Rockwell Automation 1769-OG16 User Manual

Compact TTL Output Module
Catalog Number 1769-OG16
Top ic Page
About This Publication 1
Important User Information 2
About the 1769-OG16 Module 5
Install the 1769-OG16 Module 6
Replace a Single Module Within a System 7
Mount Expansion I/O 8
Mount Module to Panel 8
Installation Instructions

About This Publication

Use this document as a guide when installing a Compact TTL Output Module.
Publication 1769-IN078A-EN-P - May 2006
2 Compact TTL Output Module

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you to identify a hazard, avoid a hazard, and recognize the consequences.
Labels may be located on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
Labels may be located on or inside the equipment, for example, a drive or motor, to alert people that surfaces may be dangerous temperatures.
Publication 1769-IN078A-EN-P - May 2006

Prevent Electrostatic Discharge

Compact TTL Output Module 3
ATTENTION
Electrostatic discharge can damage integrated circuits or semiconductors if you touch bus connector pins. Follow these guidelines when you handle the module:
Touch a grounded object to discharge static potential.Wear an approved wrist-strap grounding device.Do not touch the bus connector or connector pins.Do not touch circuit components inside the module.If available, use a static-safe work station.When not in use, keep the module in its static-shield box.

Remove Power

ATTENTION
Remove power before removing or inserting this module. When you remove or insert a module with power applied, an electrical arc may occur. An electrical arc can cause personal injury or property damage by:
sending an erroneous signal to your system’s field devices, causing
causing an explosion in a hazardous environment.
Electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance.
unintended machine motion.
Publication 1769-IN078A-EN-P - May 2006
4 Compact TTL Output Module

Hazardous Location Considerations

This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or nonhazardous locations only. The following WARNING statement applies to use in hazardous locations.
WARNING
Explosion Hazard
Substitution of components may impair suitability for Class I, Division 2.
Do not replace components or disconnect equipment unless power is switched off or the area is known to be nonhazardous.
Do not connect or disconnect components unless power is switched off or the area is known to be nonhazardous.
This product must be installed in an enclosure.
All wiring must comply with N.E.C. article 501-4(b).
Environnements dangereux
Cet équipement est conçu pour être utilisé dans des environnements de Classe 1, Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante s’applique à une utilisation dans des environnements dangereux.
AVERTISSEMENT
Danger D’explosion
La substitution de composants peut rendre cet équipement impropre à une utilisation en environnement de Classe 1, Division 2.
Ne pas remplacer de composants ou déconnecter l'équipement sans s'être assuré que l'alimentation est coupée et que l'environnement est classé non dangereux.
Ne pas connecter ou déconnecter des composants sans s'être assuré que l'alimentation est coupée ou que l'environnement est classé non dangereux.
Ce produit doit être installé dans une armoire.
Publication 1769-IN078A-EN-P - May 2006
Compact TTL Output Module 5

About the 1769-OG16 Module

Compact I/O is suitable for use in an industrial environment when installed in accordance with these instructions. Specifically, this equipment is intended for use
in clean, dry environments (Pollution degree 2
(2)
Over Voltage Category II
(IEC 60664-1)
Module Description
1
04812 15913 2 6 10 14
DC OUTPUT
TTL
10a
10
10b
8a
7a
04812 15913 2 6 10 14
DC OUTPUT
151173
TTL
5a
0
1
2
3
0
1
9
2
3
4
5
6
7
7b
T U P
0
T U
1
O C D
2
3
6 7
TT
L
7b
8b
7a
4 5
10 14
11 15
151173
8
12
91
3
2a
DANGER
Do Not Remove RTB Under Power
Unless Area is Non-Hazardous
+VDC
OUT 0
OUT 1
OUT 2
OUT 3
OUT 4
OUT 5
OUT 6
OUT 7
OUT 8
OUT 9
OUT 10
OUT 11
OUT 12
OUT 13
OUT 14
OUT 15
DC
COM
Ensure Adjacent Bus Lever is Unlatched/Latched Before/After Removing/Inserting Module
1769-OG16
2b
3
(1)
) and to circuits not exceeding
(3)
.
Labels
Item Description
1 Bus lever (with locking function)
2a Upper panel mounting tab
2b Lower panel mounting tab
3 Module status LED
4 Module door with terminal
identification label
4
6
5a Movable bus connector
with female pins
5b Stationary bus connector
with male pins
6 Nameplate label
7a Upper
tongue-and-groove slots
7b Lower
5b
tongue-and-groove slots
8a Upper DIN rail latch
8b Lower DIN rail latch
9 Write-on label (user ID tag)
10 Removable terminal block (RTB)
with finger-safe cover
10a RTB upper retaining screw
10b RTB lower retaining screw
(1)
Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that occasionally a temporary conductivity caused by condensation is expected.
(2)
Over Voltage Category II is the load level section of the electrical distribution system. At this level, transient voltages are controlled and do not exceed the impulse voltage capability of the product’s insulation.
(3)
Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC) designations.
Publication 1769-IN078A-EN-P - May 2006
6 Compact TTL Output Module

