ABB AC Circuit switching contactors Catalog Page

AC Circuit switching contactors
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Type TAL & TAE
contactors
AC Circuit
switching
1
1
Description
1
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
1
AC Circuit
switching
contactors
TAL9-30-01
TAL9 - TAE110
D.C. Operated 3 & 4 pole
3 Pole
General purpose Maximum motor Standard Catalog List current horsepower ratings
AC1 AC3 208V 240V 480V 575/600V N.O. N.C.
22 9 2 2 5 7.5
0 1 TAL9-30-01-
25 11 3 3 7.5 10
0 1 TAL12-30-01-
28 16 5 5 10 15
0 1 TAL16-30-01-
45 25 7.5 10 20 25
0 1 TAL26-30-01-
55 30 10 10 25 30
0 1 TAL30-30-01-
60 42 10 15 30 40
0 1 TAL40-30-01-
100 50 15 20 40 50
1 1 TAE50-30-11-428
125 75 25 30 60 75
1 1 TAE75-30-11-600
146 96 30 30 60 75
1 1 TAE95-30-11-640
160 110 30 40 75 100
1 1 TAE110-30-11-★ 795 To select a coil voltage, substitute the code from the Coil Voltage Selection Chart for the ★
4 Pole
Rated operational Maximum motor Standard current horsepower ratings R auxiliary contacts AC1 AC1 208V 240V 480V 575/600V N.O. N.C.
0≤40°C 0≤55°C
22 20 2 2 5 7.5 0 0 TAL9-40-00- $ 190 28 25 5 5 10 15 0 0 TAL16-40-00- 268 45 40 7.5 10 20 25 0 0 TAL26-40-00- 303 70 60 10 10 25 30 0 0 TAE45-40-00- 405 100 85 15 20 40 50 0 0 TAE50-40-00- 505 125 105 25 30 60 75 0 0 TAE75-40-00- 615
To select a coil voltage, substitute the code from the Coil Voltage Selection Chart for the
R
auxiliary contacts number price
1 0 TAL9-30-10-
1 0 TAL12-30-10-
1 0 TAL16-30-10-
1 0 TAL26-30-10-
1 0 TAL30-30-10-
1 0 TAL40-30-10-
0 0 TAE50-30-00- 388
0 0 TAE75-30-00- 560
0 0 TAE95-30-00- 600
0 0 TAE110-30-00- 755
Catalog List number price
$ 141
173
218
263
338
354
4 Pole mounted with 2 N.O. & 2 N.C. main poles
Rated operational Maximum motor Standard current horsepower ratings R auxiliary contacts AC1 AC1
0≤40°C 0≤55°C
22 20 2 2 5 7.5 0 0 TAL9-22-00- $ 190 28 25 5 5 10 15 0 0 TAL16-22-00- 268 45 40 7.5 10 20 25 0 0 TAL26-22-00- 303
To select a coil voltage, substitute the code from the Coil Voltage Selection Chart for the These contactors can be used for controlling either 2 separate circuits, i.e. 2 loads with 2 separate supplies, or 1 circuit com-
prising 2 separate loads with 1 single supply. When the contactor operates, there is no mechanical overlapping between the N.O. main poles and N.C. main poles: BREAK before MAKE.
NOTE: These contactors are not suitable for a reversing starter or a star-delta starter or for controlling a single load from 2 separate supplies.
Coil characteristics
No extra voltages applicable on the Uc min. - max. values of the Coil Volt­age selection table.
Coil consumption at U
• 9 W pull-in/holding for TBC type
• 450 W pull-in/ 7 W holding for TAE 50 and TAE 75 types
• 950 W pull-in/ 7 W holding for TAE 95 and TAE 110 types
208V 240V 480V 575/600V N.O. N.C.
max. and q = 20 °C:
c
Discount schedule AA
Coil voltage selection
Min. UC Max Voltage
17 32 51 24 45 52 36 65 54 42 78 58 50 90 55 77 143 62 90 150 66 152 – 264 68