Friedrich PZH12R3SB, PZH12K3SB, PZE12R3SB, PZE15K5SB Installation Manual

0 (0)

Installation and Operation Manual

PTAC

Packaged Terminal Air

Conditioners & Heat Pumps

SG SERIES

9830 1000_00 (01/15)

 

Table of Contents

 

Congratulations.........................................................................................................................................................................................................................

3

General Instructions.................................................................................................................................................................................................................

3

General Specifications.............................................................................................................................................................................................................

4

Installation Checklist.................................................................................................................................................................................................................

4

PTAC Installation Recommendations.......................................................................................................................................................................................

5

Wall Sleeve Installation Instructions (PDXWS)........................................................................................................................................................................

6

Alternate Wall Installations.......................................................................................................................................................................................................

7

One-Piece Deep Wall Sleeve Installation (PDXWSEXT)........................................................................................................................................................

9

PXDR10 Drain Kit Installation Instructions (optional for new construction)...........................................................................................................................

10

External Drain (for new construction or unit replacement).....................................................................................................................................................

11

PXGA Standard Grille Installation Instructions......................................................................................................................................................................

12

Electrical Wiring for 265 Volt Models.....................................................................................................................................................................................

14

Chassis Install Preparation.....................................................................................................................................................................................................

16

Chassis Installation ................................................................................................................................................................................................................

18

How To Connect.....................................................................................................................................................................................................................

19

Friedrich PTAC Digital Control and Unit Features..................................................................................................................................................................

20

System Configuration.............................................................................................................................................................................................................

22

Digital Control User Input Configuration.................................................................................................................................................................................

23

Digital Control Operation........................................................................................................................................................................................................

24

Remote Control Thermostat Installation.................................................................................................................................................................................

25

Remote Thermostat and Low Voltage Control Connections..................................................................................................................................................

25

Final Inspection & Start-up Checklist.....................................................................................................................................................................................

27

Routine Maintenance..............................................................................................................................................................................................................

27

Basic Troubleshooting............................................................................................................................................................................................................

28

Service & Assistance..............................................................................................................................................................................................................

29

Accessories............................................................................................................................................................................................................................

30

NOTE:

All PTAC 7000, 9000, 12000 units come with a standard 3.5 kW power cord. All PTAC 15000 units come with a standard 5 kW power cord

 

For units using our optional heating cords (2.5 kW, 3.5 kW, and 5 kW) please refer to page 14 for the proper accessory part numbers and

 

 

power cord installation instructions.

 

2

Congratulations

Thank you for your decision to purchase Friedrich. Your new Friedrich has been carefully engineered and manufactured to give you many years of dependable, efficient operation, maintaining a comfortable temperature and humidity level. Many extra features have been built into your unit to assure quiet operation, the greatest circulation of cool, dry air, and the most economic operation.

General Instructions

This Installation and Operation Manual has been designed to insure maximum satisfaction in the performance of your unit. For years of trouble-free service, please follow the installation instructions closely. We cannot overemphasize the importance of proper installation.

WARNING

Refrigeration system under high pressure

Do not puncture, heat, expose to flame or incinerate.

Only certified refrigeration technicians should service this equipment.

R410A systems operate at higher pressures than R22 equipment. Appropriate safe service and handling practices must be used.

Only use gauge sets designed for use with R410A. Do not use standard R22 gauge sets.

Here are some suggestions to help you use your new Friedrich most efficiently:

1.Carefully read and follow the installation instructions.

2.Make sure the unit is the right capacity for the area being cooled. An undersized unit makes the unit work too hard, using more electricity than needed and increases wear. An oversized unit will cycle on and off too rapidly, and therefore cannot control humidity as well.

3.Clean the filter frequently (See Routine Maintenance, Page 27).

4.Do not block the air flow to and from the unit.

5.A dirty filter or improperly set controls can affect the cooling ability of the unit.

6.If cooling is weak and you have verified that the filter is clean

and the controls are properly set, the unit may need service and you should call your Friedrich service provider to check the unit.

