The tekmarNet®4 thermostat 545 operates two stages of heating equipment, one stage of cooling equipment, and one fan.
The fan operation includes logic to operate ventilation. The 545 can operate as a stand alone device, or communicate with
a group of tekmarNet®4 thermostats.
Features
• tN4 Compatible
• Automatic Heat / Cool Switchover
• 2 Auxiliary Temperature Sensor Inputs
• Pulse Width Modulation
• Programmable Setback and Setup Scheduling
• Scenes
• Cooling Group
• Radiant Base Load
Y1 Rc G1 G1
Com
S2
S1
tN4
C
R
W1
Rh1Rh2
W2
tNt 545
Two Stage Heat, One Stage Cool, One Fan
Power: 24 V (ac) ±10% 60 Hz 1.5 VA
Relays: 24 V (ac) 2 A
992-02
Meets Class B: Canadian ICES, FCC Part 15
Terminal Functions
G1
Fan 1 Relay
G1
Fan 1 Relay
Rc
Power Cooling
Y1
Cool 1 Relay
Com
Sensor Common
S2
Sensor 2
No Power
S1
Sensor 1
To isolate
relay, cut
jumper
tN4
C
R
Rh1
W1
Rh2
W2
DIP Switch Functions
®
tekmarNet 4
Power Neutral
Power 24 V (ac)
Heat 1 Relay
Heat 1 Relay
Heat 2 Relay
Heat 2 Relay
A tN4 System Control is a control, not a thermostat, that
the 545 thermostat connects to through the tN4 bus. All
tN4 compatible Outdoor Reset Modules are tN4 System
Controls.
• If the thermostat is connected to a tN4 System Control,
set the tN4 System Control DIP switch to tN4 System
Control (down position).
• If the thermostat is not connected to a tN4 System
Control, set the tN4 System Control DIP switch to None
(up position).
Lock / Unlock (DIP Switch #1)
Use the Lock / Unlock DIP switch to lock or unlock the
Access Level of the 545.
• To unlock the Access Level, set the DIP switch to the
unlocked (down) position.
• To lock the Access Level, set the DIP switch to the locked
(up) position. Once locked, a padlock is displayed in the
lower right corner of the display and the Access Level
cannot be changed.
Y1 Rc G1 G1
Com
S2
S1
tN4
C
R
W1
Rh1 Rh2
W2
Note: The tN4 System Control’s Lock / Unlock DIP switch
overrides the Lock / Unlock DIP switch on the 545. Set
the tN4 System Control’s Lock / Unlock DIP switch to the
Unlock position before Access Levels can be changed on
the thermostat.
The Access Level restricts the number of Menus, Items
and Adjustments that can be accessed by the user. The
Access Level setting is found in the Miscellaneous (MISC)
menu. Select the appropriate access level for the people
who work with the thermostat on a regular basis.
The 545 has five Access Levels:
• Advanced (ADV): access to all settings
• Installer (INST): settings required for installation
• User (USER): for property owners
• Limited (LTD): limited temperature adjustment
• Secure (SEC): for commercial and public installations
Display
Menu Field
Displays the
current menu
Status Field
Displays the current status
of the control’s inputs,
outputs and operation
For more information, see the Misc (Miscellaneous) Menu
section.
In the following menu tables, the access level the item is
visable in is shown in the access column.
To adjust the Access Level:
1. Set the Unlock / Lock DIP switch to the unlock position.
If a tN4 System Control is connected to the 545, the
Unlock / Lock DIP switch on the tN4 System Control
must be set to the unlock position.
2. Use the Menu button to select the Misc menu.
3. Use the Item button to select the Access menu item.
4. Use the Up and Down button to select the required
Access Level.
Item Field
Displays an abbreviated
name of the selected item
Number Field
Displays the current value
of the selected item
Symbols Description
MODE OF OPERATION
Displays whether the device is in heating
or cooling mode.
FIRST STAGE HEAT
First stage heating is operating.
SECOND STAGE HEAT
Second stage heating is operating.
FIRST STAGE COOL
First stage cooling is operating.
FAN
Fan is operating.
FILTER
Replace the filter.
SCHEDULE MASTER
Indicates that this thermostat is a
schedule master.
tN4 COMMUNICATION
A tN4 network is detected.
COOL GROUP MASTER
This thermostat is a cool group master.
