Introduction
The tekmarNet®4 thermostat 545 operates two stages of heating equipment, one stage of cooling equipment, and one fan. The fan operation includes logic to operate ventilation. The 545 can operate as a stand alone device, or communicate with a group of tekmarNet®4 thermostats.
Features
tN4 Compatible
Automatic Heat / Cool Switchover
2 Auxiliary Temperature Sensor Inputs
Pulse Width Modulation
Programmable Setback and Setup Scheduling
Scenes
Cooling Group
Radiant Base Load
Y1 Rc G1 G1
Com
S2
S1
tN4
C
R
W1
Rh1 Rh2
W2
tNt 545
Two Stage Heat, One Stage Cool, One Fan
Power: 24 V (ac) ±10% 60 Hz 1.5 VA Relays: 24 V (ac) 2 A
992-02
Meets Class B: Canadian ICES, FCC Part 15
Terminal Functions
G1
Fan 1 Relay
G1
Fan 1 Relay
Rc
Power Cooling
Y1
Cool 1 Relay
Com
Sensor Common
S2
Sensor 2
No Power
S1
Sensor 1
To isolate relay, cut jumper
tN4 C R Rh1 W1 Rh2 W2
DIP Switch Functions
®
tekmarNet 4 Power Neutral Power 24 V (ac) Heat 1 Relay Heat 1 Relay Heat 2 Relay Heat 2 Relay
1 of 40 © 2008 D 545 - 07/08
Table of Contents
Table of Contents ............................................................2
Display and DIP Switches ..............................................2
Dip Switches ...........................................................2
Access Levels .........................................................3
Display and Symbols Description............................3
User Interface .........................................................4
Setup ..............................................................................5
View Menu .............................................................5
Adjust Menu ............................................................6
Time Menu ............................................................13
Scene Menu .......................................................... 14
Schedule Menu ..................................................... 16
Monitor Menu ........................................................ 19
Test Menu ............................................................21
Miscellaneous Menu ............................................22
Testing .........................................................................23
Thermostat Operation ..................................................24
Auxiliary Sensors .................................................24
Heat or Cool Mode of Operation ..........................25
Adjusting the Temperature ...................................25
Cycles Per Hour ...................................................26
Heating Terminal Units .........................................26
Heating Operation ................................................27
Cooling Operation ................................................29
Cool Groups .........................................................29
Fan Operation ......................................................29
Filter Change .......................................................31
Time Clock ........................................................... 31
Setting the Schedule .............................................31
Optimum Start / Stop ...........................................32
Scenes .................................................................33
Away Hold ............................................................34
Radiant Base Load ..............................................34
Offset ...................................................................35
Warm Weather Shutdown ....................................35
Cold Weather Shutdown ......................................35
Units of Temperature ............................................35
Backlight ..............................................................35
tN4 Address .........................................................35
Pump Exercising ...................................................35
Error Messages ............................................................36
Cleaning the Thermostat ......................................39
Warranty .......................................................................40
Display and DIP Switches
Dip Switches
tN4 System Control (DIP Switch #2)
A tN4 System Control is a control, not a thermostat, that the 545 thermostat connects to through the tN4 bus. All tN4 compatible Outdoor Reset Modules are tN4 System Controls.
If the thermostat is connected to a tN4 System Control, set the tN4 System Control DIP switch to tN4 System Control (down position).
If the thermostat is not connected to a tN4 System Control, set the tN4 System Control DIP switch to None
(up position).
Lock / Unlock (DIP Switch #1)
Use the Lock / Unlock DIP switch to lock or unlock the Access Level of the 545.
To unlock the Access Level, set the DIP switch to the unlocked (down) position.
To lock the Access Level, set the DIP switch to the locked (up) position. Once locked, a padlock is displayed in the lower right corner of the display and the Access Level cannot be changed.
Y1 Rc G1 G1
Com
S2
S1
tN4
C
R
W1
Rh1 Rh2
W2
Note: The tN4 System Control’s Lock / Unlock DIP switch overrides the Lock / Unlock DIP switch on the 545. Set the tN4 System Control’s Lock / Unlock DIP switch to the Unlock position before Access Levels can be changed on the thermostat.
