Pilz PNOZ X3P Data Sheet

E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X3P
Gertebild
][Bildunterschrift_NOT_Sch.tuer_Licht
Approvals
PNOZ X3P
SÜDDEUTSCHLAND
Unit features
Gertemerkmale
` Positive-guided relay outputs:
– 3 safety contacts (N/O), instanta-
neous
– 1 auxiliary contact (N/C), instan-
taneous
` 1 semiconductor output ` Connection options for:
– E-STOP pushbutton – Safety gate limit switch – Reset button – Light barriers
` LED indicator for:
– Switch status channel 1/2 – Supply voltage
` Semiconductor output signals:
– Switch status channel 1/2
` Plug-in connection terminals (either
spring-loaded terminal or screw terminal)
Unit description
Bestimmung/Gertebesc hreibung NOT-AUS , Schutzt, Lichtsc hr_PNOZ
The safety relay meets the require­ments of EN 60947-5-1, EN 60204-1 and VDE 0113-1 and may be used in applications with
` E-STOP pushbuttons ` Safety gates ` Light beam devices
Safety features
][Sicherheitseigenscha ften Schaltgerät_allgem einer Teil
The relay meets the following safety requirements:
` The circuit is redundant with built-in
self-monitoring.
` The safety function remains effec-
tive in the case of a component fail­ure.
` The correct opening and closing of
the safety function relays is tested automatically in each on-off cycle.
Zulassungen
Block diagram
~
=
( )*
Power
*only with UB 24 - 240 VAC/DC
Blockschaltbild
S11 S12A1 A2
0 V 24 V
Y30 Y31
S21 S22
InputInput
Y32
S31 S32
Input
( )*
S13 S14
Reset/
Start
S33 S34
Reset/
Start
K1
K2
23 33 41
13
14 24 34 42
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-161-2010-01
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X3P
Function description
][Funktionen_einkanalig
` Single-channel operation: no re-
dundancy in the input circuit, earth faults in the reset and input circuit are detected.
][Funktionen_zweikanalig_ohne_quer
` Dual-channel operation without de-
tection of shorts across contacts: redundant input circuit, detects – earth faults in the reset and input
circuit,
– short circuits in the input circuit
Timing diagram
POWER
Reset/Start
Input
Output safe
Output aux.
Out semi CH
and, with a monitored reset, in the reset circuit too.
][Funktionen_zweikanalig_mit_quer_ber
` Dual-channel operation with detec-
tion of shorts across contacts: re­dundant input circuit, detects – earth faults in the reset and input
circuit,
– short circuits in the input circuit
and, with a monitored reset, in the reset circuit too,
– shorts between contacts in the
input circuit.
][Zeitdiagramm_auto_ueber2_aux_semiCH
1 2
t1 t2 t1 t2
t4
][Funktionen_autoStart
` Automatic start: Unit is active once
the input circuit has been closed.
][Funktionen_berStart_Wartezeit
` Monitored reset: Unit is active once
the input circuit is closed and once the reset circuit is closed after the waiting period has elapsed (see technical details).
][Funktionen_Kontaktvervielfachung
` Increase in the number of available
instantaneous safety contacts by connecting contact expansion modules or external contactors.
t1
t2
t4
t1 t2
t3
Key
` Power: Supply voltage ` Reset/Start: Reset circuit S13-S14,
S33-S34
` Input: Input circuits S11-S12, S21-
S22, S31-S32
` Output safe: Safety contacts 13-14,
23-24, 33-34
Wiring
][Verdrahtung_Si_unverz_1Hi_unverz
Please note:
` Information given in the “Technical
details” must be followed.
` Outputs 13-14, 23-24, 33-34 are
safety contacts, output 41-42 is an auxiliary contact (e.g. for display).
` To prevent contact welding, a fuse
should be connected before the output contacts (see technical de­tails).
` Calculation of the max. cable runs
in the input circuit:
l
max
R
lmax
=
I
max
Rl / km
` Output aux: Auxiliary contacts 41-
42
` Out semi CH: Semiconductor out-
put switch status channel 1/2
` c: Automatic reset ` d: Monitored reset
: Switch-on delay
` t
1
R
= max. overall cable resist-
lmax
ance (see technical details)
/km = cable resistance/km
R
l
` Use copper wire that can withstand
60/75 °C.
` Sufficient fuse protection must be
provided on all output contacts with capacitive and inductive loads.
: Delay-on de-energisation
` t
2
: Recovery time
` t
3
: Waiting period
` t
4
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-161-2010-01Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-2
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X3P
Preparing for operation
Betriebsbereitschaft her stellen
` Supply voltage
Supply voltage AC DC
A1
A2
L1
N
` Input circuit
Input circuit Single-channel Dual-channel E-STOP
without detection of shorts across con­tacts
E-STOP with detection of shorts across contacts
S21 S22
S12 S11 S32
S31
S1
S21 S22
S11 S12
A1
A2
S11
S12 S32
S22 S32 S31 S21
L+
L-
S1
S1
Safety gate without detection of shorts across con­tacts
Safety gate with detection of shorts across contacts
Light beam device with detection of shorts across contacts via ESPE (not on units with a universal power supply)
S21 S22
S12 S11 S32
S31
S1
S21 S22
A2
S21 S22
S11 S12
S12 S32
S11
S12 S32
S22 S21 S32
S31
S1
S1
S2
S2
24 V DC
GND
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-161-2010-01
Loading...