Low-level alarm for water-level limiter ...........................................................................13
Low-level alarm for water-level limiting system .............................................................13
System Malfunctions
Fault analysis, system faults 1 – 7 ........................................................................14 – 22
Operation Malfunctions
Fault finding list for troubleshooting ............................................................................... 23
Emergency Operation
Emergency operation of water-level limiting system ..................................................... 24
Annex
Factory set default node IDs .................................................................................24 – 26
Assigning/changing node ID .........................................................................................25
Declaration of conformity .............................................................................................. 27
2
Wiring Diagram
Twisted pair cable
Twisted pair cable
Protection circuit
– uninterrupted –
Further safety
equipment
Note:
The NRS 1-40 is
the first equipment
of the safety chain.
All relay contacts are
internally linked.
Photo-Mos output
24 V- 230 V AC/DC, 100 mA
Instantaneous LW alarm,
clocked malfunction signal
Fig.1
Control terminal
URB 1
Terminating resistor
120 Ω
Fig. 2
Switching
controller
NRS 1-40
Voltage supply
Terminating resistor
120 Ω
Controller
...
Level electrode
NRG16-40
CAN data line
Terminating resistor
120 Ω
Level sensor
NRG...
3
Part Drawings
Fig. 3
1
32567
4
A
A
B
Fig. 4
4
Key
Indicator LED
1
LED 1: Electrode 1
LED 2: Electrode 2
LED “Bus status”
2
LED “Power”
3
Enter /Test mode
4
Decrease
5
Increase
6
Program key
7
Two-pole code switch
8
9
Ten-pole code switch
A
Terminal strip
Screws for terminal strip
B
AlarmMalfunction
Low-level alarmMultifunction
Low-level alarmMultifunction
5
Important Notes
Usage for the intended purpose
Use switching controller NRS 1-40 only in conjunction with GESTRA level electrode
NRG 16-40, NRG 17-40 or NRG 19-40 for signalling low-water level (min. alarm).
Safety Note
Installation must only be performed by qualified staff.
Qualified staff are those persons who – through adequate training in electrical
engineering, the use and application of safety equipment in accordance with
regulations concerning electrical safety systems, and first aid & accident prevention –
have achieved a recognised level of competence appropriate to the installation and
commissioning of this safety device.
Danger
The terminal strip of the NRS 1-40 is live during operation.
This presents the danger of electric shock.
Cut off power supply before fixing or removing the housing cover.
Explanatory Notes
Scope of Supply
NRS 1-40
1 Switching controller NRS 1-40 (plug-in unit in plastic case with terminals)
1 Terminating resistor 120 Ω
1 Installation and service manual
Description
The controller type NRS 1-40 is a self-monitoring low-water level limiter with periodic
self-checking and monitoring feature of the output relay contacts, to be used in
conjunction with one level electrode type NRG 16-40, 17-40 or 19-40. The controller
has the following function:
6
Explanatory Notes – continued –
Description – continued –
■ Low-water level alarm with one level electrode
The equipment detects the min. water level (low-level limiter) and complies with the
German regulations for use in steam and hot-water plants operating without constant
supervision according to TRD 401, TRD 602 and TRD 604.
When used with two level electrodes type NRG 16-40, 17-40 or 19-40, the controller
NRS 1-40 constitutes a high-integrity low-water level limiter system with periodic selfchecking. The controller features the following function:
■ Low-water level alarm with two level electrodes
This equipment combination detects the min. water level (low-level limiting system) and
complies with the German regulations for use in steam and hot-water plants operating
without constant supervision according to TRD 604, sheet 1 and 2 (24/72 hours
operation without constant supervision).
This item of electrical equipment complies with the Technical Regulations on Protection
Circuits to DIN VDE 0116 (prEN 50156).
The level data are transferred from the electrode NRG 1...-40 to the controller via CAN
bus using the CANopen protocol. Only one low-level limiting system may be used per
CAN-based network.
Function
At regular intervals the level electrode NRG 1...-40 sends a data telegram to the
controller NRS 1-40. The data transfer is effected by means of a CAN bus according to
ISO 11898. The transferred measuring data are constantly evaluated by the controller.
