Pilz PNOZ X4 Data Sheet

Page 1
NOT-AUS Schaltgerät, Schutztürwächter
Up to Category 4, EN 954-1
PNOZ X4
Safety relay for monitoring E-STOP pushbuttons, safety gates and light barriers.
Approvals
PNOZ X4
Unit features
` Positive-guided relay outputs:
– 3 safety contacts (N/O), instanta-
neous
– 1 auxiliary contact (N/C), instan-
taneous
` Connection options for:
– E-STOP pushbutton – Safety gate limit switch – Reset button – Light barriers
` LED indicator for:
– Switch status channel 1/2 – Supply voltage
` See order reference for unit types
Unit description
The safety relay meets the require­ments of EN 60204-1 and IEC 60204­1 and may be used in applications with
` E-STOP pushbuttons ` Safety gates ` Light barriers
Safety features
` The circuit is redundant with built-in
self-monitoring.
` The safety function remains effecti-
ve in the case of a component failu­re.
` The correct opening and closing of
the safety function relays is tested automatically in each on-off cycle.
` The tranformer is short circuit-
proof. An electronic fuse is used on a DC supply.
Block diagram
~
Power
=
S11 S12A1 A2
Feed-
back
Y1 Y2
The relay conforms to the following safety criteria:
S21 S22
InputInput
S52
Input
S33 S34
Reset/
Start
Y36 Y37
Reset/
Start
K1
K2
23 33 41
13
14 24 34 42
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-128-01/05
Page 2
NOT-AUS Schaltgerät, Schutztürwächter
Up to Category 4, EN 954-1
PNOZ X4
Function description
` Single-channel operation: no red-
undancy in the input circuit, earth faults in the reset and input circuit are detected.
` Dual-channel operation without de-
tection of shorts across contacts: redundant input circuit, detects – earth faults in the reset and input
circuit,
– short circuits in the input circuit
and, with a monitored reset, in
Timing diagram
1 2
POWER
Reset/Start
Input
Output safe
Output aux.
t1 t2
t1 t2
the reset circuit too.
` Dual-channel operation with detec-
tion of shorts across contacts: red­undant input circuit, detects – earth faults in the reset and input
circuit,
– short circuits in the input circuit
and, with a monitored reset, in the reset circuit too,
– shorts between contacts in the
input circuit.
` Automatic start: Unit is active once
the input circuit has been closed.
ab
t1
t1
t2
t2
` Manual reset: Unit is active once
the input circuit is closed and then the reset circuit is closed.
` Monitored reset: Unit is active once
the input circuit is closed and once the reset circuit is closed after the waiting period has elapsed (see technical details).
` Increase in the number of available
contacts by connecting contact ex­pander modules or external contac­tors/relays.
3
t1 t2 t1 t2t3 t3
Key
` Power: Supply voltage ` Reset/start: Reset circuit S33-S34 ` Input: Input circuits S11-S12, S21-
S22, S52
` Output safe: Safety outputs 13-14,
23-24, 33-34
Wiring
Please note:
` Information given in the “Technical
details” must be followed.
` Outputs 13-14, 23-24, 33-34 are
safety contacts, output 41-42 is an auxiliary contact (e.g. for display).
` To prevent contact welding, a fuse
should be connected before the output contacts (see technical de­tails).
` Calculation of the max. cable runs
in the input circuit:
l
max
R
lmax
=
I
max
Rl / km
` Output aux: Auxiliary contacts 41-
42
` c: Automatic reset ` d: Manual reset ` e: Monitored reset ` a: Input circuit closes before reset
circuit
R
= max. overall cable resi-
lmax
stance (see technical details)
/ km = cable resistance/km
R
l
` Use copper wire that can withstand
60/75 °C.
` Sufficient fuse protection must be
provided on all output contacts with capacitive and inductive loads.
