Xylem MM 201H User Manual

Series 67 and 767 Low Water Cut-Offs For Steam Boilers
INSTRUCTION MANUAL
MM-201H
A
D
INST
ALLATION –
T
OOLS NEEDED:
One (1) tube cutter, one (1) pencil, one (1) flathead screwdriver, one (1) adjustable wrench and two (2) pipe wrenches.
The Series 67 and Series 767 low water cut-offs are float-type boiler controls designed to interrupt current to the burner whenever the water drops to the cut-off level.
The Series 767 is identical to Series 67 in all respects except one. The Series 767 is equipped with
a 2-1/2" (63.5mm) pipe tap opening in the body, and does not require the quick hook-up fittings supplied with the Series 67. The pipe tapping allows for a direct connection to the side of the boiler.
Electrical Ratings
Pump Circuit Rating (Amperes)
V
oltage Full Load Locked Rotor Pilot Duty
125 VA at
120 or 240 VAC
For Series 67 - The elevation of the control (A) is already determined by the location of the gauge glass tappings (B,C) on the boiler. The horizontal cast line (D) should be located at or above the boiler manufacturer's minimum safe water level (E).
For Series 767 - The elevation of the control (A) is already determined by the location of the 2­1/2 (63.5mm) pipe tapping on the boiler. The horizontal cast line (D) of the body (A) should be located at or above the boiler manufacturer's minimum safe water level.
STEP 1 - Determine the Ele
vation at Which the
Low Water Cut-Off Controller Must be Installed
C
A
E
B
D
IMPOR
TANT: Follow the boiler manufacturer's
instructions along with all applicable codes and ordinances for piping, blow down valve and water gauge glass installation.
OPERA
TION
Maxim
um Steam Pressure: 20 psi (1.4 kg/cm
2
)
Series 67
Series 767
Note: 11 MV is rated at 24 V
A @ 24 VAC to 120 VAC
120 VAC
240 VAC
7.4
3.7
44.4
22.2
a. Turn the boiler off.
b. Drain the water in the boiler to a level which
is below the lower gauge glass tapping (B) of the control body (A). Allow the boiler to cool to 80˚F (27˚C) and allow the pressure to release to 0 psi (0 bar).
STEP 2 - Preparation
OFF
ON
AA
B
a. Using a pipe wrench, remove the float blocking
tube (F) from the new control and tighten a 2" (13mm) NPT pipe plug (G) (provided) into the tapping on the bottom of the control body (A). Tighten the pipe plug to 31 ft•lb (42 N•m).
A
F
G
When using the tape sealant on the external threads of pipes or fittings, follow the manufacturers instructions. Use sparingly and do not place on the first thread.
!
CAUTION
STEP 3 - Installing the New Low Water Cut-Off
b. Using a pipe wrench, install a 2" (13mm)
nipple (H) into the lower gauge glass tapping (B) and pipe tee assembly (J). Tighten both connections to 31 ft•lb (42 N•m).
J
B
H
c. Using an adjustable wrench, install a a"
(9.5mm) NPT compression fitting base (K) to the upper tapping (L) in the control (A). Tighten to 31 ft•lb (42 N•m).
A
L
K
N
M
d. Using a pipe wrench, install a 2" (13mm)
nipple (M) into the upper tapping (N). Tighten to 31 ft•lb (42 N•m).
e. Using a pipe wrench, install the pipe tee (P)
(provided) onto the nipple (M) in the upper tapping (N). Tighten to 31 ft•lb (42 N•m).
N
M
P
f. Using an adjustable wrench, install 1/2 (13mm) NPT
compression fitting base (U) into the upper tee (P). Tighten to 31 ft•lb (42 N•m). Place the compression nut (R) and compression ring (S) over the top of tubing (Q). Insert tubing (Q) into compression base (U). Turn compression nut (R) hand tight. DO NOT TIGHTEN.
IMPORTANT: Do not use tape or pipe sealant on the compression fittings.
