Pilz PNOZ X2P Data Sheet

Page 1
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X2P
Gertebild
][Bildunterschrift
Approvals
PNOZ X2P
SÜDDEUTSCHLAND
Unit features
Gertemerkmale
` Positive-guided relay outputs:
– 2 safety contacts (N/O), instanta-
neous
` Connection options for:
– E-STOP pushbutton – Safety gate limit switch – Reset button
` LED indicator for:
– Switch status channel 1/2 – Supply voltage
` Plug-in connection terminals (either
spring-loaded terminal or screw terminal)
` See order reference for unit types
Unit Description
Bestimmung/Gertebeschreibung NOT-AUS, Schutz_PNOZ
The safety relay meets the require­ments of EN 60947-5-1, EN 60204-1 and VDE 0113-1 and may be used in applications with
` E-STOP pushbuttons ` Safety gates
Safety features
][Sicherheitseigenscha ften Schaltgerät_allgem einer Teil
The relay meets the following safety requirements:
` The circuit is redundant with built-in
self-monitoring.
` The safety function remains effec-
tive in the case of a component fail­ure.
` The correct opening and closing of
the safety function relays is tested automatically in each on-off cycle.
Zulassungen
Block diagram
Blockschaltbild
~
=
Power
*only applicable for UB 48 – 240 VAC/DC
S11 S12A1 A2
( )*
S21 S22
InputInput
S33 S34
Reset/
Start
Y36 Y37
Reset/
Start
13 23
K1
K2
14 24
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-143-2010-08
Page 2
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X2P
Function Description
][Funktionen_einkanalig
` Single-channel operation: no re-
dundancy in the input circuit, earth faults in the reset and input circuit are detected.
][Funktionen_zweikanalig_mit_quer_ber
` Dual-channel operation with detec-
tion of shorts across contacts: re­dundant input circuit, detects – earth faults in the reset and input
circuit,
Timing diagram
1 2
POWER
Reset/Start
Input
Output safe
t1 t2
t1 t2
Key
` Power: Supply voltage ` Reset/Start: Reset circuit S33-S34,
Y36-Y37
` Input: Input circuits S11-S12, S21-
S22
` Output safe: Safety outputs 13-14,
23-24
– short circuits in the input circuit
and, with a monitored reset, in the reset circuit too,
– shorts between contacts in the
input circuit.
][Funktionen_autoStart
` Automatic start: Unit is active once
the input circuit has been closed.
][Funktionen_manuStart
` Manual reset: Unit is active once
the input circuit is closed and then the reset circuit is closed.
][Funktionen_berStart_Wartezeit
][Zeitdiagramm_auto_manu_ueber2
ab
t1
t1
t2
` c: Automatic reset ` d: Manual reset ` e: Monitored reset ` a: Input circuit closes before reset
circuit
` b: Reset circuit closes before input
circuit
` Monitored reset: Unit is active once
the input circuit is closed and once the reset circuit is closed after the waiting period has elapsed (see technical details).
][Funktionen_Kontaktvervielfachung
` Increase in the number of available
instantaneous safety contacts by connecting contact expansion modules or external contactors.
3
t2
t1 t2 t1 t2t3 t3
t4
: Switch-on delay
` t
1
: Delay-on de-energisation
` t
2
: Waiting period
` t
3
: Recovery time
` t
4
Wiring
][Verdrahtung_Si_unverz
Please note:
` Information given in the “Technical
details” must be followed.
` Outputs 13-14, 23-24 are safety
contacts.
` Use copper wire that can withstand
60/75 °C.
` Sufficient fuse protection must be
provided on all output contacts with capacitive and inductive loads.
` To prevent contact welding, a fuse
should be connected before the output contacts (see technical de­tails).