` b: Reset circuit closes before input
circuit
: Switch-on delay
` t
1
` t2: Delay-on de-energisation
: Waiting period
` t
3
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-128-01/05Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-2
Page 3
NOT-AUS Schaltgerät, Schutztürwächter
Up to Category 4, EN 954-1
PNOZ X4
Preparing for operation
` Supply voltage
Supply voltage AC DC
A1
A2
L1
N
PE
` Input circuit
Input circuit Single-channel Dual-channel E-STOP
without detection of shorts across contacts
S21 S22
S11 S12 S52
S1
S21 S22
E-STOP with detection of shorts across con­tacts
S11 S52
Safety gate without detection of shorts across contacts
S21 S22
S11 S12 S52
S1
S21 S22
S11
S12 S52
A1
A2
S11
S12 S52
S11 S21 S22
S12
S1
L+
L-
S1
S1
S2
Safety gate with detection of shorts across con­tacts
Light barrier with detection of shorts across contacts via ESPE
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
S21 S22
S11 S52
S11 S12 S21 S22
S12 S52
S1
NSG-D-2-128-01/05
S2
24 V DC
Page 4
NOT-AUS Schaltgerät, Schutztürwächter
Up to Category 4, EN 954-1
PNOZ X4
` Reset circuit
Reset circuit E-STOP wiring (single-channel)
Safety gate (single-channel)
Automatic reset
S33 S34
Y36 Y37
Manual reset
S33 S34 Y36 Y37
Monitored reset
S33 S34 Y36 Y37
S3
S3
E-STOP wiring (dual-channel) Safety gate (dual-channel)
S33 S34 Y36 Y37
S33 S34 Y36 Y37
` Feedback loop
Feedback loop Automatic reset Manual/monitored reset Link
Y1
S33 S34
Y36 Y37
S3
S3
Y1
Contacts from external contactors
` Key
S1/S2 Two-hand button
S3 Reset button
Switch operated
Gate open
Gate closed
Y1 Y2
13 (23, 33) 14 (24, 34)
Y2
K5
K6
K5
K6
L1 N
13 (23, 33) 14 (24, 34)
Y1 Y2
Y2
K5
K6
K5
K6
L1 N
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-128-01/05Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-4
Page 5
NOT-AUS Schaltgerät, Schutztürwächter
Up to Category 4, EN 954-1
PNOZ X4
Terminal configuration
S11 S52 S12 13 23 33
Installation
` The safety relay should be installed
in a control cabinet with a protec­tion type of at least IP54.
` Use the notch on the rear of the unit
to attach it to a DIN rail.
` Ensure the unit is mounted securely
on a vertical DIN rail (35 mm) by using a fixing element (e.g. retaining bracket or an end angle).
Dimensions
A1 S11 S12
PNOZ X4
POWER CH. 1 CH. 2
A2 Y1 Y2 42S34S33
19955
S21
S22
Y3614Y372441
3313 23 41
14 24 34 42
34
121 (4.76")
75 (2.95")
87 (3.42")
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
45 (1,77")
NSG-D-2-128-01/05
Page 6
NOT-AUS Schaltgerät, Schutztürwächter
Up to Category 4, EN 954-1
PNOZ X4
Notice
Service life graph
This data sheet is only intended for use during configuration. For installation and operation, please refer to the ope­rating instructions supplied with the
10
AC15: 230 V
unit.
