Rockwell Automation 1756-RIO Installation Instructions

Installation Instructions
ControlLogix Remote I/O (RIO) Module
Catalog Number 1756-RIO/B
Topic Page
Important User Information 2 Environment and Enclosure 3 Prevent Electrostatic Discharge 4 Removal and Insertion Under Power 5 North American Hazardous Location Approval 6 About the Module 7 Before You Begin 9 Module Components 10 Power Requirements 11 Install the Module 11 Check Power Supply and Module Status 18 Module Status Indicators 19 Configure the Module 22 Uninstall the Removable Terminal Block (RTB) 22 Uninstall the Module 23 Replacing the Module 24 Additional Resources 28
About This Publication
Use this publication as a guide to install the ControlLogix Remote I/O (RIO) Module. Refer to the 1756-RIO user manual, publication 1756-UM534, for additional information. You can download a .pdf file of the manual at:
http://www.rockwellautomation.com/literature
2 ControlLogix Remote I/O (RIO) Module
IMPORTANT

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1
http://www.rockwellautomation.com/literature.)
state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from your local Rockwell Automation sales office or online at
describes some important differences between solid
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.
SHOCK HAZARD: Labels may be on or inside the equipment to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment to alert people that surfaces may reach dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010

Environment and Enclosure

ATTENTION: This equipment is intended for use in a
Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication 1770-4.1 requirements
NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure
ControlLogix Remote I/O (RIO) Module 3
, for additional installation
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
4 ControlLogix Remote I/O (RIO) Module

Prevent Electrostatic Discharge

ATTENTION: This equipment is sensitive to electrostatic
discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging
when not in use.
ATTENTION: If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
ControlLogix Remote I/O (RIO) Module 5

Removal and Insertion Under Power

WARNING: When you insert or remove the module while
backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.

Multi-point Network Communication Connections

WARNING: If you connect or disconnect the communication cable
with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
6 ControlLogix Remote I/O (RIO) Module

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous locations:
Products marked ‘CL I, DIV 2, GP A, B, C, D’ are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest ‘T’ number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
WARNING: EXPLOSION HAZARD –
•Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous.Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
•Substitution of components may impair suitability for Class I, Division 2.
•If this product contains batteries, they must only be changed in an area known to be nonhazardous.
Informations sur l’utilisation de cet équipement en environnements dangereux:
Les produits marqués ‘CL I, DIV 2, GP A, B, C, D’ ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
AVERTISSEMENT: RISQUE D’EXPLOSION –
•Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement.
•Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs.Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
•La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
•S'assurer que l'environnement est classé non dangereux avant de changer les piles.
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
ControlLogix Remote I/O (RIO) Module 7
IMPORTANT

About the Module

The ControlLogix 1756-RIO module connects a ControlLogix processor to a remote I/O network.
The module can act as a scanner or as an adapter on the network. For additional information, see publication 1756-UM534
This module is shipped in scanner mode, with a blank configuration.

1756-RIO Module as a Scanner

As a scanner, with one remote I/O channel, the 1756-RIO module scans I/O on a remote I/O network.
The module supports the following:
All remote I/O baud rates: 57.6, 115.2, 230.4 Kbaud
Rack numbers from 0…76 octal
All combinations of partial racks
Up to 32 physical adapters
To support 32 physical adapters, you must use an 82 resistor; 150 resistors allow only 16 adapters.
The module can update block transfers (BTs) automatically via the 1756-RIO module or can be controlled by the ControlLogix controller. It transfers all I/O via produced/consumed connections over the backplane to the controller.
Block transfers at all possible locations
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
8 ControlLogix Remote I/O (RIO) Module
IMPORTANT

1756-RIO Module as an Adapter

As an adapter, the 1756-RIO module lets the controller exchange data with or monitor an existing scanner. The module supports the following features:
Has one remote I/O channel
Emulates one or more racks
All remote I/O baud rates: 57.6, 115.2, 230.4 Kbaud
Rack numbers from 0…76 octal
All combinations of partial racks
Block transfers at all possible locations
Can monitor I/O on a network with an existing remote I/O scanner
(Monitor Mode)
Transfers all I/O to the controller via produced/consumed connections
over the backplane to the controller.
The module firmware can be updated using the Windows utilities software supplied with the module.
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
ControlLogix Remote I/O (RIO) Module 9