Install the 1769-OG16 Module

Attach the module to the controller or an adjacent I/O module before or after mounting. For mounting instructions, see Mount Module to Panel Using the Dimensional Template, or Mount Module to DIN Rail. To work with a system that is already mounted, see Replace a Single Module Within a System.
The following procedure shows you how to assemble the Compact I/O system.
3
4
2
1
1
5
6
30536-M
1. Disconnect power.
2. Check that the bus lever of the module to be installed is in the unlocked
(fully-right) position.
3. Use the upper and lower tongue-and-groove slots (1) to secure the modules
together (or to a controller).
4. Move the module back along the tongue-and-groove slots until the bus
connectors (2) line up with each other.
5. Use your fingers or a small screwdriver to push the bus lever back slightly to
clear the positioning tab (3).
Publication 1769-IN078A-EN-P - May 2006
Compact TTL Output Module 7
6. To allow communication between the controller and module, move the bus
lever fully to the left (4) until it clicks, making sure it is locked firmly in place.
ATTENTION
7. Attach an end-cap terminator (5) to the last module in the system by using
the tongue-and-groove slots as before.
8. Lock the end-cap bus terminator (6).
IMPORTANT
When attaching I/O modules, it is very important that the bus connectors are securely locked together to be sure of proper electrical connection.
You must use a 1769-ECR or 1769-ECL right or left end cap to terminate the end of the serial communication bus.

Replace a Single Module Within a System

The module can be replaced while the system is mounted to a panel (or DIN rail).
1. Remove power.
Refer to Remove Power on page 3.
2. Remove the upper and lower mounting screws from the module (or open
the DIN latches using a flat-blade or Phillips-style screwdriver).
3. Move the bus lever to the right to disconnect (unlock) the bus.
4. On the right-side adjacent module, move its bus lever to the right (unlock)
to disconnect it from the module to be removed.
5. Gently slide the disconnected module forward.
If you feel excessive resistance, check that the module is disconnected from the bus and that both mounting screws are removed (or DIN latches opened).
TIP
It may be necessary to rock the module slightly from front to back to remove it, or, in a panel-mounted system, to loosen the screws of adjacent modules.
Publication 1769-IN078A-EN-P - May 2006
8 Compact TTL Output Module
6. Be sure that the bus lever on the module and on the right-side adjacent
module are in the unlocked (fully right) position before installing the replacement module.
7. Slide the replacement module into the open slot.
8. Connect the modules by locking (fully left) the bus levers on the
replacement module and the right-side adjacent module.
9. Replace the mounting screws (or snap the module onto the DIN rail).

Mount Expansion I/O

ATTENTION
During panel or DIN rail mounting of all devices, be sure that all debris, including metal chips or wire strands, is kept from falling into the module. Debris that falls into the module could cause damage when cycling power.
Minimum Spacing
Maintain spacing from enclosure walls, wireways, or adjacent equipment. Allow 50 mm (2 in.) of space on all sides for adequate ventilation, as shown.
Side Side
Controller
Top
Compact I/O
Compact I/O
Bottom
Compact I/O
Compact I/O
End Cap
Compact I/O

Mount Module to Panel

Mount the module to a panel using two screws per module. Use M4 or #8 panhead screws. Mounting screws are required on every module.
Publication 1769-IN078A-EN-P - May 2006
Compact TTL Output Module 9

Mount Module to Panel Using the Dimensional Template

Spacing for single-wide modules 35mm (1.378 in.)
Spacing for one-and-a half-wide modules 52.5mm (2.067 in.)
Refer to host controller documentation for this dimension.
Host Controller
Note: Overall hole spacing tolerance: ±0.4mm (0.016 in.).
Locate holes every 17.5 mm (0.689 in.) to allow for a mix of single-wide and one-and-a-half-wide modules (for example, the 1769-OA16 module).

