Pilz PNOZ X2.8P Data Sheet

E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X2.8P
Safety relay for monitoring E-STOP pushbuttons, safety gates and light barriers.
Approvals
PNOZ X2.8P
Unit features
` Positive-guided relay outputs:
– 3 safety contacts (N/O), instanta-
neous
– 1 auxiliary contact (N/C), instan-
taneous
` Connection options for:
– E-STOP pushbutton – Safety gate limit switch – Reset button – Light barriers
` LED indicator for:
– Switch status channel 1/2 – Supply voltage
` Plug-in connection terminals (either
cage clamp terminal or screw termi­nal)
` See order reference for unit types
Unit description
The safety relay meets the require­ments of EN 60947-5-1, EN 60204-1 and VDE 0113-1 and may be used in applications with
` E-STOP pushbuttons ` Safety gates
` Light barriers
Safety features
The relay meets the following safety requirements:
` The circuit is redundant with built-in
self-monitoring.
` The safety function remains effec-
tive in the case of a component fail­ure.
` The correct opening and closing of
the safety function relays is tested automatically in each on-off cycle.
Block diagram
~
=
( )
Power
*only with UB 24 - 240 VAC/DC
S11 S12A1 A2
*
S21 S22
InputInput
S52
Input
S12 S34
Reset/
Start
K1
K2
23 33 41
13
14 24 34 42
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-332-2006-07
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X2.8P
Function description
` Single-channel operation: no re-
dundancy in the input circuit, earth faults in the reset and input circuit are detected.
` Dual-channel operation without de-
tection of shorts across contacts: redundant input circuit, detects – earth faults in the reset and input
circuit,
Timing diagram
POWER
Reset/Start
Input
Output safe
Output aux.
– short circuits in the input circuit
and, with a monitored reset, in the reset circuit too.
` Dual-channel operation with detec-
tion of shorts across contacts: re­dundant input circuit, detects – earth faults in the reset and input
circuit,
– short circuits and shorts be-
tween contacts in the input cir­cuit.
1 2
t1 t2
t1 t2
` Automatic start: Unit is active once
the input circuit has been closed.
` Manual reset: Unit is active once
the input circuit is closed and then the reset circuit is closed.
` Increase in the number of available
contacts by connecting contact ex­pander modules or external contac­tors/relays.
ab
t1
t1
t2
t2
Key
` Power: Supply voltage ` Reset/start: Reset circuit S12-S34 ` Input: Input circuits S11-S12, S21-
S22, S52
` Output safe: Safety contacts 13-14,
23-24, 33-34,
Wiring
Please note:
` Information given in the “Technical
details” must be followed.
` Outputs 13-14, 23-24, 33-34, are
safety contacts, output 41-42 is an auxiliary contact (e.g. for display).
` To prevent contact welding, a fuse
should be connected before the output contacts (see technical de­tails).
` Calculation of the max. cable runs
in the input circuit:
l
max
R
lmax
=
I
max
Rl / km
= max. overall cable resist-
R
lmax
ance (see technical details)
/km = cable resistance/km
R
l
` Use copper wire that can withstand
60/75 °C.
` Output aux: Auxiliary contacts 41-
42
` c: Automatic reset ` d: Manual reset ` a: Input circuit closes before reset
circuit
` Sufficient fuse protection must be
provided on all output contacts with capacitive and inductive loads.
