Carrier 48KHA User Manual

0 (0)
H
Carrier Corporation • Syracuse. N Y 13221
Note to Installer: After installation, leave these instructions, Owner’s Manual and Parts Replacement Guide with equipment owner.
Packaged Heating/Cooling Units
CONTENTS
SAFETY CONSIDERATIONS
INSTALLATION.................................................
Step 1 — Rig and Place Unit
...........................
...........................
• ROOFTOP INSTALLATION
• GROUND LEVEL INSTALLATION
• CLEARANCES
• CONDENSATE DISPOSAL
• VENTING
Step 2 — Make Gas Piping Connections Step 3 — Make Duct Connections
Step 4 — Make Wiring Connections ...
..................
• HIGH-VOLTAGE CONNECTIONS
• SPECIAL PROCEDURES FOR 208-V OPERATION
• LOW-VOLTAGE CONNECTIONS
• HEAT ANTICIPATOR SETTING
START-UP
SERVICE............................................................
TROUBLESHOOTING CHARTS
.........................................................
......................
Page
. 1
. 1,2
. 2-9
. 2
5
6
7
9-18 18-21 22,23
Use care in handling, rigging and setting bulky equipment.
Observe precautions in these instructions and on equipment tags, stickers and labels.
SAFETY CONSIDERATIONS
NOTE: Installation of this unit must conform to the guidelines presented in these Installation Instruc tions. Read and beeome familiar with this publica tion before starting installation.
Only trained, qualified installers and service mechanics should install, start-up and service this equipment. Consult the Owner’s Manual for routine maintenance. All other operations should be per formed by trained service personnel.
• Follow all safety codes.
• Wear safety glasses and work gloves.
© Carrier Corporation 1984
Fig. 1 — Model 48KHA.KLA
GENERAL
Models 48KHA,KLA packaged gas/ electric units
(Fig. 1) are design certified in accordance with
ANSI Z21.47-1983, ARI Standard 210-81 and ARl Standard 270-84. The units are design certified by the American Gas Association (AGA) for use with natural or propane gases with appropriate eontrols and orifices. See Table 1 for heating input ratings.
Models 48KHA,KLA units are fully self-contained, combination gas-heating/electric-cooling units designed for outdoor installation on either a rooftop or ground-level slab.
These units are equipped with an energy-saving automatic, intermittent, electric spark ignition system that does not have a continuously burning pilot. All units are manufactured with natural gas controls.
Form 48KH,KL-9SI
Table 1 — Perferjpiance Data
MODEL 48-
KLA118310BE KLA124310BE 23,800
KHA024310BF KLA130310BE
KHA030310BF KLA136310BE
KLA036510CE
KLA036610CE KHA136310BE КНА036510СЕ KHA036310BF KHA036510CF
KLA142310BE KLA042510CE KHA042310BF KHA042510CF 42,000
KLA148310BE KLA048510CE
KLA048610CE 49,000 80,000 KHA048310BF KHA048510CF
KLA160310BE KHA060310BF
*Rated in accordance with U S Government DOE test procedures and/or
ARI Standard 210-81
tSound rating per ARI 270-84
^The capacity ratings of single-phase units are in accordance with U S
Government DOE test procedures and/or AGA certification require ments For 3-phase units, the efficiency rating is a product thermal efficiency rating determined under continuous operating conditions, independent of any installed system
COOLING
CAPACITY
(Btuh)*
17,800
24,000 29,600 40,000
29,600 36,000
36,000 36,000 60,000 36,000 100,000 36,000 36,000 36,000
42,000 42,000 42,000
49,000 49,000
49,000 125,000 97,000 49,000 125,000
60,000 100,0001: 60,000 1 50,0001
RATED
HEATING
INPUT (Btuh)
40,000 40,000
75,000 58,000
75,000 58,000 60,000
60,000 45,000
100,000 125,000 97,000 1 25,000
60,000 47,000 78
60,000 45,000 125,000 97,000 125,000
80,000 80,000 60,000
OUTPUT
CAPACITY
(Btuh)
32,000 32,000
32,000
47,000
45,000 79,000 75,000 80
93,750
93,750 63,000
60,000
93,750
79,000$
11 6,0001
ARIt SOUND RATING
(Bels)
7.8
7 8
8.0
7 8
7.8
8 0
80
8 0
80
80
8.0
7 8 7 8
7.8 8 4t
8 41 8 41 8 41
8.41
8 41 8 41
handle an airflow of350 to 450 cfm per each 12,000
Btuh of rated coaling capacity. See Table 8 for cool
ing and heating airflow requirements. NOTE: When installing any accessory item, see
Installation Instructions packaged with accessory.
Units with number 1 in the 4th digit location of model number in Table 1 meet California oxides of nitrogen (NOx) maximum emission requirements.
Units are factory charged with R-22 refrigerant. To install; connect gas supply, air ducts, high- and low-voltage wiring and condensate drain, and install
a field-supplied air filter in the return-air ductwork.
All units can be connected into existing duct
systems that are properly sized and designed to
SPREADER BARS:
(2)2x4"xUNIT LENGTH PLUS lO" WITH
DEEP 90° NOTCHES EA(iH END
(2) ¿iiAxUNIT WIDTH WITH 1^
DEEP 90° NOTCHES
EACH END
LOCATE CHAINS THROUGH HOLES IN BASE CHANNELS