Mount Module to Panel Procedure Using Modules as a Template

This procedure lets you use the assembled modules as a template for drilling holes in the panel. Due to module-mounting hole tolerance, it is important to follow this procedure.
Refer to Mount Module to Panel Using the Dimensional Template on page 9 if you have sophisticated panel-mounting equipment.
1. On a clean work surface, assemble no more than three modules.
2. Using the assembled modules as a template, carefully mark the center of all
module-mounting holes on the panel.
3. Return the assembled modules to the clean work surface, including any
previously mounted modules.
4. Drill and tap the mounting holes for the recommended M4 or #8 screws.
5. Place the modules back on the panel, and check for proper hole alignment.
6. Attach the modules to the panel using the mounting screws.
TIP
7. Repeat steps 1 to 6 for any remaining modules.
If mounting more modules, mount only the last one of this group and put the others aside. This reduces the remounting time during drilling and tapping of the next group.
Publication 1769-IN078A-EN-P - May 2006
10 Compact TTL Output Module

Mount Module to DIN Rail

The module can be mounted using these DIN rails.
35 x 7.5 mm (EN 50 022 - 35 x 7.5)
35 x 15 mm (EN 50 022 - 35 x 15)
Before mounting the module on a DIN rail, close the DIN-rail latches. Press the DIN-rail mounting area of the module against the DIN rail. The latches will momentarily open and lock into place.

Wire the 1769-OG16 Module

Each terminal accepts as many as two wires with these restrictions.
Wire Restrictions
Wire Type Wire Size Terminal Screw
Torque
Solid Cu-90 °C (194 °F)
Stranded Cu-90 °C (194 °F)
2.08…0.34 mm (14…22 AWG)
1.31…0.34 mm (16…22 AWG)
2
0.68 Nm (6 in-lb) 0.46 Nm (4.1 in-lb)
2
0.68 Nm (6 in-lb) 0.46 Nm (4.1 in-lb)
Simplified Output Circuit Diagram
Retaining Screw Torque
Publication 1769-IN078A-EN-P - May 2006
Output Wiring
Compact TTL Output Module 11
General Notes:
1. Use Belden 8761, or equivalent, shielded wire.
2. Do not connect more than 2 wires to any single terminal.
3. DC power cable and I/O cables should not exceed 30 ft (10 m) in length.
4. The capacitors shown above must be 0.01uF and rated for 2000 volts (minimum).
5. User power supply must be rated Class 2 with a 5V dc range of 4.5V to 5.5V dc.
Publication 1769-IN078A-EN-P - May 2006
12 Compact TTL Output Module

Ground the 1769-OG16 Module

This product is intended to be mounted to a well-grounded mounting surface such as a metal panel. Additional grounding connections from the module’s mounting tabs or DIN rail (if used) are not required unless the mounting surface cannot be grounded.
Refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication 1770-4.1, for additional information.
A removable, write-on label is provided with the module. Remove the label from the door, mark the identification of each terminal with permanent ink, and slide the label back into the door. Your markings (ID tag) will be visible when the module door is closed.
Ground the Module
Upper Retaining Screw
Lower Retaining Screw
Wire the finger-safe terminal block.

Remove the Finger-safe Terminal Block

To remove the terminal block, loosen the upper and lower retaining screws. The terminal block will back away from the module as you remove the screws. When replacing the terminal block, torque the retaining screws to 0.46 Nm (4.1 in-lbs).
Publication 1769-IN078A-EN-P - May 2006
Compact TTL Output Module 13

Wire the Finger-safe Terminal Block

When wiring the terminal block, keep the finger-safe cover in place.
1. Loosen the terminal screws to be wired.
2. Route the wire under the terminal pressure plate.
You can use the bare wire or a spade lug. The terminals will accept a
6.35 mm (0.25 in.) spade lug.
TIP
The terminal screws are non-captive. Therefore, it is possible to use a ring lug [max 1/4 in. o.d. with a 0.139 in. minimum i.d. (M3.5)] with the module.
3. Tighten the terminal screw making sure the pressure plate secures the wire.
Recommended torque when tightening terminal screws is 0.68 Nm (6 in-lb).
TIP
If you need to remove the finger-safe cover, insert a screwdriver into one of the square, wiring holes and gently pry the cover off. If you wire the terminal block with the finger-safe cover removed, you will not be able to put it back on the terminal block because the wires will be in the way.

Configure the 1769-OG16 Module

The following I/O memory mapping lets you configure the 1769-OG16 module.