` b: Reset circuit closes before input
circuit
: Switch-on delay
` t
1
` t2: Delay-on de-energisation
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-332-2006-07Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-2
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X2.8P
Preparing for operation
` Supply voltage
Supply voltage 24 – 240 V AC/DC 24 V AC/DC
A1
A1
S21
S21
A2
A2
L1
L1
N
N
` Input circuit
Input circuit Single-channel Dual-channel
E-STOP without detection of shorts across con­tacts
E-STOP with detection of shorts across contacts
Safety gate without detection of shorts across con­tacts
S21
S22
S21
S22
S11
S12
S52
S11
S12
S52
S1
S21
S22
S11
S52
S1
S21
S22
S11
S12 S52
A1
A2
S11
S21
S22 S12
S11
S12 S52
S1
L+
L-
S1
S1
S2
Safety gate with detection of shorts across contacts
Light barrier with detection of shorts across contacts
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
S22
S22
S21
S21
S11
S52
S12
S12 S52
S52
S11 S12
S21
S22
S1
NSG-D-2-332-2006-07
S2
24 V DC
24 V DC
Gnd
Gnd
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X2.8P
` Reset circuit
Reset circuit E-STOP wiring (single-channel)
Automatic reset
Manual reset
Safety gate (single-channel)
S12
S34
S12
S34
S3
E-STOP wiring (dual-channel) Safety gate (dual-channel)
` Feedback loop
Feedback loop Automatic reset Manual reset
Contacts from external contactors
S12
S34
13 (23,33) 14 (24,34)
K5
K6
K5
K6
L1
N
` Key
S12
S34
S12
S34 13 (23, 33) 14 (24 ,34)
S12
S34
K5
K6
K5
K6
S3
S3
L1
N
S1/S2 E-STOP/safety gate switch
S3 Reset button
Switch operated
Gate open
Gate closed
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-332-2006-07Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-4
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X2.8P
Terminal configuration
13A1
23
P1
S52 S34 41 42
P2
PNOZ X2.8P
POWER
CH.1
CH.2
41
3323
33
Installation
` The safety relay should be installed
in a control cabinet with a protec­tion type of at least IP54.
` Use the notch on the rear of the unit
to attach it to a DIN rail.
` Ensure the unit is mounted securely
on a vertical DIN rail (35 mm) by us­ing a fixing element (e.g. retaining bracket or an end angle).
Dimensions
* with cage clamp terminals
141334
18992
S11 S12 S21 S22
94 (3.70")
* 101 (3.98")
24
42
P2
P1
342414A2
121 (4.76")
22,5
(0.88")
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-332-2006-07
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X2.8P
Notice
This data sheet is only intended for use during configuration. For installation and operation, please refer to the op­erating instructions supplied with the unit.
Service life graph
24 VAC/DC
U
B
10
DC13: 24 V
1
D Nennbetriebstrom (A)
GB Nominal operating current (A)
0.1
F Courant coupé (A)
E Corriente nominal de servicio (A)
I Corrente di esercizio nominale (A)
NL Nominale bedrijfsstroom (A)
10 100 1000 10000
D Schaltspielzahl x 10 GB Cycles x 10 F Nombre de manvres x 10
UB 24 - 240 VAC/DC
10
3
AC15: 230 V
AC1: 230 V
3
DC1: 24 V
AC15: 230 V
E Número de ciclos x 10 I Numero dei cicli di commutazione x 10
3
NL Aantal schakelingen x 10
3
3
DC1: 24 V
3
1
D Nennbetriebstrom (A)
GB Nominal operating current (A)
F Courant coupé (A)
0.1
E Corriente nominal de servicio (A)
I Corrente di esercizio nominale (A)
NL Nominale bedrijfsstroom (A)
10 100 1000 10000
D Schaltspielzahl x 10 GB Cycles x 10 F Nombre de manvres x 10
3
DC13: 24 V
3
E Número de ciclos x 10 I Numero dei cicli di commutazione x 10