Before You Begin

Before you install your I/O module, you should do the following:
Identify the module components. See page
Note the power requirements. See page 11.
Install and connect a ControlLogix chassis and power supply. See
publication 1756-IN080.
Install RSLogix 5000 programming software, version 17 or later, and the
associated firmware.
Install RSLinx software, version 2.54 or later, with an activation. Use
RSLinx Gateway software or RSLinx Professional software. Do not use RSLinx Lite.
Install the 1756-RIO module Add-on Profile from the CD provided
with the module.
Determine the slot location. You can install the module in any slot in any
size ControlLogix chassis. See page
The 1756-RIO/B module requires firmware revision 3.1 or above.
10.
12.
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
10 ControlLogix Remote I/O (RIO) Module
IMPORTANT
44777
1
2
3
4
43161
RIO CLX OK
2
1

Module Components

2
Clr
1
Blue
1756-RIO/B
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
Item Description
1 4-character scrolling display 2 Three status indicators:
RIO indicates the status of the remote I/O network
CLX indicates the status of the connection to the processor
OK indicates the module’s own internal state
3 3-pin connector (blue hose) that connects to the remote devices
This is also known as the removable terminal block (RTB).
4 Inside-door label with error codes
Note that a cable from a 1756-RIO/A module will plug directly into a 1756-RIO/B module, but it is rotated 180°.
ControlLogix Remote I/O (RIO) Module 11

Power Requirements

This module receives power from the 1756-chassis power supply and requires two sources of power from the ControlLogix backplane.
450 mA at 5.1V DC
5 mA at 24V DC
Add these current/power values (2.5 W) to the requirements of all other modules in the chassis to prevent overloading the power supply.

Install the Module

You can install or remove the module while chassis power is applied if you observe these precautions.
WARNING: When you insert or remove the module while backplane power is on, an electrical arc can occur. If you connect or disconnect the communications cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.
For this installation, we will assume chassis power is off.
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
12 ControlLogix Remote I/O (RIO) Module

Installing and Connecting a Chassis

Before installing the module, you must install and connect a ControlLogix chassis and power supply. See ControlLogix Chassis Installation Instructions, publication 1756-IN080
To determine the slot location in the chassis, remember that chassis slots are numbered starting from the left, at 0. Slot 0 is the first slot to the right of the power supply.
You can do the following:
Use any size chassis.
Install the module in any available slot.
Install multiple 1756-RIO modules in the same chassis, depending on
how your power supply is rated.
.
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
ControlLogix Remote I/O (RIO) Module 13
Printed Circuit Board
20861

Install the Module in the Chassis

To install the module, follow these steps.
1. Align the circuit board with the top and bottom chassis guides.
WARNING: When you insert or the remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
14 ControlLogix Remote I/O (RIO) Module
Locking Tab
20862
2. Slide the module into the chassis until the module locking tabs click.
ATTENTION: Do not force the module into the backplane connector. If you cannot seat the module with firm pressure, check the alignment. Forcing the module into the chassis can damage the backplane connector or the module. The module is fully installed when it is flush with the power supply or other installed modules.
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
ControlLogix Remote I/O (RIO) Module 15
1
2
44776
1 (Blue)
2 (Clear)
(Shield)

Install the Removable Terminal Block (RTB)

Push the removable terminal block (RTB) into the 3-pin connector.
WARNING: If you connect or disconnect the communication cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
16 ControlLogix Remote I/O (RIO) Module

Wire the Connector for the Remote I/O Network

To wire the connector for the remote I/O network, refer to the Cabling and Termination table and follow these steps.
Cabling and Termination
Connector Pin Description
1 (bottom) Line 1 (blue) N/A Shield 2 Line 2 (clear)
1. Connect Line 1 (blue) of the remote I/O cable to the lower pin on the
1756-RIO module.
2. Connect the shield to the middle pin.
3. Connect Line 2 (clear) of the remote I/O cable to the upper pin on the
1756-RIO module.
4. Terminate both ends of a remote I/O network by using external resistors
attached to the physical ends of the network.
There should be two terminators at the ends network. The terminator is connected between Line 1 (blue) and line 2 (clear).
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
ControlLogix Remote I/O (RIO) Module 17
Select the Proper Resistor
Use 82 resistors if the network operates at 230.4 kbps or if the network operates at 57.6 kbps, or 115.2 kbps and none of the devices in this table are present. The maximum number of devices on the network is 32.
Use 150 resistors if the network contains any of the devices in this table, or if the network operates at 57.6 kbps or 115.2 kbps and you do not require the network to support more than 16 devices.
Device Resistors
Cat. No. Series
1747-ASB All 1771-AS All 1771-ASB Series A 1775-S5 All 1794-ASB All 1771-DCM All 1771-SN All 1772-SD All 1772-SD2 All 1775-S4A All 1775-S4B All 1775-SR5 All
Baud Rate Cable Limits
Baud Rate Maximum Cable Length
57.6 Kbaud 3048 m (10000 ft)
115.2 Kbaud 1524 m (5000 ft)
230.4 Kbaud 762 m (2500 ft)
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
18 ControlLogix Remote I/O (RIO) Module
Apply Chassis Power
Turn on the chassis power supply.

