Schneider Electric MAx-305, MAx-318 Series, MAx-405 Through MAx-419 Series Data Sheet

Application

MA6-3xx, MA6-4xx, MA7-4xx,
MA8-3xx, MA8-4xx
(Hazardous Locations)
MA-3xx, MA5-318,
MA-4xx, MA5-419
(Standard)
For two-position operation of dampers, valves, and other equipment which require the return to normal position upon power interruption.
Hazardous location models offer a sturdy cast aluminum case with bolted cover. They have two 3/4" pipe tapped openings for joint s with rigid metal conduit. All wiring is brought out to separate termin als for ea se of installation. These factory enclosure and actuator assemblies are Underwriters Laboratories listed.
MAx-305 & MAx-318 Series
MAx-405 Through MAx-419
Series
Two-Position Actuators
General Instructions

Features

Compatible with most SPST control devices
Spring return
24, 120, 208, and 240 Vac models
Actuators with part number suffix "-500" are
equipped w
ith SPDT auxiliary
switch
Actuator has a rugged die cast aluminum housing
with
two 1/2” conduit openings
Hazardous location actuator housing has two 3/4"
p
ipe taped openings for rigid metal cond
con
nection
Oil immersed motor and gear train
uit

Applicable Literature

Electric/Electronic Products Catalog, F-27382
Valve Products Catalog, F-27384
Cross-Reference Guide, F-26789
Material Safety Data Sheet (MSDS) for BCS-51-185
Oil (Until Mar MAx
-4xx-x-x-3)
ch 2002) (MAx-3xx-x-x-3 an
d
AV -29x V alve Linkage for Hazard ous Location Gear
T
rain Actuators General Instructions, F-27441.
Apparatus for Hazardous Locations EN-56-2,
F-
18451.
AV-390 Series, Valve Linkage for Gear Train
Actu
Material Safety Data Sheet (MSDS) for BCS-51-168
Printed in U.S.A. 6/12 © Copyright 2012 Schneider Electric All Rights Reserved. F-06491-32
ators General Instructions, F-24376.
Oil (
Until Feb. 1989)
Material Safety Data Sheet (MSDS) for
BCS-
51-185-1 Oil (Current) (MAx-3xx-x-x-4 an
MAx
-4xx-x-x-4)
High Temperature Exposure Performance (UL 555S)
MAx-31x-x-x-4, MAx-41x-x-x-4 Series Actuator En
gineering Information EN-216, F-27068
d
s

SPECIFICATIONS

Actuator Inputs
Connections: Coded screw terminals. Control Circuit: Two-wire. Power Input: See Table-1.
Actuator Outputs
Torque: See Table-1. Shaft Rotation:
MA-305, MA-405, MA6-305, MA6-405, CW 180° when power is applied.
MA-318, MA-41x, MAx-318, MAx-41x, CW 180° when power is applied. Spring Return: CCW to the original position when the actuator is de-energized. Auxiliary Switch (-500 Models): SPDT makes (or breaks) the circuit at the powered end of
stroke.
Environment
Ambient Temperature Limits:
Shipping & Storage, -40 to 136 °F (-40 to 58 °C).
Operating, -40 to 136 °F (-40 to 58 °C).
Humidity: 5 to 95% RH, non-condensing.
Location: NEMA Type 4 when used with the gasket (provided) and water-tight conduit
connectors (not provided), optional hazardous location models.
Agency Listings:
US Standard UL 873, Underwriters Laboratories (File #E9429 XAPX, Temperature
Indicating and Regulating Equipment).
Candadian Standard C22.2 No. 24: Underwriters Laboratories (File #E429 Category
XAPX7, Temperature Indicating and Regulating Equipment).
Hazardous Location Models, UL file #E29291. Designed for use in hazardous locations
N.E.C., Class 1, Groups C and D, and Class 2, Groups E, F , and G. Temperature code T6 for
hazardous housing.
T able-1 Model Chart.
Power
Part Number
MA-305 MA-305-500 Yes MA-405 MA-405-500 Yes MA-318 MA-318-500 Yes MA-416 MA-416-500 Yes MA-418 MA-418-500 Yes MA-419 MA-419-500 Yes MA5-419 MA5-419-500 Yes
a 4.4 FLA, 26.4 LRA @ 24 or 120 Vac; 2.4 FLA, 13.2 LRA @ 240 Vac. b Spring return timing with full load opposing spring is approximately 60 sec.
Supply Auxiliary
60
60
50
Switch
No
No
No
No
No
No
No
Vac Hz Running Holding
24
120
24
208
120
240
a
Input
Watts
25
70
Running
25
Holding
56 56
48 48
92 32
104 38
108 42
120 39
VA Rated
Torque
lb-in. (N-m)
16 (1.8)
60 (6.8)
No Load
Timing in
Seconds at
75 °F (24 °C)
20
Mounting Application
b
Any Position
(Horizontal
Output Shaft
Position
Preferred)
Output Shaft
Must Be
Horizontal
Damper
Actuators
Damper and Valve Actuators
2 © Copyright 2012 Schneider Electric All Rights Reserved. F-06491-32
Table-2 Actuator Part Numbers for Hazardous Location Applications.
Standard
Part Numbers
Hazardous Location Actuator Assemblies
Part Numbers
a
b c d
Damper Actuators Valve Actuators
MA-305 MA6-305 — MA-305-500 — MA-405 MA6-405 — MA-405-500 MA6-405-500 — MA-318 MA6-318 MA8-318 MA-318-500 MA6-318-500 MA8-318-500 MA-416 MA6-416 — MA-416-500 MA6-416-500 — MA-418 MA6-418 MA8-418 MA-418-500 MA6-418-500 MA8-418-500 MA-419 MA6-419 — MA-419-500 MA6-419-500 — MA5-419 MA7-419 — MA5-419-500 MA7-419-500
a
MAx-31x-x-x-4 and MAx-41x-x-x-4 series actuators provide significantly improved high temperature exposure performance for use in smoke or fire dampers, or combination smoke and fire dampers. Refer to Engineering Information EN-216 (UL 555S), F-27068.
b
Class 1, Groups C & D, and Class 2, Groups E, F, and G hazardous locations; refer to EN-56-2.
c
Models for hazardous locations are only available as factory-built enclosure/actuator assemblies.
d
See standard actuator part number wiring diagrams for wiring terminations.

