E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X3
Safety relay for monitoring E-STOP
pushbuttons and safety gates.
Approvals
PNOZ X3
Unit features
` Positive-guided relay outputs:
– 3 safety contacts (N/O), instanta-
neous
– 1 auxiliary contact (N/C), instan-
taneous
` 1 semiconductor output
` Connection options for:
– E-STOP pushbutton
– Safety gate limit switch
– Reset button
` LED indicator for:
– Switch status channel 1/2
– Supply voltage
` Semiconductor output signals:
– Switch status channel 1/2
` See order reference for unit types
Unit description
The safety relay meets the requirements of EN 60947-5-1, EN 60204-1
and VDE 0113-1 and may be used in
applications with
` E-STOP pushbuttons
` Safety gates
Safety features
The relay meets the following safety
requirements:
` The circuit is redundant with built-in
self-monitoring.
` The safety function remains effec-
tive in the case of a component failure.
` The correct opening and closing of
the safety function relays is tested
automatically in each on-off cycle.
` The tranformer is short circuit-
proof. An electronic fuse is used on
a DC supply.
Block diagram
S11 S12A1 A2
~
~
Power
=
=
B1 B2 Y31
24 V
S21 S22
Y32
Input
S13 S14
Reset/
Start
S33 S34
Reset/
Start
K1
K2
23 33 41
13
14 24 34 42
S31 S32
InputInput
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-036-2006-07
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X3
Function description
` Single-channel operation: no re-
dundancy in the input circuit, earth
faults in the reset and input circuit
are detected.
` Dual-channel operation with detec-
tion of shorts across contacts: redundant input circuit, detects
Timing diagram
POWER
Reset/Start
Input
Output safe
Output aux.
Out semi CH
– earth faults in the reset and input
circuit,
– short circuits in the input circuit
and, with a monitored reset, in
the reset circuit too,
– shorts between contacts in the
input circuit.
` Automatic start: Unit is active once
the input circuit has been closed.
1 2
t1 t2 t1 t2
t3
` Monitored reset: Unit is active once
the input circuit is closed and once
the reset circuit is closed after the
waiting period has elapsed
(see technical details).
` Increase in the number of available
contacts by connecting contact expander modules or external contactors/relays.
t1
t2
t3
t1 t2
Key
` Power: Supply voltage
` Reset/start: Reset circuit S13-S14,
S33-S34
` Input: Input circuits S11-S12, S21-
S22, S31-S32
Wiring
Please note:
` Information given in the “Technical
details” must be followed.
` Outputs 13-14, 23-24, 33-34 are
safety contacts, output 41-42 is an
auxiliary contact (e.g. for display).
` To prevent contact welding, a fuse
should be connected before the
output contacts (see technical details).
` Calculation of the max. cable runs
in the input circuit:
l
max
R
lmax
=
I
max
Rl / km
= max. overall cable resist-
R
lmax
ance (see technical details)
/km = cable resistance/km
R
l
` Use copper wire that can withstand
60/75 °C.
` Output safe: Safety contacts 13-14,
23-24, 33-34
` Output aux: Auxiliary contacts 41-
42
` Out semi CH: Semiconductor out-
put switch status channel 1/2
` Sufficient fuse protection must be
provided on all output contacts with
capacitive and inductive loads.
` c: Automatic reset
` d: Monitored reset
: Switch-on delay
` t
1
` t2: Delay-on de-energisation
: Waiting period
` t
3
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-036-2006-07Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-2
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X3
Preparing for operation
` Supply voltage
Supply voltage AC DC
A1
A2
B2 PE
L1
N
` Input circuit
Input circuit Single-channel Dual-channel
E-STOP
without detection of shorts across contacts
E-STOP
with detection of shorts across contacts
Safety gate
without detection of shorts across contacts
S21
S22
S21
S22
S12
S11
S32
S31
S12
S11
S32
S31
S1
S11
S12
S1
B1
B2
S22
S32
S31
S21
L+
L-
S1
Safety gate
with detection of shorts across contacts
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
S11
S12
S22
S21
S32
S31
S1
S2
NSG-D-2-036-2006-07