7.Keep blinds, shades and drapes closed on the sunny side of the room being cooled to reduce radiant heat.

8.Proper insulation helps your unit maintain the desired inside temperature.

9.Whenever possible, shade south and west facing windows.

10.Keepwindowcoveringsawayfromtheunittoprovidefreeairflow.

WARNING

Read Installation Operation Manual

Please read this manual thoroughly prior to equipment installation or operation.

It is the installer’s responsibility to properly apply and install the equipment. Installation must be in conformance with the NFPA 70 -2008 National Electric Code or current edition, International Mechanic Code 2009 or current edition and any other applicable local or national codes.

Failure to do so can result in property damage, personal injury or death.

Your safety and the safety of others are very important.

We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety messages.

This is a safety Alert symbol.

This symbol alerts you to potential hazards that can kill or hurt you and others. All safety messages will follow the safety alert symbol with the word “WARNING” or “CAUTION”. These words mean:

WARNING

death and damage to product or other property.

 

Indicates a hazard which, if not avoided, can result in severe personal injury or

 

Indicates a hazard which, if not avoided, can result in personal injury and

 

CAUTION

damage to product or other property.

 

 

All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what will happen if the instructions are not followed.

NOTICE

Indicates property damage can occur if instructions are not followed.

 

3

General Specifications

E

MODEL NUMBER

PD

Series

PD = Friedrich Digital PTAC

System

X = Accessory

E = Cooling with or without electric heat H = Heat Pump with Auxiliary Heat

Nominal Capacity

 

 

07 = 7,000 Btuh

12 = 12,000

Btuh

09 = 9,000 Btuh

15 = 15,000

Btuh

Voltage

K = 230/208V - 1 Ph. - 60 Hz.

R = 265V - 1 Ph. - 60 Hz.

Engineering Digit

Design Series

Note: All PTAC models with a C design series or later come standard with Diamonblue seacost protection and digital controls.

Chassis

S = Standard

Nominal Heater Size (230V or 265V)

2 = 2.5 KW 3 = 3.5 KW 5 = 5.0 KW*

* 5.0 kw only available on 9,000 12,000 and 15,000 BTU models

Installation Checklist

qInspect all components and accessories for damage before and after installation.

qRemove the cardboard wall sleeve support and grill weatherboard.

qCheck for proper wall sleeve installation in accordance with the wall sleeve installation instructions.

qCheck for a subbase kit or other means of structural support which is required for ALL installations projecting more than 8" into room.

qInstall the recommended Condensate Drain Kits for complete condensate removal.

qEnsure that the chassis is installed in a 16" high x 42” wide wall sleeve that is no deeper than 13 ¾". A baffle kit is required if the sleeve exceeds that depth.

qEnsure that chassis and chassis front cover are installed and secured properly.

qEnsure that drapes, bed, bedspread, furniture, etc. DO NOT block either return or discharge air grilles.

qInspect the condenser air inlet and outlet for any obstructions (shrubbery, etc.)

qEnsure that 'reset' button is pressed on LCD device (only on cord connected models).

4

PTAC Installation Recommendations

For proper PTAC unit performance and maximum operating life refer to the minimum installation clearances below:

Figure 1

PTAC units should be installed no closer than 12" apart when two units are side by side. If three or more PTAC units are to operate next to one another allow a minimum of 36" between units. Also, a vertical clearance of 60" should be maintained between units installed. In the interior of the room the unit should be located a minimum of 1/4" from the floor and a minimum of 36" from the ceiling.

THREE OR MORE PTACs

ADJACENT 36" MINIMUM

TYPICAL

WINDOW

36"

60"

TWO ADJACENT PTACs

12" MINIMUM

 

60" VERTICAL

 

MIMUMUM

GROUND FLOOR PTACs

BETWEEN

6" MINIMUM FROM GRADE

PTACs

 

12"

6"

VIEW: OUTSIDE BUILDING ELEVATION

FRP001

For PTACs on the ground floor or anytime obstructions are present, use the following guidelines:

Figure 2

For minor obstructions such as lamp poles or small shrubbery a clearance of

12" from the outdoor louver should be maintained.

