Bosch RSSWP-2475C-FW, RSSWP-2475W-FR, RSSWP-2475C-FR Installation Manual

0 (0)

273 Branchport Ave.

Thank you for using our products.

Long Branch, N.J. 07740

(800)

631-2148

 

(800)

397-5777

INSTALLATION INSTRUCTIONS

www.wheelockinc.com

SERIES RSSWP STROBE WEATHERPROOF APPLIANCE

 

 

(WALL/CEILING MOUNT VERSION)

Use this product according to this instruction manual. Please keep this instruction manual for future reference.

GENERAL:

Wheelock’s Series RSSWP Strobes can provide a non-synchronized strobe signal when connected directly to a Fire Alarm Control Panel (FACP), or provide a synchronized strobe signal when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM), or Wheelock’s Power Supplies. The RSSWP strobe appliance is UL Listed under Standard 1638 (Visual Signaling Appliances) for indoor/outdoor use, fire protective service. The Series RSSWP Strobe Appliances are also ULC Listed under Standard CAN/ULC-S526-02 for Visual Signaling Appliances. The strobe has a 75 candela intensity on axis at -35oC and low current draw. For outdoor applications the RSSWP must be mounted to a Weatherproof Backbox (WPSBB). The strobes use a xenon flashtube with solid state circuitry enclosed in a polycarbonate lens to provide maximum visibility and reliability for effective visible signaling. All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a FACP.

NOTE: All Canadian Installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems - CAN/ULC-S524-01 and Canadian Electrical Code, Part 1. Final acceptance is subject to authorities having jurisdiction (AHJ).

WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.

CAUTION: NOT RECOMMENDED FOR USE AT REFRIGERATOR / FREEZER DOOR ENTRANCES OR OTHER AREAS WITH PERSISTENT CONDENSATION.

SPECIFICATIONS:

Table 1: UL/ULC Ratings

 

Regulated

Voltage Range Limit

Voltage Range Per

UL Rated Strobe Candela

ULC Rated Strobe

Model

Voltage

Per UL 1638

CAN/ULC-S526-02

 

(cd)

Candela

 

(VDC/VRMS)

(VDC/VRMS)

(VDC/VRMS)

At 25°C

 

At -35°C

(cd)

RSSWP-2475W

24

16.0-33.0

20.0-31.0

180

 

75

180

RSSWP-2475C

24

16.0-33.0

20.0-31.0

180

 

75

180

RSSWP-2475W is for wall applications. RSSWP-2475C is for ceiling.

NOTES:

1.Strobes will produce 1 flash per second over the “Regulated Voltage” range.

2.These strobes meet the required light distribution patterns defined in UL 1638 and ULC S526-02.

3.All models are UL/ULC Listed for indoor and outdoor use with a temperature range of -31°F to +150°F (-35°C to +66°C) and maximum humidity of 93% ± 2% RH. The effect of shipping and storage temperatures shall not adversely affect the performance of the appliance when it is stored in the original cartons and is not subjected to misuse or abuse.

4.Use RSSWP-2475W for wall and RSSWP-2475C for ceiling.

 

Table 2: Current Ratings (AMPS)

 

Maximum RMS Current

 

 

Voltage

 

75cd

DC

16-33VDC

 

0.138

FWR

16-33VRMS

 

0.222

 

 

 

 

When calculating the total currents use Table 2 to determine the highest value of RMS current for an individual strobe, then multiply these values by the total number of strobes. Be sure to add the currents for any other appliances, including audible signaling appliances powered by the same source, and to include any required safety factors.

NOTE: The maximum number of strobes on a single notification appliance circuit shall not exceed 50.

Copyright 2005 Wheelock, Inc. All rights reserved.

P84135 K

Sheet 1 of 4

Bosch RSSWP-2475C-FW, RSSWP-2475W-FR, RSSWP-2475C-FR Installation Manual

CAUTION: These notification appliances are UL Listed as “Regulated”. They are intended to be used with FACPs whose notification circuits are UL Listed as “Regulated.” These appliances shall not be used on UL Listed “Special Application” notification circuits unless the appliances are identified to be compatible in the installation instructions of the FACP or unless the FACP is identified to be compatible in this instruction manual.

WARNING: THESE APPLIANCES WERE TESTED TO THE REGULATED VOLTAGE LIMITS OF 16.0-33.0 VOLTS FOR 24V MODELS USING FILTERED DC OR UNFILTERED FULL-WAVE-RECTIFIED VOLTAGE. DO NOT APPLY VOLTAGE OUTSIDE OF THIS RANGE.

WARNING: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND SUBTRACT THE VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPLIED VOLTAGE TO THE STROBES. THE MAXIMUM WIRE IMPEDANCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS.

CAUTION: Strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off.

WARNING: MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, NOTIFICATION APPLIANCE CIRCUITS, SM, DSM SYNC MODULES, OR WHEELOCK POWER SUPPLIES DOES NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.

WIRING AND MOUNTING INFORMATION:

CAUTION: The following figure shows the maximum number of field wires (conductors) that can enter the backbox used with each mounting option. If these limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product.

CAUTION: Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathed multiconductor cable is used.

Although the limits shown for each mounting option comply with the National Electrical Code (NEC), Wheelock recommends use of the largest backbox option shown and the use of approved stranded field wires, whenever possible, to provide additional wiring room for easy installation and minimum stress on the product from wiring.

SURFACE (INDOOR/OUTDOOR)

 

WPSBB

#8-18 SCREWS

MOUNTING TAB

(SUPPLIED)

 

WOOD SCREWS

MAXIMUM NUMBER OF CONDUCTORS

AWG#18

AWG#16

AWG#14

AWG#12

4

4

4

4

WARNING: THIS UNIT MUST BE MOUNTED ON A FLAT SURFACE, SO THAT THE SURFACE COVERS THE ENTIRE BACK SURFACE OF THE BACKBOX. WHEN USED IN AN OUTDOOR APPLICATION OR A NEMA 3R APPLICATION, USE WEATHER PROOF RATED CONDUIT FITTING ON ALL KNOCKOUTS OF THE BACKBOX.

P84135 K

Sheet 2 of 4

Loading...
+ 2 hidden pages