Pilz PNOZ s4 Data Sheet

E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ s4
Gertebild
][Bildunterschrift_NOT_Sch.tuer_Licht
Approvals
PNOZ s4
SÜDDEUTSCHLAND
Unit features
Gertemerkmale
` Positive-guided relay outputs:
– 3 safety contacts (N/O), instanta-
neous
– 1 auxiliary contact (N/C), instan-
taneous
` 1 semiconductor output ` Connection options for:
– E-STOP pushbutton – Safety gate limit switch – Reset button – Light barriers – PSEN
` A connector can be used to con-
nect 1 PNOZsigma contact ex­pander module
` Operating modes can be set via ro-
tary switch
` LED indicator for:
– Supply voltage – Input status, channel 1 – Input status, channel 2 – Switch status, safety contacts – Reset circuit – Error
` Plug-in connection terminals (either
spring-loaded terminal or screw terminal)
Unit description
Bestimmung/Gertebeschreibung NOT-AUS, Schutzt, Lichtschr_PNOZ
The safety relay meets the require­ments of EN 60947-5-1, EN 60204-1 and VDE 0113-1 and may be used in applications with
` E-STOP pushbuttons ` Safety gates ` Light beam devices
Safety features
][Sicherheitseigenscha ften Schaltgerät_allgem einer Teil
The relay meets the following safety requirements:
` The circuit is redundant with built-in
self-monitoring.
` The safety function remains effec-
tive in the case of a component fail­ure.
` The correct opening and closing of
the safety function relays is tested automatically in each on-off cycle.
Sicherheitseigenschaften Zusatz - Sicherung DC_PNOZ
` The unit has an electronic fuse.
Zulassungen
Block diagram
A1 A2 S21 S22
=
(~)*
Power
* only when UB = 48 – 240 VAC/DC
Blockschaltbild
Zusatz WSNT
=
( )*
S11 S12
Reset/
Start
S34
41
23 33
13
InputInput
K1
unit
Interface
expansion
Y32
K2
14
24 34
42
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
1001742-EN-03-2010-11
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ s4
Function description
][Funktionen_einkanalig
` Single-channel operation: no re-
dundancy in the input circuit, earth faults in the reset and input circuit are detected.
][Funktionen_zweikanalig_ohne_quer
` Dual-channel operation without de-
tection of shorts across contacts: redundant input circuit, detects – earth faults in the reset and input
circuit,
– short circuits in the input circuit
and, with a monitored reset, in the reset circuit too.
][Funktionen_zweikanalig_mit_quer_ber
` Dual-channel operation with detec-
tion of shorts across contacts: re­dundant input circuit, detects – earth faults in the reset and input
Timing diagram
1 2
POWER
Reset/Start
Input
Output safe
Output aux.
Out semi
t1 t2
t1 t2
circuit,
– short circuits in the input circuit
and, with a monitored reset, in the reset circuit too,
– shorts between contacts in the
input circuit.
][Funktionen_autoStart
` Automatic start: Unit is active once
the input circuit has been closed.
][Funktionen_manuStart
` Manual reset: Unit is active once
the input circuit is closed and then the reset circuit is closed.
][Funktionen_berStart_fall_Flanke
` Monitored reset with falling edge:
Unit is active once – the input circuit is closed and
then the reset circuit is closed and opened again.
– the reset circuit is closed and
then opened again once the in-
][Zeitdiagramm_PNOZs_auto_manu_ueber1_ueber2_aux_Semi
ab
t3
t1
t2
t1
t2
t1
put circuit is closed.
][Funktionen_berStart_steig_Flanke
` Monitored reset with rising edge:
Unit is active once the input circuit is closed and once the reset circuit is closed after the waiting period has elapsed (see technical details).
][Funktionen_Start_Anlauftest
` Reset with start-up test: The unit
checks whether safety gates that are closed are opened and then closed again when supply voltage is applied.
][Funktionen_Kontaktvervielfachung_PNOZsigma
` Increase in the number of available
instantaneous safety contacts by connecting contact expander mod­ules or external contactors/relays; A connector can be used to con­nect 1 PNOZsigma contact ex­pander module.
3
ab
t3
t2
t4
t1
4
ab
t1
t2
t2
Key
` Power: Supply voltage ` Reset/start: Reset circuit S34 S34 ` Input: Input circuits S11-S12, S21-
S22
` Output safe: Safety contacts 13-14,
23-24, 33-34
` Output aux: Auxiliary contacts 41-
42
` Out semi: Semiconductor output
Y32
` c: Automatic reset ` d: Manual reset ` e: Monitored reset with rising edge ` f: Monitored reset with falling edge ` a: Input circuit closes before reset
circuit
Wiring
][Verdrahtung_Si_unverz_1Hi_unverz
Please note:
` Information given in the “Technical
details” must be followed.
` Outputs 13-14, 23-24, 33-34 are
safety contacts, output 41-42 is an auxiliary contact (e.g. for display).
` To prevent contact welding, a fuse
should be connected before the output contacts (see technical de­tails).
` Use copper wire that can withstand
` Sufficient fuse protection must be
` Calculation of the max. cable runs
in the input circuit:
l
max
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
R
lmax
=
I
max
Rl / km
R
= max. overall cable resist-
lmax
ance (see technical details)
/km = cable resistance/km
R
l
60/75 °C.
provided on all output contacts with capacitive and inductive loads.
` b: Reset circuit closes before input
circuit
: Switch-on delay
` t
1
: Delay-on de-energisation
` t
2
: Waiting period
` t
3
: Waiting period reset circuit was
` t
4
closed
1001742-EN-03-2010-11Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-2
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ s4
Preparing for operation
Betriebsbereitschaft herstellen PNOZs
` Supply voltage
Supply voltage AC DC
L
N
S21
A1
A2
` Input circuit
Input circuit Single-channel Dual-channel E-STOP
without detection of shorts across con­tacts
E-STOP with detection of shorts across contacts
S11 S12 S22
S1
A1
A2
S11
S12 S22
S11 S21 S22
S12
L+
L-
S1
S1
Safety gate without detection of shorts across con­tacts
Safety gate with detection of shorts across contacts
Light beam device or safety switch with detection of shorts across contacts via ESPE (only when U
= 24 VDC)
B
S11 S12 S22
S1
A2
S11
S12 S22
S11 S12 S21 S22
S12 S22
S1
S1
S2
S2
24 V DC
GND
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de