© 2008 D 545 - 07/08 2 of 40
Access Levels
The Access Level restricts the number of Menus, Items and Adjustments that can be accessed by the user. The Access Level setting is found in the Miscellaneous (MISC) menu. Select the appropriate access level for the people who work with the thermostat on a regular basis.
The 545 has five Access Levels:
Advanced (ADV): access to all settings
Installer (INST): settings required for installation
User (USER): for property owners
Limited (LTD): limited temperature adjustment
Secure (SEC): for commercial and public installations
Display
Menu Field
Displays the
current menu
Status Field
Displays the current status
of the control’s inputs, outputs and operation
For more information, see the Misc (Miscellaneous) Menu section.
In the following menu tables, the access level the item is visable in is shown in the access column.
To adjust the Access Level:
1. Set the Unlock / Lock DIP switch to the unlock position.
If a tN4 System Control is connected to the 545, the Unlock / Lock DIP switch on the tN4 System Control must be set to the unlock position.
2. Use the Menu button to select the Misc menu.
3. Use the Item button to select the Access menu item.
4. Use the Up and Down button to select the required
Access Level.
Item Field
Displays an abbreviated name of the selected item
Number Field
Displays the current value of the selected item
Symbols Description
MODE OF OPERATION
Displays whether the device is in heating or cooling mode.
FIRST STAGE HEAT
First stage heating is operating.
SECOND STAGE HEAT
Second stage heating is operating.
FIRST STAGE COOL
First stage cooling is operating.
FAN
Fan is operating.
FILTER
Replace the filter.
SCHEDULE MASTER
Indicates that this thermostat is a schedule master.
tN4 COMMUNICATION
A tN4 network is detected.
COOL GROUP MASTER
This thermostat is a cool group master.
LOCK
The Access Levels are locked. A menu option is visible but not adjustable.
OPTIMUM START / STOP
The Optimum Start or Optimum Stop feature is active.
WARNING
An error is present.
TEMPORARY HOLD
The temperature has been temporarily adjusted from the scheduled event.
SCHEDULED EVENT
Displays the current scheduled event.
3 of 40 © 2008 D 545 - 07/08
User Interface
Use the User Interface available on the Liquid Crystal Display (LCD) to setup and monitor the operation of the thermostat. Use the four push buttons below the LCD (Menu, Item, Up, Down) to select settings. As you enter settings, record the settings in the Job Record J 545.
Menu
The menus display in the Menu Field at the left of the LCD.
Eight menus are available:
View
Adjust
Time
Scene
Schedule
Monitor
Test
Miscellaneous
To select a menu, press and release the Menu button.
Item
In each menu, a group of items can be selected. The abbreviated name of the selected item displays in the Item field of the LCD display.
To view the next available item, press and release the Item button.
To view the previous item, hold down the Item button and press and release the Up button.
Adjusting a Setting
To adjust a setting:
1. Use the Menu button to select the appropriate menu.
2. Use the Item button to select a menu item.
3. Use the Up or Down button to adjust the setting.
Default Item
To set the default item in the View Menu, display the
item for more than five seconds.
After navigating menus, the display reverts back to the default item after 60 seconds of button inactivity.
Copy Settings
To save time in setting thermostats, you can copy the settings from one tN4 thermostat to a second tN4 thermostat.
Refer to the COPY item in the Misc menu on page 22.
Continue to next Menu
Continue to next Item
Continue to next Item
Continue to next Item
© 2008 D 545 - 07/08 4 of 40
Display Menus
View Menu (1 of 2)
The View menu items display the current operating temperatures and status information of the system.
Item Field Range
VIEW MENU
-58 to 212°F
(-50.0 to 100.0°C)
-58 to 212°F
(-50.0 to 100.0°C)
– – –, 40 to 95°F
(– – –, 4.5 to 35.0°C)
– – – (if no recent
message),
-58 to 212°F
(-50.0 to 100.0°C)
-58 to 212°F
(-50.0 to 100.0°C)
Access
SEC
LTD
USER
INST
ADV
SEC
LTD
USER
INST
ADV
USER
INST
ADV
SEC
LTD
USER
INST
ADV
SEC
LTD
USER
INST
ADV
Description
COOL AVERAGE SECTION H
Average room temperature of the cool group master and members.
