Pilz PNOZ mmc7p CC User Manual

Page 1
PNOZ mmc7p CC
Operating Manual-1003066-EN-01
Configurable Control System PNOZmulti
Page 2

Preface

This document is a translation of the original document.
All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received.
Pilz®, PIT®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®, SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarks of Pilz GmbH & Co. KG in some countries.
SD means Secure Digital
Page 3
Content
Operating Manual PNOZ mmc7p CC 1003066-EN-01
Section 1 Introduction 4
1.1 Validity of documentation 4
1.2 Retaining the documentation 4
1.3 Definition of symbols 4
Section 2 Overview 5
2.1 Scope of supply 5
2.2 Unit features 5
2.3 Front view 6
Section 3 Safety 7
3.1 Intended use 7
3.2 System requirements 7
3.3 Safety regulations 8
3.3.1 Use of qualified personnel 8
3.3.2 Warranty and liability 8
3.3.3 Disposal 8
3.3.4 For your safety 8
Section 4 Function description 9
4.1 Functions 9
4.2 Input and output data 9
4.3 Block diagram 10
Section 5 Installation 11
5.1 General installation guidelines 11
5.2 Connect the base unit and expansion modules 11
5.3 Dimensions 11
Section 6 Commissioning 12
6.1 General wiring guidelines 12
6.2 Connecting the supply voltage 12
6.3 Interface assignment 13
6.4 Download modified project to the PNOZmulti safety system 13
6.5 Connection example 14
Section 7 Operation 15
7.1 Messages 15
Section 8 Technical Details 16
Section 9 Order reference 18
3
Page 4

Introduction

Operating Manual PNOZ mmc7p CC 1003066-EN-01
1
1.1
1.2
1.3
Introduction

Validity of documentation

This documentation is valid for the product PNOZ mmc7p CC. It is valid until new documen­tation is published.
This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.

Retaining the documentation

This documentation is intended for instruction and should be retained for future reference.

Definition of symbols

Information that is particularly important is identified as follows:
DANGER!
This warning must be heeded! It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive measures that can be taken.
WARNING!
This warning must be heeded! It warns of a hazardous situation that could lead to serious injury and death and indicates preventive measures that can be taken.
CAUTION!
This refers to a hazard that can lead to a less serious or minor injury plus material damage, and also provides information on preventive measures that can be taken.
NOTICE
This describes a situation in which the product or devices could be dam­aged and also provides information on preventive measures that can be tak­en. It also highlights areas within the text that are of particular importance.
INFORMATION
This gives advice on applications and provides information on special fea­tures.
4
Page 5

Overview

Operating Manual PNOZ mmc7p CC 1003066-EN-01
2
2.1
2.2
Overview

Scope of supply

} Expansion module PNOZ mmc7p CC
} Jumper 779 260

Unit features

Using the product PNOZ mmc7p CC:
Expansion module for connection to a base unit from the configurable control system PNOZmulti Mini .
The product has the following features:
} Can be configured in the PNOZmulti Configurator
} Connection for CC-Link
} Station addresses from 1 ... 63, selected via rotary switch
} Station type: Remote Device
} Occupied stations: 2
} 24 virtual inputs and outputs on the control system PNOZmulti can be defined in the
PNOZmulti Configurator for communication with the fieldbus CC-Link . The number of inputs and outputs can be extended to 128. Please note that when the extended inputs and outputs 24 - 127 are used they have different properties (see document entitled "Communication Interfaces").
} Max. 1 PNOZ mmc7p CC can be connected to the base unit
} Plug-in connection terminals:
either spring-loaded terminal or screw terminal available as an accessory (see order reference)
} Please refer to the document "PNOZmulti System Expansion" for the PNOZmulti base
units that can be connected
5
Page 6
Overview
Operating Manual PNOZ mmc7p CC 1003066-EN-01
2.3

Front view

Legend:
} X1: CC-Link interface
} 0 V, 24 V: Supply connections
} LEDs:
– Power
– Run
– L Err
6
Page 7