Check Power Supply and Module Status

The following indicates the correct power supply status and display indicators for the 1756-RIO module.

Chassis Power-supply Status Indicators

The chassis power-supply indicator should be green. The module OK status indicator should be solid red immediately after you turn on the chassis power supply and then it turns solid green. Refer to the installation instructions for your particular 1756-chassis power supply for recommended actions for checking your power supply.

Alphanumeric Display at Powerup

The 4-character, alphanumeric display shows either ‘RIO Scanner’ or ‘RIO Adapter’, followed by the firmware version number, and any banner text defined in the module configuration.
The display shows the following messages at powerup.
Message Description
B#nn Stages in the start-up processes; nn is a hexadecimal number Boot Next stage in power-up sequence RIO Scanner v. x.xx.xx Module firmware revision
If the indicator on the 1756-RIO module does not cycle through these messages on powerup, refer to the Troubleshooting section of the 1756 RIO user manual, publication 1756-UM534
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
ControlLogix Remote I/O (RIO) Module 19
44777
RIO CLX OK

Module Status Indicators

The module has three status indicators to indicate the state of internal operations. The status indicators are labeled RIO, CLX, and OK.

RIO Status Indicator – Remote Devices Status

The RIO indicator displays the status of the remote I/O network connection. Status varies depending on the mode of the module.
Scanner Mode
This table shows status in order of priority, highest first.
Indicator Status Description
RIO Red A frame-receive error has been received in the last
Flashing red/off At least one rack that is being scanned (not inhibited)
Yel low Idle, no racks are configured. Flashing yellow/off All configured racks are inhibited. Flashing green/off No racks being scanned (not inhibited) are in error, but
Green Successful communication with all configured racks,
second (CRC error, abort, or time-out). Indicator stays red for one second after the error occurs.
One or more racks are in error.
is in error. One or more racks are inhibited.
one or more racks are inhibited.
no inhibited racks.
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
20 ControlLogix Remote I/O (RIO) Module
Adapter Mode
This table shows status in order of priority, highest first.
Indicator Status Description
RIO Red A frame-receive error has been received in the last
Flashing red/off One or more racks are not being scanned. Flashing green/off Configuration mismatch on one or more racks. Green All racks are being scanned and there are no
second (CRC error, abort, or time-out). Indicator stays red for one second after the error occurs.
configuration mismatches.

CLX Status Indicator – ControlBus Status

The CL X indicator d isplays the status of communication with th e ControlLog ix processor.
Indicator Status Description
CLX
Green The module has successfully processed a request
Flashing green/off Controlling Connection is open, but not all required
Yel low Idle, no requests received from the backplane in the
Flashing yellow/off Controlling Connection is not open. Red The module has returned a CIP error to a request from
Flashing red/off The module has returned a CIP error within the last
from the ControlBus backplane within the last five seconds. All required connections are open.
connections are open.
last five seconds. No connections; empty configuration.
the backplane within the last second. All required connections are open.
second. All required connections are not open.
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
ControlLogix Remote I/O (RIO) Module 21
IMPORTANT

OK Status Indicator – Module Health

Indicator Status Description
OK Green Indicates that module has passed all power-up
Red Indicates that module start-up diagnostics have
diagnostics and is functioning normally.
failed or a major module fault, such as watchdog time-out or jabber inhibit, has occurred.
If all three status indicators are solid red and the 4-character display shows M#xx, (where xx is the error number), a fatal error has occurred. Refer to the 1756-RIO user manual, publication 1756-UM534
, for information on clearing fatal errors. Make a note of the error code numbers to give Technical Support, if you need to call for help.

