LG ARNU093TUC4, ARNU243TLC4, ARNU123TUC4, ARNU183TLC4, ARNU243TTC4 Instruction Manual

...
0 (0)
1-Way Models:
• ARNU073TUC4
• ARNU093TUC4
• ARNU123TUC4
• ARNU183TTC4
• ARNU243TTC4
CEILING CASSETTE INDOOR UNIT
INSTALLATION MANUAL
4-Way 2’ x 2’ Models:
• ARNU053TRC4
• ARNU073TRC4
• ARNU093TRC4
• ARNU123TRC4
2-Way Models:
• ARNU183TLC4
• ARNU243TLC4
4-Way 3’ x 3’ Models:
• ARNU243TPC4
• ARNU283TPC4
• ARNU363TNC4
• ARNU423TMC4
• ARNU483TMC4
PROPRIETARY DATA NOTICE
This document, as well as all reports, illustrations, data, information, and other
materials are the property of LG Electronics U.S.A., Inc., and are
disclosed by LG Electronics U.S.A., Inc., only in confidence.
Do not throw away, destroy, or lose this manual.
Please read carefully and store in a safe place for future reference.
Content familiarity required for proper installation.
The instructions included in this manual must be followed to prevent prod-
uct malfunction, property damage, injury, or death to the user or other
people. Incorrect operation due to ignoring any instructions will cause
harm or damage. A summary of safety precautions begins on page 4.
For more technical materials such as submittals, engineering
databooks, and catalogs, visit www.lghvac.com.
For continual product development, LG Electronics U.S.A., Inc., reserves the right to change specifications without notice.
This document, as well as all reports, illustrations, data, information, and other materials are the property of LG Electronics U.S.A., Inc.
IM-MultiV-IV-CeilingCassette-01-15
©LG Electronics U.S.A., Inc.
TABLE OF CONTENTS
CONTENTS
Proprietary Data Notice ................................................................................................................................... 2
Safety Instructions ........................................................................................................................................... 4
Introduction ...................................................................................................................................................... 7
Ceiling Cassette Indoor Units ....................................................................................................................................... 7
Safety ........................................................................................................................................................................... 7
Required Tools (eld provided) ..................................................................................................................................... 7
Required Parts (eld provided) ..................................................................................................................................... 7
Unit Nomenclature ........................................................................................................................................... 9
R410A Refrigerant ......................................................................................................................................... 10
General Data ................................................................................................................................................. 11
Specications ............................................................................................................................................................. 12
Dimensions ................................................................................................................................................................ 15
Electrical Data ............................................................................................................................................................ 25
Refrigerant Piping Diagrams ...................................................................................................................................... 26
Installation Manual
General Installation Guidelines ...................................................................................................................... 27
Location Selection ...................................................................................................................................................... 27
Required Clearances .................................................................................................................................................. 27
Inspection ................................................................................................................................................................... 28
Unpack and Inspect for Freight Damage .................................................................................................................... 28
Installation ..................................................................................................................................................... 29
Install Cassette Chassis ............................................................................................................................................. 29
Refrigerant Piping .......................................................................................................................................... 31
Refrigerant Safety ....................................................................................................................................................... 33
Refrigerant Pipe Connections ..................................................................................................................................... 34
Insulate Refrigerant Pipes .......................................................................................................................................... 34
Wiring ............................................................................................................................................................ 35
4-Way Cassette Chassis ............................................................................................................................................ 35
4-Way Cassette TR, TQ Chassis ................................................................................................................................ 36
4-Way Cassette TP, TN, TM Chassis .......................................................................................................................... 38
2-Way Cassette TL Chassis ....................................................................................................................................... 40
1-Way Cassette TT, TU Chassis ................................................................................................................................. 43
Optional Wall-Mounted Sensor and Controller ........................................................................................................... 46
Wall-Mounted Sensor Installation ............................................................................................................................... 46
Wall-Mounted Controller Installation ........................................................................................................................... 46
Install Decoration Panel ................................................................................................................................. 47
4-Way Cassette .......................................................................................................................................................... 47
2-Way Cassette .......................................................................................................................................................... 48
1-Way Cassette .......................................................................................................................................................... 49
Drain Pipe Installation .................................................................................................................................... 50
Install the Condensation Drain Pipe ........................................................................................................................... 50
Controls Setup ............................................................................................................................................... 51
Installation Checklist ...................................................................................................................................... 55
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
3
SAFETY INSTRUCTIONS
WARNING
DANGER
WARNING
CAUTION
DANGER
The instructions below must be followed to prevent product malfunction, property damage, injury or death to the user or other people. Incor­rect operation due to ignoring any instructions will cause harm or damage. The level of seriousness is classified by the symbols below.