Note: This item is only available when Cooling Stage is set to 1 and this thermostat is a cool group master.
ROOM SECTION A
Current air temperature in the room. Note: This item is only available when the Room Sensor
is set to On or Sensor 1 or 2 is set to Room.
ROOM SET SECTION A
Selected room temperature. Note: This item is only available when the Room Sensor
is set to On or Sensor 1 or 2 is set to Room.
OUTDOOR SECTION A
Current temperature at the outdoor sensor. Note: This item is only available when an outdoor
sensor is connected to the tN4 network.
FLOOR SECTION A
Current floor temperature. Note: This item is only available when Sensor 1 or
2 is set to Floor.
-58 to 212°F
(-50.0 to 100.0°C)
-58 to 212°F
(-50.0 to 100.0°C)
Continued on next page.
5 of 40 © 2008 D 545 - 07/08
USER
INST
ADV
INST
ADV
REMOTE SENSOR
Current temperature at the remote sensor location. Note: This item is only available when Sensor 1 is
set to Remote.
COIL SENSOR SECTION A
Current temperature at the coil sensor. Note: This item is only available when Sensor 2 is
set to Coil.
SECTION A
View Menu (2 of 2)
Item Field Range
-58 to 212°F
(-50.0 to 100.0°C)
-22 to 266°F
VIEW MENU
After the last item, the control returns to the first item in the menu.
(-30.0 to 130.0°C)
Access
INST
ADV
INST
ADV
Adjust Menu (1 of 7)
Description
DUCT SENSOR
Current temperature at the duct sensor. Note: This item is only available when Sensor 2 is
set to Duct.
SUPPLY TEMPERATURE OF TN4 BUS
Actual water temperature of the tN4 bus for the first stage of heat.
Note: This item is only available when the thermostat is connected to an Outdoor Reset Module and the DIP switch is set to tN4 System Control.
The Adjust Menu items are the programmable settings used to operate the mechanical equipment.
SECTION A
SECTION F
Item Field Range Access Description
ADJUST MENU
Wake
UnOccupied
Occupied
YES, NO
Default = NO
OFF, HEAT,
AUTO, COOL
Default = AUTO
40 to 95°F
(4.5 to 35.0°C)
Default = 70°F (21.0°C)
Default = 62°F (16.5°C)
Default = 70°F (21.0°C)
USER
INST
ADV
USER
INST
ADV
LTD
USER
INST
ADV
CLEAR FILTER SECTION J
Indicates when to reset the air filter timer. Note: This item is only available when Filter is set to
ON, the air filter timer has expired and the Fan Mode is set to 1 or 2.
MODE OF OPERATION SECTION B
Mode of operation of the thermostat or cool group.
SET HEAT SECTION C Selected air heating temperature for each event. Note: At the Limited Access Level, you can only
adjust the temperature +/-3°F (1.5°C) from the last setting.
Away is only available when Scenes are turned on.
Sleep
Away
Continued on next page.
© 2008 D 545 - 07/08 6 of 40
Default = 62°F (16.5°C)
Default = 62°F (16.5°C)
Adjust Menu (2 of 7)
Item Field Range Access Description
Wake
UnOccupied
Occupied
50 to 100°F
(10.0 to 38.0°C)
Default = 78°F (25.5°C)
Default = 85°F (29.5°C)
Default = 78°F (21.0°C)
LTD
USER
INST ADV
SET COOL SECTION C
Select the cooling room temperature for each event. Note: At the Limited Access Level, you can only
adjust the temperature +/-3°F (1.5°C) from the last setting.
Away is only available when Scenes are turned on.
Sleep
Away
Wake
UnOccupied
Occupied
Sleep
ADJUST MENU
Default = 85°F (29.5°C)
Default = 85°F (29.5°C)
OFF, 40 to 122°F
(OFF, 4.5 to 50.0°C)
Default = 70°F (21.0°C)
Default = OFF
Default = 70°F (21.0°C)
Default = OFF
40 to 122°F
(4.5 to 50.0°C) Default = 85°F
(29.5°C)
OFF, ROOM,
FLOR (Floor),
REM (Remote)
Default = OFF
LTD
USER
INST ADV
ADV
INST ADV
FLOOR MINIMUM SECTION F
Select the minimum floor temperature for each event.