2 — 48KHA.KLA Suggested Rigging

TWO OR THREE BASE CHANNELS ATTACHED TO BOTTOM OF UNIT
SPREADER BARS
CHAIN

Step 1

INSTALLATION
Rig and Place Unit
ROOFTOP INSTALLATION
If installation requires draining the condensate water away from unit, connect a drain tube using a minimum of 7/8-in. OD copper tubing, 3/4-in. galvanized pipe or 7/8-in. plastic pipe.
undersize the tube. Pitch drain tube downward at a
Do not
slope at least one in. for every 10 ft of horizontal run. Be sure to check drain tube for leaks.
When installing a Model 48KHA,KLA end dis charge unit with a field-supplied downflow plenum, a field-supplied roof-mounting curb must be in stalled on and flashed into roof before unit installa tion. When installing a Model 48KHA,KLA end discharge unit without a downflow plenum, place
Condensate water can be drained directly onto roof in rooftop installations (where permitted) or onto a gravel apron in ground level installations. When using a gravel apron, make sure it slopes away from the unit.
unit on a level base that provides proper support. On flat roofs be sure unit is located at least 4 in.
TO DRAIN
above highest expected water level on roof to prevent flooding. Consult local codes for additional installation requirements.
GROUND LEVEL INSTALLATION — Place unit on a solid, level concrete pad that is a minimum of 4 in. thick and that extends approximately 2 in. beyond casing on all sides of unit. Do not secure unit to pad except when required by local codes.
CLEARANCES — Required minimum operating and service clearances are shown in Fig. 4 for pro viding adequate combustion, ventilation and con denser air.
VENTING — The vent cap, combustion air shroud and flue assembly are shipped in either the blower or
control compartment. Vent screen is taped to blower
housing. Remove access doors to locate assemblies. See Fig. 4 for door locations.
Condenser fan discharges through top of unit.
Ensure that fan discharge does not recirculate to condenser coil. Do not locate unit in either a corner or under a complete overhead obstruction. Mini mum clearance under a partial overhang (such as a typical house roof overhang) is 3 ft above vent cap.
Maximum horizontal extension of a partial over hang must not exceed 4 feet.
Do not locate unit where water, falling ice or snow from an overhang or roof will damage or flood the unit. Do not locate unit where grass, shrubs or other plants will interfere with the airflow either into or
out of unit. Do not install unit on carpeting, tile or other combustible material other than wood flooring.
CONDENSATE DISPOSAL NOTE: Be sure condensate water disposal methods
comply with local codes, restrictions and practices.
Models 48KHA,KLA dispose of condensate water through a 3/4-in. MPT drain fitting. See Fig. 4 for location.
Install a 3-in. trap at the drain fitting to ensure proper drainage. See Fig. 3. Make sure trap outlet is at least 2 in. lower than unit drain pan connection to prevent pan from overflowing. Prime trap with water.
NOTE: Screw holes in flue assembly and unit top are positioned to ensure proper orientation when installed. Refer to Fig. 5 and install vent cap as
follows;
1. Place combustion air shroud over combustion air opening in unit top, and line up screw holes in shroud with holes in top. Secure shroud to top, using screws with rubber washers (provided).