LOCK
The Access Levels are locked. A menu
option is visible but not adjustable.
OPTIMUM START / STOP
The Optimum Start or Optimum Stop
feature is active.
WARNING
An error is present.
TEMPORARY HOLD
The temperature has been temporarily
adjusted from the scheduled event.
Use the User Interface available on the Liquid Crystal Display
(LCD) to setup and monitor the operation of the thermostat.
Use the four push buttons below the LCD (Menu, Item, Up,
Down) to select settings. As you enter settings, record the
settings in the Job Record J 545.
Menu
The menus display in the Menu Field at the left of the
LCD.
Eight menus are available:
• View
• Adjust
• Time
• Scene
• Schedule
• Monitor
• Test
• Miscellaneous
To select a menu, press and release the Menu button.
Item
In each menu, a group of items can be selected. The
abbreviated name of the selected item displays in the Item
field of the LCD display.
• To view the next available item, press and release the
Item button.
• To view the previous item, hold down the Item button
and press and release the Up button.
Adjusting a Setting
To adjust a setting:
1. Use the Menu button to select the appropriate menu.
2. Use the Item button to select a menu item.
3. Use the Up or Down button to adjust the setting.
Default Item
• To set the default item in the View Menu, display the
item for more than five seconds.
After navigating menus, the display reverts back to the
default item after 60 seconds of button inactivity.
Copy Settings
To save time in setting thermostats, you can copy the settings
from one tN4 thermostat to a second tN4 thermostat.
Refer to the COPY item in the Misc menu on page 22.
Select the cooling room temperature for each event.
Note: At the Limited Access Level, you can only
adjust the temperature +/-3°F (1.5°C) from the last
setting.
Away is only available when Scenes are turned on.
Sleep
Away
Wake
UnOccupied
Occupied
Sleep
ADJUST MENU
Default = 85°F (29.5°C)
Default = 85°F (29.5°C)
OFF, 40 to 122°F
(OFF, 4.5 to 50.0°C)
Default = 70°F (21.0°C)
Default = OFF
Default = 70°F (21.0°C)
Default = OFF
40 to 122°F
(4.5 to 50.0°C)
Default = 85°F
(29.5°C)
OFF, ROOM,
FLOR (Floor),
REM (Remote)
Default = OFF
LTD
USER
INST
ADV
ADV
INST
ADV
FLOOR MINIMUM SECTION F
Select the minimum floor temperature for each
event.
Note: This item is only available when Sensor 1 or 2
is set to Floor. At the Limited Access Level, you can
only adjust the temperature +/-3°F (1.5°C) from the
last setting.
FLOOR MAXIMUM SECTION F
Maximum floor temperature.
Note: This item is only available when Sensor 1 or
2 is set to Floor.
SENSOR 1 SECTION A
Select the type of sensor connected to auxiliary
sensor input 1.
Select the type of sensor connected to auxiliary
sensor input 2.
ROOM SENSORSECTION A
Selects whether the built-in room sensor is functional.
Adjust Menu (3 of 7)
Item FieldRangeAccessDescription
ADJUST MENU
SYNC, AUTO
2 to 12
Default = AUTO
CTRL, HRF1, HRF2,
COIL, CONV, RAD,
BASE, OTHR ,FURN
Default =CTRL
OFF, ON
Default = ON
OFF, ON
Default = OFF
NONE, CTRL, HRF1,
HRF2, COIL, CONV,
RAD, BASE, OTHR,
FURN
Default =CTRL
ADV
INST
ADV
INST
ADV
INST
ADV
INST
ADV
HEAT CYCLES PER HOUR
Select the number of heating cycles per hour. SYNC
results in 5 CPH. All tN4 thermostats that are connected
and have the SYNC setting selected synchronize their
cycle to the same starting time.
Note: This item is only available when the tN4 System
Control DIP switch is set to None.
HEAT 1 TERMINAL
Select the type of heating terminal for first stage
heat.
Note: If CTRL is selected, the terminal unit selected
on the tN4 System Control is used.
HEAT 1 PUMP SECTION F
Select whether the system, primary, or mixing pump
on a tN4 System Control must operate while the first
stage heat is operating.
Note: This item is only available when the H1 Terminal
item is set to CTRL, HRF1, HRF2, Fan Coil, Convector,
Radiator, or Baseboard.