TABLE OF SYMBOLS
This symbol indicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury.
This symbol indicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury.
This symbol indicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury.
Note:
This symbol Indicates situations that may result in equipment or property damage accidents only.
This symbol indicates an action that should not be performed.
INSTALLATION
Don’t use or store ammable gas or combustibles near the unit.
There is risk of product failure, re, explosion, and physical injury or death.
Do not install, remove, or re-install the unit by yourself (customer). Ask the dealer or an authorized technician to install the unit.
Improper installation by the user may result in water leakage, re, explosion, electric shock, physical injury or death.
For replacement of an installed unit, always contact an authorized LG service provider.
Multi V Ceiling Cassette Indoor Unit
There is risk of re, electric shock, explosion, and physical injury or death.
The outdoor unit is shipped with refrigerant and the service valves closed. Do not open service valves on the unit until all non-condensibles have been removed from the piping system and authorization has been obtained from the com­missioning agent.
There is a risk of physical injury or death.
Do not run the compressor with the service valves closed.
There is risk of explosion, physical injury, or death.
Periodically check that the outdoor unit is not damaged.
There is risk of explosion, physical injury, or death.
Replace all control box and panel covers.
If cover panels are not installed securely, dust, water and animals may enter the unit, causing re, electric shock, and physical injury or death.
Always check for system refrigerant leaks after the unit has been installed or serviced.
Exposure to high concentration levels of refrigerant gas may lead to
illness or death.
4
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Do not install the unit using defective hanging, attaching, or mounting hardware.
There is risk of physical injury or death.
Wear protective gloves when handling equipment.
Sharp edges may cause personal injury.
Dispose the packing materials safely.
• Packing materials, such as nails and other metal or wooden parts may cause puncture wounds or other injuries.
• Tear apart and throw away plastic packaging bags so that children may not play with them and risk suffocation and death.
Do not install the unit in any location exposed to open ame
or extreme heat. Do not touch the unit with wet hands.
There is risk of re, electric shock, explosion, and physical injury or death.
Install the unit considering the potential for earthquakes.
Improper installation may cause the unit to fall, resulting in physical injury or death.
Do not change the settings of the protection devices.
If the pressure switch, thermal switch, or other protection device is
shorted and forced to operate improperly, or parts other than those
specied by LG are used, there is risk of re, electric shock, explosion,
and physical injury or death.
If the air conditioner is installed in a small space, take mea­sures to prevent the refrigerant concentration from exceed­ing safety limits in the event of a refrigerant leak.
Consult the latest edition of ASHRAE (American Society of Heating, Refrigerating, and Air Conditioning Engineers) Standard 15. If the re­frigerant leaks and safety limits are exceeded, it could result in personal injuries or death from oxygen depletion
CAUTION
SAFETY INSTRUCTIONS
INSTALLATION – CONTINUED
Be very careful when transporting the product.
• Do not attempt to carry the product without assistance.
• Some products use polypropylene bands for packaging. Do not use polypropylene bands to lift the unit.
• Suspend the unit from the base at specified positions.
Support the unit a minimum of four points to avoid slippage from rigging apparatus.
Note:
Properly insulate all cold surfaces to prevent “sweating.”
Cold surfaces such as uninsulated pip can generate condensate that may
drip and cause a slippery oor condition and/or water damage to walls.
When installing the unit in a hospital, mechanical room, or
similar electromagnetic eld (EMF) sensitive environment, provide sufcient protection against electrical noise.
Inverter equipment, power generators, high-frequency medical equip-
ment, or radio communication equipment may cause the air conditioner to operate improperly. The unit may also affect such equipment by creating electrical noise that disturbs medical treatment or image broadcasting.