Q
U S R
P
h. Insert the tubing (Q) into the upper compres-
sion fitting (U) and tighten the fitting to 31 ft•lb (42 N•m).
U
Q
g. Position the tubing (Q) next to the compression
fitting (K) and, using a pencil, mark the tubing (Q) for proper insertion into the compression fitting (K).
Remove the tubing (Q), and, using the tube
cutter, cut the tubing to its proper length.
Q
K
i. Using two (2) pipe wrenches, rotate the upper
tee (P) counterclockwise and the lower tee (J) clockwise.
j. Place the compression nut (R) and the compres-
sion ring (S) over the bottom of the tubing (Q).
P
J
Q
S
R
k. Using two (2) pipe wrenches, rotate the upper
tee (P) clockwise and the lower tee (J) counter­clockwise so that the end of the tube can be inserted into the lower compression fitting (K). NOTE: Make sure that the control is in a hori­zontal position. Using an adjustable wrench, tighten the lower compression fitting (K) to 31 ft•lb (42 N•m).
K
J
P
T
U
V
l. Using a pipe wrench, install a w" (19mm) NPT
pipe (T) into the opening of the blow down valve (U) and tighten to 47 ft•lb (64 N•m).
A
W
m. Hang the blow down card (W) (enclosed) as
close to the control (A) as possible, or remove the protective backing and affix the card on the boiler jacket close to the control.
X
a. Using a pipe wrench, install a 22" (63.5mm)
nipple (X) into the side of the boiler. Tighten to 109 ft•lb (148 N•m).
For Series 767
To prevent burning or scalding, pipe blow-off discharge from blow-down valve to floor – allowing enough height for a pail under dis­charge pipe to collect blow down discharge. This pipe must be same 3/4” size as blow­down connection; do not reduce. Do not thread end of pipe.
!
CAUTION
T
U
A
W
c. Using a pipe wrench, install a w" (19mm) NPT
pipe (T) into the opening of the blow down valve (U) and tighten to 47 ft•lb (64 N•m).
A
b. Install the control (A) by rotating it onto the 22"
(63.5mm) nipple (X, as shown in Step a on previous page). Tighten to 109 ft•lb (148 N•m).
d. Hang a blow down card (W) (enclosed) as
close to the control (A) as possible, or remove the protective backing and affix the card on the boiler jacket close to the control.
To prevent burning or scalding, pipe blow-off discharge from blow-down valve to floor – allowing enough height for a pail under dis­charge pipe to collect blow down discharge. This pipe must be same 3/4” size as blow­down connection; do not reduce. Do not thread end of pipe.
!
CAUTION
STEP 4 - Electrical Wiring
Directory: 67 Low Water Cut-Off and Uni-Match Water Feeder page 8 - 9
67 Low Water Cut-Off and 101 Water Feeder page 10 - 11
For 67 Low Water Cut-Off Installed with McDonnell & Miller Uni-Match Water-Feeder
WARNING
!
• To prevent electrical shock, turn off the electrical power before making electrical connections.
• This low water cut-off must be installed in series with all other limit and operating controls installed on the boiler. After installation, check for proper operation of all of the limit and operating controls, before leaving the site.
Failure to follow this warning could cause electrical shock, an explosion and/or a fire, which could result in property damage, personal injury or death.
a. Using a flathead screwdriver, remove the one
(1) screw that secures the low water cut-off switch cover (Y).
b. Using a flathead screwdriver, loosen the two
(2) screws and remove the feeder cover (Z).
Y
Z
c. Position the slide switch selector (AA) in the
position.
AA
NOTE: To connect wires to the terminals on the burner, or low water cut-off, place the bare end of the wire under the terminal screw and tighten the screw with a flat­head screwdriver. On the 101-A water feeder use wire nuts.
Y
a. Using a flathead screwdriver, remove the one
(1) screw that secures the low water cut-offs switch housing (Y).
BB
b. Using a flathead screwdriver, remove the
two
(2) screws that secure the feeder cover
(BB).