DC13: 24 V
1
D Nennbetriebstrom (A)
GB Nominal operating current (A)
Technical details
Electrical data
Supply voltage Supply voltage U Supply voltage U
AC 24 V, 110 V, 115 V, 120 V, 230 V, 240 V
B
DC 24 V
B
Voltage tolerance -15 %/+10 % Power consumption at U
Power consumption at U
AC 5.0 VA Order no.: 774731, 774734, 774735, 774736, 774738,
B
DC 2.5 W Order no.: 774730
B
Frequency range AC 50 - 60 Hz Residual ripple DC 160 % Voltage and current at input circuit DC: 24.0 V 40.0 mA reset circuit DC: 24.0 V 70.0 mA Order no.: 774730
feedback loop DC: 24.0 V 70.0 mA Order no.: 774730
Output contacts in accordance with EN 954-1 Category 4 Safety contacts (N/O): 3
Utilisation category in accordance with EN 60947-4-1 Safety contacts: AC1 at 240 V I
Safety contacts: DC1 at 24 V I
Auxiliary contacts: AC1 at 240 V I
Auxiliary contacts: DC1 at 24 V I
Utilisation category in accordance with EN 60947-5-1 Safety contacts: AC15 at 230 V I Safety contacts: DC13 at 24 V (6 cycles/min) I Auxiliary contacts: AC15 at 230 V I Auxiliary contacts: DC13 at 24 V (6 cycles/min) I Contact material AgSnO2 + 0.2 µm Au
0.1
F Courant coupé (A)
E Corriente nominal de servicio (A)
I Corrente di esercizio nominale (A)
NL Nominale bedrijfsstroom (A)
10 100 1000 10000
D Schaltspielzahl x 10 GB Cycles x 10 F Nombre de manvres x 10
3
3
3
774739
90.0 mA Order no.: 774731, 774734, 774735, 774736, 774738, 774739
90.0 mA Order no.: 774731, 774734, 774735, 774736, 774738, 774739
Auxiliary contacts (N/C): 1
: 0.01 A , I
min
P
: 2000 VA
max
: 0.01 A , I
min
P
: 200 W
max
: 0.01 A , I
min
: 2000 VA
P
max
: 0.01 A , I
min
P
: 200 W
max
: 5.0 A
max
: 7.0 A
max
: 5.0 A
max
: 7.0 A
max
max
max
max
max
: 8.0 A
: 8.0 A
: 8.0 A
: 8.0 A
DC1: 24 V
AC1: 230 V
E Número de ciclos x 10 I Numero dei cicli di commutazione x 10 NL Aantal schakelingen x 10
3
3
3
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-128-01/05Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-6
Page 7
NOT-AUS Schaltgerät, Schutztürwächter
Up to Category 4, EN 954-1
PNOZ X4
Electrical data
External contact fuse protection to EN 60947-5-1 Blow-out fuse, quick Safety contacts: 10 A Auxiliary contacts: 10 A Blow-out fuse, slow Safety contacts: 6 A Auxiliary contacts: 6 A Circuit breaker 24 VAC/DC, characteristic B/C Safety contacts: 6 A Auxiliary contacts: 6 A Max. overall cable resistance R single-channel at U single-channel at U
dual-channel without detect. of shorts across contacts at U dual-channel without detect. of shorts across contacts at U
dual-channel with detect. of shorts across contacts at U dual-channel with detect. of shorts across contacts at U
Times
Switch-on delay with automatic reset typ. 210 ms Order no.: 774731, 774734, 774735, 774736, 774738,
with automatic reset max. 350 ms Order no.: 774731, 774734, 774735, 774736, 774738,
with automatic reset after power on typ. 240 ms Order no.: 774731, 774734, 774735, 774736, 774738,
with automatic reset after power on max. 390 ms Order no.: 774731, 774734, 774735, 774736, 774738,
with manual reset typ. 55 ms Order no.: 774731, 774734, 774735, 774736, 774738,
with manual reset max. 350 ms Order no.: 774731, 774734, 774735, 774736, 774738,
with monitored reset typ. 30 ms Order no.: 774731, 774734, 774735, 774736, 774738,
with monitored reset max. 50 ms Order no.: 774731, 774734, 774735, 774736, 774738,
