Endress+Hauser Instruments via HART to the PlantPAx
Process Automation System
Systems with Analog I/O Modules: 1756-IF8H, 1756-IF8IH, 1756-IF16H, 1794-IF8IH, 1769sc-IF4IH, 1734sc-IE2CH, 1734sc-IE4CH
Endress+Hauser Devices: Promag 53 Electromagnetic, Flowmeter, Proline T-mass 65 Thermal Flowmeter, Promass 83 Coriolis
Mass Flowmeter, Prowirl 73 Flowmeter, Prosonic M Ultrasonic Level, Levelflex M Guided Radar Level, Micropilot M Radar Level,
Deltabar S Differential Pressure, Prosonic S Transmitter, Cerabar S Pressure Transmitter, iTEMP TMT162 Temperature Transmitter,
iTEMP TMT182 Temperature Transmitter, Liquiline M CM42 Transmitter
Module
Module
Module
Module
Status
Status
Status
Status
Network
Network
Network
Network
Status
Status
Status
Status
NODE:
NODE:
NODE:
NODE:
24VDC
220 VAC
Relay
120 VAC
Sink
Input
Output
Input
Input
0
0
0
0
4
0
0
0
0
4
1
1
1
1
5
1
1
1
1
1
5
2
2
2
2
6
2
2
2
6
3
3
3
3
7
3
3
3
7
1734
1734
1734
1734
OW4
IB8
IA4
IM4
L33ERM
RUN
NS
LINK 1
FORCE
I/O
LINK 2
SD
OK
RUN
REM
PROG
XX:XX:XX:XX:XX:XX
1 (Front)
2 (Rear)
AC/DC OUT
RELAY115 VAC
Important User Information
IMPORTANT
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1
your local Rockwell Automation® sales office or online at http://www.rockwellautomation.com/literature/
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from
) describes some
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Rockwell Software, Rockwell Automation, CompactLogix, ControlLogix, FactoryTalk, RSLogix , and and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
6Rockwell Automation Publication PROCES-UM002A-EN-P - July 2014
Preface
Preferred Integration
Rockwell Automation and Endress+Hauser have strengthened their strategic
alliance to provide complete process automation solutions that use best-in-class
instrumentation, software, and control systems.
There are hundreds of different components in a typical plant: controllers,
remote I/O, electrical drives, safety equipment, and sensors. Each must be
integrated, configured and optimized during start-up and operation. Recognizing
the challenges this creates, Rockwell Automation and Endress+Hauser are
focused on providing you with scalable, off-the-shelf solutions.
To supply robust system solutions, Rockwell Automation pre-tests many thirdparty manufactured HART, FOUNDATION Fieldbus, and Profibus field
devices in the system test laboratory for compatibility with the Integrated
Architecture based plant automation system. Each field device is connected to
the Rockwell Automation Integrated Architecture based system and is subjected
to interoperability testing procedures similar to operating procedures in your
plant. The results of each field test are recorded in a test report for integration
planning purposes.
For Endress+Hauser field devices, an additional step provides an “Integration
Document” and “Interoperability Statement” for each tested instrument. The
Integration Document provides information on installation, configuration,
startup, and operation of the integrated system. The Interoperability Statement is
assurance that the Endress+Hauser field device meets Integrated Architecture
system interoperability performance measures, as jointly established by Rockwell
Automation and Endress+Hauser and verified through completion of common
test procedures performed by either company. Both the Integration Document
and Interoperability Statement ensure a no risk solution highlighted by ease of
integration and optimum performance.
Rockwell Automation Publication PROCES-UM002A-EN-P - July 20147
Preface
The overall mission of the alliance is to provide you with proven solutions that
combine field instrumentation with fieldbus networks, such as HART,
FOUNDATION Fieldbus, and Profibus networks, with asset management
capabilities and Rockwell Automation’s system capabilities to provide a total
engineered solution.
