Multi Zone Air Conditioner
SVC MANUAL(Exploded View)
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual. Only for authorized service personnel.
MODEL : MR36TQY3JM
960-920-04
1. Specification
Outdoor Unit
|
|
|
|
|
|
Outdoor Unit |
|
MR36TQY3JM |
|
|
|
|
|
|
Capacity(*) |
|
|
Btu/h Class |
34,000 |
Power Input |
Cooling |
|
kW |
0.77~2.72~ 3.92 |
(Min.~Rated~ Max.) |
Heating |
|
kW |
1.12~3.58~4.1 |
Running Current |
Cooling |
|
A |
3.3~11.8~17.0 |
|
Heating |
|
A |
4.9~15.5~17.8 |
Starting Current |
Cooling/Heating |
|
A |
- |
Power Supply |
|
|
Ø / V / Hz |
1/208 - 230/60 |
Power Supply Cable (Outdoor) |
|
No.x AWG |
3 × 12 |
|
Transmission Cable (Outdoor to Indoor unit ) |
|
No.x AWG |
4 x 18 (Including Earth) |
|
Dimensions |
W x H x D |
|
mm(inch) |
900 x 1,165 x 370 |
|
(35 7/16 x 45 7/8 x 14 9/16) |
|||
|
|
|
|
|
Net Weight |
|
|
kg(lbs) |
95(209.4) |
Max. Number of Connectable Indoor Units |
|
4 |
||
Compressor |
Type |
|
Twin-Rotary |
|
|
Qty x Model |
|
GPT425DBA |
|
|
Motor type |
|
BLDC |
|
|
Oil charge volume |
|
cc |
1300 |
|
Oil Type |
|
FVC68D |
|
Refrigerant |
Cycle A Charge (at 7.5m) |
|
g(oz) |
3,500(123.46) |
|
Cycle B Charge (at 7.5m) |
|
g(oz) |
- |
|
Type |
|
R410A |
|
|
Control |
|
EEV |
|
Heat Exchanger |
(Rows x Column x FPI) x No. |
|
(2R x 26C x 17) x 2 |
|
|
Coil tube dia. |
|
mm(inch) |
7(0.276) |
|
Defrosting Method |
|
Reversing cycle |
|
Fan motor |
Capacitor |
|
μF/Vac |
- |
|
Drive |
|
Direct (DC) |
|
|
Discharge Direction(Side/Top) |
Side |
||
|
Air Flow Rate x No. of Fan |
|
CMM(CFM) |
60(2,118) x 2EA |
Sound Level(H) |
Sound Pressure |
|
dB(A)+3 |
57 |
Piping Connections |
Liquid(Cycle A) |
|
mm(inch) |
6.35(1/4) × 4EA |
|
Gas(Cycle A) |
|
mm(inch) |
9.52(3/8) × 4EA |
|
Liquid(Cycle B) |
|
mm(inch) |
- |
|
Gas(Cycle B) |
|
mm(inch) |
- |
Piping length spec. |
Max. total piping |
|
m(ft.) |
75(246.1) |
|
Max. OD~ID piping |
|
m(ft.) |
25(82.0) |
|
Piping length(no add'l refrigerant) |
|
m(ft.) |
30(123.0) |
Max. Elevation |
Outdoor Unit~Indoor Unit |
|
m(ft.) |
15(49.2) |
Difference |
Indoor Unit~Indoor Unit |
|
m(ft.) |
7.5(24.6) |
Operation Range |
Cooling |
|
°C(°F) |
-10 ~ 46 (14~114.8) |
(Outdoor) |
Heating |
|
°C(°F) |
-15 ~ 24 (5~75.2) |
Note:
1.Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27C(80.6F) DB/19C(66.2F) WB
-Outdoor Temperature 35C(95F) DB/24C(75.2F) WB Heating: - Indoor Temperature 20C(68F) DB/15C(59F) WB
-Outdoor Temperature 7C(44.6F) DB/6C(42.8F) WB
Piping Length - Interconnecting Piping Length 7.5m
-Level Difference of Zero
2.Wiring cable size must comply with the applicable local and national code.
3.The specification may be subject to change without prior notice for purpose of improvement.
Conversion Formula
kW = Btu/h x 0.0002931 cfm = CMM x 35.3
- 2 -
2. Function Table
Category |
Function |
A4UW363FA2 [MR36TQY3JM] |
|
|
|
|
|
|
Defrost / Deicing |
O |
|
|
High Pressure Switch |
X |
|
|
Low Pressure Switch |
X |
|
Reliability |
Phase protection |
X |
|
Restart Delay (3-minutes) |
O |
||
|
|||
|
Self Diagnosis |
O |
|
|
Soft Start |
O |
|
|
Test Function |
X |
|
Convenience |
Auto operation(Artificial intelligence) |
O |
|
Auto Restart Operation |
O |
||
|
|||
CAC Network |
Central control(LGAP) |
X |
|
PDI(Power Distribution Indicator) |
X |
||
Function |
|||
PI485 |
X |
||
|
|||
Special function kit |
Low ambient operation |
O |
|
Others |
Thermistor |
- |
Note :
•O: Applied, • X: Not applied, • - : No relation,
•Option: Model name & price are different according to options, and assembled in factory with main unit.
•Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
- 3 -