In the event of critical conditions, the EMS 2 may independently shut the engine off, either
with or without prior warning depending on the configuration, or may merely provide a
warning. The user must be informed of this and must be familiarised with limp-home mode.
! The following states can be recognised with the diagnostic lamp
DisplayStateIndicates
Important notes
Diagnostic lamp
illuminates for 2 s
from ignition on.
Warning
regarding exceeded limit
values and system faults.
Emergency engine
shut-off if shut-off limits
are exceeded or not
achieved.
The limp-home mode button has been
actuated in order to
bridge the reduction in
power or engine shut-off.
Bridging is stored in the
control unit.
A reduction in power is only possible in combination with
an engine governor, e.g. EMR and MVS.
The reduction in power can be temporarily bridged with
the limp-home mode button. (Depression of the
button is confirmed with slow flashing, see *).
After the engine has been shut-off, fault code enquiry is
possible (see **).
Attention: In a few seconds, the engine will be
automatically shut-off for the purpose of protection.
The reduction in power can be temporarily bridged with
the limp-home mode button. (Depression of the
button is confirmed with slow flashing, see *).
After the engine has been shut-off, fault code enquiry is
possible (see **).
Attention: Following actuation of the limp-home mode
button, the engine continues to run without protection for
a short time, and may become damaged! For this reason,
only actuate the button in the event of an emergency
(e.g. if life is otherwise placed at risk)!
** Fault code
enquiry
! The illumination of the maintenance/service lamp demands that the engine be maintained by the
DEUTZ Service department.
The EMS 2 is a monitoring system for the 1013, 1015 engine model series. It can be used on its own and
also in combination with the MVS (solenoid valve system) or the EMR (electronic engine governor).
The EMS 2 provides functions for engine protection, for indicating maintenance requirements and for
diagnostic purposes. With the aid of the data recorder function, an overview of the manner of operation,
capacity utilisation and possible causes of engine failure may be obtained. In addition, data exchange with
other electronic control units (e.g. EMR, MVS) is possible via the CAN interface.
The EMS 2 serves to electronically monitor the engine. Its functions include:
Engine protection functions
●
Warning the operator if limit values are exceeded or not achieved.
●
Reduction in engine power.
●
Emergency engine shut-off if operating data exceed or do not achieve the shut-off limits.
Indication of maintenance requirements
in order to remind the operator and to reduce the consumption of operating media. The maintenance
intervals can be obtained from the DEUTZ engine operating instructions, Chapter 5.1.
●
in the event of excessive air filter differential pressure.
●
if the number of operating hours leads to the achievement of the next maintenance requirements.
●
if the load population reaches a maintenance limit.
●
if calculation of the engine operating statuses (temperatures, speed, etc.) results in the oil change limit's
being exceeded.
Data exchange
with other systems via the CAN interface, e.g. with the solenoid valve system (MVS):
●
Transmission of the output reduction signal if limit values are exceeded.
●
Engine shut-off via the CAN interface sets, e.g. the fuel injection quantity to zero.
●
The integration of measurement data and fault messages via the CAN interface extends the input signals
of the EMS 2 for executing engine protection functions and system diagnosis (see above).
●
Transfer of the EMS 2 measurement data to other systems.
Diagnosis of the entire system
●
System self-diagnosis, i.e. of the control unit, the sensors and the actuators.
●
Display of engine operating data and self-diagnosis data on a PC (ISO9141 / RS232).
●
Forwarding of the engine operating data to the SAE-J1708/1587 interface for diagnostic and display
systems.
●
Actuation of a telltale and output of a flashing code for fault identification.
Data recorder
Determination of the manner of operation, capacity utilisation and causes of engine failure.
●
Recording the most important measurement variable signals.
●
Determination of the load population.
●
Storage of exceeded maintenance intervals.
●
Documentation of hours of engine operation.
Engine operation display
●
Output of a signal (telltale or relay) as soon as the speed exceeds 400 rpm.
1)
Not all functions are available in all applications.
The following table contains an overview of the measurement variables which can be monitored, together
with the relevant, possible engine protection functions.