A periodic self-checking routine tests every 3 seconds the integrity of the system and its
safety functions, with a malfunction in the controller resulting in immediate boiler shutdown. When the CAN bus line and, consequently, the data transmitting cycle are
interrupted, the controller sends a visual signal to indicate a faulty condition and the
relays are instantaneously de-energized (fail-safe position).
The controller also facilitates user-friendly performance tests and detection/
evaluation of malfunctions. To guarantee the correct and safe functioning of the lowlevel limiter a min. electrical conductivity of 0.5 µS/cm at 25 °C is required.
The relay de-energizing delay is normally set to 3 seconds at the factory but delays of
15 to 25 seconds are available on request.
Apart from the burner protection circuit there is also a separate Photo-MOS make
contact output for remote indication.
The automatic self-testing routine of the switching controllers checks every 3 sec. their
safety functions. The corresponding functions of the level electrodes will be tested by
the electrode's self-checking routine every 10 sec.
The malfunction information is updated with every self-test. If no faults have ocurred the
malfunction information will be deleted automatically. If faults persist the malfunction
information remains stored.
As part of the automatic self-testing routine of the switching controller, the switching-off
of the output relays every 6 hrs is checked, too. If a fault is detected the information on
this malfunction will be saved accordingly.
7
Explanatory Notes – continued –
Technical Data
Type approval no.
TÜV · WB · 99-403
EG BAF-MUC 0202 103881 002
Input
Interface for CAN bus to DIN ISO 11898 CANopen protocol
Output voltage supply for electrodes
18 – 36 V, short-circuit protected
Output for protection circuit
Two volt-free relay contacts, locally connected in series.
Max. contact rating for switching voltages 24 V AC/DC, 115 V AC and 230 V AC:
4 A resistive/inductive. Contact material: silver, hard-gold plated
Interference suppression
Provide contactor with external RC combination (100 Ω / 47 nF)
Signal output
Photo-MOS output, instantaneous with low level, timed malfunction signal, max. contact
rating for switching voltages 24 V AC, 115 V AC and 230 V AC/DC: 100 mA resistive
Relay de-energizing delay
Output “Low-level alarm”, set to 3 sec. (standard), optional for e. g. marine applications
15 sec. or 25 sec., internally linked for relay contact test
Indicators and adjustors
4 pushbuttons “Parameterisation/TEST”
1 red LED “Low-level alarm electrode 1”
1 red LED “Low-level alarm electrode 2”
2 red LEDs “Multifunction”
1 red LED “Bus status”
1 green LED “Power”
1 ten-pole code switch: 7 poles for setting node ID, 3 poles for setting baud rate
1 two-pole code switch for limiter/limiting system
Internal self-checking routine
Every 3 seconds
Periodic testing of output relay contacts
Every 6 hours
Supply voltage
230 V +/–10%, 50/60 Hz
115 V +/–10%, 50/60 Hz (optional)
Power consumption
10 VA
Sensitivity
≥ 0.5 µS/cm at 25 °C
Protection
Enclosure:IP 40 to DIN EN 60529
Terminal strip:IP 20 to DIN EN 60529
Admissible ambient temperature
0°C to 55°C
Enclosure material
Front panel: polycarbonate, grey. Enclosure: polycarbonate, black
Weight
Approx. 0.8 kg
8
Installation
NRS 1-40
Installation on mounting rail
1. Clip switching controller onto mounting rail 35 x 15 mm
(DIN EN 50022):
2. Align switching controller, see Fig. 11, Fig. 12
Note
■
If an external measuring pot is used, each level electrode type
NRG 16-40 requires one switching controller NRS 1-40 and one
GESTRA monitoring unit SRL 6.
Tool
■
Screwdriver (5.5/100)
Wiring
Note that screened multi-core twisted-pair control cable is required, e. g. UNITRONIC
BUS CAN 2 x 2 x ... 2 or RE-2YCYV-fl 2 x 2 x ... 2.
The baud rate (data transfer rate) dictates the cable length between the bus nodes and
the total power consumption of the sensors dictates the conductor size.