3
NL Aantal schakelingen x 10
Technical details
Electrical data
Supply voltage Supply voltage U
AC/DC 24 - 240 V, 24 V
B
Voltage tolerance -15 %/+10 % Power consumption at U
Power consumption at U
AC 3.5 VA Order no.: 777301, 787301
B
DC 2.0 W
B
4.5 VA Order no.: 777302, 787302
Frequency range AC 50 - 60 Hz Residual ripple DC 160 % Voltage and current at Input circuit DC: 24.0 V 25.0 mA Order no.: 777302, 787302
30.0 mA Order no.: 777301, 787301 Reset circuit DC: 24.0 V 50.0 mA Feedback loop DC: 24.0 V 50.0 mA Number of output contacts Safety contacts (S) instantaneous: 3 Auxiliary contacts (N/C): 1
AC1: 230 V
3
3
3
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-332-2006-07Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-6
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X2.8P
Electrical data
Category of output contacts in accordance with EN 954-1 Safety contacts (S) instantaneous: 4 Utilisation category in accordance with EN 60947-4-1 Safety contacts: AC1 at 240 V I
Safety contacts: DC1 at 24 V I
Auxiliary contacts: AC1 at 240 V I
Auxiliary contacts: DC1 at 24 V I
Utilisation category in accordance with EN 60947-5-1 Safety contacts: AC15 at 230 V I
Safety contacts: DC13 at24 V (6 cycles/min) I Auxiliary contacts: AC15 at 230 V I
Auxiliary contacts: DC13 at24 V (6 cycles/min) I Contact material AgCuNi + 0.2 µm Au Order no.: 777302, 787302
External contact fuse protection (I
= 1 kA) to EN 60947-5-1
K
Blow-out fuse, quick Safety contacts: 6 A Auxiliary contacts: 6 A Blow-out fuse, slow Safety contacts: 4 A Auxiliary contacts: 4 A Circuit breaker 24 VAC/DC, characteristic B/C Safety contacts: 4 A Auxiliary contacts: 4 A Max. overall cable resistance R input circuits, reset circuits single-channel at U
single-channel at U
DC 30 Ohm Order no.: 777301, 787301
B
AC 120 Ohm Order no.: 777301, 787301
B
dual-channel without detect. of shorts across contacts at U
dual-channel without detect. of shorts across contacts at U
dual-channel with detect. of shorts across contacts at U dual-channel with detect. of shorts across contacts at U
lmax
DC 60 Ohm Order no.: 777301, 787301
B
AC 170 Ohm Order no.: 777301, 787301
B
DC 15 Ohm
B
AC 15 Ohm Order no.: 777302, 787302
B
Times
Switch-on delay with automatic reset typ. 250 ms Order no.: 777301, 787301
with automatic reset max. 400 ms Order no.: 777302, 787302
with automatic reset after power on typ. 250 ms Order no.: 777301, 787301
with automatic reset after power on max. 450 ms Order no.: 777301, 787301
with manual reset typ. 125 ms Order no.: 777301, 787301
with manual reset max. 350 ms Order no.: 777301, 787301
: 0.01 A , I
min
P
: 1500 VA
max
: 0.01 A , I
min
P
: 150 W
max
: 0.01 A , I
min
: 1500 VA
P
max
: 0.01 A , I
min
P
: 150 W
max
: 3.0 A Order no.: 777302, 787302
max
max
max
max
max
: 6.0 A
: 6.0 A
: 6.0 A
: 6.0 A
5.0 A Order no.: 777301, 787301
: 4.0 A
max
: 3.0 A Order no.: 777302, 787302
max
5.0 A Order no.: 777301, 787301
: 4.0 A
max
AgSnO2 + 0.2 µm Au Order no.: 777301, 787301
45 Ohm Order no.: 777302, 787302
45 Ohm Order no.: 777302, 787302
80 Ohm Order no.: 777302, 787302
80 Ohm Order no.: 777302, 787302
25 Ohm Order no.: 777301, 787301
340 ms Order no.: 777302, 787302
450 ms Order no.: 777301, 787301
600 ms Order no.: 777302, 787302
800 ms Order no.: 777302, 787302
180 ms Order no.: 777302, 787302
400 ms Order no.: 777302, 787302
