Jrt<twnna y>' |
^ |
Numb^One |
|
Maker |
installation, Start-llp |
AirConditbning |
|
and Service instructior^
eDivision of
Carrier Cotporalio
Carrier Parkway • Syracuse NY 13221
|
Page |
SAFETY CONSIDERATIONS ......................... |
1 |
INSTALLATION................................................. |
, 1-4 |
Step 1 — Check Equipment and Jobsite |
. 1 |
•UNPACKAGE UNITS
•INSPECT EQUIPMENT
•COMPLETE OR CONSIDER SYSTEM REQUIREMENTS
Step 2 — Mount Heat Pump Package ..
•ON THE GROUND: MOUNT HEAT PUMP ON AN ELEVATED FRAME POSITIONED ON A LEVEL CON CRETE PAD
•ON THE ROOF: MOUNT UNIT ON A LEVEL PLATFORM OR FRAME
Step 3 — Make Ductwork Connections
•CONNECT SUPPLY AND RETURN AIR DUCTWORK
INDEX
Step 4 — Provide for Cooling Cycle Condensate Disposal for Cooling Cycle ... 4
• CONNECT DRAIN LINE
^Step 5 — Make Electrical Connections... 4
•INSTALL A BRANCH CIRCUIT DISCONNECT PER NEC
•ROUTE LINE POWER WIRES INTO UNIT
•CONNECT GROUND LEAD TO GROUND LUG IN SPLICE BOX FOR SAFETY
•SET INDOOR FAN MOTOR SPEED
•ROUTE CONTROL POWER WIRES
•ELECTRIC HEATER INSTALLATION
START-UP............................................................. |
5-7 |
SERVICE ............................................................. |
7-14 |
V TROUBLESHOOTING.................................. |
15, 16 |
^SAFETY CONSIDERATIONS
Installation and servicing of air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and quali fied service personnel should install, repair or service air conditioning equipment.
Untrained personnel can perform basic main tenance functions of cleaning coils and filters and replacing filters. All other operations should be per formed by trained service personnel. When working on air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing oper ations. Have fire extinguisher available for all braz ing operations.
INSTALLATION
Step 1 — Check Equipment and Jobsite
UNPACKAGE UNITS — Move units to final loca tion. Slide units from cartons taking special care nob to damage unit.
INSPECT EQUIPMENT — File claim with ship ping company if shipment is damaged or incomplete.
COMPLETE OR CONSIDER SYSTEM RE QUIREMENTS before installing the 50YQ units.
Consult local building codes and National Elec trical Code (NEC) for special installation requirements.
Provide sufficient space for coil airflow clearance, wiring, and servicing unit. (See Fig. 1.) Locate unit where supply and return air ducts can be con veniently brought out to unit duct connections.
Unit may be placed with duct side as close to building as condensate drain, top removal, duct con nections and power connections permit. Position unit so water or ice from roof does not drop directly on top of unit or in front of coil. Make provisions for condensate drainage and defrost water disposal.
Roof installation method for 50YQ depends on building construction and special requirements of local building codes. Ensure that roof can support unit weight. Protect unit from prevailing winds to ensure adequate defrost.
© Carrier Corporation 1979 |
781 |
Form 50YQ-3SI |
0'-6J3^
■g CONDUIT
CONTROL-*“»
WIRING
If DKO
ELECTRIC^
HEAT X
l| DKO
LINE
WIRING'
CONN
L> INDOOR AIRFLOW
^ OUTDOOR AIRFLOW |
RIGHT SIDE VIEW |
Ceitified dimension drawings available on request
Fig. 1 Dimensions and Connections
Table 1 — Installation Data (See Fig. 1)
UNIT |
50YQ024 |
50YQ030 |
OPER WEIGHT (lb) |
303 |
320 |
DTMENSTONS (ft-in ) |
|
|
A |
|
|
B |
|
|
|
|
|
C' |
1-11-5/8 |
1-11-5/8 |
DUCT CONN (ft-in ) |
|
|
D |
1- 7-3/4 |
1- 7-3/4 |
FILTER SIZEt (in.) |
|
|
|
|
|
Disposable |
20x25 |
15x20 (2) |
Permanent |
15x20 |
20x20 |
|
|
|
‘Dimension "C" includes 1-in built-in base support |
channels |
|
fRecommended field-supplied filters are 1-in thick |
|
Step 2 — Mount Heat Pump Package
ON THE GROUND; MOUNT HEAT PUMP ON AN ELEVATED FRAME POSITIONED ON A LEVEL CONCRETE PAD See Pig. 2 for pad dimensions. Ensure pad does not obstruct coil slots in unit basepan. (Slots drain water during heating and defrost cycles. See Fig. 2 for drain slot loca tions.) Construct pad a minimum of 6 in. thick to provide clearance under basepan coil slots for drainage and ice buildup. In areas where prolonged subfreezing temperatures or snowfall occur, increase clearance to 12 to 18 inches by constructing an angle-iron frame to support unit 12 to 18 in. off concrete base. Design cross angle of frame so as to not obstruct basepan coil slots. See Fig. 3 for recom mended frame construction. Alternate construction should follow dimensions. Extend a 24-in. gravel apron around pad for condensate and defrost water drainage field.