For major obstructions such as a solid fence, wall or other heat rejecting device like a condensing unit, a minimum distance of 36" should be kept.

TYPICAL BUILDING ( PLAN VIEW )

 

36"

 

36"

PTAC

 

PTAC

PTAC

 

 

12"

 

12" MINIMUM, MINOR

POLE

36"

SHRUB

OBSTRUCTIONS

 

 

 

36" MIMUMUM, MAJOR

 

 

 

OBSTRUCTIONS

 

FENCE OR WALL

CONDENSING UNIT

FRP002

The above suggestions are for reference only and do not represent all possible installations. Please contact Friedrich for information regarding affects of other installation arrangements. By following these simple recommendations you can be confident that your Friedrich PTAC will provide years of worry free operation.

5

Wall Sleeve Installation Instructions (PDXWS)

NOTE: Insure that the unit is only installed in a wall structurally adequate to support the unit including the sleeve, chassis and accessories. If the sleeve projects more than 8" into the room, a subbase or other means of support MUST be used. Please read these instructions completely before attempting installation.

WARNING

Falling Object Hazard

Not following Installation Instructions for mounting your air conditioner can result in property damage, injury, or death.

NOTICE

DO NOT allow any pitch toward the inside.

Flashing on all 4 sides of the opening is recommended.

Potential property damage can occur if instructions are not followed.

For Deep Wall Installation (Greater than 13 1/4") See Page 9

The following instructions apply ONLY to walls less than 13 ¼" in depth.

1.The PXDR10 Drain Kit (optional for new construction) see page 10 if applicable, must be installed before the wall sleeve is installed into the wall.

2.The External Drain (for new construction or unit replacement) see page 11, if applicable, must be installed before the wall sleeve is installed into the wall.

Figure 3

Typical Wall Sleeve Installation

LINTEL TO SUPPORT

42-¼"

MIN.

MASONRY WALLS

 

3.From inside the building, position the wall sleeve in the opening and push it into the wall until it protrudes at least ¼” on the outside. Do not allow sleeve to be pulled. (See Figure 11, Page 10).

4.Position the wall sleeve with a slight tilt towards the outside to facilitate condensate drainage. It should be level side-to-side and the front should be ¼ bubble higher than the back.

ELECTRICAL

RECEPTACLE

16-¼"

 

 

60"

 

 

MAX.

 

20" MAX.

13-¾"

SMOOTH SIDE OF SCREW CLIP FACING INTO ROOM

INSULATION

ELECTRICAL

RECEPTACLE

WALL OPENING

WALL SLEEVE

INSULATION

NOTE: All 230/208V units are manufactured with a 60” power cord and all 265V units with a 18” power cord.

FRP008

6

Friedrich PZH12R3SB, PZH12K3SB, PZE12R3SB, PZE15K5SB Installation Manual

Alternate Wall Installations

Figure 4

Panel Wall

OPTIONAL SUBBASE

LEVELING SCREW

FRP003

Figure 5

Frame and Brick Veneer

1/4" MIN PROJECTION

WOOD FRAME

STEEL

LINTEL

11" MIN.

WITH SUBBASE

OPTIONAL SUBBASE

LEVELING SCREW

FRP005

Figure 6

Curtain Wall

WALL OR

1/4" MIN

WINDOW

PROJECTION

CASE FLANGE (BY OTHERS)

OPTIONAL SUBBASE

LEVELING SCREW

FRP004

Figure 7

Block and Brick Veneer

1/4" MIN PROJECTION

CONCRETE LINTEL

STEEL

LINTEL

13-3/4" MIN. WITHOUT SUBBASE

RECEPTACLE

FINISHED FLOOR

POWER SUPPLY CONDUIT

(SUPPLIED BY INSTALLER)

 

 

FRP006

NOTE:

Follow all wall system manufacturer installation instructions. For sunrooms and modular buildings, adhere to their installation instructions for

 

supporting and sealing sleeve to their frames. All wall and window/wall installations must provide for proper drainage. In applications where the

 

drain holes on the PTAC wall sleeve are not exposed beyond the wall an internal drain system is recommended. It is the installer's responsibility

 

to ensure there is adequate drainage for the PTAC unit.