Monitorable measurement variable
Possible engine protection function
WarningPower reductionEmergency engine
shut-off
Speedxx
Oil temperaturexxx
Coolant temperaturexxx
Cylinder temperature 1xxx
Cylinder temperature 2xxx
Oil pressurexxx
Coolant leveldxxx
Oil levelxxx
Reserve signal T1xxx
1
The configuration is programmed in the factory.
1
●
If the measurement variable lies within the warning range, the diagnostic lamp is continuously illuminated. As a result of a command via the CAN interface to the EMR or MVS, the power is reduced. If the
measurement variable exceeds/does not achieve the recovery threshold, the lamp is extinguished again.
●
A reduction in power is only possible in combination with EMR and MVS.
●
If the measurement lies within the shut-off range, emergency engine shut-off is carried out following
the expiry of a waiting period. The diagnostic lamp flashes rapidly (frequency approx. 1 Hz). Shut-off is
effected either
-via a shut-off solenoid or
-via the CAN interface on other electronic control units (EMR, MVS)
●
Limit values which are exceeded or not achieved are documented in the fault memory.
●
The fault message is output if the diagnostic button is actuated during engine standstill
-as a flashing code via the diagnostic lamp.
-with a notebook connected via the ISO9141 interface with the SERDIA diagnostic programme.
-via the ISO J1708/1587 interface according to standard.
●
Starting prevention can be recognised via the rapid flashing of the diagnostic lamp (1Hz) in the event of
engine standstill. If the EMS 2 has shut the engine off on the basis of the engine monitoring functions,
restarting is prevented. The same applies if monitoring is carried out during standstill, and engine starting is blocked due e.g. a low coolant level.
●
The engine can be restarted by switching the ignition off/on (terminal 15).
●
Outputs may also be used to initialise lamps or relays if limit values are exceeded or not achieved, see
Chapter entitled Outputs 5.2.
In safety-critical cases, emergency engine shut-off or output reduction can be suppressed with the
limp-home button/diagnostic button (override signal). The EMS 2 is programmed in such a manner that
the overwriting of these engine protection functions applies only for a specific period of time (limp-home
time) or until the engine is shut-off.
●
Depression of the button is confirmed via slow slashing (frequency approx. 0.5 Hz). The limp-home
time (override time) begins again each time the button is depressed. Excessively frequent actuation of
the button may damage the engine and lead to the expiry of the warranty (responsibility of the user).
●
Override procedures are stored in the control unit.
●
Following the expiry of the override time, the warning, reduction in power or the shut-off function are
reactivated insofar as the relevant conditions for this are still present.
4.2.3Speed monitoring
Speed monitoring prevents engine damage as a result of excessive speed, and is defined prior to delivery
depending on the combination (e.g. EMS with MVS) and model series. The speed signal can be supplied to
the EMS 2 control unit in three ways:
●
With a pick-up (magnetic speed sensor).
●
Via the W terminal of the alternator.
●
With data exchange via the CAN interface.
4.2.4Temperature monitoring
Depending on the engine model series, temperature sensors are available for engine oil, coolant, cylinder
head 1 and 2, and reserve temperatures. Connection to the EMS 2 is carried out in two ways:
●
Either via the inputs (see Chapter 5.1).
●
Or via the CAN interface from other systems (MVS, EMR).
In addition, each time the temperature is exceeded, an output for initialising a lamp or a relay may be allocated, see Chapter entitled Outputs 5.2.
If the temperature falls below the recovery threshold, the diagnostic lamp is shut-off, and the power reduction or emergency shut-off engine protection functions are reset.
4.2.5Engine oil pressure and reserve pressure monitoring
Oil pressure monitoring is activated following the expiry of a fixed period of time after the engine has been
started.
Depending on the application, the connection to the EMS 2 can be carried out in two ways:
●
Via the inputs (see Chapter 5.1).
●
Or via the CAN interface from other systems (MVS, EMR).
In addition, each time the temperature is exceeded, an output for initialising a lamp or a relay may be allocated, see Chapter entitled Outputs 5.2.
The warning limit is speed-dependent. In order to take pressure fluctuations into consideration, the oil pressure may fall below the warning limit for a speed-dependent period of time before the engine protection
functions respond.