ON THE ROOF: MOUNT UNIT ON A LEVEL PLATFORM OR FRAME — Elevate unit for proper clearance as described under ground installa tion above. Design roof and plan water runoff so as to prevent unit and its duct flashing from sitting in water, in accordance with all applicable codes.
|
50YQ036 |
|
50YQ042 |
|
50YQ048 |
|
50YQ060 |
333 |
375 |
417 |
448 |
||||
|
|
4-0-7/16 |
|
|
|
|
|
|
|
3-6-1/4 |
|
2-7-5Z8 |
3-1-5/8 |
||
1-11-5/8 |
2- 3-5/8 |
|
|||||
|
Side-by-Side Rectangular |
|
|
|
|
||
1- 7-3/4 1 1-11-3/4 |
2-3-3/4 |
2-9-3/4 |
|||||
|
15x20 |
|
20x20 (2) |
|
20x25 |
|
25x25 |
|
|
|
|
||||
|
20x20 |
|
|
20x20 |
|
_2.Ûx25 ^ |
|
|
|
|
|
|
|||
|
20x25 |
|
20x25 |
|
15x20 (2) |
|
20x20 (2) |
|
|
|
|
|
|
|
|
Step 3 — Make Ductwork Connections
CONNECT RETURN AND SUPPLY AIR DUCTWORK — Connect ductwork to unit supply and return air duct connections. Refer to Fig. 1 and Table 1 for unit supply and return air connection sizes and locations.
|
NtWfTSaX:OFU1«T |
|
|
«ïTH «JCT coitwecTfONS. |
|
«Nfraasc |
i |
|
y-t ■ |
||
|
||
?ïEAfîsii«e8?a«(T^ |
A / ■ |
|
|
||
UNIT OUTÏ-iN?- |
|
•JEF^SSBE
|
|
WT» Access &msjs |
ooKOT |
fMm |
i««oei%E»soss«E«T> |
|
||
mnotutcPimz |
|
^ |
d47«IS AilES. |
|
|
mres. |
|
«ievSKNf |
t to 3f«as «lowiait <w ssibir«i!iife9 |
|
|
fr««» as(Xi, <S«!«>s.on A «• 4S >o, |
<s 3S sncsse«^ 1« |
|
3r«AS where eievsieci f:e«» is f.oi |
A w A2 |
iHmee&'cm B js 3T xiches
2 AJiow a 3'*t service, ctoarahce at frotrt fear anc feit sioe of unit
Fig. 2 — Concrete Pad Dimensions
|
iz TOS'« |
|
0C |
|
□ «Sy iSJRSS |
<D’= |
|
|
O'i- |
3 |
3}í(J}fiS£0 |
!_ |
re“ fc&5 fíBi |
|
Ajrets íftOfí - li TO f-s COMMt STO { ■POTAL í&6ftMTrTY 2Sf 7035Ÿ >
m.0 FRA«E TO^TtíE».
PAífíT WlTH2l«C-ÍÍ}C» ?*»ÍT(StíSTf«OOP>
Flanges are provided on unit for rectangular duct connections. Figure 4 shows a typical duct system with 50YQ installed. Do not operate unit longer than 5 minutes without ductwork. If necessary, refer to Carrier System Design Manual, Part 2, for sys tem air duct design. When designing and installing ductwork, consider the following:
a. When connecting ductwork to unit, do not drill holes in area shown below. Coil may be damaged.
b.Install field-supplied filters in return air duct
work. Recommended sizes for filters are shown in Table I.
c. Avoid abrupt duct size increases and reductions.