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-332-2006-07
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X2.8P
Times
Delay-on de-energisation with E-STOP typ. 10 ms Order no.: 777302, 787302
12 ms Order no.: 777301, 787301
with E-STOP max. 20 ms Order no.: 777302, 787302
30 ms Order no.: 777301, 787301 with power failure typ. 50 ms Order no.: 777301, 787301 with power failure max. 60 ms Order no.: 777301, 787301 with power failure typ. U with power failure max. U 787302 with power failure typ. U with power failure max. U Recovery time at max. switching frequency 1/s after E-STOP 50 ms after power failure 100 ms Order no.: 777301, 787301
after power failure on universal power supply 1500 ms Order no.: 777302, 787302 Min. start pulse duration with a monitored reset with rising edge 30 ms Simultaneity, channel 1 and 2 Supply interruption before de-energisation 10 ms Order no.: 777301, 787301
Environmental data
EMC EN 60947-5-1, EN 61000-6-2, EN 61000-6-4 Vibration to EN 60068-2-6 Frequency 10 - 55 Hz Amplitude 0.35 mm Climatic suitability EN 60068-2-78 Airgap creepage VDE 0110-1 Ambient temperature -10 - 55 °C Storage temperature -40 - 85 °C Protection type Mounting (e.g. cabinet) IP54 Housing IP40 Terminals IP20
Mechanical data
Housing material Housing PPO UL 94 V0 Front ABS UL 94 V0 Max. cross section of external conductors with screw terminals 1 core flexible 0.25 - 2.50 mm² , 24 - 12 AWG Order no.: 777301, 777302 2 core, same cross section, flexible: with crimp connectors, without insulating sleeve 0.25 - 1.00 mm² , 24 - 16 AWG Order no.: 777301, 777302 without crimp connectors or with TWIN crimp connectors 0.20 - 1.50 mm² , 24 - 16 AWG Order no.: 777301, 777302 Torque setting with screw terminals 0.50 Nm Order no.: 777301, 777302 Max. cross section of external conductors with cage clamp termi­nals/spring-loaded terminals: Flexible without crimp connectors Cage clamp terminals/spring-loaded terminals: Terminal points per connection Stripping length 8 mm Order no.: 787301, 787302 Dimensions Height 101.0 mm Order no.: 787301, 787302
Width 22.5 mm Depth 121.0 mm Weight 195 g Order no.: 777301, 787301
AC/DC: 24 V Order no.: 777302, 787302 180 ms Order no.: 777302, 787302
B
AC/DC: 24 V Order no.: 777302,
B
AC : 240 V 1,100 ms Order no.: 777302, 787302
B
AC : 240 V 1500 ms Order no.: 777302, 787302
B
230 ms Order no.: 777302, 787302
250 ms Order no.: 777302, 787302
20 ms Order no.: 777302, 787302
0.20 - 1.50 mm² , 24 - 16 AWG Order no.: 787301, 787302
2 Order no.: 787301, 787302
94.0 mm Order no.: 777301, 777302
205 g Order no.: 787302
210 g Order no.: 777302
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-332-2006-07Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-8
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X2.8P
The standards current on 11/03 apply.
Conventional thermal current
Number of contacts I 1 6.00 A 6.00 A 2 6.00 A 6.00 A 3 4.50 A Order no.: 777302, 787302
Order reference
Type Features Terminals Order no.
PNOZ X2.8P C 24 VAC 24 VDC Cage clamp terminals 787 301 PNOZ X2.8P 24 VAC 24 VDC Screw terminals 777 301 PNOZ X2.8P C 24 - 240 VAC 24 - 240 VDC Cage clamp terminals 787 302 PNOZ X2.8P 24 - 240 VAC 24 - 240 VDC Screw terminals 777 302
(A) at UBDC Ith(A) at UBAC
th
4.50 A Order no.: 777302, 787302
5.00 A Order no.: 777301, 787301
5.00 A Order no.: 777301, 787301
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-332-2006-07