ACCESSORIES

Damper Only AM-111 Crank arm for 5/16" diameter damper shaft AM-112 Crank arm for 3/8" diameter damper shaft AM-113 Crank arm for 1/2" diameter damper shaft AM-115 Crank arm for 7/16" diameter damper shaft AM-122 Linkage connector straight type AM-123 Damper clip AM-125 5/16" diameter x 20" damper rod AM-125-048 5/16" diameter x 48" damper rod AM-132 Ball joint connector AM-161 Damper linkage kit AM-161-1 Damper linkage kit AM-301 90° mounting bracket (not used with MA6-xxx, MA7-xxx, & MA8-xxx)
Valve Only (To be used with 60 lb-in. (6.8 N-m) actuators only, excluding MA7-xxx & MA8-xxx)
AV-29 & AV-300 Linkage for 2-1/2" & 3" discontinued VB-9323 AV-391 Linkage for 1/2" to 2" VB-7xxx and 1/2" to 1-1/4" discontinued VB-9xxx AV-392 Linkage for 1-1/2" and 2” discontinued VB-9xxx AV-395 Linkage for 2-1/2" to 4" VB-931x or discontinued VB-92xx
Valve Only (To be used with 60 lb-in. (6.8 N-m) MA7-xxx & MA8-xxx hazardous location actuators only)
AV-291 Linkage for 1/2" to 2" VB-7xxx valves assembled with hazardous location actuator
assemblies.
AV-295 Linkage for 2-1/2" and 3" VB-9xxx valves assembled with hazardous location actuator
assemblies.
F-06491-32 © Copyright 2012 Schneider Electric All Rights Reserved. 3

TYPICAL APPLICATIONS (Wiring Diagrams)

3
2
4
MA-318, MA-416 MA-418, MA-419
Series Actuator
1 Actuator rotates 180° CW when thermostat or switch contacts are closed.
Actuator spring returns when thermostat or switch contacts are open.
2 High Input (Running)
3 Low Input (Holding)
4 Aux. Switch for -500 Models
NO
NC
Thermostat
or Switch
L1 or H
L2 or G
1
NC
NO
COM
Thermostat
L1 or H
L2 or G
1 Actuator rotates 180° CW when thermostat or switch contacts are closed.
Actuator spring returns when thermostat or switch contacts are open.
2 Aux. Switch for -500 Models
or Switch
Figure-1 Typical Wiring for MA-305 and MA-405 Series.
MA-305 MA-405
1
Series Actuator
Motor
Field Coil
COM
2
NC
NO
Figure-2 Typical Wiring for MA-318, MA-416, MA-418, and MA-419 Series.
4 © Copyright 2012 Schneider Electric All Rights Reserved. F-06491-32
Loading...
+ 8 hidden pages