■d. Use flexible connectors between ductwork and unit to prevent transmission of vibration. When electric heater is installed, use fireproof canvas
(or similar heat resistant material) connector be tween ductwork and unit discharge connection. If flexible duct is used, insert a sheetmetal sleeve inside duct. Design this connector or sleeve so that it extends 24 in. from electric heater element.
e.Size ductwork for cooling air quantity (cfm). The minimum air quantity for proper heating/ cooling operation and electric heater operation is 400 cfm per ARI cooling ton as listed below:
UNIT 50YQ |
MIN CFM |
024 |
8 3 3 |
030 |
1 0 0 0 |
036 |
1 1 8 3 |
042 |
1 3 6 6 |
048 |
1 6 3 3 |
060 |
1 9 3 3 |
Heater limit switches may trip at air quantities below those recommended.
Insulate and make weatherproof all external ductwork. Insulate and cover with a vapor barrier all ductwork passing thru unconditioned spaces. Follow latest SMACNA (Sheet Metal and Air Conditioning Contractors National Association) and NESCA (National Environ mental Systems Contractors Association) mini mum installation standards for residential heat ing and air conditioning systems.
g.Secure all ducts to building structure. Weather proof duct openings in wall or roof according to good construction practices.
"Separate disconnect required for electric heater
> Fig. 4 — Typical Installation — 50YQ
Step 4 — Provide for Cooling Cycle Conden sate Disposal — Condensate may be drained directly onto gravel apron or connected by drain line(s) to a dry well. Follow local codes.
CONNECT DRAIN LINE to rubber condensate drain fitting on side of unit (see Fig. 5). Use clamp provided. Install factory-supplied condensate trap (taped to indoor fan compartment for shipment) at end of drain line. If a drain line is not used, connect condensate trap to unit drain fitting as shown in Fig. 5.
CONDENSATE
TRAP (SHIPPING
LOCATION, INSTALL
ON CONDENSATE
DRAIN LINE)
CONDENSATE
DRAIN LINE
¡i DKO LINE POWER
Fig. 5 — Condensate Drain and Trap Details
Step 5 — Make Electrical Connections — In stall field wiring in compliance with local and national fire, safety and electrical codes. Be sure
voltage to unit is within ± 10% of voltage indicated on nameplate. On 3-phase units, check that phases are balanced within 2%. Contact local power company for correction of improper line voltage.
Oisrratton «kf tïiïÿi <M3t 3t |
|
wth exijessm phase |
¡as |
affect waCFaïïty, |
coiaM |
|
See Table 2 for recommended wire and fuse sizes.
INSTALL A BRANCH CIRCUIT DISCONNECT PER NEC of adequate size to handle unit starting current. Provide a separate disconnect for unit and for each accessory electric heater circuit as required. (See electrie heater Installation, Start-Up and Service Instructions.) Locate disconnect(s) within sight of and readily accessible from the unit, per Section 440-14 of National Electrical Code (NEC).
ROUTE LINE POWER LEADS INTO UNIT ^ Extend leads from disconnect per NEC thru hole provided (Fig. 1) into line wiring splice box (Fig. 6). Use copper or copper-clad aluminum wire. (Do not make connections with aluminum wire.)
UNIT |
CONTROL WIRING |
CONTROL WIRING |
CONTROL BOX |
TERMINAL BOX |
CONDUIT, |
Fig. 6 — Unit Control Box
CONNECT GROUND LEAD TO GROUND LUG IN SPLICE BOX FOR SAFETY — Connect power wiring. See Fig. 7. Connect line power leads to yellow and black pigtails on single-phase units; yellow, blue and black pigtails on 3-phase units.
SET INDOOR FAN MOTOR SPEED — Refer to page 3 for minimum allowable air quantity for safe electric heater operation. Three-speed indoor fan motor is factory wired for high-speed operation. Fan motor is equipped with spade-type speed selec tor terminals marked 1, 2 and 3. For electric heater operation, set motor at: “Low” — sizes 024 thru 042; “High” — size 048; “Med” — size 060.
MOTOR TERMINAL |
1 |
2 |
3 |
FAN SPEED |
High |
Medium |
Low |
|
|
|
|
ROUTE CONTROL POWER WIRES (24-v) thru 7/8-in. conduit provided in unit. Fig. 1 and 5. Ex tend leads to unit control wiring terminal board in unit control box. Connect leads to terminal board as directed in Fig. 8.
The 50YQ unit transformer supplies 24-v power for complete system including accessory electric heater.