Through preferred integration and support of increasing requirements for plantwide control, the alliance offers the following benefits:
• Reduced integration costs throughout engineering, commissioning, and
start-up
• Optimized plant availability and output
• Ensured product quality and consistency
• Optimized traceability to meet regulatory demands
• Predictive maintenance through intelligent instruments
For new construction, process improvements at an existing plant, or operating
cost reductions, the alliance delivers the following:
• Integration reduces risk, reduces integration costs, and protects investment
with assured interoperability. Both companies believe open systems and
standardized interfaces bring maximum benefits.
• Advanced diagnostics with plant-wide support offers better visibility of
plant health and easier access to instrument diagnostics, which leads to
faster troubleshooting and improves decision-making.
• Collaborative lifecycle management to design, engineer, and startup
systems faster. This collaboration increases productivity, manages
information about instrumentation assets, optimizes plant assets, and
results in a complete lifecycle management solution.
Application Overview
This document provides a step-by-step approach to integrating Endress+Hauser
devices into a Rockwell Automation Integrated Architecture for Process Control
system.
This SectionDescribes
Application overviewDetails about the field instrument and control system.
System detailsSpecifications on the required hardware and software components.
InstallationHow to:
ConfigurationHow to:
VisualizationHow to implement and configure a graphical display of device information.
8Rockwell Automation Publication PROCES-UM002A-EN-P - July 2014
• Connect the measurement instrument to the HART I/O module.
• Connect a HART handheld device.
• Configure the HART I/O module.
• Configure the measurement instrument and manage parameters.
Preface
Integrated Asset Management
Process Automation
System Server (PASS)
Operator
Work stati on (OW S)
Engineering
Work stati on (E WS)
POINT I/O
System
CompactLogix
System
ControlLog ix
System
FLEX I/O System
The tested HART devices are the following:
• Promass 83 flowmeter
• Promag 53 flowmeter
• Proline t-mass 65 flowmeter
• Prosonic S transmitter
• Prowirl 73 flowmeter
• Levelflex M guided level-radar
• Micropilot M level-radar
• Prosonic M ultrasonic level
• Liquiline M CM42 transmitter
• Cerabar S pressure transmitter
• Deltabar S differential pressure
• iTEMP TMT162 temperature transmitter
• iTEMP TMT182 temperature transmitter
The ControlLogix platform provides a full range of input and output modules to
span a wide variety of applications. The ControlLogix architecture uses
producer/consumer technology, allowing input information and output status to
be shared by all ControlLogix controllers in the system.
L33ERM
RUN
NS
LINK 1
FORCE
I/O
LINK 2
SD
OK
RUN
REM
PROG
XX:XX:XX:XX:XX:XX
1 (Front)
2 (Rear)
AC/DC OUT
RELAY115 VAC
Module
Module
Module
Module
Status
Status
Status
Status
Network
Network
Network
Network
Status
Status
Status
Status
NODE:
NODE:
NODE:
NODE:
24VDC
220 VAC
Relay
120 VAC
Sink
Input
Output
Input
Input
0
0
0
0
4
0
0
0
0
4
1
1
1
1
5
1
1
1
1
1
5
2
2
2
2
6
2
2
2
6
3
3
3
3
7
3
3
3
7
1734
1734
1734
1734
OW4
IB8
IA4
IM4
Rockwell Automation Publication PROCES-UM002A-EN-P - July 20149
Preface
Control System
The control system includes these components:
ComponentDescription
ControllerThe ControlLogix controller is a modular, high performance controller, that uses RSLogix 5000 programming software
to configure, program, and monitor a system. The ControlLogix controller is certified by TUV for SIL 1 and SIL 2
applications.
HART I/O moduleThe HART analog I/O module converts to or from 4...20 mA analog signals and the digital values used in the controller.
The I/O module automatically collects dynamic process data from the HART field instrument. The I/O module also
bridges HART messages from CIP clients to HART field instruments.
