Multi Air Conditioner

SVC MANUAL(Exploded View)

MODEL : A4UW36GFA0 [LMU36CHV]

CAUTION

Before Servicing the unit, read the safety precautions in General SVC manual. Only for authorized service personnel.

1. Specification

 

Outdoor unit

 

 

A4UW36GFA0

 

 

 

[LMU36CHV]

 

 

 

 

Testing Combination

 

 

 

AMNW09GDBL1 * 4EA

 

Cooling

Min.~Rated~Max.

kW

9.37

Capacity

Min.~Rated~Max.

Btu/h

32,000

 

Heating

Min.~Rated~Max.

kW

10.6

 

 

Min.~Rated~Max.

Btu/h

36,000

 

 

Power Input

Cooling

Min.~Rated~Max.

kW

2.46

Heating

Min.~Rated~Max.

kW

2.54

 

EER

 

 

Btu/Wh

13

SEER / HSPF

 

 

-

22.0/10.0

Power Supply

 

 

V , Ø , Hz

208/230, 1. 60

Running Current

Cooling

Min.~Rated~Max.

A

11

Heating

Min.~Rated~Max.

A

11.4

 

Starting Current

Cooling

Max.

A

-

Heating

Max.

A

-

 

 

Power Supply Cable (included Earth)

No. x mm2 (AWG)

3C x 2.5 (12)

Wiring Connections

Power and Communication Cable

Outdoor ~ BD unit

No. x mm2 (AWG)

-

 

 

(included Earth)

 

 

 

 

Sum of Indoor Units Capacity

 

kBtu/h

48

Combination

Number of Indoor Units

 

EA

4

 

Number of BD Units

 

EA

-

Casing Color

 

 

-

Warm Gray

Dimensions

 

W x H x D

mm

950 × 834 × 330

 

W x H x D

inch

37-13/32 x 32-27/32 x 13

 

 

Net Weight

 

 

kg (lbs)

62(136.7)

 

Type

 

-

Twin Rotary

Compressor

Model

 

Model x No.

GJT240MA x 1

Motor type

 

-

BLDC

 

 

 

Motor Output

 

W x No.

2,020 (at 60Hz) x 1

 

Type

 

-

R410A

 

Precharged Amount

 

g (oz)

2,800 (98.8)

Refrigerant

Chargeless-Pipe Length

 

m (ft)

30 (98.4)

 

Additional Charging Volume

 

g/m (oz/ft)

20 (0.22)

 

Control

 

-

Electronic Expansion Valve

Refrigerant Oil

Type

 

-

FVC68D

Charged volume

 

cc x No.

900 x 1

 

 

Heat Exchanger

(Row x Column x Fins per inch) x No.

-

(2 x 38 x 14) x 1

Fan

Type

 

-

Propeller

Air Flow Rate

 

m3/min x No. x No.

60 x 1

 

 

Fan Motor

Type

 

-

BLDC

Output

 

W x No.

124.2 x 1

 

 

Sound Pressure Level

Cooling

Rated

dB(A)

52

Heating

Rated

dB(A)

55

 

Sound Power Level

Cooling

Rated

dB(A)

62

Piping Connections

Liquid

Outer Dia.

mm(inch) x No.

Ø 6.35 (1/4) x 4

Gas

Outer Dia.

mm(inch) x No.

Ø 9.52 (3/8) x 4

 

 

Total Piping

Max.

m (ft)

75 (246)

Piping Length

Main Piping

Max.

m (ft)

-

Total Branch Piping

Max.

m (ft)

-

 

 

Each Branch Piping

Max.

m (ft)

25 (82.0)

Maximum Height Difference

Outdoor Unit ~ Indoor Unit

Max.

m (ft)

15 (49.2)

Indoor Unit ~ Indoor Unit

Max.

m (ft)

7.5 (24.6)

 

Operation Range

Cooling

Min. ~ Max.

DB ( DB)

-18 (0.4)* ~ 48 (118.4)

(Outdoor Temperature)

Heating

Min. ~ Max.

WB ( WB)

-20 (-4.0) ~ 18 (64.4)

Note:

1.All data are based on the following conditions:

-Cooling Temperature : Indoor 26.7°C(80°F) DB / 19.4°C(67°F) WB

Outdoor 35°C(95°F) DB / 23.9°C(75°F) WB - Heating Temperature : Indoor 21.1°C(70°F) DB / 15.6°C(60°F) WB

Outdoor 8.3°C(47°F) DB / 6.1°C(43°F) WB

-Piping Length : Interconnected Pipe Length = 7.5m

-Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.

2.Wiring cable size must comply with the applicable local and national code.

3.Due to our policy of innovation some specifications may be changed without notification.

4.Sound Level Values are measured at Anechoic chamber.

Therefore, these values can be increased(maximum 3dB(A)) owing to ambient conditions during operation.

* : This temperature (-20 ~ -10°C) can be operated only when Low Ambient Kit is installed.

Copyright ©2014 LG Electronics. Inc. All right reserved.

- 2 -

Only for training and service purposes

LGE Internal Use Only

 

2.List of Functions & Accessory

2.1List of Functions

 

Function

A4UW36GFA0

 

[LMU36CHV]

 

 

 

 

 

Defrost / Deicing

O

 

 

Phase Protection

X

Reliability

 

Restart Delay(3-minutes)

O

 

Self Diagnosis

O

 

 

 

 

Soft Start

O

 

 

Test Function

X

 

 

Wiring Error Check

O

 

 

Night Quiet Mode

O

Convenience

 

Mode Lock

O

 

 

Peak Control

O

 

 

Forced Operation

O

 

 

Central Control(LGAP)

O

CAC Network Function

 

PDI(Power Distribution Indicator)

O

 

 

PI485

O

Note :

O : Applied, × : Not applied

*Option : Model name & price are different according to options, and assembled in factory with main unit.

Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

2.2 List of Accessory

 

Device

A4UW36GFA0

 

[LMU36CHV]

 

 

 

 

 

Simple Controller

X

 

 

Function controller

X

 

 

Function Scheduler

X

 

 

AC Ez

PQCSZ250S0

Central Controller

 

AC Smart ll

PQCSW320A1E

 

Option Kit (SD card type)

PQCSE341A0 / PQCSE342A0

 

 

 

 

ACP(Advanced Control Platform)

PQCPA11A0E / PQCPB11A0E

 

 

AC Manager

X

 

 

PI485

PMNFP14A0 / PMNFP14A1

 

 

DO(Digital Output) Kit

PQNFP00T0

BNU (Building Network Unit)

 

LONWORKS Gateway

PQNFB16A1

 

BACnet Gateway

PQNFB17B0

 

 

 

 

Y branch X X

X

Installation

 

Header branch

X

 

 

Air Guide

X

ODU Dry Contact

 

 

X

Low Ambient Kit

 

 

O (Logical operation)

Copyright ©2014 LG Electronics. Inc. All right reserved.

- 3 -

Only for training and service purposes

LGE Internal Use Only

 