HEAT 1 DELAY SECTION F
Select whether the system, primary, or mixing pump
on a tN4 System Control is delayed to allow a first
stage heat thermal motor zone valve to open. Select
On for thermal motor, select Off for zone pump or
motorized zone valve.
Note: This item is only available when the H1 Terminal
item is set to CTRL, HRF1, HRF2, Fan Coil, Convector,
Radiator, or Baseboard.
HEAT 2 TERMINAL SECTION E
Select the type of heating terminal for second stage
heat. If NONE is selected, the second stage heat is
disabled.
Note: If CTRL is selected, the terminal unit selected
on the tN4 System Control is used.
Select the tN4 bus on which the second stage
heat zone operates. This setting determines water
temperature and system pump operation.
Note: This item is only available when the H2 Terminal
item is set to CTRL, HRF1, HRF2, Fan Coil, Convector,
Radiator, or Baseboard.
HEAT 2 PUMP SECTION F
Select whether the system, primary, or mixing pump
on a tN4 System Control must operate while the
second stage heat is operating.
Note: This item is only available when the H2 Terminal
item is set to CTRL, HRF1, HRF2, Fan Coil, Convector,
Radiator, or Baseboard.
Adjust Menu (4 of 7)
Item FieldRangeAccessDescription
OFF, ON
Default = OFF
NONE, 1 to 16
Default = NONE
NONE, 1 to 16
Default = NONE
INST
ADV
ADV
ADV
HEAT 2 DELAY
Select whether the system, primary, or mixing pump
on a tN4 System Control is delayed to allow a second
stage heat thermal motor zone valve to open. Select
On for thermal motor, select Off for zone pump or
motorized zone valve.
Note: This item is only available when the H2 Terminal
item is set to CTRL, HRF1, HRF2, Fan Coil, Convector,
Radiator, or Baseboard.
COOL MASTER SECTION H
Select the cool group for which this thermostat is the
master. Select None if this thermostat is not a cool
group master.
Note: This item is only available when the thermostat
is connected to a tN4 network and the Cool Stage
is set to 1.
COOL MEMBER SECTION H
Select the cool group of which this thermostat is a
member. Select None if this thermostat is not a cool
group member.
Note: This item is only available when the thermostat
is connected to a tN4 network, Cool Master is set to
NONE and the Cool Stage is set to NONE.
SECTION F
ADJUST MENU
NONE, 1
Default = 1
0:30 to 6:00 min
Default = 2:00
0:30 to 10:00 min
Default = 5:00
AUTO, 2 to 12
Default = AUTO
10 to 180 min
Default = 30
INST
ADV
ADV
ADV
ADV
ADV
COOL STAGES SECTION G
Select the number of cooling stages. Select None if
cooling is not used.
MINIMUM COOL RUN TIME SECTION G
Select the minimum running time for the cooling
equipment.
Note: This item is only available when the Cool Stage
is set to 1.
MINIMUM COOL OFF TIME SECTION G
Select the minimum off time for the cooling
equipment.
Note: This item is only available when the Cool Stage
is set to 1.
COOL CYCLES PER HOUR SECTION D
Select the number of cooling cycles per hour.
Note: This item is only available when the Cool Stage
is set to 1.
INTERLOCK SECTION G
Select how long heating must be off before cooling
starts.
Note: This item is only available when the Cool Stage
is set to 1.
Select whether heating has priority or cooling has
priority.
Note: This item is only available when the Cool Stage
is set to 1.
FAN MODE
Select the operation of the Fan 1 output.
FAN 1 VENTILATION
Select whether Fan 1 output operates to provide
ventilation.
Note: This item is only available when the Fan Mode
is set to None.
VENTILATION PRE-VENT SECTION I
Select how long the ventilation operates continuously
prior to the Wake or Occupied events.
Note: This item is only available when the Fan Mode
is set to None and F1 Vent is set to On.
SECTION I
SECTION I
SECTION G
ADJUST MENU
Wake
UnOccupied
Occupied
Sleep
AUTO, OFF,
10% to 90%, ON
Default = AUTO
OFF, 70 to 180°F
(OFF, 21.0 to 82.0°C)
Default = 110°F
(43.0°C)
40 to 80°F, OFF
(4.5 to 26.5°C, OFF)
Default = OFF
LTD
USER
INST
ADV
ADV
ADV
FAN OPERATION SECTION I
The minimum percentage of time the ventilation fan
operates during each event.
