Bosch BP007-1HZC-FRS, CP030-1VTN-FRT, BP007-1HZN-FRS, BP007-1HZC-FLS, BP007-1HZN-FLS Installation And Maintenance Manual

...
0 (0)
Installation and Maintenance Manual
CP/BP Series
6 720 220 045
Revised 05-12
©Copyright 2012 Bosch, Inc All rights reserved
Table of Contents
TABLE OF CONTENTS
CP/BP Series
3
Model Nomenclature ............................................. 3
Initial Inspection ................................................... 4
General Description .............................................. 4
Moving and Storage .............................................. 4
Safety Considerations ........................................... 4
Location ................................................................ 4
Installation ............................................................ 5
Mounting Vertical Units ......................................... 5
Mounting Horizontal Units .................................... 5
Condensate Drain ................................................. 6
Duct System .......................................................... 6
Electrical ............................................................... 7
Thermostat Connections ...................................... 8
Safety Devices and the UPM Controller ................. 8
Sequence Of Operation ...................................... 10
Unit Options........................................................ 10
Fluid Differential Pressure Switch ....................... 13
Earth Coupled Systems ....................................... 15
Unit Start-up ....................................................... 15
Heat Recovery Package ....................................... 15
Water Tank Preparation ....................................... 16
HR Water Piping ................................................. 16
Typical Connection Piping ................................... 16
Water Tank Rell ................................................. 17
Initial Start up ..................................................... 17
Maintenance ....................................................... 17
In-warranty Material Return ................................ 18
Unit Specications .............................................. 18
Physical Data ................................................ 18
Dimensions ................................................... 19
Fluid Pressure Drops ..................................... 20
Air Temperature Rise/Fall .............................. 21
Refrigerant Pressure Ranges ......................... 22
Blower Performance ..................................... 23
Water Piping ....................................................... 13
Well Water Systems ............................................. 13
Fresh Water Systems ........................................... 14
MODEL NOMENCLATURE
CP/BP 048 - 1 VT C - F L T
SERIES: CP/BP
NOMINAL CAPACITY: MBTUH
VOLTAGE DESIGNATION: 1- 208-230/1/60
CABINET CONFIGURATION: VT - VERTICAL HZ - HORIZONTAL
WATER TO REFRIGERANT HEAT EX: C - COPPER N - CUPRO-NICKEL
Typical Wiring Diagrams ...................................... 24
Unit Check-out Sheet .......................................... 28
Troubleshooting .................................................. 29
SUPPLY AIR LOCATION:
T - TOP (VT ONLY)
S - STRAIGHT THRU (HZ ONLY)
E - END BLOW (HZ ONLY)
RETURN AIR LOCATION:
L - LEFT
R - RIGHT
WATER CONNECTION LOCATION
F - FRONT
6 720 220 045
Initial Inspection
4
CP/BP Series
INITIAL INSPECTION
Be certain to inspect all cartons or crates on each unit as received at the job site before signing the freight bill. Verify that all items have been received and that there are no visible damages; note any shortages or damages on all copies of the freight bill. In the event of damage or shortage, remember
that the purchaser is responsible for  ling the
necessary claims with the carrier. Concealed damages not discovered until after removing the units from the packaging must be reported to the carrier within 24 hours of receipt.
GENERAL DESCRIPTION
These Packaged System Heat Pumps provide the
best combination of performance and ef ciency
available. Safety devices are built into each unit to provide the maximum system protection possible when properly installed and maintained.
The CP/BP Water-to-Air Heat Pumps are Underwriters Laboratories (UL) and (cUL) listed for safety. The water-to-Air Heat Pumps are designed to
operate with entering  uid temperature between
25°F to 80°F in the heating mode and between 50°F
to 110°F in the cooling mode. Ef ciencies and capacities will vary as entering  uid and return air
temperatures vary.
50°F Min. EWT for well water applications
suffi cient water fl ow to prevent freezing. Antifreeze solution is required for all closed loop applications where the fl uid temperature may drop below 50°F. Cooling Tower/Boiler and Earth Coupled (Geo Thermal) applications should have suffi cient antifreeze solution to protect against extreme conditions and equipment failure. Frozen water coils are not covered under warranty.
This product should not be used for temporarily
heating/cooling during construction. Doing so may affect the unit’s warranty.