Following the expiry of the waiting period, the diagnostic lamp is continuously illuminated, insofar as the
signal still lies in the warning range.
If the oil pressure exceeds the recovery threshold, the diagnostic lamp is shut-off, and the power reduction
or emergency shut-off engine protection functions are reset.
Other pressures may be monitored depending on the application and the input assignment of the control
unit.
Depending on the engine model series, sensors are available for engine oil, coolant or reserve fluid filling
levels. Connection to the EMS 2 is carried out in two ways:
●
Via the inputs (see Chapter 5.1).
●
Or via the CAN interface from other systems (MVS, EMR).
If the warning threshold is not achieved, the diagnostic lamp is continuously illuminated. If the level rises
above the recovery threshold due to the fluid's being topped up, the diagnostic lamp is shut-off.
Whilst engine is stationary
Fluid levels are monitored whilst the engine is stationary and the ignition is switched on (terminal 15). If the
level falls below the shut-off limit, starting is prevented following a period of time which is specified in the
factory. During this enquiry time, engine starting is released until starting is prevented.
During engine operation
The engine oil level is not monitored during engine operation. For the other fluid levels, monitoring during
engine operation may also be programmed in the factory.
4.3Indication of maintenance requirements
Maintenance requirements may be indicated in the following manner:
●
Via the maintenance/service lamp.
●
Via the ISO 9141 interface with SERDIA.
After maintenance has been carried out, the maintenance messages can be reset with SERDIA or by connecting the L lead of the ISO9141 interface to ground for a minimum of 5 to a maximum of 10 seconds. The
functions described in the following may report maintenance requirements, whereby each may initialise the
maintenance lamp. An enquiry regarding the functions which are reporting the maintenance requirements
can be made with the flashing code.
4.3.1With operating time counter
When the operating time counter reaches the next maintenance interval, the maintenance/service lamp is
switched on, and the operator is reminded that maintenance is due.
4.3.2With load population
This function is only possible if the EMS 2 receives a load signal, e.g. from another electronic control unit via
the CAN interface.
Maintenance is signalised with the aid of the maintenance/service lamp in accordance with the capacity utilisation of the engine throughout the engine operation period.
4.3.3With air filter differential pressure sensor
Depending on the engine model series, the engine is equipped with air filter differential pressure sensors. If
the air filter differential pressure exceeds the specified limit during engine operation, i.e. at engine speeds in
excess of 400 rpm, the maintenance/service lamp is switched on. The maintenance message is only reset if
the air filter differential pressure returns to normal.
4.3.4Oil change interval calculation
This procedure is not applied in the case of all engine model series. The oil change interval depends on the
manner in which the engine is operated. Calculation of the time of the next oil change is carried out with
characteristic engine variables such as temperatures, speed, etc. When the calculation reached the oil
change limit, the maintenance/service lamp is initialised.
The EMS 2 contains a maximum of 32 memory domains, in which a maximum of 32 measurement and calculation values (speed, temperatures, pressures, fluid levels, output signals, etc.) can be recorded. Some of
these signals, e.g. charge air pressure and charge air temperature, can also be read in from engine governor
systems via the CAN interface. In the relevant memory domains, identical measurement signals with different sampling rates can be recorded (most rapid sampling rate 5 Hz).
Depending on the spacing of the measurement points, measurement value recording of up to several thousand is possible. Either the current, maximum, minimum or the mean measurement values are recorded.
Depending on the engine model series and system expansion, values from the following table may be
recorded:
Possible measurement signals
Charge air pressure
Charge air temperature
Operating time counter
Speed
Oil temperature
Coolant temperature
Cylinder head temperature 1
Cylinder head temperature 2
Reserve temperature 1
Reserve temperature 2
Engine oil pressure
Reserve oil pressure 1
Reserve oil pressure 2
Coolant level
Engine oil leve
Fluid level 1
Fluid level 2
Fluid level 3
Load signal
Fuel injection quantity (via CAN)
Output switching statuses
Power reduction signal
Override signal
Shut-off limit exceeded
Test operation mode
The EMS 2 is programmed with a sensible data recording configuration in the factory. Changes must be
coordinated with head office, and are only possible with SERDIA.