Output Data File

For each module, slot x, word 0 in the output data file contains the state of the module’s output points. The module implements inverted logic on the TTL outputs. An Output Data File bit set to 1 results in a logic low output voltage on the corresponding output point. An Output Data File bit cleared to 0 results in a logic
high output voltage on the corresponding output point.
Output Data File
Bit Position
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Word
(1)
0
(1)
wwwwwwwwwwwwwww
w
w = write.
Publication 1769-IN078A-EN-P - May 2006
14 Compact TTL Output Module

Input Data File

For each module, slot x, word 0 in the input data file contains the state of the module’s output data file (output data echo). During normal operation, these input bits represent the logic state that the outputs are directed to by the control program. They are also dependent upon the:
Program mode configuration (if supported by the controller).
Fault mode configuration (if supported by the controller).
The module implements inverted logic on the TTL outputs. An Output Data File bit set to 1 directs a logic low output voltage on the corresponding output point. An Output Data File bit cleared to 0 directs a logic high output voltage on the
corresponding output point.
Input Data File
Bit Position
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Word
(1)
0
(1)
r = read.
rrrrrrrrrrrrrrr
r
IMPORTANT
The output module’s input data file reflects the output data echo of the module, not necessarily the electrical state of the output terminals. It does not reflect shorted or open outputs.
It is important to use this input word if the controller adapter supports the Program mode or Fault mode function, and if it is configured to use them.
Publication 1769-IN078A-EN-P - May 2006
Compact TTL Output Module 15

Configuration File

The read/writable configuration data file allows the setup of the hold last state and user-defined safe state conditions.
The manipulation of the bits from this file is normally done with programming software (such as RSLogix 500 or RSNetworx for DeviceNet) during initial configuration of the system. In that case, graphical dialogs are provided via the programmer to simplify configuration. However, some systems (for example, 1769-ADN DeviceNet adapter) also allow the bits to be altered as part of the control program using communication rungs. In that case, it is necessary to understand the bit arrangement.
Configuration File
Bit Position
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Word
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 PFE
1 Program State for Output Array Word 0
2 Program Value for Output Array Word 0
3 Fault State for Output Array Word 0
4 Fault Value for Output Array Word 0

Program State Word

Condition Bit Setting
Word 1, the program state word, selects the hold last state or user-defined safe state condition for each individual output on a system transition from Run to Program.

Program Value Word

(1)
The program value word, word 2, is used to program the user-defined safe state value (0 = Off, 1 = On). Each output is individually configurable for on or off.
(1)
TTL outputs are inverted (On = 1 = logic low voltage = 0…0.4V dc; Off = 0 = logic high voltage = 4.5…5.5V dc). Use a NOT instruction in the ladder program to convert to traditional True = High logic.
User-defined Safe State 0
Hold Last State 1
Value Bit Setting
Off 0
On 1
Publication 1769-IN078A-EN-P - May 2006
16 Compact TTL Output Module

Fault State Word

Word 3, the fault state word, selects the hold last state or user-defined safe state condition for each individual output on a system transition from Run to Fault.

Fault Value Word

(1)
The fault value word, word 4, is used to program the fault state value (0 = Off, 1 = On). Each output is individually configurable for on or off.

Program to Fault Enable Bit (PFE)

Word 0, bit 0, allows the selection of which data value, the program or fault value, to apply to the output if a system in Program mode undergoes a system fault, resulting in a change to the Fault mode.

Module Default Condition

(1)
The modules default condition is all zeros.
Programming Conditions
Condition Bit Setting
User-defined Safe State 0
Hold Last State 1
Value Bit Setting
Off 0
On 1
Value Applied Bit Setting
Program 0
Fault 1
Word or Bit Affected Condition Applied
Word 0, Bit 0 Program-to-fault Enable Program Value
Word 1 Program State User-defined Safe State
Word 2 Program Value Off
Word 3 Fault State User-defined Safe State
Word 4 Fault Value Off
(1)
TTL outputs are inverted (On = 1 = logic low voltage = 0…0.4V dc; Off = 0 = logic high voltage = 4.5…5.5V dc). Use a NOT instruction in the ladder program to convert to traditional True = High logic.
Publication 1769-IN078A-EN-P - May 2006
Compact TTL Output Module 17