` Calculation of the max. cable runs
in the input circuit:
l
max
R
lmax
=
I
max
Rl / km
R
= max. overall cable resist-
lmax
ance (see technical details)
/km = cable resistance/km
R
l
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-143-2010-08Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-2
Page 3
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X2P
Preparing for operation
Betriebsbereitschaft her stellen
` Supply voltage
Supply voltage AC DC
24 VAC/DC
U
B
48 - 240 VAC/DC
U
B
A2
A1
A2
A1
L1
N
L1
N
PE
` Input circuit
Input circuit Single-channel Dual-channel E-STOP
without detection of shorts across con­tacts
(only when U
S21 S22
24 VAC/DC)
B
A1
S11 S12
S1
L+
A1
A2
A1
A2
L+
L-
L+
L-
PE
E-STOP with detection of shorts across contacts
Safety gate without detection of shorts across con­tacts
Safety gate with detection of shorts across contacts
(only when U
S21 S22
24 VAC/DC)
B
A1
S11 S12
S1
L+
S11 S12 S21 S22
S11 S21 S22
S12
S1
S1
S2
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-143-2010-08
Page 4
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X2P
` Reset circuit
Reset circuit E-STOP wiring (single-channel)
Safety gate (single-channel)
Automatic reset (only when U
Manual reset (only when U
Monitored reset (only when U
24 VAC/DC)
B
24 VAC/DC)
B
S33 S34 Y36 Y37
24 VAC/DC)
B
S33
S34
S33 S34
Y36 Y37
S3
S3
E-STOP wiring (dual-channel) Safety gate (dual-channel)
` Feedback circuit
Feedback circuit Automatic reset Monitored reset Contacts from external contactors
S33 S34
13 (23) 14 (24)
K5
K6
K5
K6
L1 N
S33 S34 Y36 Y37
S33
S34
S33
S34 13 (23) 14 (24)
S33 S34
Y36 Y37
K5
K6
K5
K6
S3
S3
S3
L1 N
` Key
S1/S2 E-STOP/safety gate switch
S3 Reset button
Switch operated
Gate open
Gate closed
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-143-2010-08Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-4
Page 5
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X2P
Terminal configuration
Klemmenbelegung
UB 24 VAC/DC
A1
P 1
S33
S34
P 2
PNOZ X2P
POWER CH.1 CH.2 13
14
19877
P 2
S12
S11
P 1
A2
13 23
23
24
S21
14
Y37Y36
S22
24
Installation
Montage_PNOZ_X
` The safety relay should be installed
in a control cabinet with a protec­tion type of at least IP54.
` Use the notch on the rear of the unit
to attach it to a DIN rail.
` Ensure the unit is mounted securely
on a vertical DIN rail (35 mm) by us­ing a fixing element (e.g. retaining bracket or an end angle).
U
48 - 240 VAC/DC
B
Dimensions
Abmessungen
* with spring-loaded terminals
A1
P 1
S33
S34
P 2
PNOZ X2P
POWER CH.1 CH.2 13
14
19436
P 2
S12
S11
P 1
A2
13 23
23
24
S21
14
Y37Y36
S22
24
121 (4.76")
94 (3.70")
* 101 (3.98")
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
22,5
(0.88")
NSG-D-2-143-2010-08
Page 6
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X2P
Notice
][WICHTIG_PDB_al t
This data sheet is only intended for use during configuration. For installation and operation, please refer to the op­erating instructions supplied with the
Service life trend
Lebensdauerkurve
10
AC15: 230 V
unit.
DC13: 24 V
1
D Nennbetriebstrom (A)
GB Nominal operating current (A)
][Technische Daten PNOZ
Technical details
Electrical data
Supply voltage Supply voltage U
AC/DC 24 V, 48 - 240 V
B
Voltage tolerance -15 %/+10 % Power consumption at U
Power consumption at U
AC 3.5 VA No. 777307, 787307
B
DC 1.0 W No. 777307, 787307
B
Frequency range AC 50 - 60 Hz Residual ripple DC 160 % Voltage and current at Input circuit DC: 24.0 V 15.0 mA No. 777307, 787307
Reset circuit DC: 24.0 V 25.0 mA No. 777307, 787307
Feedback loop DC: 24.0 V 25.0 mA No. 777307, 787307
Number of output contacts Safety contacts (S) instantaneous: 2 Utilisation category in accordance with EN 60947-4-1 Safety contacts: AC1 at 240 V I
Safety contacts: DC1 at 24 V I
Utilisation category in accordance with EN 60947-5-1 Safety contacts: AC15 at 230 V I Safety contacts: DC13 at 24 V (6 cycles/min) I Contact material AgSnO2 + 0.2 µm Au External contact fuse protection (I
= 1 kA) to EN 60947-5-1
K
Blow-out fuse, quick Safety contacts: 6 A Blow-out fuse, slow Safety contacts: 4 A Circuit breaker 24 VAC/DC, characteristic B/C Safety contacts: 4 A
0.1
F Courant coupé (A)
E Corriente nominal de servicio (A)
I Corrente di esercizio nominale (A)
NL Nominale bedrijfsstroom (A)
10 100 1000 10000
D Schaltspielzahl x 10 GB Cycles x 10 F Nombre de manuvres x 10
3
3
3
4.5 VA No. 777303, 787303
2.0 W No. 777303, 787303
25.0 mA No. 777303, 787303
50.0 mA No. 777303, 787303
50.0 mA No. 777303, 787303
: 0.01 A , I
min
P
: 1500 VA
max
: 0.01 A , I
min