®
8S9S01SetarduaBhtgnelelbaC
FFONOFFOs/tiBk052m521
gnittesyrotcaF
NONOFFOs/tiBk521m0525.0x2x2
FFOFFONOs/tiBk001m53357.0x2x2
NOFFONOs/tiBk05m005
FFONONOs/tiBk02m0001
NONONOs/tiBk01m0001
sriapforebmuN
2
]
mm[ezisrotcudnocdna
43.0x2x2
notnedneped,tseuqerno
noitarugifnocsub
The baud rate is set via a code switch. Reduce baud rate if cable is longer than
specified in the table. Make sure that all bus nodes have the same settings.
To protect the switching contacts fuse circuit with 2.5 A (anti-surge fuse) or according
to TRD regulations (1.0 A for 72 hrs operation).
When a max. cable length of more than 125 m (up to 1000 m) is desired, make
sure to modify the baud rate accordingly. Refer to pages 25 and 26 for more
details.
UNITRONIC® is a registered trademark of LAPP Kabelwerke GmbH, Stuttgart
9
Wiring – continued –
Wiring Diagram
Wiring diagram see page 3.
Attention
■
Wire equipment in series. Star-type wiring is not permitted.
■
Interlink screens of control cables such that electrical continuity is
ensured and connect them once to the central earthing point (CEP).
■
To protect the switching contacts fuse circuit with 2.5 A (slow blow) or
according to TRD regulations (1.0 A for 72 hrs operation).
■
If more than one system component is connected to a CAN bus network
provide the first and last equipment with a terminating resistor of 120 Ω.
Fig. 2
■
Use only one water-level limiting system per CAN bus network.
■
The CAN bus line must not be interrupted while operating with one or
more system components.
An interruption will result in disconnection caused by a
malfunction.
If the switching controller has to be replaced be sure to remove first the
terminal strips , Fig. 4
Note: Make sure that all system components connected are
operating
before removing the CAN bus line from the terminal strip.
A
not
10
Note
■
Connect screen only to terminal 3, ensuring electrical continuity and
connect equipment once to the central earthing point (CEP).
■
The loop resistance must be under 10 Ω.
■
The rated voltage is stated on the name plate.
■
When switching off inductive loads, voltage spikes are produced that
may impair the operation of control and measuring systems. Inductive
loads should therefore be provided with commercial arc suppressor
RC combinations, e. g. 0.1 µF/ 100 Ω.
■
Despite correct wiring H. F. interference caused by the installation may
lead to system breakdowns and malfunction messages. If necessary
refer to the “Fault finding list for troubleshooting” on page 23.
■
In the event of a shut-down due to a malfunction the signal output
(terminals 7 and 8) is cyclically opened and closed in order to ensure an
optical distinction between “Low-level alarm” (signal output closed) and
“Malfunction shut down”.
If necessary connect terminals 7 and 8 externally to an indicator lamp,
Fig. 1.
Wiring – continued –
Tools
■
Screwdriver for slotted screws, size 2.5, completely insulated according to
VDE 0680
Basic Adjustments
CAN Bus
All level and conductivity controllers and associated electrodes are interconnected by
means of a CAN bus using the CANopen protocol. Every item of equipment features an
electronic address (Node ID). The four-core bus cable serves as power supply and data
highway for high-speed data exchange.
The CAN address (node ID) can be set between 1 and 123.
The NRS 1-40 is configured at our works and ready for service with other GESTRA
system components without having to set the node ID.
If several systems of the same kind are to communicate in one CAN bus
network, be sure to assign one node ID for each individual system component
(e. g. controller). Refer to pages 24 and 25 for more details.
Node ID
Note
■
The node ID 3* for the second level electrode NRG 16-40 must be
adjusted on site since the equipment features the factory set default
value 2 when delivered.
Factory setting
The switching controller features the following factory set default values:
■ Baud rate: 250 kb/s
■ Sensitivity: 0.5 µS/cm
■ Node ID: 001
■ Configuration: Operation with two level electrodes NRG 1...-40
■ Relay de-energizing delay: 3 s
11
Commissioning
NRS 1-40
Apply power to the unit.