For 67 Low Water Cut-Off Installed with McDonnell & Miller Series 101-A Water-Feeder
For the 120V Burner/120V Feeder setups.
BURNER
120 VAC SUPPLY
12 34
N
H
101A
69
c. Using a wire nut, connect a wire from the
neutral side of the power supply to one of the wires inside the feeders junction box. (Does not make a difference which one). Connect a wire from the "hot" side of the power supply to terminal #2 of the Series 67 junction box. Connect the neutral side of the power supply to the burner.
BURNER
120 VAC SUPPLY
12 34
N
H
101A
d. Connect the wire from the burner to terminal
#1 of the low water cut-off. Connect a "jumper" from terminal #2 to terminal #3 of the low water cut-off. Connect a wire from termi­nal #4 of the low water cut-off to the remain­ing wire in the 101A water feeder.
10
For the 24V Burner/24V Feeder setups.
BURNER
101A-24
120 VAC SUPPLY
24V TRANSFORMER (101-24V-48)
12 34
N
H
24V
69
c. Connect the "hot" wire from the boiler trans-
former to terminal #2 of the low water cut-off. Connect the "hot" side of the water feeder transformer to terminal #3 of the low water cut-off. Connect the neutral side of the boiler transformer to the burner. Using a wire nut, connect the neutral side of the water feeder transformer to the water feeder.
BURNER
101A-24
120 VAC SUPPLY
24V TRANSFORMER (101-24V-48)
12 34
N
H
24V
d. Connect the wire from the burner to terminal
#1 of the low water cut-off. Connect a wire from terminal #4 of the low water cut-off to the remaining wire in the water feeder. Wire nut together.
BURNER
101A
120 VAC SUPPLY
N
H
24V
12 34
69
Wiring Alternative For the 120V Burner/24V Feeder setups. For the 24V Burner/120V Feeder setups.
BURNER
101A-24
120 VAC SUPPLY
24V TRANSFORMER (101-24V-48)
TO AVOID DAMAGE TO 101A SOLENOID COIL, TRANSFORMER 101-24V-48 MUST BE USED.
N
H
12 34
69
11
IMPORTANT: It is very important that you use the transformer supplied with the 101-A-24. The boiler
transformer in most cases is not big enough to handle the current draw of the 101-A-24. Use the supplied transformer (101-24-48). In most cases it will handle both the boiler and feeder. Do not try to use two transformers in the same circuit.
For All Installations
The BX outlet (GG) on the control is mov
able into any of the four positions by simply removing the two black-headed screws and rotating the housing.
BOTTOM TOP LEFT RIGHT
ALLA
INST
MAINTENANCE
SCHEDULE:
• Blo
w down weekly (at least once) when the
boiler is in operation.
• Disassemble and inspect annually. Replace the low water cut-off if it is worn, corroded, or if components no longer operate properly.
• Inspect the float chamber and equalizing piping annually. Remove all sediment and debris.
• Replace every 10 years. More frequent replace-
ment may be required when severe conditions exist such as rapid switch cycling, surging water levels, and use of water treatment chemicals.
TION COMPLETE
PROCEDURE:
To
prevent serious personal injury from steam and hot water, make sure there is a discharge line from the blow down valve to a proper place of disposal.
Failure to follow this caution could cause personal injury.
1. Blo
w down the low water cut-off when the water level is at its normal level and the burner is on. Fully open the blow down valve and observe the water level fall in the gauge glass. Close the valve after verifying that the feeder contacts have closed and the burner shuts off. If this does not happen, immediately shut off the boiler and correct the problem.
CAUTION
!
Xylem Inc.
8200 N. Morton Grove, Illinois 60053 Phone: (847) 966-3700 Fax: (847) 965-8379 www.mcdonnellmiller.com
McDonnell & Miller is a trademark of
© 2014 Xylem Inc. MM-201H March 2014 Part No. 246752
Austin Avenue
Xylem Inc. or one of its subsidiaries.
Loading...