MOVING AND STORAGE
If the equipment is not needed for immediate installation upon its arrival at the job site, it should be left in its shipping carton and stored in a clean,
dry area. Units must only be stored or moved in the normal upright position as indicated by the “UP” arrows on each carton at all times. If unit stacking is required, stack units as follows: Vertical units less than 6 tons, no more than two high; horizontal units less than 6 tons, no more than three high. Do not stack units larger than 6 tons.
SAFETY CONSIDERATIONS
Installation and servicing of this equipment can be hazardous due to system pressure and electrical
components. Only trained and quali ed personnel
should install, repair, or service the equipment. Untrained personnel can perform basic functions of maintenance
such as cleaning coils and replacing  lters.
Before performing service or maintenance operations on the system, turn off main power to the unit. Electrical shock could cause personal injury or death.
When working on equipment, always observe precautions described in the literature, tags, and labels attached to the unit. Follow all safety codes. Wear safety glasses and work gloves. Use a
quenching cloth for brazing, and place a  re
extinguisher close to the work area.
The blower motor should only be operated when a duct is installed and secured to heat pump duct collar in order to avoid possible injury.
LOCATION
Locate the unit in an indoor area that allows easy
removal of the  lter and access panels, and has
enough room for service personnel to perform
maintenance or repair. Provide suf cient room to make  uid, electrical, and duct connection(s). If the unit is located in a con ned space such as a closet,
provisions must be made for return air to freely enter the space. On horizontal units, allow adequate room below the unit for a condensate drain trap and do not locate the unit above supply piping. These units are not approved for outdoor installation; therefore, they must be installed inside the structure being conditioned.
Do not locate units in areas that are subject to freezing.
6 720 220 045
Subject to change without prior notice Revised 05-12
VIBRATION
PAD
FULL SIZE
Installation
CP/BP Series
5
INSTALLATION
Remove shipping block under blower housing.
Loosen compressor mounting bolts.
The installer should comply with all local codes and regulations which govern the installation of this type of equipment. Local codes and regulations take precedent over any recommendations contained in these instructions. In lieu of local codes, the equipment should be installed in accordance with the recommendations made by the National electric code, and in accordance with the recommendations made by the National Board of Fire Underwriters. All local seismic codes for seismic restraint of equipment, piping, and duct work shall be strictly adhered to.
MOUNTING VERTICAL UNITS
Vertical units up to six tons are available in left or
right air return con gurations. Vertical units should
be mounted level on a vibration absorbing pad slightly larger than the base to minimize vibration transmission to the building structure. It is not
necessary to anchor the unit to the  oor. (See
Figure #1).
MOUNTING HORIZONTAL UNITS
While horizontal units may be installed on any level surface strong enough to hold their weight, they are typically suspended above a ceiling by threaded rods. The rods are usually attached to the unit corners by hanger bracket kits (P/N 930-008). (See Figure #2). The rods must be securely anchored to the ceiling. Refer to the hanging bracket assembly and installation instructions for details. Horizontal units installed above the ceiling must conform to all local codes. An auxiliary drain pan if required by code should be at least four inches larger than the bottom of the heat pump. Plumbing connected to the heat pump must not come in direct contact with joists, trusses, walls, etc.
If the unit is located in a con ned space such as a
closet, provisions must be made for return air to freely enter the space.
VIBRATION
PAD
FULL SIZE
Figure #1 – Vertical unit on vibration pad
Figure #2 – Typical horizontal unit hanging bracket
Some applications require an attic  oor installa-
tion of the horizontal unit. In this case the unit should be set in a full size secondary drain pan on top of a vibration absorbing mesh. The secondary
drain pan prevents possible condensate over ow
or water leakage damage to the ceiling. The secondary drain pan is usually placed on a ply­wood base isolated from the ceiling joists by additional layers of vibration absorbing mesh. In both cases, a 3/4” drain connected to this second­ary pan should be run to an eave and able to drain to a location that will be noticeable. If the unit is located in a crawl space, the bottom of the unit
must be at least 4” above grade to prevent  ood-
ing of the electrical parts due to heavy rains.
Locate the heat pump unit in an area that provides
suf cient room to make water and electrical
connections, allowing easy removal of the access
6 720 220 045
6
Condensate Drain
CP/BP Series
panels, and replacement of air lters for routine
maintenance. This will ensure proper work space for service personnel to perform maintenance or repair.
See Unit Specications for replacement lter sizes
in the back of this manual to ensure proper clearances are provided during installation. Allow adequate room below the unit for a condensate drain trap on horizontal units.