Note: This item is only available when Sensor 1 or 2 is set to Floor. At the Limited Access Level, you can only adjust the temperature +/-3°F (1.5°C) from the last setting.
FLOOR MAXIMUM SECTION F
Maximum floor temperature. Note: This item is only available when Sensor 1 or
2 is set to Floor.
SENSOR 1 SECTION A
Select the type of sensor connected to auxiliary sensor input 1.
OFF, ROOM,
FLOR (Floor),
OUT (Outdoor),
COIL, DUCT
Default = OFF
OFF, ON
Default = ON
Continued on next page.
7 of 40 © 2008 D 545 - 07/08
INST ADV
INST ADV
SENSOR 2 SECTION A
Select the type of sensor connected to auxiliary sensor input 2.
ROOM SENSOR SECTION A
Selects whether the built-in room sensor is functional.
Adjust Menu (3 of 7)
Item Field Range Access Description
ADJUST MENU
SYNC, AUTO
2 to 12
Default = AUTO
CTRL, HRF1, HRF2,
COIL, CONV, RAD,
BASE, OTHR ,FURN
Default =CTRL
OFF, ON
Default = ON
OFF, ON
Default = OFF
NONE, CTRL, HRF1,
HRF2, COIL, CONV,
RAD, BASE, OTHR,
FURN
Default =CTRL
ADV
INST
ADV
INST
ADV
INST
ADV
INST
ADV
HEAT CYCLES PER HOUR
Select the number of heating cycles per hour. SYNC results in 5 CPH. All tN4 thermostats that are connected and have the SYNC setting selected synchronize their cycle to the same starting time.
Note: This item is only available when the tN4 System Control DIP switch is set to None.
HEAT 1 TERMINAL
Select the type of heating terminal for first stage heat.
Note: If CTRL is selected, the terminal unit selected on the tN4 System Control is used.
HEAT 1 PUMP SECTION F
Select whether the system, primary, or mixing pump on a tN4 System Control must operate while the first stage heat is operating.
Note: This item is only available when the H1 Terminal item is set to CTRL, HRF1, HRF2, Fan Coil, Convector, Radiator, or Baseboard.
HEAT 1 DELAY SECTION F
Select whether the system, primary, or mixing pump on a tN4 System Control is delayed to allow a first stage heat thermal motor zone valve to open. Select On for thermal motor, select Off for zone pump or motorized zone valve.
Note: This item is only available when the H1 Terminal item is set to CTRL, HRF1, HRF2, Fan Coil, Convector, Radiator, or Baseboard.
HEAT 2 TERMINAL SECTION E
Select the type of heating terminal for second stage heat. If NONE is selected, the second stage heat is disabled.
Note: If CTRL is selected, the terminal unit selected on the tN4 System Control is used.
SECTION E
SECTION D
BOIL, MIX1,
MIX2, MIX3
Default = BOIL
OFF, ON
Default = ON
Continued on next page.
© 2008 D 545 - 07/08 8 of 40
ADV
INST
ADV
HEAT 2 SOURCE SECTION F
Select the tN4 bus on which the second stage heat zone operates. This setting determines water temperature and system pump operation.
Note: This item is only available when the H2 Terminal item is set to CTRL, HRF1, HRF2, Fan Coil, Convector, Radiator, or Baseboard.
HEAT 2 PUMP SECTION F
Select whether the system, primary, or mixing pump on a tN4 System Control must operate while the second stage heat is operating.
Note: This item is only available when the H2 Terminal item is set to CTRL, HRF1, HRF2, Fan Coil, Convector, Radiator, or Baseboard.
Adjust Menu (4 of 7)
Item Field Range Access Description
OFF, ON
Default = OFF
NONE, 1 to 16
Default = NONE
NONE, 1 to 16
Default = NONE
INST
ADV
ADV
ADV
HEAT 2 DELAY
Select whether the system, primary, or mixing pump on a tN4 System Control is delayed to allow a second stage heat thermal motor zone valve to open. Select On for thermal motor, select Off for zone pump or motorized zone valve.
Note: This item is only available when the H2 Terminal item is set to CTRL, HRF1, HRF2, Fan Coil, Convector, Radiator, or Baseboard.