Specifications

Compact TTL Output Module - 1769-OG16
Attribute Value
Bus Current Draw, Max 200 mA at 5V dc
Heat Dissipation 1.2 Total Watts (The Watts per point, plus the minimum Watts, with all
points energized.)
Power Supply Distance Rating 8 (The module may not be more than 8 modules away from the power
Vendor I.D. Code 1
Product Type Code 7
Product Code 78 (decimal)
Input Data File Size 1 word
Output Data File Size 1 word
Configuration Data File Size 5 words
Dimensions (HxDxW), Approx. 118 x 87 x 35 mm (4.65 x 3.43 x 1.38 in.)
Weight, Approx. (with carton) 250 g (0.55 lb)
Voltage Category 5V dc TTL output
Operating Voltage Range 4.5…5.5V dc
Number of Outputs 16
Signal Delay, Max (resistive load) Turn-on: 0.25 ms
Off-state Voltage
On-state Voltage
On-state Load Current, Min 0.15 mA
Continuous Current per Point, Max 24 mA
Output Point to Bus (CompactBus) Isolation
(1)
TTL outputs are inverted (On = 1 = logic low voltage = 0…0.4V dc; Off = 0 = logic high voltage = 4.5…5.5V dc). Use a NOT instruction in the ladder program to convert to traditional True = High logic.
(1)
(Typical)
(1)
supply or controller.)
Height including mounting tabs is 138 mm (5.43 in.)
50 mV peak-to-peak ripple, max
Turn-off: 0.50 ms
4.5…5.5V dc
0…0.4V dc
Verified by one of the following dielectric tests: 1200V ac for 2 s or 1697V dc for 2 s 75V dc working voltage (IEC Class 2 reinforced insulation)
Publication 1769-IN078A-EN-P - May 2006
18 Compact TTL Output Module
Environmental Specifications
Attribute Value
Storage Temperature -40…+85 °C (-40…+185°F)
Operating Temperature 0…60 °C (32…140 °F)
Operating Humidity 5…95% non-condensing
Operating Altitude 2000 m (6561 ft)
Vibration Operating: 10…500 Hz, 5 g, 0.030 in. max peak-to-peak
Shock Operating: 30 g panel mounted (20 g DIN-rail mounted)
Non-operating: 40 g panel mounted (30 g DIN-rail mounted)
Radiated and Conducted Emissions
Electrical /EMC The module has passed testing at the following levels
ESD Immunity (IEC61000-4-2) 4 kV contact, 8 kV air, 4 kV indirect
Radiated Immunity (IEC61000-4-3) 10V/m, 80…1000 MHz, 80% amplitude
Fast Transient Burst (IEC61000-4-4)
Conducted Immunity (IEC61000-4-6)
(1)
Conducted Immunity frequency range may be 150 kHz…30 MHz if the radiated immunity frequency range is 30…1000 MHz.
EN50081-2 Class A
2 kV, 5 kHz
10V, 0.15…80 MHz
(1)
Certifications
Attribute Value
Agency Certification • C-UL certified (under CSA C22.2 No. 142)
Hazardous Environment Class Class I, Division 2, Hazardous Location, Groups A, B, C, D
Publication 1769-IN078A-EN-P - May 2006
• UL 508 listed
• CE compliant for all applicable directives
(UL 1604, C-UL under CSA C22.2 No. 213)
Compact TTL Output Module 19

Additional Resources

You can view or download publications at http://literature.rockwellautomation.com. To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative.
Related Documentation
For Refer to This Document Pub. No.
A more detailed description of how to use your Compact I/O with MicroLogix 1200/1500 programmable controllers
A more detailed description of how to install and use your Compact I/O system with the 1769-ADN DeviceNet adapter
A more detailed description of how to install and use your Compact I/O system with the CompactLogix system
More information on proper wiring and grounding techniques
MicroLogix 1200 and MicroLogix 1500 Programmable Controllers Reference Manual
1769-ADN DeviceNet Adapter User Manual
CompactLogix System User Manual 1769-UM007
Industrial Automation Wiring and Grounding Guidelines
1764-RM001
1769-UM001
1770-4.1
Publication 1769-IN078A-EN-P - May 2006
Rockwell Automation Support
Rockwell Automation provides technical information on the web to assist you in using its products. At http://support.rockwellautomation.com knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com
.
Installation Assistance
If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running:
United States 1.440.646.3223 Monday – Friday, 8am – 5pm EST
Outside United States Please contact your local Rockwell Automation representative for any technical
support issues.
New Product Satisfaction Return
Rockwell tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned:
United States Contact your distributor. You must provide a Customer Support case number (see
Outside United States Please contact your local Rockwell Automation representative for return procedure.
Compact, CompactLogix, MicroLogix, RSLogix 500, and RSNetWorx for DeviceNet are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
phone number above to obtain one) to your distributor in order to complete the return process.
, you can find technical manuals, a
Publication 1769-IN078A-EN-P - May 2006 PN 40071-215-01(1)
Copyright © 2006 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
´H',/!¶1T¨
Loading...