Water freezes at 32°F. Frozen water coils are not covered under the limited product warranty. It is the installer’s responsibility to insure that the heat pump unit is installed in a location or have taken the proper precautions in order to prevent rupturing the water coil due to freezing conditions.
The heat pump unit is designed for conditioned space installation only. If the source water is subjected to conditions where ambient temperatures can fall below freezing, some form of freeze protection should be employed. In an open loop system this may entail running the water pump continuously to prevent freezing. An antifreeze solution wherever possible should be used if water will be subject to freezing. Consult the factory in these instances for guidance.
CONDENSATE DRAIN
A drain line must be connected to the heat pump and pitched away from the unit a minimum of 1/8”
per foot to allow the condensate to ow away from
the unit.
Figure #3 – Heat Pump Condensate Trapping
(Heat Pumps are not internally trapped). A vertical air vent is sometimes required to avoid air pockets (See Figure #3). The length of the trap depends on the amount of positive or negative pressure on the drain pan. A second trap must not be included.
The horizontal unit should be pitched approximately 1/4” towards the drain in both directions, to facilitate condensate removal. See Figure 4 below.
Figure #4 – Sloped horizontal unit installation
DUCT SYSTEM
A supply air outlet collar and return air duct ange
are provided on all units to facilitate duct
connections. See Unit Specications for duct collar
connection sizes in the back of this manual.
A exible connector is recommended for supply
and return air duct connections on metal duct systems. All metal ducting should be insulated with a minimum of one inch duct insulation to avoid heat loss or gain and prevent condensate forming during the cooling operation. Application of the unit to uninsulated duct work is not recommended as the unit’s performance will be adversely affected. Do not connect ducts directly to the blower outlet; factory supplied duct collars should be used for
connection. The factory provided air lter must be removed when using a lter back return air grill. The factory lter should be left in place on a free return
system.
This connection must be in conformance with local plumbing codes. A trap must be installed in the
condensate line to insure free condensate ow.
6 720 220 045
If the unit will be installed in a new installation which includes new duct work, the installation should be designed using current ASHRAE procedures for duct sizing. If the unit is to be connected to existing ductwork, a check should be made to assure that the duct system has the
Subject to change without prior notice Revised 05-12
Electrical
CP/BP Series
7
capacity to handle the air required for the unit application. If the duct system is too small, larger ductwork should be installed. Check for existing leaks and repair as necessary to ensure a tight air seal within duct. The duct system and all diffusers
should be sized to handle the designed air ow
quietly. To maximize sound attenuation of the unit blower, the supply and return air plenums should be insulated. There should be no direct straight air path thru the return air grille into the heat pump. The return air inlet to the heat pump must have at least one 90 degree turn away from the space
return air grille. If air noise or excessive air ow are
a problem, the blower speed can be changed to a
lower speed to reduce air ow. (Refer to ECM
motor speeds and settings in Table #1)
Always disconnect power to the unit before changing motor speed to prevent damage to the motor, injury or death due to electrical
shock.
ELECTRICAL
Always disconnect power to the unit before servicing to prevent injury or death due to electrical shock or contact with moving parts.
All eld wiring must comply with local and national re, safety and electrical codes. Power to the unit
must be within the operating voltage range indicated on the unit’s nameplate. On three phase units, phases must be balanced within 2%.
Operating the unit with improper line voltage or with excessive phase imbalance is hazardous to the unit and constitutes abuse and is not covered under warranty.
Properly sized fuses or HACR circuit breakers must be installed for branch circuit protection. See equipment rating plates for proper size.
The heat pump units are provided with a concentric knock-out in the front right corner post for attaching common trade sizes of conduit. Route power supply wiring through this opening. Flexible wiring and conduit should be used to isolate vibration and noise from the building structure. Be certain to connect the ground lead to the ground lug in the control box. Connect the power leads as indicated on the unit wiring diagrams.
Table 1: CP/BP Motor CFM Selection (ECM Motor)otor Only)
Units
CP/BP015 450-153 1/3 LOW MED HIGH - -
CP/BP018 450-153 1/3 - LOW - MED HIGH
CP/BP024 450-157 1/3 LOW MED HIGH - -
CP/BP030 450-154 1/3 LOW MED HIGH - -
CP/BP036 450-158 3/4 LOW MED HIGH - -
CP/BP042 450-155 3/4 LOW MED HIGH - -
CP/BP048 450-155 3/4 - LOW MED HIGH -
CP/BP060 450-156 1 LOW MED HIGH - -
CP/BP070 450-156 1 LOW - - MED HIGH
Motor Part
Number
Motor HP Tap1 Tap2 Tap3 Tap4 Tap5
6 720 220 045
8
Thermostat Connections
CP/BP Series
THERMOSTAT CONNECTIONS
Thermostat wiring is connected to a 7 position low voltage terminal block in the electrical box. The thermostat connections and their functions are as follows:
Y Compressor Operation
G Fan
O Reversing Valve (energized in cooling)
C Transformer 24 VAC Common – 3 Connections
R Transformer 24 VAC Hot
If the unit is being connected to a thermostat with a malfunction light, this connection is made at the unit alarm output.
