Pilz PNOZ x3 Data Sheet

Page 1
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X3
Safety relay for monitoring E-STOP pushbuttons and safety gates.
PNOZ X3
Unit features
` Positive-guided relay outputs:
– 3 safety contacts (N/O), instanta-
neous
– 1 auxiliary contact (N/C), instan-
taneous
` 1 semiconductor output ` Connection options for:
– E-STOP pushbutton – Safety gate limit switch – Reset button
` LED indicator for:
– Switch status channel 1/2 – Supply voltage
` Semiconductor output signals:
– Switch status channel 1/2
` See order reference for unit types
Unit description
The safety relay meets the require­ments of EN 60947-5-1, EN 60204-1 and VDE 0113-1 and may be used in applications with
` E-STOP pushbuttons ` Safety gates
Safety features
The relay meets the following safety requirements:
` The circuit is redundant with built-in
self-monitoring.
` The safety function remains effec-
tive in the case of a component fail­ure.
` The correct opening and closing of
the safety function relays is tested automatically in each on-off cycle.
` The tranformer is short circuit-
proof. An electronic fuse is used on a DC supply.
Block diagram
S11 S12A1 A2
~
~
Power
=
=
B1 B2 Y31
24 V
S21 S22
Y32
Input
S13 S14
Reset/
Start
S33 S34
Reset/
Start
K1
K2
23 33 41
13
14 24 34 42
S31 S32
InputInput
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-036-2006-07
Page 2
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X3
Function description
` Single-channel operation: no re-
dundancy in the input circuit, earth faults in the reset and input circuit are detected.
` Dual-channel operation with detec-
tion of shorts across contacts: re­dundant input circuit, detects
Timing diagram
POWER
Reset/Start
Input
Output safe
Output aux.
Out semi CH
– earth faults in the reset and input
circuit,
– short circuits in the input circuit
and, with a monitored reset, in the reset circuit too,
– shorts between contacts in the
input circuit.
` Automatic start: Unit is active once
the input circuit has been closed.
1 2
t1 t2 t1 t2
t3
` Monitored reset: Unit is active once
the input circuit is closed and once the reset circuit is closed after the waiting period has elapsed (see technical details).
` Increase in the number of available
contacts by connecting contact ex­pander modules or external contac­tors/relays.
t1
t2
t3
t1 t2
Key
` Power: Supply voltage ` Reset/start: Reset circuit S13-S14,
S33-S34
` Input: Input circuits S11-S12, S21-
S22, S31-S32
Wiring
Please note:
` Information given in the “Technical
details” must be followed.
` Outputs 13-14, 23-24, 33-34 are
safety contacts, output 41-42 is an auxiliary contact (e.g. for display).
` To prevent contact welding, a fuse
should be connected before the output contacts (see technical de­tails).
` Calculation of the max. cable runs
in the input circuit:
l
max
R
lmax
=
I
max
Rl / km
= max. overall cable resist-
R
lmax
ance (see technical details)
/km = cable resistance/km
R
l
` Use copper wire that can withstand
60/75 °C.
` Output safe: Safety contacts 13-14,
23-24, 33-34
` Output aux: Auxiliary contacts 41-
42
` Out semi CH: Semiconductor out-
put switch status channel 1/2
` Sufficient fuse protection must be
provided on all output contacts with capacitive and inductive loads.