The four indicator LEDs flash rapidly.
The LED “Power” lights up.
The test cycle takes about 3 sec.
Note
■
To analyse and eliminate malfunctions that may occur during the commissioning procedure refer to section “System Malfunctions” on
page 14.
Operation
NRS 1-40
Normal operation, electrode(s) submerged.
The four indicator LEDs are not illuminated.
The LED “Power” lights up.
Indicator LEDs flash rapidly
LED “Power” illuminated
Indicator LEDs extinguished
Test Cycle
NRS 1-40
Press button briefly.
The test mode is activated for about
10 sec. Be sure to press
button or within these 10 sec.
Note:
The safety circuit will be interrupted during
the test cycle.
12
LED “Power” illuminated
Test Cycle – continued –
NRS 1-40
Press button for 3 sec.
LED 1 flashes rapidly and remains
permanently illuminated after 3 sec.
A low-level alarm is simulated for
electrode 1.
Indicator LED 1 changes after 3 sec. from rapid
flashing to lighting
3 sec.
Press button briefly.
LED 2 flashes rapidly and remains
permanently illuminated after 3 s.
A low-level alarm is simulated for
electrode 2.
This test cycle is performed for the water-
level limiting
system (two level electrodes).
Alarm
There are four different alarm conditions:
■
Low-level alarm for
water-level limiter
(one level electrode).
■
Low-level alarm for
water-level limiting system
(two level electrodes).
Low-level alarm for water level limiter
LED 1 flashes rapidly.
LED 1 remains permanently illuminated after
the de-energizing delay.
Indicator LED 2 changes after 3 sec. from rapid
flashing to lighting
Low-level alarm for water level limiting system
LED 1 and 2 flash rapidly.
LED 1 and 2 remain permanently illuminated
after the de-energizing delay.
13
Alarm – continued –
Note
■
The switching controller does not have its own lock-out circuit.
Lock-out and manual reset facilities are to be provided externally.
■
The signal output (terminal 7, 8) is instantaneously energized
(no delay of response) in the event of an alarm.
System Malfunctions
Faulty installation and/or configuration of CAN bus components, excessive
temperatures in the devices, defective electronic component parts or electromagnetic
interferences of the supply system can result in system malfunctions.
There are four system malfunctions that might occur in the level electrode and the
switching controller.
■ Max. admissible temperature in electrode terminal box exceeded
■ No or faulty communication between controller and electrode
■ Fault in CAN bus
■ Failure of 24 V power supply unit built in switching controller NRS 1-40
The malfunction information is updated with every self-test (switching controller:
every 3 sec., level electrodes: every 10 sec.). If no faults have ocurred the malfunction
information will be deleted automatically. If faults persist the malfunction information
remains stored.
As part of the automatic self-testing routine of the switching controller, the switchingoff of the output relays every 6 hrs is checked, too. If a fault is detected the signal
output (terminals 7 and 8) will be opened and closed as a function of time.
14
Danger
The terminal strip of the NRS 1-40 is live during operation.
This presents the danger of electric shock.
Cut off power supply before fixing or removing the equipment.
System Malfunctions – continued –
Systematic Malfunction Analysis
The sources of malfunctions occurring in CAN bus systems operating with several
bus-based stations must be analysed systematically since faulty components or
incorrect settings can give rise to negative interactions with intact bus devices in the
CAN bus system. These unwanted interactions can cause error messages in fully
functional bus devices, which will make fault detection even more difficult.
We recommend the following systematic fault finding procedure:
15
System Malfunctions – continued –
Danger
The terminal strip of the NRS 1-40 is live during operation.
This presents the danger of electric shock.
Cut off power supply before fixing or removing the equipment.
System Malfunction 1
LED 1 flashes slowly.
LED 1 flashes slowly
A system malfunction in level
electrode 1 was detected.
Hold down button .
LED 1 and 2 flashes slowly
LED 1 and 2 flashes slowly
Fault
:The max. admissible temperature in the terminal box of the electrode
has been exceeded.