Safety

Operating Manual PNOZ mmc7p CC 1003066-EN-01
3
3.1
Safety

Intended use

The fieldbus module PNOZ mmc7p CC is an expansion module of the configurable control system PNOZmulti. It is used for communication between the configurable control system PNOZmulti and the CC-Link . CC-Link is designed for fast data exchange at field level. The expansion module CC-Link is a passive subscriber (Slave) in CC-Link. The basic communication functions with CC-Link conform to CC-Link V1.10. The central controller (master) reads input information from the slaves and writes output information to the slaves as part of each cycle. As well as the cy­clical transfer of usable data, the expansion module PNOZ mmc7p CC also has diagnostic and commissioning functions. Data traffic is monitored on the Master/Slave side.
The expansion module may only be connected to a base unit from the configurable control system PNOZmulti (please refer to the document "PNOZmulti System Expansion" for de­tails of the base units that can be connected)
The configurable control system PNOZmulti is used for the safety-related interruption of safety circuits and is designed for use in:
} E-STOP equipment
} Safety circuits in accordance with VDE 0113 Part 1 and EN 60204-1
3.2
The expansion module may not be used for safety-related functions.
Intended use includes making the electrical installation EMC-compliant. The product is de­signed for use in an industrial environment. It is not suitable for use in a domestic environ­ment, as this can lead to interference.
The following is deemed improper use in particular:
} Any component, technical or electrical modification to the product
} Use of the product outside the areas described in this manual
} Use of the product outside the technical details (see chapter entitled “Technical De-
tails”)

System requirements

Please refer to the "Product Modifications" document in the "Version overview" section for details of which versions of the base unit and PNOZmulti Configurator can be used for this product.
7
Page 8
Safety
Operating Manual PNOZ mmc7p CC 1003066-EN-01
3.3
3.3.1
3.3.2

Safety regulations

Use of qualified personnel

The products may only be assembled, installed, programmed, commissioned, operated, maintained and decommissioned by competent persons.
A competent person is someone who, because of their training, experience and current pro­fessional activity, has the specialist knowledge required to test, assess and operate the work equipment, devices, systems, plant and machinery in accordance with the general standards and guidelines for safety technology.
It is the company’s responsibility only to employ personnel who:
} Are familiar with the basic regulations concerning health and safety / accident preven-
tion
} Have read and understood the information provided in this description under "Safety"
} And have a good knowledge of the generic and specialist standards applicable to the
specific application.

Warranty and liability

All claims to warranty and liability will be rendered invalid if
} The product was used contrary to the purpose for which it is intended
} Damage can be attributed to not having followed the guidelines in the manual
} Operating personnel are not suitably qualified
} Any type of modification has been made (e.g. exchanging components on the PCB
boards, soldering work etc.).
3.3.3
3.3.4

Disposal

} In safety-related applications, please comply with the mission time tM in the safety-relat-
ed characteristic data.
} When decommissioning, please comply with local regulations regarding the disposal of
electronic devices (e.g. Electrical and Electronic Equipment Act).

For your safety

The unit meets all necessary conditions for safe operation. However, you should always en­sure that the following safety requirements are met:
} This operating manual only describes the basic functions of the unit. Information on the
advanced functions can be found in the online help for the PNOZmulti Configurator and in the PNOZmulti technical catalogue. Only use these functions after you have read and understood the documentation. All necessary documentation can be found on the PNOZmulti Configurator CD.
} Do not open the housing or make any unauthorised modifications.
} Please make sure you shut down the supply voltage when performing maintenance
work (e.g. exchanging contactors).
8
Page 9

Function description

Operating Manual PNOZ mmc7p CC 1003066-EN-01
4
4.1
4.2
Function description

Functions

The virtual inputs and outputs that are to be transferred via the fieldbus CC-Link are select­ed and configured in the PNOZmulti Configurator. The base unit and the fieldbus module PNOZ mmc7p CC are connected via a jumper. After the supply voltage is switched on or the control system PNOZmulti is reset, the fieldbus module PNOZ mmc7p CC is configured and started automatically.
LEDs indicate the status of the fieldbus module on the fieldbus CC-Link .
The configuration is described in detail in the PNOZmulti Configurator's online help.

Input and output data

The data is structured as follows:
} Input area
– Inputs on PNOZmulti Configurator: i00 … i23
– Input data CC-Link: RYn, RY1n with n = 0 … F
Example: i23 -> RY17
s F L B C B A 9 8 7 6 5 4 3 2 1 0
RY0n i15 i14 i13 i12 i11 i10 i09 i08 i07 i06 i05 i04 i03 i02 i01 i00
RY1n - - - - - - - - i23 i22 i21 i20 i19 i18 i17 i16
} Output area
– Outputs on PNOZmulti Configurator: o00 … o23
– Output data CC-Link: RXn, RX1n with n = 0 … F
Example: o22 -> Rx16
s F L B C B A 9 8 7 6 5 4 3 2 1 0
RX0n o15 o14 o13 o12 o11 o10 o09 o08 o07 o06 o05 o04 o03 o02 o01 o00
RX1n - - - - - - - - o23 o22 o21 o20 o19 o18 o17 o16
Detailed information on data exchange is available in the document "Communication Inter­faces" in the section entitled "Fieldbus modules".
The number of virtual inputs and outputs can be extended to 128 (see document "Commu­nication Interfaces" in the section entitled "Fieldbus modules")
INFORMATION
When polling the tables and segments of the PNOZmulti, please note that communication on the CC-Link is via the Register.
9
Page 10
Function description
Operating Manual PNOZ mmc7p CC 1003066-EN-01
4.3