` c: Automatic reset ` d: Monitored reset
: Switch-on delay
` t
1
` t2: Delay-on de-energisation
: Waiting period
` t
3
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-036-2006-07Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-2
Page 3
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X3
Preparing for operation
` Supply voltage
Supply voltage AC DC
A1
A2
B2 PE
L1
N
` Input circuit
Input circuit Single-channel Dual-channel
E-STOP without detection of shorts across con­tacts
E-STOP with detection of shorts across contacts
Safety gate without detection of shorts across con­tacts
S21
S22
S21
S22
S12
S11
S32 S31
S12
S11
S32 S31
S1
S11
S12
S1
B1
B2
S22
S32
S31 S21
L+
L-
S1
Safety gate with detection of shorts across contacts
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
S11
S12
S22
S21
S32 S31
S1
S2
NSG-D-2-036-2006-07
Page 4
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X3
` Reset circuit
Reset circuit E-STOP wiring, safety gate Safety gate (dual-channel)
Automatic reset
S13
S14
Monitored reset
S33
S34
S3
` Feedback loop
Feedback loop Automatic reset Monitored reset
Contacts from external contactors
S13
S14
13 (23, 33) 14 (24, 34)
K5
K6
K5
K6
L1
N
` Semiconductor output
Y31
Y32
B2
24 V DC
SPS Input
SPS 0 V
0 V
S13
S14
S33
S34 13 (23, 33) 14 (24 ,34)
K5
K6
K5
K6
S2S1
S3
L1
N
` Key
S1/S2 E-STOP/safety gate switch
S3 Reset button
Switch operated
Gate open
Gate closed
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-036-2006-07Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-4
Page 5
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X3
Terminal configuration
19968
S31 S32 S11 S12 S13 S14
A1 B1 13
PNOZ X3
POWER
CH. 1
CH. 2
14 24 34 A2B242
Y32
Y31
S2123S2233S3341S34
3313 23 41
14 24 34 42
Installation
` The safety relay should be installed
in a control cabinet with a protec­tion type of at least IP54.
` Use the notch on the rear of the unit
to attach it to a DIN rail.
` Ensure the unit is mounted securely
on a vertical DIN rail (35 mm) by us­ing a fixing element (e.g. retaining bracket or an end angle).
Dimensions
75 (2.95")
87 (3.42")
121 (4.76")
45
(1.77")
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-036-2006-07
Page 6
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X3
Notice
Service life graph
This data sheet is only intended for use during configuration. For installation and operation, please refer to the op­erating instructions supplied with the
10
AC15: 230 V
unit.
DC13: 24 V
1
D Nennbetriebstrom (A)
GB Nominal operating current (A)
F Courant coupé (A)
Technical details
Electrical data
Supply voltage Supply voltage U Supply voltage U
AC 24 V, 42 V, 48 V, 110 V, 115 V, 120 V, 230 V, 240 V
B
DC 24 V
B
Voltage tolerance -15 %/+10 % Power consumption at U Power consumption at U
AC 5.0 VA
B
DC 2.5 W
B
Frequency range AC 50 - 60 Hz Residual ripple DC 160 % Voltage and current at Input circuit DC: 24.0 V 50.0 mA Reset circuit DC: 24.0 V 35.0 mA Feedback loop DC: 24.0 V 20.0 mA Number of output contacts Safety contacts (S) instantaneous: 3 Auxiliary contacts (N/C): 1 Category of output contacts in accordance with EN 954-1 Safety contacts (S) instantaneous: 4 Utilisation category in accordance with EN 60947-4-1 Safety contacts: AC1 at 240 V I
Safety contacts: DC1 at 24 V I
Auxiliary contacts: AC1 at 240 V I
Auxiliary contacts: DC1 at 24 V I
Utilisation category in accordance with EN 60947-5-1 Safety contacts: AC15 at 230 V I Safety contacts: DC13 at24 V (6 cycles/min) I Auxiliary contacts: AC15 at 230 V I Auxiliary contacts: DC13 at24 V (6 cycles/min) I Contact material AgSnO2 + 0.2 µm Au
0.1
E Corriente nominal de servicio (A)
I Corrente di esercizio nominale (A)
NL Nominale bedrijfsstroom (A)
10 100 1000 10000