Remedy
Hold down button .
: Insulate electrode flange against heat radiation.
LED 2 flashes slowly
LED 2 flashes slowly.
Fault:
Remedy:
The electronic circuit board of the level electrode is defective.
Replace electronic circuit board of the level electrode 1.
The system will continue to work once
the causes of the system malfunctions
are completely eliminated.
16
System Malfunctions – continued –
System Malfunction 2
LED 2 flashes slowly.
A system malfunction in level
electrode 2 was detected.
Hold down button .
LED 1 and 2 flashes slowly.
Fault:
The max. admissible temperature in the terminal box of the electrode
has been exceeded.
Remedy:
Insulate electrode flange against thermal radiation.
Hold down button .
LED 2 flashes slowly.
LED 2 flashes slowly
LED 1 and 2 flashes slowly
LED 2 flashes slowly
Fault:
Remedy:
The electronic circuit board of the level electrode is defective.
Replace the electronic circuit board of the level electrode 2.
Press button twice for a few seconds
to acknowledge the malfunction
messages.
The system will continue to work once
the causes of the system malfunctions
are completely eliminated.
17
System Malfunctions – continued –
System Malfunction 3
LED 3 flashes slowly.
A communication malfunction in the
bus line has been detected.
Hold down button .
LED 1 flashes rapidly.
A bus communication malfunction
between level switch and level
electrode 1 has been detected.
Fault:
Remedy
The data transfer between level switch and electrode is interrupted.
: Make sure that the bus lines are wired in accordance with the wiring
diagram (observe polarity). All end-of-line devices must be provided
with a terminating resistor of 120 Ω! (see wiring diagram).
Cut off power supply and re-start the system after 5 sec.
Fault:
Remedy:
The baud rate of one or more bus devices is not set correctly.
Check baud rate settings of all bus devices. The baud rate settings
must be identical. Please refer to section “Annex”.
Cut off power supply and re-start the system after 5 sec.
LED 3 flashes slowly
LED 1 flashes rapidly
Fault:
Remedy:
Fault:
Remedy:
18
The overall length of the bus line does not correspond to the baud rate
setting.
Change baud rate settings of all bus based equipment as described under
“Annex”.
Cut off power supply and re-start the system after 5 sec.
In spite of correct wiring and commissioning of the equipment an
interference signal is indicated.
The interference signal is caused by H. F. interferences coming from the
installation. For interference suppression of the voltage supply we supply
ferrite rings, stock code 147253. The 230 V supply lines should be looped
through the ferrite ring five to ten times. If several controllers are used in
the system, they can be fed from the interference suppressed supply
lines. For the interference suppression of the bus line we supply hingedshell ferrite rings, stock code 147254. The hinged-shell ferrite rings are
clamped onto the bus line close to the terminal strip of the controller.
Restart the system after installation.
System Malfunctions – continued –
System Malfunction 3 – continued –
Hold down button .
LED 2 flashes rapidly.
A bus communication malfunction
between level switch and level
electrode 2 has been detected.
Fault:
Remedy
Fault:
Remedy:
Fault:
Remedy:
Fault:
Remedy:
The data transfer between level switch and electrode is interrupted.
: Make sure that the bus lines are wired in accordance with the wiring
diagram (observe polarity). All end-of-line devices must be provided
with a terminating resistor of 120 Ω! (see wiring diagram).
Cut off power supply and re-start the system after 5 sec.
The baud rate of one or more bus devices is not set correctly.
Check baud rate settings of all bus devices. The baud rate settings
must be identical. Please refer to section “Annex”.
Cut off power supply and re-start the system after 5 sec.
The overall length of the bus line does not correspond to the baud rate
setting.
Change baud rate settings of all bus based equipment as described under
“Annex”.
Cut off power supply and re-start the system after 5 sec.
In spite of correct wiring and commissioning of the equipment an
interference signal is indicated.