If the thermostat is provided with a malfunction
light powered off of the common (C) side of the transformer, a jumper between “R” and “COM”
terminal of “ALR” contacts must be made.
below or remains at freeze limit trip for 30 seconds, the controller will shut down the compressor and enter into a soft lockout condition. The default freeze limit trip is 30°F, however this can be changed to 15°F by cutting the R42 resistor located on top of DIP switch SW1.
• The optional condensate over ow protection
sensor (standard on horizontal units) is located in the drain pan of the unit and connected to the ‘COND’ terminal on the UPM board.
If the thermostat is provided with a malfunction
light powered off of the hot (R) side of the transformer, then the thermostat malfunction light connection should be connected directly to the
(ALR) contact on the unit’s UPM board.
SAFETY DEVICES AND THE UPM CONTROLLER
Each unit is factory provided with a Unit Protection Module (UPM) that controls the compressor opera­tion and monitors the safety controls that protect the unit.
Safety controls include the following:
• High pressure switch located in the refrigerant
discharge line and wired across the HPC terminals on the UPM
• Low pressure switch located in the unit
refrigerant suction line and wired across terminals LPC1 and LPC2 on the UPM.
Freeze Protection Sensor
• Optional freeze protection sensor, mounted close
to condensing water coil, monitors refrigerant temperature between condensing water coil and thermal expansion valve. If temperature drops
6 720 220 045
If freeze protection sensor is not installed, a
jumper between freeze contacts must be installed
on the UPM board otherwise unit will not start.
Subject to change without prior notice Revised 05-12
Safety Devices and the UPM Controller
CP/BP Series
9
The UPM includes the following features:
ANTI-SHORT CYCLE TIME—5 minute delay on break timer to prevent compressor short cycling.
RANDOM START—Each controller has a unique random start delay ranging from 270 to 300 seconds to reduce the chances of multiple units simultaneously starting after initial power up or after a power interruption, creating a large electrical spike.
LOW PRESSURE BYPASS TIMER—If the compressor is running and the low pressure switch opens, then the control will keep the compressor on for 120 seconds. After 2 minutes if the low pressure switch remains open, the control will shut down the compressor and enter a soft lockout. The compressor will not be energized until the low pressure switch closes and the anti-short cycle time delay expires. If the low pressure switch opens 2–4 times in 1 hour, the unit will enter a hard lock out and need to be reset.
BROWNOUT/SURGE/POWER INTERRUPTION PROTECTION—The brownout protection in the UPM
board will shut down the compressor if the incoming power falls below 18 VAC. The compressor will remain off till the voltage goes above 18 VAC and the anti short cycle timer (300 seconds) times out. The unit will not go into a hard lockout.
MALFUNCTION OUTPUT—Alarm output is Normally Open (NO) dry contact. If 24 VAC output is needed R must be wired to the ALR-COM terminal; 24VAC will be available on the ALR-OUT terminal when the unit is in alarm condition. If pulse is selected the alarm output will be pulsed. The fault output will depend on the dip switch setting for “ALARM”. If it set to “CONST’, a constant signal will be produced to indicate a fault has occurred and the unit requires inspection to determine the type of fault. If it is set to “PULSE”, a pulse signal is produced and a fault code is detected by a remote device indicating the fault. See L.E.D. Fault Indication below for blink code explanations. The remote device must have a malfunction detection capability when the UPM board is set to “PULSE”.
TEST DIP SWITCH—A test dip switch is provided to reduce all time delay settings to 10 seconds
during troubleshooting or veri cation of unit
operation. Note that operation of the unit while in test mode can lead to accelerated wear and
premature failure of the unit. The “TEST” switch must be set back to “NO” for normal operation.
