Schneider Electric TAC Xenta 421A, TAC Xenta 422A Installation Instructions

TAC Xenta® 421A/422A
02-00002-01-en
Universal Input and Digi­tal Output Module
LONMARK CONFIGURATION AND VARIABLES
TAC Xenta 421A/422A can be used as a normal Xenta I/O module or as a certifi ed L
• 4 Universal Inputs (UI)
• 5 Digital Outputs (DO)
In addition, TAC Xenta 422A has fi ve manual switches, one for each DO that can be set
• manual Off
• manual On
• Auto
To confi gure the inputs and outputs, and to specify the trans­mission of values, either ordinary TAC Menta®/Xenta confi gu­ration or nci SNVTs are used. The usage is explained overleaf ("SNVT vs TAC Xenta I/O module Communication".)
The use of SNVTs requires explicit information listed below.
UI Confi guration
Each of the four UI:s (1-4) is confi gured with
nciInput1-4 0 = not connected (default value) 1 = 1.8 kohm thermistor 2 = DI, green indication 3 = 0-10 V 4 = 0-20 mA 5 = 10 kohm thermistor 6 = DI, red indication 7 = DI, green inverted indication 8 = DI, red inverted indication
ONMARK® device. It has
Off: state=0, value=0 On: state=1, value=100 Invalid: state=255
nvoTemp1-4 (thermistor, any type; invalid=327.67)
UI Value Transmission
The UI value will be transmitted
a) when the change in value is large enough (set individually
b) at a specifi ed time interval (common for all UIs)
a) is determined by
nciSndDelta1-4 (dimensionless; default value=2) Size of change to cause transmission Ex.: 1 means
- if confi gured as analog input: 1%
- if confi gured as temperature input: 1 °
If the UI is confi gured as a digital input, a status change will always be transmitted.
b) is determined by
nciSndHrtBt "Heartbeat" interval in seconds (default=60)
A valid and confi gured UI value will be sent at least once dur­ing each interval regardless of change.
The transmissions will be distributed over time to avoid mo­mentary communication overload.
Confi guration Instruction
per UI)
DO Values
If confi gured to be a digital input (DI, any type), its function is further determined by the corresponding bit in
nciDigInNONC:
If bit=0: NO, normally open (default value)
If bit=1: NC, normally closed
Pulse counting is not available for SNVT communication.
UI Values
Depending on the UI confi guration, each UI n=1-4 generates a valid value in one of these (the other two are set invalid):
nvoAnalog1-4 (0-10 V or 0-20 mA, converted to 0-100%; invalid=163.835)
nvoDigital1-4 (DI, any type)
02-00002-01-en, Nov 2009 (4)
Bit 0 Bit 15
DI 1 DI 2 DI 3 DI 4
The digital output values to the output (DO, n=1-5) are re­ceived as:
nviDO1-5 switch:state state=0 or >1: Off state=1: On
For the TAC Xenta 422A, the DO values may be overridden by manual switches. Their status is indicated in
nvoHandBoard1-5 switch:state. state=0: manual Off state=1: manual On state=255 ('invalid'): Auto
Any DO status change will immediately be transmitted.
DO Values in the Off-line Condition
The DO values are expected to be updated regularly. How­ever, this may be prevented by communication failure or, tem­porarily, after power-up.
(continued ...)
To determine if all nviDO1-5 are to be considered valid, an interval counter is used:
nciRcvHrtBt No. of seconds until nviDO1-5 are consid-
If bit=1: Use default value as specifi ed by
nciOffl ineVal, using the following bits, where the value to be used is specifi ed (0 or 1). (Default value=0.)
ered invalid. (0: function is not used; default value.)
If this happens, due to communication failure, the behavior is determined by
nciOffl ineBeh, using the following bits:
Bit 0 Bit 15
DO 1 DO 2 DO 3 DO 4 DO 5
If bit=0: Keep latest value (default).
SNVT vs TAC XENTA I/O MODULE COMMUNICATION
Bit 0 Bit 15
DO 1 DO 2 DO 3 DO 4 DO 5
The TAC Xenta 421A/422A can be used in networks with either LONMARK communication or TAC Xenta I/O module com­munication. The device automatically determines which type of communication to use.
Green
Power-up
SNVT
received
Green blink at comm. or 0.1 Hz
In the Power-up state, the green LED blinks "Off-line". The
State diagram
SNVT
TAC Xenta I/O module comm. established
off-line blink
TAC Xenta I/O module communication established
TAC Xenta I/O module
communication
I/O on-line: green 0.5 Hz
device is open for both SNVT and TAC Xenta I/O module communi cation.
Previous confi guration, if defi ned, will apply until a change is initiated.
SNVT received
The device enters the SNVT state. The device is confi gured when the nci:s are updated. The green LED will light up when there is communication or approximately every 10 seconds.
SNVT transmission is determined by the nciSndDelta1-4 or the nciSndHrtBt values.
The device remains in the SNVT state until a TAC Xenta I/O module communication state is established, or until the next power-up. In the SNVT state it is possible to change the con­fi guration by updating the network confi guration inputs nci:s.
TAC Xenta I/O module Communication
The TAC Xenta I/O module communication state is accepted only after a thorough protocol initiation. This may be initiated at any time.
In the TAC Xenta I/O module communication state, no nvi:s or nci:s can be used. The green LED blinks on-line at about
0.5 Hz.
Input SNVTs are ignored, also when the device is off-line from the controller.
However, output SNVT transmission is still performed using a hard-coded interval of about 10 seconds.
Once in the TAC Xenta I/O module communication state, the device can only enter the SNVT state after a new Power-up. At this stage all nci:s must be updated, since the same memory area is used by both the SNVT and TAC Xenta I/O module communication confi guration parameters.
Note! As the TAC Xenta I/O module communication state is a 'dead-end' (until power-up), any mis-addressed communi­cation may cause the I/O module to loose its SNVT communi­cation state.
TAC Xenta I/O module communication is inititiated by the con­troller at events specifi ed below. If an I/O module intended for SNVT communication has been used in another confi guration and happens to have an address that is used by the I/O mod­ule communication, the I/O module will be 'lost' in this state.
TAC Xenta I/O module communications will be initiated by the following events:
• Controller power-up
• I/O module power-up
• Controller application download
• Recovery after communication failure
Service pin
Red LED (Confi guration error)
- blinking: unconfi gured node
- steady: appl.less (or hw fault)
Green LED (Communication)
- SNVT: at communication or ~ once in 10 sec.s
- TAC Xenta I/O mod communication: on-line ~ every other sec; off-line ~ 5 blinks per sec
LED indicators on front panel
(4) 02-00002-01-en, Nov 2009
Loading...
+ 2 hidden pages