The interference signal is caused by H. F. interferences coming from the
installation. For interference suppression of the voltage supply we supply
ferrite rings, stock code 147253. The 230 V supply lines should be looped
through the ferrite ring five to ten times. If several controllers are used in
the system, they can be fed from the interference suppressed supply
lines. For the interference suppression of the bus line we supply hingedshell ferrite rings, stock code 147254. The hinged-shell ferrite rings are
clamped onto the bus line close to the terminal strip of the controller.
Restart the system after installation.
LED 2 flashes rapidly
19
System Malfunctions – continued –
System Malfunction 4
LED 4 flashes slowly.
A malfunction in the level switch has
been detected.
Fault:
The electronic circuit board of the level switch is defective (e. g. output
relay).
Remedy:
Fault:
Remedy:
Replace level switch. Restart system.
No voltage across terminal 25, self-checking routine unsuccessful.
Wire NRS 1-40 as first device in the safety chain.
Wire NRS 1-40 according to wiring diagram (ensure constant voltage
supply across terminal 25). Restart system.
Fault:
Remedy:
Voltage across terminal 26 and/or 30.
Do not connect these terminals.
System Malfunction 5
LEDs 1 to 4 flash rapidly.
A general communication
malfunction has been detected.
LED 4 flashes slowly
LEDs flash rapidly
Fault:
Remedy:
20
No communication between bus devices possible.
Check wiring, node ID, baud rate setting and bus cable.
Cut off power supply and re-start system after 5 sec.
System Malfunctions – continued –
System Malfunction 6
LED “Bus status” flashes slowly.
LED flashes slowly
Fault:
Remedy:
Fault:
Remedy:
Fault:
Remedy:
Data transfer in CAN bus interrupted.
The bus cables have to be connected correctly according to the wiring
diagram (observe polarity!).
Make sure that all end-of-line nodes are provided with 120 Ω terminating
resistors.
Cut off power supply and re-start system after 5 sec.
The baud rate of one or more nodes is not set correctly.
Check baud rate settings of all bus nodes. The baud rates must beidentical. Refer to section “Annex” for more details.
Cut off power supply and re-start system after 5 sec.
The overall length of the bus cable does not correspond to the selected
baud rate.
Change baud rate settings of all nodes according to page Annex.
Cut off power supply and re-start system after 5 sec.
21
System Malfunctions – continued –
System Malfunction 7
LED “Power” flashes slowly.
LED flashes slowly
Fault:
Remedy:
Fault:
Remedy:
The power supply unit (PSU) is overloaded. The power supply unit may be
misused for other components.
Check load of power supply unit. Be sure to use the PSU only for the
voltage supply of bus-based network components.
Cut off power supply and restart the system after 5 sec.
Power supply unit defective.
Replace power supply unit.
22
Operation Malfunctions
Danger
The terminal strip of the NRS 1-40 is live during operation.
This presents the danger of electric shock.
Cut off power supply before fixing or removing the equipment.
Fault finding list for troubleshooting
Equipment does not work – Malfunction message
Fault:
Remedy:
Water level below switchpoint LOW LEVEL – no function
Fault:
Remedy:
Water level not yet below switchpoint LOW LEVEL – Low level alarm is raised
Fault:
Remedy:
Fault:
Remedy:
In spite of correct wiring and commissioning of the equipment an
interference signal is indicated.
The interference signal is caused by H. F. interferences coming from the
installation. For interference suppression of the voltage supply we supply
ferrite rings, stock code 147253. The 230 V supply lines should be
looped through the ferrite ring five to ten times. If several controllers are
used in the system, they can be fed from the interference suppressed
supply lines. For the interference suppression of the bus line we supply
hinged-shell ferrite rings, stock code 147254. The hinged-shell ferrite
rings are clamped onto the bus line close to the terminal strip of the
controller.
Restart the system after installation.
LED “Power” does not light up.
Apply power. Connect the equipment properly, referring to wiring
diagram on page 3.
Low-level alarm is given despite the electrode being submerged.
The conductivity of the fluid to be monitored is < 0.5 µS/cm.
The electrode body does not have earth connection to the vessel.
Clean seating surfaces and insert metal joint ring
(of stainless steel 1.4301) D 27 x 32 to DIN 7603.