Programming softwareRSLogix 5000 programming software is the design and configuration tool for HART I/O that includes status and
diagnostic information. The software has predefined data struc tures for status and configuration. A common tag
database in the controller allows HMI development to directly reference I/O and controller tags without the need to
manage another database in your HMI software.
Operating softwareFactoryTalk View Site Edition software is an HMI software program for monitoring, controlling, and acquiring data from
manufacturing operations throughout an enterprise. A generic display provides a graphical representation via
faceplates of the field instrument connected to the HART input module.
Asset management softwareFactoryTalk AssetCentre software and FieldCare software are options asset management options for configuring and
managing the intelligent field devices in your plant.
• Support Ethernet, HART, and Profibus networks.
• Support Endress+Hauser field instruments.
• Integrate third-party devices, such as actuators, I/O systems, and sensors that support the FDT standard.
• Ensure full functionality for all devices with DTMs.
• Offer generic profile operation for any third-party fieldbus device that does not have a vendor DTM.
HART Handheld Device (Optional)
The Field Xpert handheld device is an industrial PDA with integrated 3.5" touch
screen based on Windows Mobile. The PDA meets the needs and requirements
of the process industry with protection from static electricity, water and dust with
shockproof housing. It is available in different versions for operation both inside
and outside of explosion hazardous areas.
10Rockwell Automation Publication PROCES-UM002A-EN-P - July 2014
Preface
System Details
These components and specifications are recommended for preferred
integration.
Hardware Components
ComponentCatalog Number
HART deviceSee appropriate appendix
ControlLogix controller1756-L7 controllers
HART input module (select any one)1756-IF8H
1756-IF8IH
1756-IF16H
1794-IF8H
1769sc-IF4IH
1734sc-IE2CH
1734sc-IE4CH
Software Components
ComponentCatalog Number
RSLogix 5000 Enterprise Series programming software,
Professional edition
Includes:
• RSLinx Classic software
• RSLinx Enterprise software
FactoryTalk View Site Edition (SE) software9701-VWSXXXXXENE
FactoryTalk AssetCentre softare9515-ASTCAPXXXXX
FieldCare Standard Asset Management software (optional)
9324-RLD700NXENE
SFE551
Includes:
• DTM library
RSLinx Communication DTM software (optional)1756-Backplane
For specifications of the engineering workstation (EWS) and operator
workstation (OWS), see the Integrated Architecture for Process Control System
Recommendations Manual, publication PROCES-RM001
.
Rockwell Automation Publication PROCES-UM002A-EN-P - July 201411
Preface
Performance Considerations
Keep in mind these considerations when integrating HART instruments:
• The HART communication protocol has a relatively slow baud rate at
1200/2400 bits per second.
• The 1756-IF8H HART module executes one HART command per
instrument at a time. Analog (4-20ma) data are delivered from all channels
simultaneously.
• The time of execution for Universal Command 3 is estimated from
200...600 ms, but varies based on the complexity and response time of the
instrument.
• Upload and download time of instrument parameters to and from
FieldCare software can take several minutes depending on the instrument.
Additional Resources
These documents contain additional information concerning related products
from Rockwell Automation.
ResourceDescription
Control System Components
ControlLogix Controllers User Manual, publication 1756-UM001
ControlLogix Analog HART I/O Modules User Manual, publication 1756-UM533How to install, configure, operate, and maintain a 1756-IF8H input module.
Accessing HART Device Parameters using CIP Messages, Knowledgebase document
required. Please contact your sales representative.)
Operator Components
Add-On Instructions and Faceplates for Visualizing HART Instrument Data in FactoryTalk
View SE, Knowledgebase document (Login required. Please contact your sales
representative.)
FactoryTalk View Site Edition User's Guide Volume 1, publication VIEWSE-UM004
FactoryTalk View Site Edition User's Guide Volume 2, publication VIEWSE-UM005
Faceplates, Add-On Instructions, project files, etc. (Login required. Please contact your
sales representative.)
www.products.endress.com/fieldcare
www.products.endress.com/dtm-downloadInformation about field instrument DTMs.
