1. Specification

 

Indoor unit type

 

Ceiling Concealed Duct - Low Static

 

 

 

 

 

 

Model

 

AMNW09GB1A0 [LMDN095HV]

AMNW12GB1A0 [LMDN125HV]

 

 

 

 

 

Power Supply

 

Ø / V / Hz

1/ 208~230/ 60

1/ 208~230/ 60

 

 

 

 

 

Capacity(*)

 

Btu/h class

9,000

12,000

 

 

 

 

 

Current

Running Current

A

0.25

0.25

 

 

 

 

 

Fan

Motor Type

 

BLDC

BLDC

 

 

 

 

 

 

Fan Type

 

Sirocco Fan

Sirocco Fan

 

 

 

 

 

 

Motor Output(W) x No. of Unit

5 x 1, 19 x 1

5 x 1, 19 x 1

 

 

 

 

 

 

Air Flow Rate

CMM

9.5 / 8.5 / 7.5

15.0 / 13.5 / 11.5

 

 

 

 

 

 

(H / M / L)

CFM

300/ 265/ 230

335 / 300 / 265

 

 

 

 

 

 

External Static Pressure

mmAq

4

4

 

 

 

 

 

 

Capacitor

µF / Vac

-

-

 

 

 

 

 

 

Drive

 

Direct Drive

Direct Drive

 

 

 

 

 

Coil

Row x Column x FPI

 

2R x 12C x 21

2R x 12C x 21

 

 

 

 

 

Dimensions

Body

mm(inch)

820 x 190 x 575(32 9/32x7 1/2x 22 21/32)

820 x 190 x 575(32 9/32x7 1/2x 22 21/32)

 

 

 

 

 

(W x H x D)

Decorative Panel

mm(inch)

-

-

 

 

 

 

 

Net Weight

Body

kg (lbs)

20.5(45.2)

20.5(45.2)

 

 

 

 

 

 

Decorative Panel

kg (lbs)

-

-

 

 

 

 

 

Air Filter

 

 

Long life filter

Long life filter

 

 

 

 

 

Sound Level (H / M / L)

dB(A)+3

32/ 26/ 25

33/ 31/26

 

 

 

 

 

Piping

Liquid

mm (inch)

6.35 (1/4)

6.35 (1/4)

 

 

 

 

 

Connections

Gas

mm (inch)

9.52 (3/8)

9.52 (3/8)

 

 

 

 

 

 

Drain(OD/ID)

mm(inch)

32/25(1.26/0.984)

32/25(1.26/0.984)

 

 

 

 

 

Dehumidification Rate

l/h

1.0

1.2

 

 

 

 

 

Safety Devices

 

 

Fuse, thermal protector for fan motor

Fuse, thermal protector for fan motor

 

 

 

 

 

Temperature Sensor

 

 

Thermistor

Thermistor

 

 

 

 

 

Referigerant

 

 

R410A

R410A

 

 

 

 

 

Referigerant Control

 

 

EEV(in Outdoor unit)

EEV(in Outdoor unit)

 

 

 

 

 

Transmission Interunit Cable

No. x AWG

4 x 18 (Including Earth)

4 x 18 (Including Earth)

 

 

 

 

 

Note:

1.Capacities are based on the following conditions:

Cooling: - Indoor Temperature 26.7˚C(80˚F) DB/19.4˚C(67˚F)

-Outdoor Temperature 35˚C(95˚F) DB/23.9˚C(75˚F) Heating: - Indoor Temperature 21.1˚C(70˚F) DB/15.6˚C(60˚F) WB

-Outdoor Temperature 8.3˚C(47˚F) DB/6.1˚C(43˚F) WB

Piping Length - Interconnecting Piping Length 7.5m(24.6 ft.)

-Level Difference of Zero

2.Wiring cable size must comply with the applicable local and national code.

3.The specification may be subject to change without prior notice for purpose of improvement.

4.For more Capacity(*),refer to the combination table

Conversion Formula

kW = Btu/h class X 0.0002931

cfm = CMM x 35.3

Copyright ©2008 LG Electronics. Inc. All right reserved.

- 2 -

Only for training and service purposes

LGE Internal Use Only

 

2. FunctionTable

Category

Function

AMNW09GB1A0 [LMDN095HV]

AMNW12GB1A0 [LMDN125HV]

 

 

 

 

 

Air supply outlet

1

1

 

Airflow direction control(left & right)

-

-

 

Airflow direction control(up & down)

-

-

 

Auto swing(left & right)

-

-

Air flow

Auto swing(up & down)

-

-

 

Airflow steps(fan / cool / heat)

3 / 3 / 3

3 / 3 / 3

 

Chaos swing

-

-

 

Chaos wind(auto wind)

X

X

 

Jet cool(Power wind)

X

X

 

Swirl wind

X

X

 

Deodorizing filter

X

X

Air purifying

Plasma air purifier

X

X

 

Prefilter(washable / anti-fungus)

O

O

 

Drain pump

O

O

Installation

E.S.P. control

O

O

Electric heater(operation)

X

X

 

 

High ceiling operation

-

-

 

Hot start

O

O

Reliability

Self diagnosis

O

O

 

Soft dry operation

O

O

 

Auto changeover

X

X

 

Auto cleaning

X

X

 

Auto operation(artificial intelligence)

O

O

 

Auto restart operation

O

O

 

Child lock

O

O

Convenience

Energy-Saving Cooling Mode

X

X

 

Forced operation

X

X

 

Group control

O

O

 

Sleep mode

X

X

 

Timer(on/off)

X

X

 

Timer(weekly)

X

X

 

Two thermistor control

O

O

 

Wide wired remote controller

Accessory (PQRCUSA0)

Accessory (PQRCUSA0)

 

Deluxe wired remote controller

Accessory (PQRCUDS0)

Accessory (PQRCUDS0)

Individual

Simple wired remote controller

O

O

Simple wired remote controller(for hotel use)

Accessory (PQRCFCS0C)

Accessory (PQRCFCS0C)

control

Wireless remote controller(simple)

X

X

 

 

Wireless LCD remote control

X

X

 

Wireless LCD remote control(Ez)

X

X

 

General central controller (Non LGAP)

X

X

CAC network

Dry contact

Accessory (PQDSB)

Accessory (PQDSB)

Central control(LGAP)

Accessory (PQCSB101S0)

Accessory (PQCSB101S0)

function

PDI(power distribution indicator)

Accessory (PQNUD1S00)

Accessory (PQNUD1S00)

 

 

PI 485

Accessory (PMNFP14A0)

Accessory (PMNFP14A0)

Special

CTIE

X

X

function kit

Zone control

Accessory (ABZCA)

Accessory (ABZCA)

Others

Thermistor

-

-

Note :

O : Applied, X : Not applied, - : No relation

*Option : Model name & price are different according to options, and assembled in factory with main unit.

*Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

Copyright ©2008 LG Electronics. Inc. All right reserved.

- 3 -

Only for training and service purposes

LGE Internal Use Only

 

Loading...
+ 4 hidden pages