Block diagram

24 V 0 V
24 V 0 V
10
Page 11

Installation

Operating Manual PNOZ mmc7p CC 1003066-EN-01
5
5.1
Installation

General installation guidelines

} The unit should be installed in a control cabinet with a protection type of at least IP54.
} Fit the safety system to a horizontal mounting rail. The venting slots must face upwards
and downwards. Other mounting positions could destroy the safety system.
} Use the notch on the rear of the unit to attach it to a mounting rail.
} In environments exposed to heavy vibration, the unit should be secured using a fixing
element (e.g. retaining bracket or end angle).
} Push the unit upwards or downwards before lifting it from the mounting rail.
} To comply with EMC requirements, the mounting rail must have a low impedance con-
nection to the control cabinet housing.
} The ambient temperature of the PNOZmulti units in the control cabinet must not exceed
the figure stated in the technical details, otherwise air conditioning will be required.
CAUTION!
Damage due to electrostatic discharge!
Electrostatic discharge can damage components. Ensure against discharge before touching the product, e.g. by touching an earthed, conductive surface or by wearing an earthed armband.
5.2
5.3

Connect the base unit and expansion modules

Connect the base unit and the expansion module as described in the operating instructions for the base units.
} Connect the black/yellow terminator to the expansion module.
} Install the expansion module in the position in which it is configured in the PNOZmulti
Configurator.

Dimensions





11
Page 12

Commissioning

Operating Manual PNOZ mmc7p CC 1003066-EN-01
6
6.1
Commissioning

General wiring guidelines

The wiring is defined in the circuit diagram of the PNOZmulti Configurator.
Note:
} Information given in the "Technical details" must be followed.
} Always connect the mounting rail to the protective earth via an earthing terminal. This
will be used to dissipate hazardous voltages in the case of a fault.
} The power supply must meet the regulations for extra low voltages with safe separation.
CAUTION!
Only connect and disconnect the expansion module when the supply volt­age is switched off.
NOTICE
When installing, you must refer to the guidelines of theCC-Link -user group.
6.2

Connecting the supply voltage

Connect the supply voltage to the fieldbus module:
} Terminal 24 V: + 24 V DC
} Terminal 0 V: 0 V
12
Page 13
Commissioning
Operating Manual PNOZ mmc7p CC 1003066-EN-01
6.3
6.4

Interface assignment

It is possible to define which outputs on the safety system will communicate with CC-Link. The connection to CC-Link is made via a 5-pin screw connector.

 
  
 




1: DA (Channel A)
2: DB (Channel B)
3: DG (Earth)
4: SLD (Cable shield)
5: FG/PE (Functional earth)

Download modified project to the PNOZmulti safety system

As soon as an additional expansion module has been connected to the system, the project must be amended using the PNOZmulti Configurator. Proceed as described in the operat­ing instructions for the base unit.
NOTICE
For the commissioning and after every program change, you must check whether the safety devices are functioning correctly.
13
Page 14
Commissioning
Operating Manual PNOZ mmc7p CC 1003066-EN-01
6.5

Connection example

PNOZ mmc7p CC
14
Page 15

Operation

Operating Manual PNOZ mmc7p CC 1003066-EN-01
7
7.1
LED Key
Power
Operation
When the supply voltage is switched on, the PNOZmulti safety system copies the configu­ration from the chip card.
The LEDs "POWER","DIAG", "FAULT", "IFAULT" and "OFAULT" light up on the base unit.
The expansion module PNOZ mmc7p CC is configured and started automatically.

Messages

Legend:
Green Supply voltage is present
} Supply voltage is not present
LED on
LED off
RUN
L Err
Green Bus connection available
} Bus connection is not available
} Status: timeout
} No supply voltage at the fieldbus module PNOZ mmc7p CC
Red Fault detected: Wrong station address or transmission rate
} Bus connection available
} No supply voltage at the fieldbus module PNOZ mmc7p CC
15
Page 16