FREEZE SENSOR—The freeze sensor input is active all the time, if a freeze option is not selected the freeze terminals will need a jumper. There are
2 con gurable freeze points, 30°F & 15°F. The unit
will enter a soft lock out until the temperature climbs above the set point and the anti-short cycle time delay has expired. The freeze sensor will shut the compressor output down after 90 seconds of
water  ow loss and report a freeze condition. It is recommended to have a  ow switch to prevent the unit from running if water  ow is lost.
If unit is employing a fresh water system (no
anti-freeze protection), it is extremely important to have the “Freeze” jumper R42 resistor set to 30°F in order to shut down the unit at the appropriate leaving water temperature and protect your heat pump from freezing if a freeze sensor is included.
L.E.D. FAULT INDICATION—Two L.E.D. indicators are provided:
• Green: Power L.E.D. indicates 18—30 VAC
present at the board.
• Red: Fault indicator with blink codes as follows:
- One blink—High pressure lockout
- Two blinks—Low pressure lockout
- Three blinks—Freeze sensor lockout
- Four blinks—Condensate over ow
- Five blinks—Brownout
INTELLIGENT RESET—If a fault condition is initiated, the 5 minute delay on break time period is initiated and the unit will restart after these delays expire. During this period the fault LED will indicate the cause of the fault. If the fault condition still exists or occurs 2 or 4 times (depending on 2 or 4 setting for Lockout dip switch) before 60 minutes, the unit will go into a hard lockout and requires a manual lockout
reset. A single condensate over ow fault will cause
the unit to go into a hard lockout immediately, and will require a manual lockout reset.
6 720 220 045
10
CP/BP Series
Sequence of Operation
LOCKOUT RESET—A hard lockout can be reset by turning the unit thermostat off and then back on when the “RESET” dip switch is set to “Y” or by shutting off unit power at the circuit breaker when the “RESET” dip switch is set to “R”.
The blower motor will remain active during a
lockout condition.
UPM BOARD DEFAULT SETTINGS—Your UPM board will come from the factory with the following default settings:
Freeze—“Terminals not jumped” on all the time
Temp—30°F
Lockout—2
Reset—“Y”
Alarm—“PULSE”
Test—“NO”
Dry Contact—“Normally Open (NO)”
Considerations
1. Always check incoming line voltage power
supply and secondary control voltage for adequacy. Transformer primaries are dual tapped for 208 and 230 volts. Connect the appropriate tap to ensure a minimum of 18 volts secondary control voltage. 24 volts is ideal for best operation.
SEQUENCE OF OPERATION
Cooling Mode
See Typical Wiring Diagrams at the end of the document. Energizing the “O” terminal energizes the unit reversing valve in the cooling mode. The fan motor starts when the “G” terminal is energized.
When the thermostat calls for cooling (Y), the loop pump or solenoid valve if present is energized and compressor will start.
Once the thermostat is satis ed, the compressor
shuts down accordingly and the fan ramps down to either fan only mode or off over a span of 30 seconds (ECM Motors).
Note that a fault condition initiating a lockout will de-energize the compressor.
Heating Mode
Heating operates in the same manner as cooling, but with the reversing valve de-energized. The compressor will run until the desired setpoint temperature on the thermostat is achieved.
Once the thermostat is satis ed, the compressor
shuts down and the fan ramps down in either fan only mode or turns off over a span of 30 seconds. Auxiliary electric heating coils are not available on the BP/CP product line.
UNIT OPTIONS HOT GAS REHEAT (HGR)
2. Long length thermostat and control wiring
leads may create voltage drop. Increase wire gauge or up-size transformers may be required to insure minimum secondary voltage supply.
3. FHP recommends the following guidelines for
wiring between a thermostat and the unit: 18 GA up to 60 foot, 16 GA up to 100 ft and 14 GA up to 140 ft.
4. Do not apply additional controlled devices to
the control circuit power supply without consulting the factory. Doing so may void equipment warranties.
5. Check with all code authorities on requirements
involving condensate disposal/over  ow
protection criteria.
6 720 220 045
Hot gas reheat allows the user to not only control space temperature, but also humidity levels within the conditioned space. An excess of moisture in the space can allow mold growth leading to damage in the structure or interior surfaces as well as reducing the air quality and creating an unhealthy environment.
The typical control of a unit is by a thermostat that senses the temperature in the space. By utilizing a humidistat in addition to the thermostat we are able to monitor the humidity levels in the space as well. The HGR option allows cooling and
dehumidi cation to satisfy both the thermostat and
humidistat.
Subject to change without prior notice Revised 05-12
Loading...
+ 22 hidden pages