Pilz PNOZ X3.10P Data Sheet

Page 1
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X3.10P
Gertebild
][Bildunterschrift_NOT_Sch.tuer_Licht
Approvals
PNOZ X3.10P
SÜDDEUTSCHLAND
Zulassungen
Unit features
Gertemerkmale
` Positive-guided relay outputs:
– 3 safety contacts (N/O), instanta-
neous
– 1 auxiliary contact (N/C), instan-
taneous
` 1 semiconductor output ` Connection options for:
– E-STOP pushbutton – Safety gate limit switch – Reset button – Light barriers
` LED indicator for:
– Switch status channel 1/2 – Supply voltage
` Semiconductor output signals:
– Switch status channel 1/2
` Plug-in connection terminals (either
spring-loaded terminal or screw terminal)
` See order reference for unit types
Unit description
Bestimmung/Gertebesc hreibung NOT-AUS , Schutzt, Lichtsc hr_PNOZ
The safety relay meets the require­ments of EN 60947-5-1, EN 60204-1 and VDE 0113-1 and may be used in applications with
` E-STOP pushbuttons ` Safety gates ` Light beam devices
Safety features
][Sicherheitseigenscha ften Schaltgerät_allgem einer Teil
The relay meets the following safety requirements:
` The circuit is redundant with built-in
self-monitoring.
` The safety function remains effec-
tive in the case of a component fail­ure.
` The correct opening and closing of
the safety function relays is tested automatically in each on-off cycle.
Block diagram
~
~
Power
Power
=
=
Blockschaltbild
S11 S12A1 A2
S11 S12A1 A2
0 V 24 V
0 V 24 V
Y30 Y31
Y30 Y31
S21 S22
S21 S22
InputInput
InputInput
Y32
Y32
S31 S32
S31 S32
Input
Input
Reset/
Reset/
Start
Start
S13 S14
S13 S14
Reset/
Reset/
Start
Start
S15 S16
S15 S16
Reset/
Reset/
Start
Start
S33 S34
S33 S34
K1
K1
K2
K2
23 33 41
23 33 41
13
13
14 24 34 42
14 24 34 42
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-322-2010-01
Page 2
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X3.10P
Function description
][Funktionen_einkanalig
` Single-channel operation: no re-
dundancy in the input circuit, earth faults in the reset and input circuit are detected.
][Funktionen_zweikanalig_mit_quer_ber
` Dual-channel operation with detec-
tion of shorts across contacts: re­dundant input circuit, detects – earth faults in the reset and input
circuit,
Timing diagram
1 2
POWER
Reset/Start
Input
Output safe
Output aux.
Out semi CH
t1 t2
t1 t2
– short circuits in the input circuit
and, with a monitored reset, in the reset circuit too,
– shorts between contacts in the
input circuit.
][Funktionen_autoStart
` Automatic start: Unit is active once
the input circuit has been closed.
][Funktionen_manuStart
` Manual reset: Unit is active once
the input circuit is closed and then the reset circuit is closed.
][Funktionen_berStart_Wartezeit
][Zeitdiagramm_auto_manu_ueber2_aux_semiCH
ab
t1
t1
t2
` Monitored reset: Unit is active once
the input circuit is closed and once the reset circuit is closed after the waiting period has elapsed (see technical details).
][Funktionen_Kontaktvervielfachung
` Increase in the number of available
instantaneous safety contacts by connecting contact expansion modules or external contactors.
3
t2
t1 t2 t1 t2t4 t4
t3
Key
` Power: Supply voltage ` Reset/Start: Reset circuit S13-S14,
S33-S34
` Input: Input circuits S11-S12, S21-
S22, S31-S32
` Output safe: Safety contacts 13-14,
23-24, 33-34
` Output aux: Auxiliary contacts 41-
42
Wiring
][Verdrahtung_Si_unverz_1Hi_unverz
Please note:
` Information given in the “Technical
details” must be followed.
` Outputs 13-14, 23-24, 33-34 are
safety contacts, output 41-42 is an auxiliary contact (e.g. for display).
` To prevent contact welding, a fuse
should be connected before the output contacts (see technical de­tails).
` Calculation of the max. cable runs
in the input circuit:
l
max
R
lmax
=
I
max
Rl / km
` Out semi CH: Semiconductor out-
put switch status Y32
` c: Automatic reset ` d: Manual reset ` e: Monitored reset ` a: Input circuit closes before reset
circuit
` b: Reset circuit closes before input
circuit
R
= max. overall cable resist-
lmax
ance (see technical details)
/km = cable resistance/km
R
l
` Use copper wire that can withstand
60/75 °C.
` Sufficient fuse protection must be
provided on all output contacts with capacitive and inductive loads.