Do not use the product for special purposes such as preserv­ing foods, works of art, wine coolers, or other precision air conditioning applications. This equipment is designed to provide comfort cooling and heating.
There is risk of property damage.
Do not make refrigerant substitutions. Use R410A only.
If a different refrigerant is used, or air mixes with original refrigerant, the unit will malfunction and be damaged.
Do not install the unit in a noise sensitive area.
When connecting refrigerant tubing, remember to allow for pipe expansion.
Improper piping may cause refrigerant leaks and system malfunction.
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant ac­cording to applicable U.S. Environmental Protection Agency (EPA) rules.
Periodically check that the outdoor unit is not damaged.
There is a risk of equipment damage.
Install the unit in a safe location where no one can step on or fall onto it. Do not install the unit with defective hanging, attaching, or mounting hardware.
There is risk of unit and property damage.
Install the drain hose to ensure adequate drainage.
There is a risk of water leakage and property damage.
Don’t store or use ammable gas / combustibles near the
unit.
There is risk of product failure.
Always check for system refrigerant leaks after the unit has been installed or serviced.
Low refrigerant levels may cause product failure
The unit is shipped with refrigerant and the service valves closed. Do not open service valves on the unit until all non­condensibles have been removed from the piping system and authorization to do so has been obtained from the com­missioning agent.
There is a risk of refrigerant contamination, refrigerant loss and equip­ment damage.
Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
5
SAFETY INSTRUCTIONS
DANGER
WARNING
WIRING
High voltage electricity is required to operate this system. Adhere to the National Electrical Codes and these instructions when wiring.
Improper connections and inadequate grounding can cause accidental injury or death.
Always ground the unit following local, state, and National Electrical Codes.
The information contained in this manual is intended for use
by an industry-qualied, experienced, certied electrician
familiar with the U.S. National Electric Code (NEC) who is equipped with the proper tools and test instruments.
Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury or death.
Ensure the unit is connected to a dedicated power source that provides adequate power.
If the power source capacity is inadequate or the electric work is not per-
formed properly, it may result in re, electric shock, physical injury or death.
Note:
Do not cut, lengthen or shorten the communications and power cable between any dry contact unit and its connected indoor unit. Do not install the unit in a location where the communica­tions and power cable cannot be safely and easily connected between the two units. Do not allow strain on this cable.
Multi V Ceiling Cassette Indoor Unit
Poor cable connections can cause equipment malfunction.
Turn the power off at the nearest disconnect before servicing the equipment.
Electric shock can cause physical injury or death.
Properly size all circuit breakers or fuses.
There is risk of re, electric shock, explosion, physical injury or death.
Refer to local, state, and federal codes, and use power wires
of sufcient current capacity and rating.
Wires that are too small may generate heat and cause a re.
Secure all eld wiring connections with appropriate wire
strain relief.
Improperly securing wires will create undue stress on equipment power
lugs. Inadequate connections may generate heat, cause a re and
physical injury or death.
Properly tighten all power connections.
Loose wiring may overheat at connection points, causing a re, physical
injury or death.
6
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
OPERATION
DANGER
WARNING
CAUTION
Do not provide power to or operate the unit if it is ooded or
submerged.
There is risk of re, electric shock, physical injury or death.
Use a dedicated power source for this product.
There is risk of re, electric shock, physical injury or death.
Do not operate the disconnect switch with wet hands.
There is risk of re, electric shock, physical injury or death.
Do not allow water, dirt, or animals to enter the unit.
There is risk of unit failure, re, electric shock, physical injury or death.
Avoid excessive cooling and periodically perform ventilation to the unit.
Inadequate ventilation is a health hazard.
Do not touch the refrigerant piping during or after operation.
It can cause burns or frostbite.
Do not operate the unit with the panel(s) or protective cover(s) removed; keep ngers and clothing away from moving parts.
The rotating, hot, cold, and high-voltage parts of the unit can cause physical injury or death.
Periodically check power cable and connection for damage.
Cable must be replaced by the manufacturer, its service agent, or similar qualied persons in order to avoid physical injury and/or electric shock.
Do not open the inlet grille of the unit during operation. Do
SAFETY INSTRUCTIONS
Periodically verify the hanging bolts and other hardware securing the unit have not deteriorated.