781
i-r'
tv
Table 2 — Unit Electrical Data (60-Hz)
|
|
|
|
|
|
OPER |
|
COMPRESSOR |
IFM |
|
OFM |
|
|
BRANCH CIRCUIT |
|
|||||
|
|
|
|
|
|
VOLTAGE* |
|
|
|
|
|
|
|
|
|
|
Min Gnd |
|
|
|
|
MODEL |
|
V/PH |
|
|
|
|
|
|
|
|
Min |
Max |
|
Max Fuse |
Min |
||||
|
|
|
|
|
|
|
|
|
|
|
|
Wire |
|
Wire |
or HACR |
|||||
|
|
|
|
|
LRA |
|
RLA |
BCSC |
FLA |
|
FLA |
Ft |
|
Circuit |
||||||
|
|
|
|
|
|
Max |
Min |
|
|
Size |
|
Size |
Type Ckt»* |
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
Wire |
|
Amps |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(AWG)t |
|
(AWG)t |
Bkr Amps |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
50YQ024 |
|
|
|
|
66 |
|
154 |
— |
2 4 |
|
1 3 |
10 |
48 |
|
}— -1 |
35 |
23 0 |
||
|
|
|
|
|
|
|
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
50YQ030 |
|
|
|
|
72 |
|
16 1 |
— |
24 |
|
1 3 |
10 |
46 |
|
10 |
35 |
23 8 |
||
|
^ 50YQ036 |
230/1 |
|
253 |
207 |
88 |
|
18 2 |
— |
3 6 |
|
2 1 |
10 |
38 |
|
10 |
45 |
28 5 |
||
|
50YQ042 |
|
|
|
|
94 |
|
21.0 |
21 2 |
49 |
|
1 9 |
8 |
52 |
|
10 |
50 |
33 3 |
||
|
50YQ048 |
|
|
|
|
106 |
|
25 0 |
27 9 |
49 |
|
2 2 |
6 |
71 |
|
10 |
60 |
42 0 |
||
|
50YQ060 |
208/230/1 |
|
253 |
187tt |
150 |
|
29 2/33 4 |
35 3 |
6 4 |
|
20 |
4 |
43 |
|
6 |
60 |
52 5 |
||
|
50YQ042 |
200/3 |
|
220 |
180 |
79 |
|
146 |
16 6 |
49 |
|
20 |
10 |
55 |
|
10 |
40 |
27 6 |
||
|
50YQ048 |
|
87 |
|
16 9 |
183 |
49 |
|
2 2 |
10 |
48 |
|
10 |
45 |
30 0 |
|||||
|
|
|
|
|
|
|
|
|||||||||||||
|
50YQ036 |
200/230/3 |
|
253 |
180 |
87 |
|
12 5/11 7 |
— |
3 6 |
|
2 1 |
10 |
74 |
|
10 |
30 |
21.3/25 3 |
||
|
50YQ042 |
230/3 |
|
253 |
207 |
GT~ |
|
U6 |
143 |
49” |
|
i¥~ |
|
67 |
|
id |
|
24 7 |
||
|
50YQ048 |
|
70 |
|
14 8 |
16 4 |
4 9 |
|
2 2 |
10 |
58 |
|
10 |
40 |
27 6 |
|||||
|
|
|
|
|
|
|
|
|||||||||||||
|
50YQ042 |
460/3 |
|
506 |
414 |
35 |
|
g 3 |
|
49 |
|
1 9 ‘ |
14 |
104 |
|
14 |
15 |
12 4 |
||
|
|
|
|
|
|
|
||||||||||||||
|
50YQ048 |
|
35 |
|
7.5 |
8 8 |
4 9 |
|
2 2 |
14 |
90 |
|
12 |
20 |
14 6 |
|||||
|
|
|
|
|
|
|
|
|||||||||||||
|
50YQ042 |
575/3 |
|
632 |
518 |
27 |
|
49 |
6 8 |
49 |
|
1 9 |
14 |
164 |
|
14 |
15 |
11 2 |
||
|
50YQ048 |
|
30 |
|
60 |
64 |
49 |
|
2 2 |
14 |
141 |
|
14 |
15 |
10 9 |
|||||
|
|
|
|
|
|
|
|
|||||||||||||
|
AWG |
|
|
American Wire Gage |
|
|
|
|
^Permissible limits of the voltage range at which units will operate |
|||||||||||
|
BCSC |
|
Branch Circuit Selection Current |
|
|
|
satisfactorily |
|
|
|
|
|
|
|
||||||
|
FLA |
|
Full Load Amps |
|
|
|
|
|
tCopper wire sizes based on 60 C Use copper or copper-clad aluminum wire |
|||||||||||
|
IFM |
|
Indoor Fan Motor |
|
|
|
|
|
only Use latest NEC for copper-clad aluminum conductor sizing |
|
||||||||||
|
LRA |
|
Locked Rotor Amps |
|
|
|
|
^Required when using nonmetallic conduit |
|
|
||||||||||
|
OFM |
|
Outdoor Fan Motor |
|
|
|
|
|
“Maximum dual element fuse |
|
|
|
|
|
||||||
|
RLA |
|
Rated Load Amps |
|
|
|
|
|
ttMinimum voltage is 197 when outdoor ambient temperature exceeds |
|||||||||||
|
HACR — Heating Air Conditioning & Refrigeration |
|
|
105 F |
|
|
|
|
|
|
|
ELECTRIC HEATER INSTALLATION — For complete heater installation data, refer to accessory electric heater Installation, Start-Up and Service Instructions.