: Switch-on delay
` t
1
` t2: Delay-on de-energisation
: Recovery time
` t
3
: Waiting period
` t
4
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-322-2010-01Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-2
Page 3
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X3.10P
Preparing for operation
Betriebsbereitschaft her stellen
` Supply voltage
Supply voltage AC DC
A1
A2
L1
N
` Input circuit
Input circuit Single-channel Dual-channel E-STOP
without detection of shorts across con­tacts
E-STOP with detection of shorts across contacts
S21 S22
S12 S11 S32
S31
S1
S21 S22
S11 S12
A1
A2
S11
S12 S32
S22 S32 S31 S21
L+
L-
S1
S1
Safety gate without detection of shorts across con­tacts
Safety gate with detection of shorts across contacts
Light beam device with detection of shorts across contacts via ESPE
S21 S22
S12 S11 S32
S31
S1
S21 S22
S21 S22
S11 S12
S12 S32
S11
S12 S32
S22 S21 S32
S31
S1
S1
S2
S2
24 V DC
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-322-2010-01
Page 4
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X3.10P
` Reset circuit
Reset circuit E-STOP wiring, safety gate Safety gate (dual-channel) Automatic reset
S13
S15
S14
S16 S13 S14
S2S1
Manual reset
S13
S14
Monitored reset
S33
S34
S3
S3
` Feedback circuit
Feedback circuit Automatic reset Monitored reset Contacts from external contactors
S13 S14
13 (23, 33) 14 (24, 34)
K5
K6
K5
K6
L1 N
` Semiconductor output
S33
S34
S33
S34 13 (23, 33) 14 (24 ,34)
K5
K6
K5
K6
S3
S3
L1 N
Y31 Y32
Y30
24 V DC SPS Input
0 V
` Key
S1/S2 E-STOP/safety gate switch
S3 Reset button
Switch operated
Gate open
Gate closed
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-322-2010-01Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-4
Page 5
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X3.10P
Terminal configuration
Klemmenbelegung
A1S32
S31A1
X113P3
S14S12 S13S11
X2 P4
4123 33
Installation
Montage_PNOZ_X
` The safety relay should be installed
in a control cabinet with a protec­tion type of at least IP54.
` Use the notch on the rear of the unit
to attach it to a DIN rail.
` Ensure the unit is mounted securely
on a vertical DIN rail (35 mm) by us­ing a fixing element (e.g. retaining bracket or an end angle).
PNOZ X3.10P
18995
Dimensions
Abmessungen
* with spring-loaded terminals
POWER CH.1 CH.2
S15A2S16
Y32
Y31Y30A2
S21
X414P4
3313 23 41
14 24 34 42
X3 P3
S33S22 S34
121 (4.76")
4224 34
94 (3.70")
* 101 (3.98")
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
45
(1.77")
NSG-D-2-322-2010-01
Page 6
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X3.10P
Notice
][WICHTIG_PDB_al t
This data sheet is only intended for use during configuration. For installation and operation, please refer to the op­erating instructions supplied with the
Service life graph
10
AC15: 230 V
unit.
DC13: 24 V
1
D Nennbetriebstrom (A)
GB Nominal operating current (A)
][Technische Daten PNOZ
Technical details
Electrical data
Supply voltage Supply voltage U
AC/DC 24 V
B
Voltage tolerance -15 %/+10 % Power consumption at U Power consumption at U
AC 5.0 VA
B
DC 2.5 W
B
Frequency range AC 50 - 60 Hz Residual ripple DC 160 % Voltage and current at Input circuit DC: 24.0 V 40.0 mA Reset circuit DC: 24.0 V 70.0 mA Feedback loop DC: 24.0 V 20.0 mA Number of output contacts Safety contacts (S) instantaneous: 3 Auxiliary contacts (N/C): 1 Utilisation category in accordance with EN 60947-4-1 Safety contacts: AC1 at 240 V I
Safety contacts: DC1 at 24 V I
Auxiliary contacts: AC1 at 240 V I
Auxiliary contacts: DC1 at 24 V I
Utilisation category in accordance with EN 60947-5-1 Safety contacts: AC15 at 230 V I Safety contacts: DC13 at 24 V (6 cycles/min) I Auxiliary contacts: AC15 at 230 V I Auxiliary contacts: DC13 at 24 V (6 cycles/min) I Contact material AgSnO2 + 0.2 µm Au
0.1
F Courant coupé (A)
E Corriente nominal de servicio (A)
I Corrente di esercizio nominale (A)
NL Nominale bedrijfsstroom (A)
10 100 1000 10000
D Schaltspielzahl x 10 GB Cycles x 10 F Nombre de manuvres x 10
: 0.01 A , I
min
P
: 2000 VA
max
: 0.01 A , I
min
: 200 W
P
max
: 0.01 A , I
min
P
: 2000 VA
max
: 0.01 A , I
min
P
: 200 W
max
: 5.0 A
max
: 6.0 A
max
: 5.0 A
max
: 6.0 A
max