If the unit falls from its installed location, it can cause property damage, product failure, physical injury or death.
If refrigerant gas leaks out, ventilate the area before operat­ing the unit.
If the unit is mounted in an enclosed, low-lying, or poorly ventilated area and the system develops a refrigerant leak, it may cause re, electric
shock, explosion, physical injury or death.
not operate the unit with the panels or guards removed. Do not insert hands or other objects through the inlet or outlet
when the unit is powered. Do not touch the electrostatic lter,
if the unit includes one.The unit contains sharp, rotating, hot,
and high voltage parts that can cause personal injury and/or
electric shock.
Ensure no power is connected to the unit other than as directed in this manual. Remove power from the unit before removing or servicing the unit.
There is risk of unit failure, re, electric shock, physical injury or death.
Do not open the inlet grille of the unit during operation. Do not operate the unit with the panels or guards removed. Do not insert hands or other objects through the inlet or outlet with the unit is plugged in. Do not touch the electrostatic
lter, if the unit includes one.
The unit contains sharp, rotating, hot, and high voltage parts that can cause personal injury and/or electric shock.
Securely attach the electrical cover to the unit.
Non-secured electrical covers can result in burns or electric shock due to dust or water in the service panel.
Installation Manual
To avoid physical injury, use caution when cleaning or servicing the air conditioner.
Note:
Clean up the site after installation is nished, and check
that no metal scraps, screws, or bits of wiring have been left inside or surrounding the unit.
Do not use this equipment in mission critical or special­purpose applications such as preserving foods, works of art, wine coolers or refrigeration. This equipment is designed to provide comfort cooling and heating.
Provide power to the compressor crankcase heaters at least six (6) hours before operation begins.
Starting operation with a cold compressor sump(s) may result in severe bearing damage to the compressor(s). Keep the power switch on during
the operational season.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Do not block the inlet or outlet.
Unit may malfunction.
Securely attach the electrical cover to the indoor unit. Non-
secured covers can result in re due to dust or water in the
service panel.
Periodically verify the equipment mounts have not deterio­rated.
If the base collapses, the unit could fall and cause property damage or product failure.
Do not allow water, dirt, or animals to enter the unit.
There is risk of unit failure.
7
Multi V Ceiling Cassette Indoor Unit
8
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Ceiling Cassette Indoor Units
WARNING
(Optional)
This manual describes how to install the LG Electronics, Inc. 4-Way, 2-Way, and 1-Way Ceiling Cassette indoor units (IDU) for Multi V Variable Refrigerant Flow (VRF) heat pump and heat recovery sys­tems. Table 1 lists the available models. Refer to LG’s Multi V Indoor Unit Engineering Manual for complete detailed engineering data and selection procedures.
Safety
Safety of personnel is the primary concern during all procedures. Read and understand the safety summary at the front of this manual. Read and understand this installation procedure before beginning installation. Use the appropriate tools and accessories during instal­lation. Plan your work and do not work alone, if possible. Know how to obtain emergency medical and fire fighting assistance.
Installation Personnel
This equipment is intended for installation by personnel trained in the required construction, mechanical, electrical, and/or other disciplines.
Applicable Codes
Personnel must be familiar with and follow the applicable national, state, and/or local codes. In the event of a conflict between any applicable code and the instructions in this manual, comply with the applicable code.
Supply Air
INTRODUCTION
Figure 1: 4-Way TQ, TR, TM, TN, TP Chassis
Return Air
TEMP
Remote Controller
Wired Remote Controller (Optional)
Figure 2: 2-Way TL Chassis
Filter
Installation Manual
Filter
Installation work must be performed by trained, authorized personnel and in accordance with national wiring standards and all local or other
applicable codes. Improper installation can result in re, electric shock, physical injury, or death and can prevent proper operation of the unit.
Note:
Please read all instructions before installing this product. Become familiar with the unit, it’s components and connections, and the order of installa-
tion. Incorrect installation can degrade or prevent proper operation.