Technical Details

Operating Manual PNOZ mmc7p CC 1003066-EN-01
8
General 772035 Approvals CCC, CE, GOST
Electrical data 772035
Supply voltage
for Module supply Voltage 24 V Type DC Voltage tolerance -20 %/+25 % Output of external power supply (DC) 1,5 W
Status indicator LED
Fieldbus interface 772035
Fieldbus interface CC-Link V1.10 Unit type Slave Station address 1 ... 63d Transmission rates 10 MBit/s, 156 kbit/s, 2,5 MBit/s, 5 MBit/s, 625
Connection 5-pin Combicon plug-in connector Assigned stations 2 Galvanic isolation Yes Test voltage 500 V AC
Times 772035 Supply interruption before de-energisation 20 ms
Environmental data 772035
Ambient temperature
In accordance with the standard EN 60068-2-14 Temperature range 0 - 60 °C Forced convection in control cabinet off 55 °C
Storage temperature
In accordance with the standard EN 60068-2-1/-2 Temperature range -25 - 70 °C
Climatic suitability
In accordance with the standard EN 60068-2-30, EN 60068-2-78
Humidity 93 % r. h. at 40 °C Condensation during operation Not permitted EMC EN 61131-2 Vibration
In accordance with the standard EN 60068-2-6
Frequency 10,0 - 150,0 Hz
Acceleration 1g Shock stress
In accordance with the standard EN 60068-2-27
Acceleration 15g
Duration 11 ms Max. operating height above sea level 2000 m
Technical Details
kbit/s
16
Page 17
Technical Details
Operating Manual PNOZ mmc7p CC 1003066-EN-01
Environmental data 772035
Airgap creepage
In accordance with the standard EN 61131-2
Overvoltage category II
Pollution degree 2 Rated insulation voltage 30 V Protection type
In accordance with the standard EN 60529
Mounting (e.g. cabinet) IP54
Housing IP20
Terminals IP20
Potential isolation 772035
Potential isolation between Fieldbus and module voltage Type of potential isolation Functional insulation Rated surge voltage 500 V
Mechanical data 772035
Mounting position Horizontal on top hat rail DIN rail
Top hat rail 35 x 7,5 EN 50022
Recess width 27 mm Material
Bottom PC
Front PC
Top PC Conductor cross section with screw terminals
1 core flexible 0,25 - 2,50 mm², 24 - 12 AWG
2 core with the same cross section, flexible with
0,20 - 1,50 mm², 24 - 16 AWG
crimp connectors, no plastic sleeve
2 core with the same cross section, flexible without
0,20 - 1,50 mm², 24 - 16 AWG
crimp connectors or with TWIN crimp connectors
Rigid single-core, flexible multi-core or multi-core
0,5 - 1,5 mm²
with crimp connector Torque setting with screw terminals 0,50 Nm Connection type Spring-loaded terminal, screw terminal Conductor cross section with spring-loaded terminals:
0,20 - 2,50 mm², 24 - 12 AWG
flexible with/without crimp connector Spring-loaded terminals: Terminal points per connec-
2
tion Stripping length 9 mm Dimensions
Height 100,0 mm
Width 22,5 mm
Depth 110,0 mm Weight 90 g
The standards current on 2011-09 apply.
17
Page 18

Order reference

Operating Manual PNOZ mmc7p CC 1003066-EN-01
9
Order reference
Product type Features Order no.
PNOZ mmc7p CC Fieldbus module, CC-Link 772035
Order reference: Terminator, jumper
Product type Features Order no.
PNOZ mm0.xp connector left
Order reference: Acces­sories
Product type Features Order no.
Spring terminals
PNOZ mmcxp 1 pc.
Spring terminals
PNOZ mmcxp 10 pcs.
Order reference
Jumper yellow/black to connect the modules, 1 piece 779 260
Spring-loaded terminals, 1 piece 783 542
Spring-loaded terminals, 10 pieces 783 543
Screw terminals
PNOZ mmcxp 1 pc.
Screw terminals
PNOZ mmcxp 10 pcs.
Screw terminals, 1 piece 793 542
Screw terminals, 10 pieces 793 543
18
Page 19
...
Sachnummer Printed in Germany
© Pilz GmbH & Co. KG, 2011
+49 711 3409-444 support@pilz.com
Pilz GmbH & Co. KG Felix-Wankel-Straße 2 73760 Ostfildern, Germany Telephone: +49 711 3409-0 Telefax: +49 711 3409-133 E-Mail: pilz.gmbh@pilz.de Internet: www.pilz.com
Technical support
In many countries we are represented by our subsidiaries and sales partners.
Please refer to our homepage for further details or contact our headquarters.
InduraNET p
®
, Pilz
®
, PIT
®
, PMCprotego
®
, PMI
®
, PNOZ
®
, Primo
®
, PSEN
®
, PSS
®
, PVIS
®
, SafetyBUS p
®
, SafetyEYE
®
, SafetyNET p
®
, the spirit of safety
®
are registered and protected trademarks
of Pilz GmbH & Co. KG in some countries. We would point out that product features may vary from the details stated in this document, depending on the status at the time of publication and the scope
of the equipment. We accept no responsibility for the validity, accuracy and entirety of the text and graphics presented in this information. Please contact our Technical Support if you have any questions.