Interpret the Alphanumeric Display

The remote I/O (RIO) communication interface module displays alphanumeric messages that provide diagnostic information about your module. The warning messages appear twice on the display, then the normal display resumes. The table summarizes the messages.
Alphanumeric Display Message Descriptions
Message Description
RIO Scanner v. x.xx.xx [banner] RIO Adapter v. x.xx.xx [banner]
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
The module’s firmware revision, displayed at powerup. The three parts of the revision number are the major revision, the minor revision, and the build number. This is followed by the status banner.
22 ControlLogix Remote I/O (RIO) Module
44776
1
2

Configure the Module

Once installed, your 1756-RIO module must be configured. Refer to the 1756-RIO user manual, publication 1756-UM534, for information on module configuration.

Uninstall the Removable Terminal Block (RTB)

To remove the RTB, grasp firmly and pull out.
WARNING: If you connect or disconnect the communication cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
ControlLogix Remote I/O (RIO) Module 23
20856
20857

Uninstall the Module

WARNING: When you insert or the remove the module while
backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.
To remove the module, follow the steps below.
1. Push in top and bottom locking tab.
2. Pull the module out of the chassis.
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
24 ControlLogix Remote I/O (RIO) Module

Replacing the Module

If you are replacing an existing module with an identical one, and you want to resume identical system operation, you must do the following:
Install the new module in the same slot.
Run the configuration program and download the appropriate
configuration to the module.
Check that the module has the correct firmware, scanner, or adapter
version.
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
ControlLogix Remote I/O (RIO) Module 25

Specifications

Technical Specifications - 1756-RIO
Attribute 1756-RIO
Module location 1756 ControlLogix chassis Backplane current, max 450 mA @ 5.1V DC
5 mA @ 24 V DC
Isolation voltage 50V (continuous), basic insulation type, RIO
Power dissipation 2.5 W Screw terminal torque 0.5…0.6 N•m (5…7 lb•in) Wiring category
(1)
Wire size 0.52 mm Wire type Belden 9463 twinaxial Enclosure type rating None (open-style) North American temperature code T4A
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication 1770-4.1
communication lines to backplane. Type tested at 500V AC for 60 s
2 - on communication ports
2
(20 AWG)
.
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
26 ControlLogix Remote I/O (RIO) Module
Environmental Specifications - 1756-RIO
Attribute 1756-RIO
Operating temperature IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
Nonoperating temperature IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold) IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating
Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged
Nonoperating Thermal Shock) Surrounding air temperature, max 60 °C (140 °F) Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) Operating shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock) Nonoperating shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock) Vibration
IEC 60068-2-6 (Test Fc, Operating) Emissions
CISPR 11 ESD immunity
IEC 61000-4-2 Radiated RF immunity
IEC 61000-4-3
0…60 °C (32…140 °F)
-40…85 °C (-40…185 °F)
5…95% noncondensing
30 g
50 g
2 g @ 10…500 Hz
Group 1, Class A
6 kV contact discharges 8 kV air discharges
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 Mhz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
Rockwell Automation Publication 1756-IN610B-EN-P - November 2010
Environmental Specifications - 1756-RIO
Attribute 1756-RIO
EFT/B immunity IEC 61000-4-4
Surge transient immunity IEC 61000-4-5
Conducted RF immunity IEC 61000-4-6
±2 kV at 5 kHz on communication ports
± 2 kV line-earth (CM) on communication ports
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications
Certification
(1)
- 1756-RIO
(2)
1756-RIO
c-UL-us UL Listed Industrial Control Equipment, certified for U.S. and Canada.
See UL File E65584. UL listed for Class 1, Division 2 Group A,B,C,D Hazardous Locations,
certified for U.S. and Canada. See UL File E194810.
CE European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:
(1) When product is marked.
(2) See the Product Certification link at http://www.ab.com
and other certification details.
AS/NZS CISPR 11; Industrial Emissions
for Declarations of Conformity, Certificates,
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400

Additional Resources

These documents contain additional information concerning related Rockwell Automation products.
Resource Description
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Product Certification website,
http://www.ab.com
You can view or download publications at
http://www.rockwellautomation.com/literature
technical documentation, contact your local Rockwell Automation distributor or sales representative.
Provides general guidelines for installing a Rockwell Automation industrial system.
Provides declarations of conformity, certificates, and other certification details.
. To order paper copies of
Allen-Bradley, Rockwell Software, Rockwell Automation, ControlLogix , RSLogix 5000, R SLinx, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Ro ckwell Automation are property of their respective companies.
Publication 1756-IN610B-EN-P - November 2010 PN-92344
Supersedes Publication 1756-IN610A-EN-P - March 2009 Copyright © 2010 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Loading...