Required Tools (field provided)
• Level
• Screwdriver
• Electrical lineman pliers
• Electric drill
• Holesaw
• Drill
• Flaring tool set
• Tubing cutter
• Tube/pipe reamer
• Torque wrenches
• Allen wrench
• Gas-leak detector
• Thermometer
Required Parts (field provided)
• Connecting cable (power and control)
• Pipes - vapor line and liquid line, with insulation
• 3/8” or 1/2” Threaded hanger rods
3/8” or 1/2” nuts, at washers, and lock/split washers
• Insulated drain hose
• Additional drain hose
Supply Air
Supply Air
Remote Controller
Figure 3: 1-Way TU, TT Chassis
Filter
Return Air
Wired Remote Controller (Optional)
Return Air
Wired
TE MP
TE
M
R em
P
ot e Contr
o lle r
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
9
INTRODUCTION
Table 1: Multi V Cassette Indoor Units
Unit Model Number
Ceiling Cassette: 4-Way (2' x 2')
Ceiling Cassette: 4-Way (3′ x 3′)
Ceiling Cassette: 2-Way
ARNU053TRC4
ARNU073TRC4
ARNU093TRC4
ARNU123TRC4
ARNU153TQC4
ARNU183TQC4
ARNU243TPC4
ARNU283TPC4
ARNU363TNC4
ARNU423TMC4
ARNU483TMC4
ARNU183TLC4
Multi V Ceiling Cassette Indoor Unit
Ceiling Cassette 1-Way
10
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ARNU243TLC4
ARNU073TUC4
ARNU093TUC4
ARNU123TUC4
ARNU183TTC4
ARNU243TTC4
Cassette Indoor Units Nomenclature
UNIT NOMENCLATURE
Family
ARN = Multi V Indoor Unit (Refrigerant R410A)
Type
U = Inverter Heat Pump/Heat Recovery
Nominal Capacity (Nominal cooling capacity in Btu/h)
05 = 5,500 07 = 7,500 09 = 9,600 12 = 12,300
Electrical Ratings
3 = 208–230V/60Hz/1Phase
Chassis/Model Type
TP = 4-Way Ceiling Cassette (3’x3’) TN = 4-Way Ceiling Cassette (3’x3’) TM = 4-Way Ceiling Cassette (3’x3’)
15 = 15,400 18 = 19,100 24 = 24,200 28 = 28,000
36 = 36,200 42 = 42,000 48 = 48,000
TR = 4-Way Ceiling Cassette (2’x2’) TQ = 4-Way Ceiling Cassette (2’x2’)
ARN
U 05 3 TR C
TL = 2-Way Ceiling Cassette TU = 1-Way Ceiling Cassette TT = 1-Way Ceiling Cassette
4
Installation Manual
Feature
C = Plasma Filter
Generation
4 = Fourth
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
11
R410A REFRIGERANT
WARNING
Note:
R410A refrigerant has a higher operating pressure in comparison to R22 refrigerant and, therefore, all piping system materials installed must have a higher resisting pressure than the materials traditionally used in R22 systems.
R410A refrigerant is an azeotrope of R32 and R125, mixed at 50:50, so the ozone depletion potential (ODP) is 0.
To prevent the refrigerant cylinder from exploding, do not place it in direct sunlight.
Do not use any piping that has not been approved for use in high-pressure refrigerant systems.
To prevent the piping from softening, do not heat it more than necessary during installation.
• Piping wall thickness must comply with the applicable local, state, and federal codes for the 551 psi design pressure of R410A.
• Because R410A is a combination of R32 and R125, the required additional refrigerant must be charged in its liquid state. If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.