COOL MASTER SECTION H
Select the cool group for which this thermostat is the master. Select None if this thermostat is not a cool group master.
Note: This item is only available when the thermostat is connected to a tN4 network and the Cool Stage is set to 1.
COOL MEMBER SECTION H
Select the cool group of which this thermostat is a member. Select None if this thermostat is not a cool group member.
Note: This item is only available when the thermostat is connected to a tN4 network, Cool Master is set to NONE and the Cool Stage is set to NONE.
SECTION F
ADJUST MENU
NONE, 1
Default = 1
0:30 to 6:00 min
Default = 2:00
0:30 to 10:00 min
Default = 5:00
AUTO, 2 to 12
Default = AUTO
10 to 180 min
Default = 30
INST
ADV
ADV
ADV
ADV
ADV
COOL STAGES SECTION G
Select the number of cooling stages. Select None if cooling is not used.
MINIMUM COOL RUN TIME SECTION G
Select the minimum running time for the cooling equipment.
Note: This item is only available when the Cool Stage is set to 1.
MINIMUM COOL OFF TIME SECTION G
Select the minimum off time for the cooling equipment.
Note: This item is only available when the Cool Stage is set to 1.
COOL CYCLES PER HOUR SECTION D
Select the number of cooling cycles per hour. Note: This item is only available when the Cool Stage
is set to 1.
INTERLOCK SECTION G
Select how long heating must be off before cooling starts.
Note: This item is only available when the Cool Stage is set to 1.
Continued on next page.
9 of 40 © 2008 D 545 - 07/08
Adjust Menu (5 of 7)
Item Field Range Access Description
HEAT, COOL
Default = COOL
NONE, 1, 2
Default = 1
OFF, ON
Default = OFF
OFF, 1 to 60 min
Default = OFF
ADV
INST
ADV
ADV
ADV
PRIORITY HEATING OR COOLING
Select whether heating has priority or cooling has priority.
Note: This item is only available when the Cool Stage is set to 1.
FAN MODE
Select the operation of the Fan 1 output.
FAN 1 VENTILATION
Select whether Fan 1 output operates to provide ventilation.
Note: This item is only available when the Fan Mode is set to None.
VENTILATION PRE-VENT SECTION I
Select how long the ventilation operates continuously prior to the Wake or Occupied events.
Note: This item is only available when the Fan Mode is set to None and F1 Vent is set to On.
SECTION I
SECTION I
SECTION G
ADJUST MENU
Wake
UnOccupied
Occupied
Sleep
AUTO, OFF,
10% to 90%, ON
Default = AUTO
OFF, 70 to 180°F
(OFF, 21.0 to 82.0°C)
Default = 110°F
(43.0°C)
40 to 80°F, OFF
(4.5 to 26.5°C, OFF)
Default = OFF
LTD
USER
INST
ADV
ADV
ADV
FAN OPERATION SECTION I
The minimum percentage of time the ventilation fan operates during each event.
Auto operates with heat or cool. On operates continuously. % sets a minimum On time for each cycle. Note: This item is only available when the Fan Mode
is set to 1 or F1 Vent is set to On.
HEAT COIL MINIMUM SECTION I
Set the minimum coil temperature before turning on the fan for heating. This allows the fan coil to heat up and prevents the fan from blowing cold air.
Note: This item is only available when H1 or H2 Terminal is set to Coil, Sensor 2 is set to Coil and Fan Mode is set to 2.
COOL COIL MAXIMUM SECTION I
Set the maximum coil temperature before turning on the fan for cooling. This allows the fan coil to cool off and prevents the fan from blowing hot air.
Note: This item is only available when Cool Stage is set to 1, Sensor 2 is set to Coil and Fan Mode is set to 1 or 2.
Continued on next page.
© 2008 D 545 - 07/08 10 of 40
Adjust Menu (6 of 7)
Item Field Range Access Description
0:00 to 2:00 min
(10 sec increments)
Default = 0:30
0:00 to 3:00 min
(10 sec increments)
Default = 0:30
70 to 160°F, OFF
(21.0 to 71.0°C, OFF)
Default = 110°F
(43.0°C)
OFF, 40 to 70°F
(OFF, 4.5 to 21.0°C)
Default = 60°F
(15.5°C)
ADV
ADV
ADV
ADV
FAN DELAY
Set the fan’s delay time after a heating zone calls for heat. This allows the fan coil to heat up and prevents the fan from blowing cold air.