7

EXPANSION ANCHOR BOLT

Figure 8

Wall Sleeve Attachment

WALL

SLEEVE

ALTERNATE FASTENING METHODS (Field Supplied)

WOOD SCREW TOGGLE BOLT

NOTE: The Wall Sleeve must be horizontally level (side-to-side) and pitched 1/4 bubble to the outside when installed in an opening.

The mounting hole location should be approximately 2-4” from the top and bottom of the sleeve.

MOUNTING

HOLES

PLASTIC ANCHORS

SCREWS

FRP007

 

Figure 9

Dimensions

A

¼" MIN.

 

A

 

B

C

Dimension*

Allow

Allow

Allow

 

 

 

 

 

for wall

for floor

for proper

 

 

 

finishing

finishing

drainage

 

 

 

(Minimum)

Min.

Max.

(Front-to-Back)

 

C

No Accessories

¼"

¼"

---

---

 

 

With Subbase

1-¾"

3-½"

5"

---

13-¾"

B

WALL

With Lateral Duct

¾"

¼"

---

---

Wall Sleeve Tilt

---

---

---

¼"

*If more than one accessory is to be used, use the maximum dimension. If the wall thickness is more than 13-¾" - (A+ ¼"), a sleeve extension must be used.

FRP009

8

5.Drill two 3/16" holes through each side of the sleeve approximately 4" from top and 4" from bottom of sleeve. Screw four #10 x 1" screws (included) or appropriate fasteners for your installation, through the holes in the sides of the wall sleeve.

6.Applysealantaroundthewallsleevewhereitprojectsthroughthe inside and outside wall surfaces. Apply the sealant to the screw heads or the tops of the fasteners used in Step #5.

7.If the chassis and exterior grille are to be installed later, leave the weatherboard and center support in place, otherwise remove and dispose of them. (See Figure 13, Page 12).

8.Provide a support lintel if the wall sleeve is installed in a concrete or masonry wall (See Figure 10, Page 9).

Figure 10

MAIN STUDS

Lintel Installation

JACK STUDS

 

 

LINTEL

JACK STUDS

MOUNTING

 

MAIN STUDS

SCREW HOLES

NO HOLES IN BOTTOM OF WALL

SLEEVE UNLESS DRAIN KIT IS USED

NOTE: Construct wall opening to comply with all applicable building codes.

FRP010

One-Piece Deep Wall Sleeve Installation (PDXWSEXT)

Ifthewallisthickerthan131/4”adeepwallsleeveorwallsleeveextension

MUST be used. The deep wall sleeve may be special ordered through your Sales Representative.

9

PXDR10 Drain Kit Installation Instructions (optional for new construction)

NOTE:

Determine whether drain will be located within the wall, on the

 

indoor side, or will drain to the exterior of the building. Follow

 

appropriate instructions below depending on your particular

 

type of installation.

Internal Drain

NOTE:

If installing an internal drain, you MUST install a drain kit on

 

the wall sleeve before the wall sleeve is installed.

1.Refer to Figure 11 and locate the drain within the “Preferred” area of best drainage. Maintain at least a ½” clearance from the embossed area.

2.Using the mounting plate with the ½” hole as a template, mark and drill two, 3/16” mounting holes and a ½” drain hole in the sleeve bottom.

3.Remove the backing from the gasket and mount it on the flat side of the mounting plate. (See Figure 12, Page 11). Insert the drain tube through the hole in the gasket and mounting plate so the tube flange will be against the wall sleeve.