Multi V Ceiling Cassette Indoor Unit
12
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 2: 4-Way Cassette Indoor Units Specications
GENERAL DATA
Specications
Type
4-Way Ceiling Cassette – 2 ft x 2 ft Models – TR/TQ Chassis
ARNU053TRC4 ARNU073TRC4 ARNU093TRC4 ARNU123TRC4 ARNU153TQC4 ARNU183TQC4
Cooling Mode Performance
Capacity (Btu/h)
Power Input1 (W)
5,500 7,500 9,600 12,300 15,400 19,100
30 30 30 30 30 30
Heating Mode Performance
Capacity (Btu/h)
Power Input1 (W)
6,100 8,500 10,900 13,600 17,100 21,500
30 30 30 30 30 30
Entering Mixed Air
Cooling Max (°F WB)
Heating Min (°F DB)
76 76 76 76 76 76
59 59 59 59 59 59
Unit Data
Refrigerant Type
2
Refrigerant Control
Net Unit Weight (lbs)
Shipping Weight (lbs)
Grille Weight (lbs)
Grille Shipping Weight (lbs)
Communication Cable
3
(No. x AWG)
R410A R410A R410A R410A R410A R410A
EEV EEV EEV EEV EEV EEV
29 29 32 32 35 35
34 34 38 38 40 40
7 7 7 7 7 7
11 11 11 11 11 11
2 x 18 2 x 18 2 x 18 2 x 18 2 x 18 2 x 18
Fan
Quantity
Airflow Rate H/M/L (CFM)
1 1 1 1 1 1
265 / 247 / 212 265 / 247 / 212 283 / 265 / 251 307 / 283 / 247 388 / 353 / 328 396 / 388 / 353
Piping
Liquid Line (in, OD)
Vapor Line (in, OD)
Condensate Line (in, ID)
1
Power Input is rated at high speed.
2
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
3
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must comply with applicable local and national codes. Ensure the communication cable is properly grounded at the master outdoor unit only. Do not ground the ODU−IDU com­munications cable at any other point.
EEV: Electronic Expansion Valve Power wiring is field supplied and must comply with the applicable local and national
codes. Power Supply (V/Hz/Ø): 208-230/60/1
1/4 Flare 1/4 Flare 1/4 Flare 1/4 Flare 1/4 Flare 1/4 Flare
1/2 Flare 1/2 Flare 1/2 Flare 1/2 Flare 1/2 Flare 1/2 Flare
1 1 1 1 1 1
Installation Manual
This unit comes with a dry nitrogen charge. This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft
level difference between outdoor and indoor units. All capacities are net with a combina­tion ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
13
GENERAL DATA
Specications
Table 2: 4-Way Cassette Indoor Units Specications – continued
Type
4-Way Ceiling Cassette – 3 ft x 3 ft Models – TP, TN, TM Chassis
ARNU243TPC4 ARNU283TPC4 ARNU363TNC4 ARNU423TMC4 ARNU483TMC4
Cooling Mode Performance
Capacity (Btu/h)
Power Input1 (W)
24 200 28 000 36 200 42 000 48 100
33 33 144 144 144
Heating Mode Performance
Capacity (Btu/h)
Power Input1 (W)
27 300 31 500 40 600 43 800 51 200
33 33 144 144 144
Entering Mixed Air
Cooling Max (°F WB)
Heating Min (°F DB)
76 76 76 76 76
59 59 59 59 59
Unit Data
Refrigerant Type
2
Refrigerant Control
Net Unit Weight (lbs)
Shipping Weight (lbs)
Grille Weight (lbs)
Grille Shipping Weight (lbs)
Communication Cable
3
(No. x AWG)
R410A R410A R410A R410A R410A
EEV EEV EEV EEV EEV
48 48 54 59 59
58 58 64 69 69
13 13 13 13 13
20 20 20 20 20
2 x 18 2 x 18 2 x 18 2 x 18 2 x 18
Fan
Quantity
Airflow Rate H/M/L (CFM)
Multi V Ceiling Cassette Indoor Unit
Piping
Liquid Line (in, OD)
Vapor Line (in, OD)
Condensate Line (in, ID)
1
Power Input is rated at high speed.
2
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
3
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must comply with applicable local and national codes. Ensure the communication cable is properly grounded at the master outdoor unit only. Do not ground the ODU−IDU com­munications cable at any other point.