|
|
|
GROUND LUG |
|
|
|
|
|
(IN SPLICE BOX) |
|
|
|
|
|
|
|
|
|
|
--GROUND LEAD- |
|
|
|
l-PHASE |
|
________________ |
|
|
|
CONN |
Ll |
BLK----------- |
( |
||
TO |
|
|
|
|
|
DISCONNECT |
|
________________ |
|
|
|
PER NEC |
L2 |
-YEL---------- |
i |
||
|
|
|
50YQ HEAT PUMP |
||
|
|
|
GROUND LUG |
|
|
|
|
|
(IN SPLICE BOX) |
|
|
|
|
------ GROUND LEAD- |
|
|
|
3-PHASE |
LI---------------------------------------------- |
|
■ -^-BLK-- |
|
|
|
|
|
|
|
|
CONN |
|
|
|
|
|
TO |
L2- |
|
|
BLU----------- |
i |
DISCONNECT |
|
|
|
|
|
PER NEC |
|
|
|
|
|
|
L3 |
______________________________ -YPl------------------------ |
YEL |
i |
|
|
|
|
50YQ HEAT PUMP |
|
|
_____ Field Wiring |
Splice Connections |
|
|
||
NOTE Use copper or copper-clad aluminum wire |
|
|
Fig. 7 — Line Power Connections
The 50YQ unit compressors are equipped with crankcase heaters. It is recommended that heater be energized a minimum of 24 hours before starting unit. To energize heater only, set thermostat at OFF posi tion; turn on unit main power at disconnect switch.
Heat Anticipator Settings for Room Thermo stat — Set anticipator settings for room thermostat according to Table 3. These settings may be changed slightly to provide a greater degree of comfort for a particular installation.
Table 3 — Thermostat Anticipator Setting
|
FIRST STAGE |
ACCESS. |
SECOND STAGE |
||
UNIT |
ELECTRIC |
||||
ANTICIPATOR |
HTR (Kw) |
ANTICIPATOR |
|||
|
SETTING |
|
|
SETTING |
|
|
240 V |
280 V |
|||
|
|
-gg— — |
|||
|
|
5 0 |
3 75 |
||
|
|
26 |
|||
50YQ024, |
|
7 5 |
5 6 |
||
|
100 |
7 5 |
26 |
||
030,036, |
|
||||
Fixed |
15 0 |
11 3 |
52 |
||
042,048, |
|||||
|
20 0 |
150 |
52 |
||
060 |
|
||||
|
25 0 |
188 |
52 |
||
|
|
||||
|
|
27 0 |
22 25 |
78 |
|
|
|
|
|
|
Accessory Outdoor Thermostat provides adjust able outdoor control of accessory electric heaters of 15 Kw and over. This thermostat makes contact when a drop in outdoor temperature occurs. It ener gizes a stage of electric heat when the outdoor tem perature setting is reached, provided the room thermostat is on the second stage of heating. One outdoor thermostat is recommended for each stage of electric heat after the first stage. Set the outdoor thermostat(s) progressively lower for each stage. Refer to heat load of building and unit capacity to determine the correct outdoor thermostat settings.
The accessory emergency heat relay is required when 2 outdoor thermostats are used. It is auto matically energized by the manually operated emer gency heat switch in the indoor thermostat subhase. The indoor thermostat locks out compressor and the relay bypasses the outdoor thermostats for electric heater operation during heat pump shutdown. When one outdoor thermostat is used, an emergency heat relay is not required. The emergency heat switch in the indoor thermostat subbase bypasses outdoor thermostat, locks out compressor and acti vates electric heater.
184