Delay-on de-energisation with E-STOP typ. 15 ms with E-STOP max. 30 ms with power failure typ. 50 ms Order no.: 774730
with power failure max. 70 ms Order no.: 774730
Recovery time at max. switching frequency 1/s after E-STOP 50 ms after power failure 100 ms
DC 20 Ohm Order no.: 774730
B
AC 150 Ohm Order no.: 774731, 774734, 774735, 774736, 774738,
B
input circuits, reset circuits
lmax
774739
DC 20 Ohm Order no.: 774730
B
AC 150 Ohm Order no.: 774731, 774734, 774735, 774736, 774738,
B
774739
DC 15 Ohm Order no.: 774730
B
AC 100 Ohm Order no.: 774731, 774734, 774735, 774736, 774738,
B
774739
774739 270 ms Order no.: 774730
774739 600 ms Order no.: 774730
774739 270 ms Order no.: 774730
774739 600 ms Order no.: 774730
774739 70 ms Order no.: 774730
774739 600 ms Order no.: 774730
774739 40 ms Order no.: 774730
774739
70 ms Order no.: 774730
55 ms Order no.: 774731, 774734, 774735, 774736, 774738,
774739
80 ms Order no.: 774731, 774734, 774735, 774736, 774738, 774739
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-128-01/05
Page 8
NOT-AUS Schaltgerät, Schutztürwächter
Up to Category 4, EN 954-1
PNOZ X4
Times
Waiting period with a monitored reset 150 ms Order no.: 774731, 774734, 774735, 774736, 774738,
774739 250 ms Order no.: 774730
Min. start pulse duration with a monitored reset 30 ms Simultaneity, channel 1 and 2 Supply interruption before de-energisation 20 ms
Environmental data
EMC EN 60947-5-1, EN 61000-6-2 Vibration in accordance with EN 60068-2-6 Frequency 10 - 55 Hz Amplitude 0.35 mm Climatic suitability EN 60068-2-78 Airgap creepage VDE 0110-1 Ambient temperature -10 - 55 °C Storage temperature -40 - 85 °C Protection type Mounting (e.g. control cabinet) IP54 Housing IP40 Terminals IP20
Mechanical data
Housing material Housing PPO UL 94 V0 Front ABS UL 94 V0 Max. cross section of external conductors with screw terminals 1 core flexible 0.20 - 4.00 mm² , 24 - 10 AWG 2 core, same cross section, flexible: with crimp connectors, without insulating sleeve 0.20 - 2.50 mm² , 24 - 14 AWG without crimp connectors or with TWIN crimp connectors 0.20 - 2.50 mm² , 24 - 14 AWG Torque setting with screw terminals 0.60 Nm Dimensions Height 87.0 mm Width 45.0 mm Depth 121.0 mm Weight 270 g Order no.: 774730
370 g Order no.: 774731, 774734, 774735, 774736, 774738, 774739
The standards current on 09/00 apply.
Max. continuous current
Number of contacts I 1 8.00 A Order no.: 774730, 774732 8.00 A Order no.: 774731, 774734, 774735, 774736,
2 8.00 A Order no.: 774730, 774732 7.50 A Order no.: 774731, 774734, 774735, 774736,
3 7.00 A Order no.: 774730, 774732 6.50 A Order no.: 774731, 774734, 774735, 774736,
Order reference
Type Features Terminals Order no.
PNOZ X4 24 VAC Screw terminals 774 731 PNOZ X4 110 VAC Screw terminals 774 734 PNOZ X4 115 VAC Screw terminals 774 735
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
(A) at UBDC I
max
(A) at UBAC
max
774738, 774739
774738, 774739
774738, 774739
NSG-D-2-128-01/05Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-8
Page 9
NOT-AUS Schaltgerät, Schutztürwächter
Up to Category 4, EN 954-1
PNOZ X4
Type Features Terminals Order no.
PNOZ X4 120 VAC Screw terminals 774 736 PNOZ X4 230 VAC Screw terminals 774 738 PNOZ X4 240 VAC Screw terminals 774 739 PNOZ X4 24 VDC Screw terminals 774 730
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-128-01/05