Pilz PNOZ X2.1VP Data Sheet

E-STOP relays, safety gate monitors
Up to PL d of EN ISO 13849-1
PNOZ X2.1VP
Gertebild
][Bildunterschrift
Safety relay for monitoring E-STOP pushbuttons and safety gates.
PNOZ X2.1VP
SÜDDEUTSCHLAND
Unit features
Gertemerkmale
` Positive-guided relay outputs:
– 2 safety contacts (N/O), delay-on
de-energisation
` 1 semiconductor output ` Connection options for:
– E-STOP pushbutton – Safety gate limit switch – Reset button
` LED indicator for:
– Switch status channel 1/2 – Supply voltage – Semiconductor output
` Semiconductor output signals:
– Switch status channel 1/2
` Plug-in connection terminals (either
spring-loaded terminal or screw terminal)
` See order reference for unit types
Unit description
Bestimmung/Gertebeschreibung NOT-AUS, Schutz_PNOZ
The safety relay meets the require­ments of EN 60947-5-1, EN 60204-1 and VDE 0113-1 and may be used in applications with
` E-STOP pushbuttons ` Safety gates
Safety features
][Sicherheitseigenscha ften Schaltgerät_allgem einer Teil
The relay meets the following safety requirements:
` The circuit is redundant with built-in
self-monitoring.
` The safety function remains effec-
tive in the case of a component fail­ure.
` The correct opening and closing of
the safety function relays is tested automatically in each on-off cycle.
Sicherheitseigenschaften Zusatz - Sicherung DC_PNOZ
` The unit has an electronic fuse.
Zulassungen
Block diagram
A1 A2
=
Power
=
Blockschaltbild
S11 S12
Y11 Y12
S21 S22
InputInput
S31 S32
Input
S33 S34
Reset/
Start
27 37
K1
K2
28 38
NSG-D-2-252-2010-01
E-STOP relays, safety gate monitors
Up to PL d of EN ISO 13849-1
PNOZ X2.1VP
Function description
][Funktionen_einkanalig
` Single-channel operation: no re-
dundancy in the input circuit, earth faults in the reset and input circuit are detected.
][Funktionen_zweikanalig_mit_quer_manu
` Dual-channel operation with detec-
tion of shorts across contacts: re­dundant input circuit, detects
Timing diagram
POWER
Reset/Start
Input
Output safe
Semi
Key
` Power: Supply voltage ` Reset/Start: Reset circuit S33-S34 ` Input: Input circuits S11-S12, S21-
S22, S31-S32
` Output safe: Safety contacts, de-
layed 27-28, 37-38
– earth faults in the reset and input
circuit,
– short circuits and shorts be-
tween contacts in the input cir­cuit.
][Funktionen_autoStart
` Automatic start: Unit is active once
the input circuit has been closed.
][Funktionen_manuStart
][Zeitdiagramm_auto_manu_semi_del
1 2
t1 t2
` Semi: Semiconductor output ` c: Automatic reset ` d: Manual reset ` a: Input circuit closes before reset
circuit
` Manual reset: Unit is active once
the input circuit is closed and then the reset circuit is closed.
][Funktionen_Kontaktvervielfachung
` Increase in the number of available
instantaneous safety contacts by connecting contact expansion modules or external contactors.
ab
t1t1 t2
t1
t2
3
t
t2
` b: Reset circuit closes before input
circuit
: Switch-on delay
` t
1
: Delay-on de-energisation
` t
2
: Recovery time
` t
3
Wiring
][Verdrahtung_Si_verz
Please note:
` Information given in the “Technical
details” must be followed.
` Outputs 27-28, 37-38 are delay-on
de-energisation safety contacts.
` To prevent contact welding, a fuse
should be connected before the output contacts (see technical de­tails).
` Calculation of the max. cable runs
in the input circuit:
l
max
R
lmax
=
I
max
Rl / km
R
= max. overall cable resist-
lmax
ance (see technical details)
/km = cable resistance/km
R
l
` Use copper wire that can withstand
60/75 °C.
` Sufficient fuse protection must be
provided on all output contacts with capacitive and inductive loads.
NSG-D-2-252-2010-01
-2
E-STOP relays, safety gate monitors
Up to PL d of EN ISO 13849-1
PNOZ X2.1VP
Preparing for operation
Betriebsbereitschaft her stellen
` Supply voltage
Supply voltage AC DC
` Input circuit
Input circuit Single-channel Dual-channel E-STOP
without detection of shorts across con­tacts
E-STOP with detection of shorts across contacts
S21 S22
S12 S11 S32
S31
S1
S11 S12
A1
A2
S22 S32 S31 S21
L+
L-
S1
Safety gate without detection of shorts across con­tacts
S12 S21 S22
S11
S32
S31
Safety gate with detection of shorts across contacts
` Reset circuit
Reset circuit E-STOP wiring (single-channel)
Safety gate (single-channel)
Automatic reset
Manual reset
S33
S34
S33
S3
S1
S11 S12
S22 S21 S32
S31
S1
E-STOP wiring (dual-channel) Safety gate (dual-channel)
S33
S34
S33
S2
S3
S34
S34
NSG-D-2-252-2010-01
Loading...
+ 5 hidden pages