4.Position the assembly beneath the drilled holes and secure it with

#10-24 x ½" machine screws and lock nuts provided. Seal the tops of the screws with silicone caulking.

5.Use½"I.D.coppertube,PVCpipe,orvinylhose(obtainedlocally) to connect the internal drain tube to the drain system in the building.

6.Referring to Figure 12, Detail A, Page 11, locate and assemble the

(2) two cover plates and gaskets over the drain holes at the rear of the wall sleeve. Attach them with the #10 sheet metal screws provided. Make certain that the four overflow slots at the rear of the wall sleeve are not blocked (See drawing of the back of the sleeve Figure 12, Page 11).

7.If a deep wall extension (PDXWSEXT) is used, after installing the fieldsuppliedflashing,caulkasrequired. Besuretocaulkaround the flashing and the wall sleeve where the hole was drilled for the drain tube.

Figure 11

 

SCREW

Drain Kit Location and Installation

WALL SLEEVE

 

OPTIONAL AREA

 

PREFERRED AREA-

GASKET

 

FOAM INSULATION

 

 

MOUNTING

 

 

PLATE

 

 

DRAIN TUBE

NUT

 

 

SIDE VIEW

IF THE

 

 

LOCATED

 

 

AREA,

 

 

MUST BE

3"

 

REMOVED TO ALLOW ACCESS

 

TO THE DRAIN.

 

 

 

 

FRONT VIEW

 

 

FRP011

 

 

 

 

 

 

 

 

PXDR10

 

QUANTITY

DESCRIPTION

 

2

COVER PLATES

 

1

MOUNTING PLATE

 

1

DRAIN TUBE

 

3

MOUNTING PLATE GASKET

 

4

#10 X ½” SHEET METAL SCREWS

 

2

#10-24 X ½ ” MACH. SCREWS

 

2

#10-24 X ½" LOCKNUTS

10

External Drain (for new construction or unit replacement)

When using an external drain system, the condensate is removed through either of two drain holes on the back of the wall sleeve. Select the drain hole which best meets your drainage situation and install the drain kit. Seal off the other with a cover plate.

Drain Tube Installation (See Figure 12)

1.Peel the backing tape off the gaskets and apply the sticky side to one cover plate and one mounting plate as shown in Details A and B.

2.Place the drain tube through the gasket and the mounting plate with the flange toward the wall sleeve.

3.Attach the drain tube assembly to one of the two drain holes at the rear of the wall sleeve. The large flange on the mounting plate is positioned at the bottom of the sleeve facing toward the sleeve, Detail B. When the drain tube is positioned at the desired angle, tighten the screws.

Cover Plate Installation

4.Mount the foam gasket to the cover plate. Using two #10 x ½" sheet metal screws (provided), attach the cover plate to the remaining drain hole. Make certain the large flange on the plate is positioned at the bottom of the sleeve.

5.Discard the additional cover plate, gasket, machine screws, and locknuts.

NOTICE

If the wall sleeve has not been installed, the drain tube must be rotated to a horizontal position until after the sleeve is installed. Tighten the mounting plate screws when the tube is in the proper position. Make certain that the four overflow slots at the rear of the wall sleeve are not blocked (See Figure 12).

When sealing the sleeve on the outside of the building, be careful NOT to let the sealant block the two condensate drain holes or the four overflow slots at the bottom flange of the sleeve.

Potential property damage can occur if instructions are not followed.

Figure 12

COVER

Drain Kit Installation

PLATE

MOUNTING

FOAM

PLATE

 

GASKET

NUT

DETAIL A

 

 

OVERFLOW

 

SLOTS

FOAM

SCREWS

 

GASKET

½” O.D. TUBE

DETAIL B

FRP012

 

NOTE:

The large flange on the mounting plate is positioned at the bottom of the sleeve facing toward the sleeve. The drain tube must be rotated to a

 

horizontal position to allow for the wall sleeve to be installed into the wall. Once the wall sleeve is installed, return the drain tube to a downward

 

angle.

11

Loading...
+ 25 hidden pages