Data recording is only carried out whilst the engine is running.
The data are read out with SERDIA, and are available in a standard format for commercially available gra-
If a load signal is transmitted from an electronic control unit via the CAN interface, the EMS 2 is able to
determine the capacity utilisation of the engine. In order to achieve this, the hours of engine operation are
allocated to the relevant load and speed ranges. Optimally-designed engines may therefore be made
available to the customer for special usages.
Load population:
S1 to S9 are operating time counters for the relevant range.
For maintenance information, the range counters are weighted with factors.
The load population can be displayed and printed out with SERDIA.
4.4.3Override memory
If limit values are exceeded, the operator can, as in the case of the engine protection functions, see 4.2,
prevent the reduction in power or emergency engine shut-off via a button for a brief period of time or until
the engine is next stationary (depending on the EMS 2 programme).
The interruption of the protective functions is stored in the control unit of the EMS 2, and cannot be deleted.
4.4.4Maintenance overdue memory
The EMS 2 stores the point in time at which maintenance was required and the reset time, i.e. when maintenance was acknowledged.
These values may also be read with SERDIA.
n
1
n
2
4.5Engine operation display
The EMS 2 may also be used for the purpose of engine operation display. As soon as the engine speed
exceeds a speed threshold of 400 rpm, a lamp is initialised. This function is not in use in all engine model
series.
The following table provides an overview of the possible outputs at the EMS 2.
No. PinGND Designationcan be connectedmeasuredEspecially suitable for
1
1A 1
1B 10, 27Pick-up
22529Limp-home and
38PWM inputPWM signal switchPulse-duty fac-
415 13Pressure mea-
51431NTC inputNTC (temperature-
63230PT100-1PT100 (temperature717PT100-2
Speed input
diagnosis
surement input
W terminalFrequencyFor speed measurement only.
Sensor to groundVoltages 0 and 5
V (digital)
tor (digital)
Voltage sensorVoltages 0 to 5 V
(analogue)
Resistors (ana-
dependent resistor)
dependent resistor)
logue)
Resistors (ana-
logue)
For error code enquiry and limphome only.
Integration of a physical variable
from another control unit (e.g. oil
pressure).
Oil pressure measurement
Coolant temperature
Oil temperature
Cylinder head temperature
816Analogue 1Voltage sensor Voltages 0 to
U
934Analogue 2
10 3312Analogue 3Voltage sensor Voltages 0 to 5 V
1
Speed input available as an option only.
An example of pin assignment (engine 1015, EMS and MVS) is shown in Chapter 11.8.
The EMS 2 control unit can be configured in the factory in such a manner that further input signals can be
read via the CAN bus.
Batt
(analogue)
(analogue)
Suitable for many signals, e.g.
air filter differential pressure,
fluid levels, etc.
Suitable for many signals, e.g.
pressures, temperatures, fluid
levels, etc.
Via configuration, a digital value (e.g. "Speed in the shut-off range") may be allocated as a parameter to
each digital output (with the exception of the diagnostic lamp output).
Parameters can be used to set whether the output is switched on or off on the occurrence of the condition.
If outputs 3 and 4 are configured as PWM outputs (PWM = pulse-width modulation), analogue measure-
ment values, which enter the control unit via CAN or the inputs, and internal EMS 2 variables, can be output.
A measurement value (e.g. "Speed") may be allocated to each PWM output via configuration.
The output frequency of the PWM signal can be parameterised in the range from 85 Hz to 500 Hz, whilst the
pulse-width, i.e. the high or low time, changes in the same manner as the variable which is adjusted via a
characteristic curve.
In the event of a fault, a cable break or a short-circuit can be diagnosed for all outputs.
The following Table provides an overview of the possible outputs at the EMS 2.
Nr. Pin DesignationCan e.g. be used for
121Digital 3Oil pressure telltale
222Digital 4Shut-off solenoid relay initialisation
33Digital / PWM1Coolant temperature telltale
44Digital / PWM2Air filter differential pressure telltale
55Maintenance/service lamp Maintenance/service lamp
623Diagnostic lampDiagnostic lamp only
This output actuates a diagnostic lamp for displaying fault codes, e.g. continuous illumination, slow flashing
or rapid flashing to ground.