Process Control Information
Integrated Architecture for Process Control System Recommendations Manual,
publication PROCES-RM001
http://www.rockwellautomation.com/process
http://literature.rockwellautomation.com
http://www.endress.com
How to install, configure, operate, and maintain a ControlLogix controller.
(Login
How to use MSG instructions in controller logic to access instrument parameters.
How to implement the HART Add-On-Instruction in controller logic to work with the
FactoryTalk View faceplates for HART instruments.
How to design, develop, and deploy FactoryTalk View SE applications.
Download AOIs, Faceplates and Global Object graphics, and project files.
Information about FieldCare Asset Management software.
Process system recommendations that organize Rockwell Automation products
functionally as system elements, which can then be applied in proven, scalable
configurations for continuous and batch control.
Information about Rockwell Automation process control and Integration Documents.
Available Rockwell Automation publications, including Integration Documents.
Information about Endress+Hauser field instruments.
You can view or download publications at
http:/www.rockwellautomation.com/literature/
technical documentation, contact your local Allen-Bradley distributor or
Rockwell Automation sales representative.
12Rockwell Automation Publication PROCES-UM002A-EN-P - July 2014
. To order paper copies of
Installation
Top icPag e
Connect a 2-Wire Field Instrument13
Connect a 4-Wire Field Instrument17
Chapter 1
Connect a 2-Wire Field
Instrument
HART communication is active only with current inputs. Connect a 2-wire field
instrument to any channel of the HART input module in a 2-wire configuration
for current input.
HART devices that support 2-wire connections include the following.
DeviceSee appendix
Prowirl 73 flowmeterAppendix D on page 97
Levelflex M guided level-radarAppendix F on page 10 9
Micropilot M level-radarAppendix G on page 115
Prosonic M ultrasonic levelAppendix E on page 103
Liquiline M CM42 transmitterAppendix M on page 147
Cerabar S pressure transmitterApp endix H on page 119
Deltabar S differential pressureAppendix I on page 125
iTEMP TMT162 temperature transmitterAppendix K on page 139
iTEMP TMT182 temperature transmitterAppendix L on page 143
Rockwell Automation Publication PROCES-UM002A-EN-P - July 201413
-V = COM = C-35 and C-51
Chassis Ground = Terminals B-16, B-33, C-38, C-40…45, and C-47
NC = No connection
For daisy-chaining: Supply in - C-34 (+) and C-35 (-)
_
+
_
+
Ch5
Supply out - C-50 (+) and C-51 (-)
_
+
Ch2
+
Chassis Grounds for Shields
InstallationChapter 1
+V
-V
22 Ω
+
Sig
-
_
+
3hC1hC0hC
_
+
7hC6hC4hC
(1794-TB3G shown)
91 Ω
17V
_
4 to 20mA
Xmit
I
P
Chassis
Ground
+V -V (COM)
CNCN
24C dc
Supply Out
4 to 20mA
Xmit
I
P
40072
A
B
C
Figure 4 - 2-Wire Connection to 1794-IF8IH Input Module
Rockwell Automation Publication PROCES-UM002A-EN-P - July 201415
Chapter 1Installation
Figure 5 - 2-Wire Connection to 1769sc-IF4IH Input Module
Ch0+
2 Wire Current Input
24V DC
Power
