Pilz PNOZ x2 Data Sheet

E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X2
Safety relay for monitoring E-STOP pushbuttons and safety gates.
PNOZ X2
Unit features
` Positive-guided relay outputs:
2 safety contacts (N/O), instantane­ous
` Connection options for:
– E-STOP pushbutton – Safety gate limit switch – Reset button
` LED indicator for:
– Switch status channel 1/2 – Supply voltage
` See order reference for unit types
Unit description
The safety relay meets the require­ments of EN 60204-1 and IEC 60204­1 and may be used in applications with
` E-STOP pushbuttons ` Safety gates
Safety features
The relay conforms to the following safety criteria:
` The circuit is redundant with built-in
self-monitoring.
` The safety function remains effecti-
ve in the case of a component failu­re.
` The correct opening and closing of
the safety function relays is tested automatically in each on-off cycle.
` The unit has an electronic fuse.
Block diagram
~
Power
=
S11 S12A1 A2
S21 S22
InputInput
S33 S34
Reset/
Start
13 23
K1
K2
14 24
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-053-11/04
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X2
Function description
` Single-channel operation: no red-
undancy in the input circuit, earth faults in the reset circuit are detec­ted.
` Dual-channel operation with detec-
tion of shorts across contacts: red­undant input circuit, detects
Timing diagram
Output safe
Key
` Power: Supply voltage ` Reset/start: Reset circuit S33-S34 ` Input: Input circuits S11-S12, S21-
S22
– earth faults in the reset and input
circuit,
– short circuits in the input circuit
and, with a monitored reset, in the reset circuit too,
– shorts between contacts in the
input circuit.
` Monitored reset: Unit is active once
the input circuit is closed and once
POWER
Reset/Start
Input
t
1
t
3
t
2
` Output safe: Safety contacts 13-14,
23-24
: Switch-on delay
` t
1
` t2: Delay-on de-energisation
the reset circuit is closed after the waiting period has elapsed (see technical details).
` Increase in the number of available
contacts by connecting contact ex­pander modules or external contac­tors/relays.
t
2
t
1
t
3
` t
: Waiting period
3
Wiring
Please note:
` Information given in the “Technical
details” must be followed.
` Outputs 13-14, 23-24 are safety
contacts.
` To prevent contact welding, a fuse
should be connected before the output contacts (see technical de­tails).
` Calculation of the max. cable runs
in the input circuit:
l
max
R
lmax
=
I
max
Rl / km
= max. overall cable resi-
R
lmax
stance (see technical details)
/km = cable resistance/km
R
l
` Use copper wire that can withstand
60/75 °C.
` Sufficient fuse protection must be
provided on all output contacts with capacitive and inductive loads.
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-053-11/04Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-2
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X2
Preparing for operation
` Supply voltage
Supply voltage AC DC
A1
A2
L1
N
` Input circuit
Input circuit Single-channel Dual-channel E-STOP
without detection of shorts across contacts
S21 S22
S11 S12
A1
S1
L+
E-STOP with detection of shorts across con­tacts
Safety gate with detection of shorts across con­tacts
S11 S12 S21 S22
A1
A2
S11 S21 S22
S12
S1
L+
L-
S1
S2
` Reset circuit
Reset circuit E-STOP wiring (single-channel)
Safety gate (single-channel)
Monitored reset
S33
S34
S3
E-STOP wiring (dual-channel) Safety gate (dual-channel)
` Feedback loop
Feedback loop Automatic reset Monitored reset Contacts from external contactors
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
S33
S34
S33
K5
S34 13 (23) 14 (24)
NSG-D-2-053-11/04
K6
K5
K6
S3
S3
L1 N
Loading...