When the ignition is switched on, the lamp illuminates for approx. 2 s for a lamp test.
Continuous illumination indicates a warning, i.e. either a measurement variable is in the warning range or
a system component reports faulty behaviour such as, e.g. sensor cable break or short-circuit (see Fault
messages).
Rapid flashing indicates imminent or current engine protection shut-off.
If the operator interrupts one of the engine protection functions, such as a reduction in power or imminent
engine shut-off, by pressing the limp-home button whilst the engine is running, this is acknowledged with
slow flashing.
If the limp-home button/diagnostic button is actuated whilst the engine is stationary, flashing codes are
output for the fault messages.
The ISO interface is a serial data interface which is standardised according to ISO 9141, and which enables
the exchange of data with the control unit. The ISO interface has the following functions:
●
Diagnosis with SERDIA.
●
Exchange of diagnostic data.
●
Control unit end-of-tape programming (reading and programming of parameters).
●
Execution of engine test functions.
●
Reading of measured and calculated variables.
●
Reading the data recorder out.
6.2CAN interface
The CAN interface is a rapid serial data bus which is standardised according to SAE J1939, and which enables the exchange of data between several control units (e.g. EMR, MVS, transmission electronics, traction
control). The CAN interface has the following functions:
●
Exchange of diagnostic data (error messages, deletion of error memory).
●
Reading of measured and calculated variables.
●
Suppression of fuel injection.
●
Reduction of output.
6.3SAE-J1708/1587 interface
●
Output of all data received via the inputs or via the CAN interfaces.
●
Output of the fault memory.
●
Deletion of all fault messages.
Note:
☞
In the event of communication via the ISO9141 interface, the SAE-J1587 interface is shut-off!
Self-diagnosis becomes active when a minimum supply voltage (> 9 V) is exceeded.
In this case, both internal control unit faults are determined and the inputs and outputs and the sensors and
output loads are checked for cable break and short-circuit. The fault must be present for a minimum period
of time before it is stored. Continuous diagnostic lamp illumination indicates that a fault is currently present.
A maximum of 15 faults are stored simultaneously. The individual faults which this involves can be seen
from the fault message Table.
The fault messages are displayed as flashing codes as described in Section 7.2, and via the interfaces to
PCs and diagnostic units as described in Chapter 8.2.
7.2Diagnosis with flashing codes
The diagnostic lamp informs the operator of the presence of a fault or exceeded limit values, as described
in the case of the engine protection functions in Chapter 4.2, with continuous illumination.
When the engine is stationary, each depression of the diagnostic/override button leads to the output of a
flashing code which indicates which fault or signal has exceeded the limit value.
Each time the button is pressed, the next fault is displayed. Following the last fault, the first fault message is
output again.
The flashing code is comprised of long and short flashing pulses which the operator counts.
The appropriate fault can be seen in the fault message Table (Chapter 8.4).
7.3Diagnosis with SERDIA software
Together with the interface and notebook (or PC), SERDIA (Service Diagnosis software) forms a combined
special service tool. With the aid of the SERDIA diagnostic software, information regarding the following
can be displayed:
- Fault memory
- Configuration (authorisation is determined via the interface level)
- Measurement values
- Maintenance data
- Load population.
Fault messages for passive or eradicated faults can be deleted with SERDIA.
SERDIA (Service Diagnosis) is a software programme which the operator can use, via the PC, to monitor
measurement values and detect faulty operating behaviour whilst the diesel engine is running.
In order to achieve this, the PC is connected to the diagnostic interface via an interface. Communication
with the control unit is carried out via a special EMS 2 protocol.
With regard to handling SERDIA, see separate manual. The acquisition of SERDIA is explained via a DEUTZ
The EMS 2 is able to communicate with other electronic engine regulation systems via the CAN interface.
Such an application includes the MVS (solenoid valve system). This transmits the fault messages to the
EMS 2, and the diagnostic lamp is continuously illuminated. The messages can then be output via only one
lamp as a flashing code. The nature of the flashing code indicates the system in which a fault is present (see
code Table, Chapter 8.4). The operator is only required to heed one lamp, wiring expenditure is reduced.