Supply
2 Wire
XMTR
+ -
+
-
N/C
N/C
Ch1+
Ch1-iRtn
Ch1-
N/C
Ch3+
Ch3-iRtn
Ch3-
Ch0-iRtn
Ch0-
N/C
Ch2+
Ch2-iRtn
Ch2-
N/C
N/C
Figure 6 - 2-Wire Connection to 1734sc-IE2CH Input Module
0
IN 0
2
+ 24
4
COM
6
FGN
1
IN 1
3
+ 24
5
COM
7
FGN
Figure 7 - 2-Wire Connection to 1734sc-IE4CH Input Module
0
IN 0
2
IN 2
4
COM
6
FGN
IN 1
IN 3
+ 24
FGN
1
2 Wire
Device
3
5
7
2 Wire
Device
16Rockwell Automation Publication PROCES-UM002A-EN-P - July 2014
InstallationChapter 1
RTN
IN4+
IN4IN5+
IN5RTN
IN6+
IN6IN7+
IN7-
IN0+
IN0IN1+
IN1-
IN2+
IN2IN3+
IN3-
I RTN- 0
NC
I RTN- 1
NC
I RTN- 2
NC
I RTN- 3
NC
RTN
I RTN- 4
NC
I RTN- 5
NC
RTN
I RTN- 6
NC
I RTN- 7
NC
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
+
-
+
+
--
4-wire Current Input
4-wire
MTR
24V DC
Power
Supply
Connect a 4-Wire Field
Instrument
HART communication is active only with current inputs. Connect a 4-wire field
instrument to any channel of the HART input module in a 4-wire configuration
for current input.
HART devices that support 4-wire connections include the following.
DeviceSee appendix
Promass 83 flowmeterAppendix A on page 83
Promag 53 flowmeterAppendix C on page 93
Proline t-mass 65 flowmeterAppendix B on page 89
Prosonic S transmitterAppendix J on page 133
Figure 8 - 4-Wire Connection to 1756-IF8H Input Module
Rockwell Automation Publication PROCES-UM002A-EN-P - July 201417
Figure 9 - 4-Wire Connection to 1756-IF16H Input Module
Figure 10 - 4-Wire Connection to 1794-IF8IH Input Module
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
16
39 40 41 42 43 44 45 46
Label placed at top of wiring area
Current
input
Row A
3332221202918124 2526 2728 2930 313217
Row B
51
059484748373635334
Row C
Row A
Row B
Row C
1794-TB3S shown
18Rockwell Automation Publication PROCES-UM002A-EN-P - July 2014
Figure 11 - 4-Wire Connection to 1769sc-IF4IH Input Module
0
IN 0
2
+ 24
4
COM
6
FGN
1
IN 1
3
+ 24
5
COM
7
FGN
4 Wire
Device
AC/DC Pwr
A
Ch0+
+
24V DC
+
-
4 Wire
XMTR
--
Power
Supply
4 Wire Current Input
N/C
N/C
Ch1+
Ch1-iRtn
Ch1-
N/C
+
Ch3+
Ch3-iRtn
Ch3-
Ch0-iRtn
Ch0-
N/C
Ch2+
Ch2-iRtn
Ch2-
N/C
N/C
InstallationChapter 1
Figure 12 - 4-Wire Connection to 1734sc-IE2CH Input Module
Figure 13 - 4-Wire Connection to 1734sc-IE4CH Input Module
0
IN 0
2
IN 2
4
COM
6
FGN
FGN
C/DC Pwr
4 Wire
Device
1
IN 1
3
IN 3
5
+ 24
7
Rockwell Automation Publication PROCES-UM002A-EN-P - July 201419
Chapter 1Installation
Notes:
20Rockwell Automation Publication PROCES-UM002A-EN-P - July 2014
Chapter 2
Configure the HART Device in RSLogix 5000
Programming Software
Top icPag e
Configure a HART Input Module in a ControlLogix System21
Configure a HART Input Module in a Compact I/O System27
Configure a HART Input Module in a FLEX I/O System29
Configure a HART Input Module in a POINT I/O System31
The examples in this chapter use RSLogix 5000 programming software,
version 20.
Configure a HART Input
Module in a ControlLogix
System
In RSLogix 5000 software, you must have a project open with a ControlLogix
controller already configured. Make sure the project path is set to the correct
controller.