: 150 W
P
max
: 5.0 A
max
: 4.0 A
max
max
max
: 6.0 A
: 6.0 A
DC1: 24 V
AC1: 230 V
E Número de ciclos x 10 I Numero dei cicli di commutazione x 10 NL Aantal schakelingen x 10
3
3
3
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-143-2010-08Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-6
Page 7
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X2P
Electrical data
Max. overall cable resistance R input circuits, reset circuits single-channel at U
single-channel at U
dual-channel with detect. of shorts across contacts at U
dual-channel with detect. of shorts across contacts at U
Min. input resistance in the starting torque 19 Ohm No. 777307, 787307
Safety-related characteristic data
PL in accordance with EN ISO 13849-1 PL e (Cat. 4) Category in accordance with EN 954-1 Cat. 4 SIL CL in accordance with EN IEC 62061 SIL CL 3 PFH in accordance with EN IEC 62061 2.31E-09 SIL in accordance with IEC 61511 SIL 3 PFD in accordance with IEC 61511 2.03E-06 t
in years 20
M
Times
Switch-on delay with automatic reset typ. 120 ms No. 777307, 787307
with automatic reset max. 150 ms No. 777307, 787307
with automatic reset after power on typ. 130 ms No. 777307, 787307
with automatic reset after power on max. 100 ms No. 777303, 787303
with manual reset typ. 38 ms with manual reset max. 150 ms No. 777307, 787307
on monitored reset with rising edge typ. 38 ms on monitored reset with rising edge max. 50 ms Delay-on de-energisation with E-STOP typ. 12 ms No. 777307, 787307
with E-STOP max. 30 ms with power failure typ. 40 ms No. 777307, 787307
with power failure max. 110 ms No. 777303, 787303
with power failure typ. U with power failure max. U Recovery time at max. switching frequency 1/s after E-STOP 50 ms after power failure 150 ms No. 777303, 787303
Waiting period with a monitored reset with rising edge 180 ms Min. start pulse duration with a monitored reset with rising edge 30 ms Simultaneity, channel 1 and 2 Supply interruption before de-energisation 20 ms
DC 100 Ohm No. 777307, 787307
B
AC 100 Ohm No. 777307, 787307
B
lmax
150 Ohm No. 777303, 787303
50 Ohm No. 777303, 787303
DC 100 Ohm No. 777307, 787307
B
AC 100 Ohm No. 777307, 787307
B
AC : 240 V 320 ms No. 777307, 787307
B
AC : 240 V 500 ms No. 777307, 787307
B
15 Ohm No. 777303, 787303
30 Ohm No. 777303, 787303
21 Ohm No. 777303, 787303
60 ms No. 777303, 787303
90 ms No. 777303, 787303
60 ms No. 777303, 787303
160 ms No. 777307, 787307
90 ms No. 777303, 787303
17 ms No. 777303, 787303
70 ms No. 777303, 787303
70 ms No. 777307, 787307
550 ms No. 777307, 787307
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-143-2010-08
Page 8
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ X2P
Environmental data
EMC EN 60947-5-1, EN 61000-6-2, EN 61000-6-3 Vibration to EN 60068-2-6 Frequency 10 - 55 Hz Amplitude 0.35 mm Climatic suitability EN 60068-2-78 Airgap creepage in accordance with EN 60947-1 Pollution degree 2 Overvoltage category III Rated insulation voltage 250 V Rated impulse withstand voltage 4.00 kV Ambient temperature -10 - 55 °C Storage temperature -40 - 85 °C Protection type Mounting (e.g. cabinet) IP54 Housing IP40 Terminals IP20
Mechanical data
Housing material Housing PPO UL 94 V0 Front ABS UL 94 V0 Cross section of external conductors with screw terminals 1 core flexible 0.25 - 2.50 mm² , 24 - 12 AWG No. 777303, 777307 2 core, same cross section, flexible: with crimp connectors, without insulating sleeve 0.25 - 1.00 mm² , 24 - 16 AWG No. 777303, 777307 without crimp connectors or with TWIN crimp connectors 0.20 - 1.50 mm² , 24 - 16 AWG No. 777303, 777307 Torque setting with screw terminals 0.50 Nm No. 777303, 777307 Cross section of external conductors with spring-loaded termi­nals: Flexible with/without crimp connectors Spring-loaded terminals: Terminal points per connection 2 No. 787303, 787307 Stripping length 8 mm No. 787303, 787307 Dimensions Height 101.0 mm No. 787303, 787307
Width 22.5 mm Depth 121.0 mm Weight 200 g
Technische Daten_Satz No .
No. stands for order number.
Technische Daten_Satz No rmen
The standards current on 2009-11 apply.
Bestelldaten
0.20 - 1.50 mm² , 24 - 16 AWG No. 787303, 787307
94.0 mm No. 777303, 777307
Order reference
Type Features Terminals Order no.
PNOZ X2P C 24 VAC 24 VDC Spring-loaded terminals 787 303 PNOZ X2P 24 VAC 24 VDC Screw terminals 777 303 PNOZ X2P C 48 - 240 VAC 48 - 240 VDC Spring-loaded terminals 787 307 PNOZ X2P 48 - 240 VAC 48 - 240 VDC Screw terminals 777 307
NSG-D-2-143-2010-08Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
-8