Auto operates with heat or cool.
On operates continuously.
% sets a minimum On time for each cycle.
Note: This item is only available when the Fan Mode
is set to 1 or F1 Vent is set to On.
HEAT COIL MINIMUM SECTION I
Set the minimum coil temperature before turning on
the fan for heating. This allows the fan coil to heat up
and prevents the fan from blowing cold air.
Note: This item is only available when H1 or H2
Terminal is set to Coil, Sensor 2 is set to Coil and
Fan Mode is set to 2.
COOL COIL MAXIMUM SECTION I
Set the maximum coil temperature before turning on
the fan for cooling. This allows the fan coil to cool off
and prevents the fan from blowing hot air.
Note: This item is only available when Cool Stage
is set to 1, Sensor 2 is set to Coil and Fan Mode is
set to 1 or 2.
Set the fan’s delay time after a heating zone calls for
heat. This allows the fan coil to heat up and prevents
the fan from blowing cold air.
Note: This item is only available when H1 or H2
Terminal is set to Coil or Furnace, Sensor 2 is not
set to Coil and Fan Mode is set to 2.
FAN PURGE SECTION I
Set how long the fan operates after a call for heating or
cooling ends. This purges any heat or cold remaining
in the fan coil.
Note: This item is only available when H1 or H2
Terminal is set to Coil or Furnace, Sensor 2 is not
set to Duct and Fan Mode is set to 1 or 2.
HEAT PURGE FAN SECTION I
Set the minimum duct temperature. This purges heat
from the coil after the call for heat is removed.
Note: This item is only available when H1 or H2
Terminal is set to Coil or Furnace, Sensor 2 is set to
Duct and Fan Mode is set to 2.
COOL PURGE FAN SECTION I
Set the maximum duct temperature. This purges cooling
from the coil after the call for cooling is removed.
Note: This item is only available when Cool Stage
is set to 1, Sensor 2 is set to Duct and Fan Mode is
set to 1 or 2.
SECTION I
ADJUST MENU
Continued on next page.
OFF, 200 to 2000 hr
Default = 500 hr
NONE, ZONE, CTRL
Default = CTRL
40 to 100°F, OFF
(4.5 to 38.0°C, OFF)
Default = 72°F
(22.0°C)
INST
ADV
ADV
INST
ADV
FILTER SECTION J
Set the number of hours Fan 1 should operate before
you replace the filter. When the time expires, the filter
symbol appears.
Note: This item is only available when the Fan Mode
is set to 1 or 2.
WARM WEATHER SHUT DOWN
Set the outdoor temperature at which warm weather
shutdown occurs. Select whether the thermostat
follows the tN4 System Control’s or the zone’s WWSD
for scheduled events.
WWSD OCCUPIED AND WAKE
Set the Warm Weather Shut Down (WWSD) temperature
during Occupied and Wake events.
Note: This item is only available when WWSD is set
to Zone.
Set the Warm Weather Shut Down temperature during
Unoccupied and Sleep events.
Note: This item is only available when WWSD is set
to Zone.
CWSD OCCUPIED AND WAKE SECTION S
Set the Cold Weather Shut Down (CWSD) temperature
for the cooling system during the Occupied and Wake
events.
Note: This item is only available when Cool Stage
is set to 1.
CWSD UNOCCUPIED AND SLEEP SECTION S
Set the Cold Weather Shut Down temperature for
the cooling system during the Unoccupied and Sleep
events.
Note: This item is only available when Cool Stage
is set to 1.
OPTIMUM START / STOP SECTION M
Select whether to use Optimum Start / Stop for heating,
cooling, or both.
Note: This item is only available when either a heating
schedule and / or a cooling schedule is selected.
Heat can be selected if the heating schedule setting
is on. Cool can be selected if the cooling schedule
setting is on, and Cool Stages is set to 1. To select
H/C, both schedules must be on with Cool Stages
set to 1.
Lo, 2, 3, Hi
ADV
Default = Hi
After the last item, the control returns to the first item in the menu.
Select the radiant heating load relative to the overall
heating load.
Note: This item is only available when H1 Terminal
is set to HRF1 or HRF2. H2 Terminal is set to Coil,
Convector, Radiator, Baseboard or Other, and Sensor
1 and 2 are not set to FLOR.
SECTION P