Use RSWHO Active in RSLogix 5000 software to verify that the controller,
HART input module, and devices are active.
Rockwell Automation Publication PROCES-UM002A-EN-P - July 201421
Chapter 2Configure the HART Device in RSLogix 5000 Programming Software
To configure the I/O module, follow these steps within the configuration tree.
1. From the configuration tree, right click the 1756 backplane and choose
New Module.
If the controller communicates with the I/O module over a network, the
network interfaces must be added to the configuration tree before adding
the I/O module.
2. From the list, select the 1756-IF8H input module.
22Rockwell Automation Publication PROCES-UM002A-EN-P - July 2014
Configure the HART Device in RSLogix 5000 Programming SoftwareChapter 2
3. On the General tab, enter the configuration information for the module.
4. Click Change.
5. For Input Data, choose Analog and HART PV.
6. On the Configuration tab, enable HART for each channel connected to a
device.
Each channel must be enabled to pass HART data to the controller.
Rockwell Automation Publication PROCES-UM002A-EN-P - July 201423
Chapter 2Configure the HART Device in RSLogix 5000 Programming Software
7. On the Configuration tab, for Passthrough, choose Once per channel
scanned.
This passthrough selection is the fastest and best for asset management
software.
8. When complete, click OK.
9. Click Download to go online.
24Rockwell Automation Publication PROCES-UM002A-EN-P - July 2014
Configure the HART Device in RSLogix 5000 Programming SoftwareChapter 2
10. From the HART Device Info tab in the HART module properties, verify
that the instrument is connected.
Rockwell Automation Publication PROCES-UM002A-EN-P - July 201425
Chapter 2Configure the HART Device in RSLogix 5000 Programming Software
11. Check Controller Tags to verify that the HART instrument is connected
and passing data.
A connected instrument displays values in the PV, SV, TV, and FV fields.
This tag example shows that the HART input module is in slot 6.
26Rockwell Automation Publication PROCES-UM002A-EN-P - July 2014
Configure the HART Device in RSLogix 5000 Programming SoftwareChapter 2
If HART data is not present, make sure the HART function is enabled.
Configure a HART Input
Module in a Compact I/O
System
Use RSWHO Active in RSLogix 5000 software to verify that the controller,
HART input module, and devices are active.
This example has a 1769-L35E CompactLogix controller and the Spectrum
1769sc-IF4IH module and uses the Spectrum sample ACD file.
Rockwell Automation Publication PROCES-UM002A-EN-P - July 201427
Chapter 2Configure the HART Device in RSLogix 5000 Programming Software
The Spectrum 1769sc-IF4IH is configured as shown.
Make sure that Enable Channel and Enable HART Communication are both
checked.
The Spectrum 1769sc-IF4IH has these controller tags.
28Rockwell Automation Publication PROCES-UM002A-EN-P - July 2014
Configure the HART Device in RSLogix 5000 Programming SoftwareChapter 2
This example shows the PV values from the device mapped to the data structure.
Configure a HART Input
Module in a FLEX I/O System
In RSLogix 5000 software, you must have a project open with a controller already
configured. Make sure the project path is set to the correct controller.
Use RSWHO Active in RSLogix 5000 software to verify that the controller,
HART input module, and devices are active.
To configure the I/O module, follow these steps within the configuration tree.
This example assumes you have a 1756-ENBT interface and a 1794-AENT
adapter.
1. From the configuration tree, right click the 1794-AENT adapter and
choose New Module.
2. From the list, select the HART input module and click Create.
Rockwell Automation Publication PROCES-UM002A-EN-P - July 201429
Chapter 2Configure the HART Device in RSLogix 5000 Programming Software
3. Enter the configuration information for the module and choose the
HART communication format.
4. Click OK.
5. Go online and check the controller tags to make sure the device is
connected.
30Rockwell Automation Publication PROCES-UM002A-EN-P - July 2014
Loading...
+ 130 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.