The faults and measurement values from other control units (e.g. MVS), which are read by EMS 2 via the
CAN bus, are also output via the ISO9141 interface to a notebook with the SERDIA diagnostic programme.
8.2Output of messages on a notebook or diagnostic systems
The EMS 2 stores the fault messages and transits these as a fault code via the ISO9141 interface. The
codes are listed in the fault message Table (Chapter 8.4).
The fault messages can be read with the SERDIA diagnostic software and a notebook. In addition, measurement values which existed at the point in time at which the fault occurred are displayed on the screen for
each fault.
Instead of using the ISO9141 interface for fault messages, the user may also use the SAE-J1708/1587
interface of the EMS 2 for outputting the faults on diagnostic systems.
8.3Deletion of fault messages
Insofar as the faults no longer occur, the fault messages are automatically deleted after the ignition key has
been actuated a number of times. If the fault messages are to be deleted directly following a repair operation, the ignition is actuated a corresponding number of times in succession, whereby waiting must be carried out each time during the lamp test time (approx. 3 seconds).
The fault messages can also be deleted with the SERDIA diagnostic programme and a notebook via the
ISO9141 interface or also with also diagnostic systems according to the SAE-J1708/1587 standard.
The following table contains an overview of the possible fault messages and codes.
Notes in the event of diagnosis with telltale:
Depending on the flashing code, the telltale provides a sequence of short and long flashing impulses.
Example: Flashing code S1 L1 S2: one short flash, one long, two short
Note in the event of diagnosis with SERDIA:
The programme displays the location of the fault, the type of fault and the frequency of the fault on the
screen.
Example:
●
Location of the fault: Oil pressure input
●
Type of fault: Cable break or short-circuit to U
Batt
Location of the faultType of faultFlashing code
S-short
L-long
Zero fault informationS1dispen-
SAE
J1587
FMI
PID/SID
SAE-J1587
xxx
sed
with
Speed pick-up input Cable breakS1 L1 S15xxx
Oil pressure inputShort-circuit to GND
Cable break or short-circuit to U
NTC inputShort-circuit to GND
Cable break or short-circuit to U
PT100-1 inputShort-circuit to GND
Cable break or short-circuit to U
PT100-2 inputShort-circuit to GND
Cable break or short-circuit to U
Analogue input 1Short-circuit to GND
Cable break or short-circuit to U
Analogue input 2Short-circuit to GND
Cable break or short-circuit to U
S1 L1 S24
Batt
S1 L1 S34
Batt
S1 L1 S44
Batt
S1 L1 S54
Batt
S1 L1 S64
Batt
S1 L1 S74
Batt
xxx
3
xxx
3
xxx
3
xxx
3
xxx
3
xxx
3
1
Analogue input 3Short-circuit to GND
Cable break or short-circuit to U
S1 L1 S84
Batt
3
xxx
CAN connectionS1 L2 S112SID 231
Override/diagnostic button faultS1 L2 S2-Digital output 3Cable break or short-circuit to GND
Short-circuit to U
Batt
S1 L2 S34
SID 26
3
Digital output 4Cable break or short-circuit to GND
Short-circuit to U
Batt
S1 L2 S44
SID 40
3
Digital / PWM output 1Cable break or short-circuit to GND
L-long
Engine protection shut-off
executed
Start prevention executedS1 L5 S2-Reduction in power override
executed
Engine shut-off override
executed
Control unit EEPROM
memory fault
Control unit RAM or
RAM buffering defective
Bosch control unit CAN fault
codes
Maintenance interval reached
(operating hours)
All components can only be replaced (repair is not possible) and are available individually. As the control
unit has to be programmed with an engine-specific data record, the following specifications are necessary:
●
Engine number.
●
Complete part number.
Please contact your DEUTZ service partner.
Attention:
In order to avoid damaging the control units, the plug connections on the control unit must be disconnected
prior to electric welding operations!
Depending on the design of the configuration, the wiring to be carried out by the customer can be seen
in the engine-specific wiring diagram, which is delivered together with the engine.
