oper­ ation down to 55 degrees F DB such as when used with a thermostat night setback. Return air temperature must not exceed a maximum of 85 degrees F DB.

A WARNING

Improper histaUation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poison­ ing, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, local gas supplier or your Distributor or Branch for information or assistance. The qualified installer or agency must use only factory authorized and listed kits or accessories when modifying this product. A failure to adhere to this warning can cause electrical shock, fire, personal injury, or death.

FURNACE

■PLENUM

A73383

Fig. 4—Furnace on a Concrete Siab

WA

Fig. 5—Furnace, Plenum, and

Base Installed on a Combustible Floor

A CAUTION

Do not insteill furnace in a damp, corrosive, or contami­ nated atmosphere. Make sure all combustion and circu­ lating air requirements listed in “Procedures for Natured-Draft Gas-Fired Furnaces” are adhered to, in addition to all local codes and ordinances.

Do not use this furnace during construction when adhe­ sives, sealers and/or new carpets are being installed. If the furnace is required during construction, use clean outside air for combustion and ventilation. Compounds of chlorine and fluorine when burned with combustion air form acids which wiU cause corrosion of the heat exchangers and metal vent system. Some of these com­ pounds are paneling and dry wall adhesives, paints, thinners, masonry cleaning materials, and many other solvents commonly used in the construction process.

The design of the downflow gas-fired furnace is A.G.A. cer­ tified for installation on noncombustible flooring. The fur­ nace may be installed on combustible flooring when installed with the accessory downflow subbase. This furnace is for installation in alcoves, basements, closets, or utility rooms. This furnace fine is not A.G.A. design certified for installation in a mobile home, recreation vehicle, or outdoors.

Installation comprises the following:

*1. Inspection

*11. Location, Ventilation, and Air for Combustion *III. Gas Piping

*IV. Venting

V. Supply-Air Plenum Installation

VI. Electrical

VII. Sequence of Operation

VIII. Füter

IX. Startup and Adjustment

X. Care and Maintenance

*To perform these sections (or installation steps), refer to the appropriate sections of “Procedures for Natural-Draft Gas-Fired Furnaces” booklet packaged with this unit.

For accessory installation details, refer to the applicable installation hterature. Terminals EAC-1 and EAC-2 in the control box are for direct connection of an electronic air cleaner.

V.SUPPLY-AIR PLENUM INSTALLATION

A.Installation on a concrete slab

1.See Fig. 2 for dimensions and location of supply-air opening in furnace bottom.

2.Construct hole in floor per dimensions in Fig. 3 and Table 4.

3.Place plenum and furnace as shown in Fig. 4.

Fig. 6—Amp Draw Check With Ammeter

A79077

Fig. 7—PrInted-CIrcult Control Center

- FIELD24-VOLTWIRlNC

TRAN

FUSED DISCONNECT ILK SWITCH

SW ITCH (WHEN REQ'D)

CAP

(WHEN USED)

 

 

TO THERMOSTAT

YEL

 

LOD-

BREAKAWAY TAB REMOVED WHEN CONNECTING VENT DAMPER (SEE INSTALLATION INSTRUCT IONS)CWHEN-

USED)

 

 

 

NOTES:

m DOWNFLOW FURNACES ONLY

I.I----rz—I HEATING FAN RELAY CONTACT IS

•-rkF* NORMALLY CLOSED UNTIL 115V AC IS HFR APPLIED TO FURNACE.

2. TO CHANGE MOTOR SPEED, MOVE RED WIRE TO DESIRED SPEED SETTING.

3.IF ANY OF ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH AWM C105°C) WIRE OR ITS

EQUIVALENT.

ELECTRONIC

4. MOTOR IS THERMALLY OVERLOAD PROTECTED.

5. FACTORY SPEED SELECTION IS FOR AVERAGE

AIR CLEANER

CONDITIONS, SEE INSTALLATION INSTRUCTIONS

(WHEN USED)

FOR OPTIMUM SPEED SELECTION. MOTOR MAY

EAC-2

BE 3 OR 4 SPEED.

 

6. SYMBOLS ARE ELECT. REPRESENTATION ONLY.

 

7. FACTORY CONNECTED WHEN ACCESSORY NOT USED.

 

LEGEND

 

 

ALS

AUXILIARY LIMIT SWITCH, MANUAL-RESET

 

CAP

C5PST-NC)

 

RUN CAPACITOR

 

CFR

COOLING FAN RELAY CDPDT

 

FL

FUSIBLE LINK

 

FU2

FIELD FUSE

 

GV

GAS VALVE

 

HFR

HEATING FAN RELAY CSPST-NC)

 

ILK

SWITCH, BLOW. DOOR INTERLOCK CSPST-NO)

 

LOD

LOCKOUt TIMER DEVICE CSPST-NO)

 

LS

LIMIT SWITCH, AUTO.-RESET CSPST-NC)

 

MTR

MOTOR, BLOWER

 

PCB

PRINTED CIRCUIT BOARD

 

PI

PILOT IGNITER

 

SP

SAFETY PILOT (FLAME SENSING)

 

TRAN

TRANSFORMER

 

VSS5

VENT SAFETY SHUTOFF SWITCH, MANUAL-

 

 

RESET CSPST-NC)

 

 

FIELD SPLICE

 

 

PLUG RECEPTACLE

 

O

JUNCTION

 

UNMARKED TERMINAL

 

 

TERMINAL PCB FACTORY CONN.

 

 

FACTORY WIRING. C120V AC)

 

 

FACTORY WIRING CLOW VOLTAGE)

 

 

FIELD WIRING C120V AC)

 

 

FIELD WIRING C24V AC)

 

0

CONDUCTOR ON PRINTED CIRCUIT BOARD

 

SCREW TERMINAL FOR FIELD WIRING

 

 

FIELD GROUND

314296-401 REV. A

/ f y

EQUIP. GROUND

Fig. 9—Wiring Diagram (IID Pilot)

A89168

 

Loading...
+ 8 hidden pages