This data sheet is only intended for use
during configuration. For installation
and operation, please refer to the operating instructions supplied with the
Voltage tolerance-15 %/+10 %
Power consumption at U
Power consumption at U
AC5.0 VA
B
DC2.5 W
B
Frequency range AC50 - 60 Hz
Residual ripple DC160 %
Voltage and current at
Input circuit DC: 24.0 V50.0 mA
Reset circuit DC: 24.0 V35.0 mA
Feedback loop DC: 24.0 V20.0 mA
Number of output contacts
Safety contacts (S) instantaneous:3
Auxiliary contacts (N/C):1
Category of output contacts in accordance with EN 954-1
Safety contacts (S) instantaneous:4
Utilisation category in accordance with EN 60947-4-1
Safety contacts: AC1 at 240 VI
Safety contacts: DC1 at 24 VI
Auxiliary contacts: AC1 at 240 VI
Auxiliary contacts: DC1 at 24 VI
Utilisation category in accordance with EN 60947-5-1
Safety contacts: AC15 at 230 VI
Safety contacts: DC13 at24 V (6 cycles/min)I
Auxiliary contacts: AC15 at 230 VI
Auxiliary contacts: DC13 at24 V (6 cycles/min)I
Contact materialAgSnO2 + 0.2 µm Au
0.1
E Corriente nominal de servicio (A)
ICorrente di esercizio nominale (A)
NL Nominale bedrijfsstroom (A)
10100100010000
D Schaltspielzahl x 10
GB Cycles x 10
F Nombre de manvres x 10
: 0.01 A , I
min
P
: 2000 VA
max
: 0.01 A , I
min
: 200 W
P
max
: 0.01 A , I
min
P
: 2000 VA
max
: 0.01 A , I
min
P
: 200 W
max
: 5.0 A
max
: 6.0 A
max
: 5.0 A
max
: 6.0 A
max
3
3
: 8.0 A
max
max
max
max
3
: 8.0 A
: 8.0 A
: 8.0 A
DC1: 24 V
AC1: 230 V
E Número de ciclos x 10
INumero dei cicli di commutazione x 10
NL Aantal schakelingen x 10
External contact fuse protection (IK = 1 kA) to EN 60947-5-1
Blow-out fuse, quick
Safety contacts:10 A
Auxiliary contacts:10 A
Blow-out fuse, slow
Safety contacts:6 A
Auxiliary contacts:6 A
Circuit breaker 24 VAC/DC, characteristic B/C
Safety contacts:6 A
Auxiliary contacts:6 A
Semiconductor outputs (short circuit proof) 24.0 V DC, 20 mA
External supply voltage24.0 V DC
Voltage tolerance-20 %/+20 %
Max. overall cable resistance R
input circuits, reset circuits
single-channel at U
single-channel at U
dual-channel with detect. of shorts across contacts at U
dual-channel with detect. of shorts across contacts at U
Times
Switch-on delay
with automatic reset typ.250 ms
with automatic reset max.500 ms
with automatic reset after power on typ.280 ms
with automatic reset after power on max.550 ms
on monitored reset with rising edge typ.35 ms
on monitored reset with rising edge max.50 ms
Delay-on de-energisation
with E-STOP typ.15 ms
with E-STOP max.30 ms
with power failure typ.50 ms
with power failure max.70 ms
Recovery time at max. switching frequency 1/s
after E-STOP50 ms
after power failure100 ms
Waiting period with a monitored reset
with rising edge300 ms
Min. start pulse duration with a monitored reset
with rising edge30 ms
Simultaneity, channel 1 and 2∞
Supply interruption before de-energisation 20 ms
Environmental data
EMCEN 12015, EN 12016, EN 60947-5-1, EN 61000-6-2
Vibration to EN 60068-2-6
Frequency10 - 55 Hz
Amplitude0.35 mm
Climatic suitabilityEN 60068-2-78
Airgap creepageEN 60947-1
Rated insulation voltage250 V
Rated impulse withstand voltage4.0 kV
Ambient temperature-20 - 55 °C
Storage temperature-40 - 85 °C
Protection type
Mounting (e.g. cabinet)IP54
HousingIP40
TerminalsIP20