3
3
: 8.0 A
max
max
max
max
Lebensdauerkurve
: 8.0 A
: 8.0 A
: 8.0 A
DC1: 24 V
AC1: 230 V
E Número de ciclos x 10 I Numero dei cicli di commutazione x 10
3
NL Aantal schakelingen x 10
3
3
3
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-322-2010-01Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-6
Page 7
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X3.10P
Electrical data
External contact fuse protection (IK = 1 kA) to EN 60947-5-1 Blow-out fuse, quick Safety contacts: 10 A Auxiliary contacts: 10 A Blow-out fuse, slow Safety contacts: 6 A Auxiliary contacts: 6 A Circuit breaker 24 VAC/DC, characteristic B/C Safety contacts: 6 A Auxiliary contacts: 6 A Semiconductor outputs (short circuit proof) 24.0 V DC,20 mA External supply voltage 24.0 V DC Voltage tolerance -20 %/+20 % Max. overall cable resistance R input circuits, reset circuits single-channel at U single-channel at U dual-channel without detect. of shorts across contacts at U dual-channel without detect. of shorts across contacts at U dual-channel with detect. of shorts across contacts at U dual-channel with detect. of shorts across contacts at U
Safety-related characteristic data
PL in accordance with EN ISO 13849-1 PL e (Cat. 4) Category in accordance with EN 954-1 Cat. 4 SIL CL in accordance with EN IEC 62061 SIL CL 3 PFH in accordance with EN IEC 62061 2.31E-09 SIL in accordance with IEC 61511 SIL 3 PFD in accordance with IEC 61511 2.03E-06 t
in years 20
M
Times
Switch-on delay with automatic reset typ. 250 ms with automatic reset max. 500 ms with automatic reset after power on typ. 280 ms with automatic reset after power on max. 550 ms with manual reset typ. 200 ms with manual reset max. 500 ms on monitored reset with rising edge typ. 35 ms on monitored reset with rising edge max. 50 ms Delay-on de-energisation with E-STOP typ. 15 ms with E-STOP max. 30 ms with power failure typ. 180 ms with power failure max. 260 ms Recovery time at max. switching frequency 1/s after E-STOP 50 ms after power failure 350 ms Waiting period with a monitored reset with rising edge 300 ms Min. start pulse duration with a monitored reset with rising edge 30 ms Simultaneity, channel 1 and 2 Supply interruption before de-energisation 150 ms
DC 150 Ohm
B
AC 180 Ohm
B
lmax
DC 300 Ohm
B
AC 360 Ohm
B
DC 15 Ohm
B
AC 30 Ohm
B
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-322-2010-01
Page 8
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X3.10P
Environmental data
EMC EN 60947-5-1, EN 61000-6-2 Vibration to EN 60068-2-6 Frequency 10 - 55 Hz Amplitude 0.35 mm Climatic suitability EN 60068-2-78 Airgap creepage in accordance with EN 60947-1 Pollution degree 2 Overvoltage category III Rated insulation voltage 250 V Rated impulse withstand voltage 4.00 kV Ambient temperature -20 - 55 °C Storage temperature -40 - 85 °C Protection type Mounting (e.g. cabinet) IP54 Housing IP40 Terminals IP20
Mechanical data
Housing material Housing PPO UL 94 V0 Front ABS UL 94 V0 Cross section of external conductors with screw terminals 1 core flexible 0.25 - 2.50 mm² , 24 - 12 AWG Order no.: 777314 2 core, same cross section, flexible: with crimp connectors, without insulating sleeve 0.25 - 1.00 mm² , 24 - 16 AWG Order no.: 777314 without crimp connectors or with TWIN crimp connectors 0.20 - 1.50 mm² , 24 - 16 AWG Order no.: 777314 Torque setting with screw terminals 0.50 Nm Order no.: 777314 Cross section of external conductors with spring-loaded termi­nals: Flexible with/without crimp connectors Spring-loaded terminals: Terminal points per connection 2 Order no.: 787314 Stripping length 8 mm Order no.: 787314 Dimensions Height 101.0 mm Order no.: 787314
Width 45.0 mm Depth 121.0 mm Weight 270 g Order no.: 787314
Technische Daten_Satz No rmen
The standards current on 2007-09 apply.
][Dauerstrom_ACDC
0.20 - 1.50 mm² , 24 - 16 AWG Order no.: 787314
94.0 mm Order no.: 777314
280 g Order no.: 777314
Conventional thermal current
Number of contacts I 1 8.00 A 8.00 A 2 8.00 A 7.00 A 3 7.00 A 6.00 A
Order reference
Type Features Terminals Order no.
PNOZ X3.10P C 24 VAC/DC Spring-loaded terminals 787 314 PNOZ X3.10P 24 VAC/DC Screw terminals 777 314