Note: This item is only available when H1 or H2 Terminal is set to Coil or Furnace, Sensor 2 is not set to Coil and Fan Mode is set to 2.
FAN PURGE SECTION I
Set how long the fan operates after a call for heating or cooling ends. This purges any heat or cold remaining in the fan coil.
Note: This item is only available when H1 or H2 Terminal is set to Coil or Furnace, Sensor 2 is not set to Duct and Fan Mode is set to 1 or 2.
HEAT PURGE FAN SECTION I
Set the minimum duct temperature. This purges heat from the coil after the call for heat is removed.
Note: This item is only available when H1 or H2 Terminal is set to Coil or Furnace, Sensor 2 is set to Duct and Fan Mode is set to 2.
COOL PURGE FAN SECTION I
Set the maximum duct temperature. This purges cooling from the coil after the call for cooling is removed.
Note: This item is only available when Cool Stage is set to 1, Sensor 2 is set to Duct and Fan Mode is set to 1 or 2.
SECTION I
ADJUST MENU
Continued on next page.
OFF, 200 to 2000 hr
Default = 500 hr
NONE, ZONE, CTRL
Default = CTRL
40 to 100°F, OFF
(4.5 to 38.0°C, OFF)
Default = 72°F
(22.0°C)
INST
ADV
ADV
INST
ADV
FILTER SECTION J
Set the number of hours Fan 1 should operate before you replace the filter. When the time expires, the filter symbol appears.
Note: This item is only available when the Fan Mode is set to 1 or 2.
WARM WEATHER SHUT DOWN
Set the outdoor temperature at which warm weather shutdown occurs. Select whether the thermostat follows the tN4 System Control’s or the zone’s WWSD for scheduled events.
WWSD OCCUPIED AND WAKE
Set the Warm Weather Shut Down (WWSD) temperature during Occupied and Wake events.
Note: This item is only available when WWSD is set to Zone.
SECTION R
SECTION R
11 of 40 © 2008 D 545 - 07/08
Adjust Menu (7 of 7)
Item Field Range Access Description
ADJUST MENU
40 to 100°F, OFF
(4.5 to 38.0°C, OFF)
Default = 60°F
(15.5°C)
OFF, 35 to 100°F
(OFF, 1.5 to 38.0°C)
Default = OFF
OFF, 35 to 100°F
(OFF, 1.5 to 38.0°C)
Default = OFF
HEAT, COOL,
H/C, OFF
Default = H/C
INST
ADV
ADV
ADV
INST
ADV
WWSD UNOCCUPIED AND SLEEP SECTION R
Set the Warm Weather Shut Down temperature during Unoccupied and Sleep events.
Note: This item is only available when WWSD is set to Zone.
CWSD OCCUPIED AND WAKE SECTION S
Set the Cold Weather Shut Down (CWSD) temperature for the cooling system during the Occupied and Wake events.
Note: This item is only available when Cool Stage is set to 1.
CWSD UNOCCUPIED AND SLEEP SECTION S
Set the Cold Weather Shut Down temperature for the cooling system during the Unoccupied and Sleep events.
Note: This item is only available when Cool Stage is set to 1.
OPTIMUM START / STOP SECTION M
Select whether to use Optimum Start / Stop for heating, cooling, or both.
Note: This item is only available when either a heating schedule and / or a cooling schedule is selected.
Heat can be selected if the heating schedule setting is on. Cool can be selected if the cooling schedule setting is on, and Cool Stages is set to 1. To select H/C, both schedules must be on with Cool Stages set to 1.
Lo, 2, 3, Hi
ADV
Default = Hi
After the last item, the control returns to the first item in the menu.
© 2008 D 545 - 07/08 12 of 40
RADIANT BASE LOAD
Select the radiant heating load relative to the overall heating load.
Note: This item is only available when H1 Terminal is set to HRF1 or HRF2. H2 Terminal is set to Coil, Convector, Radiator, Baseboard or Other, and Sensor 1 and 2 are not set to FLOR.
SECTION P