Do not insulate the level electrode with hemp or PTFE tape!
Fault:
Remedy:
Fault:
Remedy:
If faults occur that are not listed above or cannot be corrected, please contact our
service centre or authorized agency in your country.
The vent hole in the protection tube does not exist, is obstructed or flooded.
Check protection tube and, if necessary, provide vent hole.
The isolating valves of the external measuring pot (optional item) are
closed.
Open isolating valves.
23
Emergency Operation
Emergency operation of water-level limiting system
If one level electrode fails to operate the installation can continue to operate in
emergency mode under constant supervision according to TRD 401 with one level
electrode.
1. Undo screws and remove the lower terminal strip , Fig. 4.
2. Set code selector switches “S1”and “S2” to “
3. Set code selector switches “S1” to “
B
8
9
ON” and “S2 - S7” to “OFF”. The switching
A
OFF”, Fig. 6, Fig. 8.
controller NRS 1-40 has now the node ID “1”, Fig. 7.
4. Set node ID of the working electrode to “2” (cf. section “Emergency operation”
in the Installation Manual for level electrodes NRG 16-40, 17-40, 19-40).
5. Affix lower terminal strip .
A
Attention
■ Enter beginning of emergency operation in the boiler log.
■ An installation operating in emergency mode has to be constantly
supervised.
■ Install a visible sign or signal in the control room to indicate emergency
operation.
■ Immediately replace faulty level electrode.
■ Enter end of emergency operation in the boiler log.
Annex
Danger
The terminal strip of the NRS 1-40 is live during operation.
This presents the danger of electric shock.
Cut off power supply before fixing or removing the equipment.
Factory set default node IDs
Switching
Level electrode
controller
The individual node IDs must be manually adjusted on the equipment.
Please observe the installation instructions of the device in question.
24
Annex – continued –
Assigning/ changing node ID
If several systems of the same kind are to communicate in one CAN bus network, be
sure to assign one node ID for each individual system component (e. g. controller).
Detach terminal strips in order to change the code switch settings and .
Attention
■ Do not assign the same node ID twice within the CAN bus network.
A89
98
Fig. 5
25
Annex – continued –
88
Electrode
ON
S1
ON
S2
Fig. 6Fig. 8
ON
S1
OFFS2
OFFS3
OFFS4
OFFS5
OFFS6
OFFS7
Fig. 7 (Factory setting)Fig. 9 (Example)
S8
OFF
ON
OFF
ON
OFF1000 m
ON
Fig. 10 (Factory setting: 250 kBits/s)
S9S0
ON
ON
OFF
OFF
ON
ON
1+2
Node ID
1
2
4
8
16
32
64
OFF
OFF
ON
ON
ON
ON
1
Baud rate
250 kBit/s
125 kBit/s
100 kBit/s
50 kBit/s
20 kBit/s
50 kBit/s
S1
S1
S3
S4
Cable length
Electrode
OFF
OFFS2
Node ID
OFF
OFFS2
ON
ON
OFFS5
OFFS6
OFFS7
125 m
250 m
335 m
500 m
1000 m
1
99
12
1
2
4
8
16
32
64
26
Annex – continued –
Declaration of conformity
We hereby declare that the equipment NRS 1-40 conforms to the following
European guidelines:
■
LV guideline 73/23/eec version 93/68/eec
■
EMC guideline 89/336/eec version 93/68/eec
■
Pressure Equipment Directive
PED 97/23/eec of 29
The equipment is a safety accessory as defined in section 1, paragraph 2.1.3,
Conformity assessment procedure applied according to Annex III, Module B and D.
which are based on the following harmonised standards:
■
LV standard DIN EN 50178
■
EMC standard DIN EN 50 081-2, DIN EN 61 000-6-2
Other technical rules and regulations applied: VdTÜV Bulletin “Water Level 100”
(4/1990 and draft 8/2001).
This declaration is no longer valid if modifications are made to the equipment without
consultation with us.
Vertretungen weltweit · Agencies all over the world · Représentations dans le monde entier · Representaciones en todo el mundo · Agenzie in tutto il mondo