EEV: Electronic Expansion Valve Power wiring is field supplied and must comply with the applicable local and national
codes. Power Supply (V/Hz/Ø): 208-230/60/1
1 1 1 1 1
600 / 530 / 459 671 / 565 / 494 883 / 777 / 706 1059 / 918 / 812 1130 / 953 / 883
3/8 Flare 3/8 Flare 3/8 Flare 3/8 Flare 3/8 Flare
5/8 Flare 5/8 Flare 5/8 Flare 5/8 Flare 5/8 Flare
1 1 1 1 1
This unit comes with a dry nitrogen charge. This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft
level difference between outdoor and indoor units. All capacities are net with a combina­tion ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
14
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 2: 2-Way Cassette Indoor Units Specications
GENERAL DATA
Specications
Type
ARNU183TLC4 ARNU243TLC4
Cooling Mode Performance
Capacity (Btu/h)
Power Input1 (W)
19,100 24,200
144 144
Heating Mode Performance
Capacity (Btu/h)
Power Input1 (W)
21,500 27,300
144 144
Entering Mixed Air
Cooling Max (°F WB)
Heating Min (°F DB)
76 76
59 59
Unit Data
Refrigerant Type
2
Refrigerant Control
Net Unit Weight (lbs)
Shipping Weight (lbs)
Grille Weight (lbs)
Grille Shipping Weight (lbs)
Communication Cable
3
(No. x AWG)
R410A R410A
EEV EEV
56 56
66 66
13 13
20 20
2 x 18 2 x 18
Fan
Quantity
Airflow Rate H/M/L (CFM)
1 1
565/530/424 742/671/600
Piping
Liquid Line (in, OD)
Vapor Line (in, OD)
Condensate Line (in, ID)
1
Power Input is rated at high speed.
2
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
3
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must comply with applicable local and national codes. Ensure the communication cable is properly grounded at the master outdoor unit only. Do not ground the ODU−IDU com­munications cable at any other point.
EEV: Electronic Expansion Valve Power wiring is field supplied and must comply with the applicable local and national
codes. Power Supply (V/Hz/Ø): 208-230/60/1
3/8 Flare 3/8 Flare
5/8 Flare 5/8 Flare
1 1
2-Way Ceiling Cassette – TL Chassis
Installation Manual
This unit comes with a dry nitrogen charge. This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft
level difference between outdoor and indoor units. All capacities are net with a combina­tion ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
15
GENERAL DATA
Specications
Table 2: 1-Way Cassette Indoor Units Specications
Type
ARNU073TUC4 ARNU093TUC4 ARNU123TUC4 ARNU183TTC4 ARNU243TTC4
Cooling Mode Performance
Capacity (Btu/h)
Power Input1 (W)
7 500 9 600 12 300 19 100 24 200
40 40 40 70 70
Heating Mode Performance
Capacity (Btu/h)
Power Input1 (W)
8 500 10 900 13 600 21 500 24 200
40 40 40 70 70
Entering Mixed Air
Cooling Max (°F WB)
Heating Min (°F DB)
76 76 76 76 76
59 59 59 59 59
Unit Data
Refrigerant Type
2
Refrigerant Control
Net Unit Weight (lbs)
Shipping Weight (lbs)
Grille Weight (lbs)
Grille Shipping Weight (lbs)
Communication Cable
3
(No. x AWG)
R410A R410A R410A R410A R410A
EEV EEV EEV EEV EEV
33 33 33 42 42
40 40 40 49 49
10 10 10 13 13
16 16 16 20 20
2 x 18 2 x 18 2 x 18 2 x 18 2 x 18
Fan
Quantity
Airflow Rate H/M/L (CFM)
Multi V Ceiling Cassette Indoor Unit
Piping
Liquid Line (in, OD)
Vapor Line (in, OD)
Condensate Line (in, ID)
1
Power Input is rated at high speed.
2
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
3
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must comply with applicable local and national codes. Ensure the communication cable is properly grounded at the master outdoor unit only. Do not ground the ODU−IDU com­munications cable at any other point.
EEV: Electronic Expansion Valve Power wiring is field supplied and must comply with the applicable local and national
codes. Power Supply (V/Hz/Ø): 208-230/60/1
1 1 1 1 1
290 / 258 / 226 325 / 304 / 290 353 / 325 / 290 470 / 427 / 385 515 / 470 / 406
1/4 Flare 1/4 Flare 1/4 Flare 1/4 Flare 3/8 Flare
1/2 Flare 1/2 Flare 1/2 Flare 1/2 Flare 5/8 Flare
1 1 1 1 1
1-Way Ceiling Cassette – TU, TT Chassis
This unit comes with a dry nitrogen charge. This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft
level difference between outdoor and indoor units. All capacities are net with a combina­tion ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
16
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
GENERAL DATA
Dimensions – TR Chassis
Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
17
GENERAL DATA
Dimensions – TQ Chassis
Multi V Ceiling Cassette Indoor Unit
18
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.