D Schaltspielzahl x 10 GB Cycles x 10 F Nombre de manvres x 10
: 0.01 A , I
min
P
: 2000 VA
max
: 0.01 A , I
min
: 200 W
P
max
: 0.01 A , I
min
P
: 2000 VA
max
: 0.01 A , I
min
P
: 200 W
max
: 5.0 A
max
: 6.0 A
max
: 5.0 A
max
: 6.0 A
max
3
3
: 8.0 A
max
max
max
max
3
: 8.0 A
: 8.0 A
: 8.0 A
DC1: 24 V
AC1: 230 V
E Número de ciclos x 10 I Numero dei cicli di commutazione x 10 NL Aantal schakelingen x 10
3
3
3
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-036-2006-07Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-6
Page 7
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X3
Electrical data
External contact fuse protection (IK = 1 kA) to EN 60947-5-1 Blow-out fuse, quick Safety contacts: 10 A Auxiliary contacts: 10 A Blow-out fuse, slow Safety contacts: 6 A Auxiliary contacts: 6 A Circuit breaker 24 VAC/DC, characteristic B/C Safety contacts: 6 A Auxiliary contacts: 6 A Semiconductor outputs (short circuit proof) 24.0 V DC, 20 mA External supply voltage 24.0 V DC Voltage tolerance -20 %/+20 % Max. overall cable resistance R input circuits, reset circuits single-channel at U single-channel at U dual-channel with detect. of shorts across contacts at U dual-channel with detect. of shorts across contacts at U
Times
Switch-on delay with automatic reset typ. 250 ms with automatic reset max. 500 ms with automatic reset after power on typ. 280 ms with automatic reset after power on max. 550 ms on monitored reset with rising edge typ. 35 ms on monitored reset with rising edge max. 50 ms Delay-on de-energisation with E-STOP typ. 15 ms with E-STOP max. 30 ms with power failure typ. 50 ms with power failure max. 70 ms Recovery time at max. switching frequency 1/s after E-STOP 50 ms after power failure 100 ms Waiting period with a monitored reset with rising edge 300 ms Min. start pulse duration with a monitored reset with rising edge 30 ms Simultaneity, channel 1 and 2 Supply interruption before de-energisation 20 ms
Environmental data
EMC EN 12015, EN 12016, EN 60947-5-1, EN 61000-6-2 Vibration to EN 60068-2-6 Frequency 10 - 55 Hz Amplitude 0.35 mm Climatic suitability EN 60068-2-78 Airgap creepage EN 60947-1 Rated insulation voltage 250 V Rated impulse withstand voltage 4.0 kV Ambient temperature -20 - 55 °C Storage temperature -40 - 85 °C Protection type Mounting (e.g. cabinet) IP54 Housing IP40 Terminals IP20
DC 150 Ohm
B
AC 180 Ohm
B
lmax
DC 15 Ohm
B
AC 30 Ohm
B
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-036-2006-07
Page 8
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X3
Mechanical data
Housing material Housing PPO UL 94 V0 Front ABS UL 94 V0 Max. cross section of external conductors with screw terminals 1 core flexible 0.20 - 4.00 mm² , 24 - 10 AWG 2 core, same cross section, flexible: with crimp connectors, without insulating sleeve 0.20 - 2.50 mm² , 24 - 14 AWG without crimp connectors or with TWIN crimp connectors 0.20 - 2.50 mm² , 24 - 14 AWG Torque setting with screw terminals 0.60 Nm Dimensions Height 87.0 mm Width 45.0 mm Depth 121.0 mm Weight 375 g
The standards current on 08/02 apply.
Conventional thermal current
Number of contacts I 1 8.00 A 8.00 A 2 8.00 A 7.50 A 3 7.00 A 6.50 A
Order reference
Type Features Terminals Order no.
PNOZ X3 24 VAC/DC 24 VDC Screw terminals 774 310 PNOZ X3 42 VAC 24 VDC Screw terminals 774 311 PNOZ X3 48 VAC 24 VDC Screw terminals 774 312 PNOZ X3 110 VAC 24 VDC Screw terminals 774 314 PNOZ X3 115 VAC 24 VDC Screw terminals 774 315 PNOZ X3 120 VAC 24 VDC Screw terminals 774 316 PNOZ X3 230 VAC 24 VDC Screw terminals 774 318 PNOZ X3 240 VAC 24 VDC Screw terminals 774 319
(A) at UBDC Ith(A) at UBAC
th
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-036-2006-07Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-8