●
With regard to the mechanical installation of the control unit, reference is made to the installation guidelines regarding the installation of electronic systems in DEUTZ diesel engines, order No. 0399 1990/1.
Further information can be obtained from
DEUTZ AG
Installation Consultancy Department
Tel.: (0221) 822 3140
Fax.: (0221) 822 3198
Sensors and actuators must not, either for checking or test purposes, be individually connected to or between external voltage sources, but only in combination with the EMS 2, as the risk of destruction otherwise
exists!
Despite polarity reversal protection in the control units, polarity reversal must be avoided. Polarity reversal
may lead to damage to the control units!
The control unit plug connections are only dust and water-tight when the counter-plugs are connected!
Until the counter-plugs are connected, the control units must be protected against spray water and electrical discharge at the contacts due to touching!
Attention:
Sensors and actuators must not, either for checking or test purposes, be individually connected to or between external voltage sources, but only in combination with the EMS 2, as the risk of destruction otherwise
exists!
Despite polarity reversal protection in the control units, polarity reversal must be avoided. Polarity reversal
may lead to damage to the control units!
The control unit plug connections are only dust and water-tight when the counter-plugs are connected!
Until the counter-plugs are connected, the control units must be protected against spray water and electrical discharge at the contacts due to touching!
The following tables contain an overview of the technical data of the EMS 2.
11.1.1Input table
No. PinGND DesignationRange
1A 1Speed input0/U
1B 10, 27
22529Limp-home and diagnosisButton only (0/U
38PWM input0 to U
41513Pressure measurement input 0 to 5 V (analog)
51431NTC input0° C to 130° C
63230PT100-10° C to 300° C
717PT100-20° C to 300° C
816Analogue 10 to U
934Analogue 20 to U
10 3312Analogue 30 to 5 V (analogue)
Batt
Batt
Batt
Batt
Technical data
Batt
(digital)
(analogue)
(analogue)
)
11.1.2Outputs table
1
No. PinDesignationmax. current load
121Digital 33 A
222Digital 43 A
33Digital / PWM10.5 A
44Digital / PWM20.5 A
55Maintenance/Service
0.5 A
lamp
623Diagnostic lamp0.5 A
11.2Electrical specifications
Nominal voltages:12 V and 24 V,
each unit functions with both nominal voltages
Operating voltage range:U
Polarity reversal protection:The unit is protected against battery voltage polarity reversal.
Overvoltage protection:The unit is equipped with load-dump protection against 65 V for
Short-circuit strength:All of the unit's connections are short-circuit-proof in the case of
Off-ground nature:The housing is off-ground.
Stray power emission:Via air convection.
Terminal 30 load:< 10 mA with terminal 15 shut-off
EN 61000-4-4
EN 61000-4-2
ISO 7637-2
ISO 7637-3
ISO 11452-2100 kHz - 1 GHz100 V/m
57 MHz - 61 MHz50 V/m Class B, else Class A
ISO TR 10605
11.4Climatic conditions
Operating temperature:-40 °C to 80 °C
Storage temperature:-55 °C to 80 °C not temporally restricted
Temperature change:IEC 68-2-14
Humidity:
relative humidity:up to 95%
maximum temperature:+55 °C
Salt spray resistance:The system is resistant to salt spray in accordance with
IEC 68-2-52.
Salt content (NaCl):max. (5±1) % percentage per mass
Low air pressure:The unit is resistant to vacuum.
Transportation and storage:max. 150 mbar ±1%
Operation:max. 533 mbar ±5%
Industrial climate:according to DIN 50018, 6 cycles
11.5Contamination
The unit is resistant to being coated with the following media:
Free fall:The unit must survive a free fall from a height of 1 m onto concrete or
steel in each of the three main axes without damage. Falling onto the
plug side is not taken into consideration
Vibration:
For any of the main axes, the following maximum values apply:
Amplitude:0,35 mm
Frequency:10 Hz to 60 Hz.
Acceleration amplitude:50 m/s
Frequency:60 Hz to 500 Hz.
Shock resistance:According to IEC-68-2-27
Peak acceleration:294 m/s