2. The flue gasket is shipped in the literature as sembly envelope. Place gasket and flue assembly through hole in combustion air shroud, orient screw holes in base of flue assembly with holes in unit top, and secure gasket and flue assembly to unit top, using screws provided.
3. Form flat wire screen (provided) into circular shape around protruding lip of combustion-air shroud and bend wire ends through holes of screen mesh to secure screen in place. Make sure that no sharp edges are left exposed.
4. Place vent cap sleeve inside flue assembly. Orient spring clip of vent cap with slot in assembly. Be sure clip snaps into slot to secure clip onto assembly.
# MPT
PLUGGED ACCESS HOLE ” FOR REFRIGERANT j!lH PRESSURE GAGE HOSES
drain conn
*NOTON MODELS48KLAII8 THROUGH
136¡ KHA024 THROUGH 030.
CONTROLS ACCESS DOOR
BLOWER ACCESS DOOR
* LOW VOLTAGE
INLET
K HIGH VOLTAGE­INLET
C> EVAPORATOR AIRFLOW ¿CONDENSER AIRFLOW
■VENT CAP
COMBUSTION AIR INLET BOX
V ^4
NOT ON MODELS
48KLAII8 THROUGH 136;
FPT GAS INLET
KHA024 THROUGH 030
MODEL 48-
KLA118 KLA124
KHA024 KLA130 КНАОЗО KLA136 KLA036
КНА136 кнАОзе KLA142 KLA042 КНА042
Dimensions
(ft-in.)
A
B
4- 5%
2- 6% 3- 4% 3- 8% C 3- 2Vb 3- 5Ув D
E 1- 4
1- 4 1-7
4- 5% 5- 5%
3-10У8 4- 6У8
2- 0 2-8
1-4 1- 1У4
F 0- 7У4 0- 8Уе 0- 8Ув
G
H 1- ЗУ4 1- ЗУ4 1- 8У4 1- 8У4
J
K
L
M
0-11%
0- 1Уз2
0- 1У8
0- 4 Мб N 1-10
MODEL
48-
KLA118 KLA124 83 КНА024 KLA130 КНАОЗО KLA136 KLA036 КНА136 КНА036 KLA142 KLA042^ КНА042 KLA148 KLA048 КНА048 KLA160 КНА060
CORNER WT (Ib)
A В
82 79
81 79
96
94
97
93 90 92 372
97
93 91 94 98 97 92 98 97 92
122
120 116 117 475
122
120 116 117 475 108 105 102 108
105 102 105 420 113 111 107 130
135 130
135 137 134
139
144
148 155 151
0-10% 0-10%
0- 1У8 0- 1% 0- 1У8 0- 6 Мб
2-4 2- 4
С D
'“'ТР
79
82 94
91
93 93 380
105 109 440
137
133 535 133
144
138 144
139 148
151
1-10'Уз2
1- 4 1-5
0- 8Мб 0- 8Уб
TOTAL
OPERATING
WT (lb)
320 325 375
375 380
420
535 555 575 605 615
KLA148
KLA048 КНА048 KLA160 КНА060
6- 0% 3- 8%
1- 1У4
0- 8Уе 0-1 1У8
2- ОзУз2
0- 1%
2-4

Weight Data

TOTAL
SHIPPING
WT (lb)
330 335 385 382 385 390 390 485 485 430 430 450 545 545 565 585
VIEW AA
CLEARANCES (ft-in.)
Above flue vent .. ................................... 3-0
Duct side of unit
.............................
.
................
0-6
Side opposite ducts...................................................... 2-6
Blower access panel side ... ...
..............
2-6
Side opposite blower access panel............................................... 2-6
Bottom of unit
......................
.................... .. .. ....0
NOTE: Provision must be made for fresh ambient air to reach the outdoor coil without recirculation of the air from the outdoor fan discharge
L

Fig. 4 — Dimensions and Clearances (ft-in.)

4

Step 2 — Make Gas Piping Connections — A

manual shutoff valve is shipped loose in the burner compartment or blower compartment. Connect one end of a field-supplied 1/2-in. straight nipple to the gas valve inlet. Connect the other end of the nipple to the manual shutoff valve as shown in Fig. 6. The gas supply pipe enters unit through access hole pro vided. See Fig. 4 for location. The gas connection to unit is made to the 1/2-in. FPT gas inlet on manual shutoff. See Fig. 6 for inlet location.
Install a separate gas supply line that runs directly
from meter to heating section. Do not use cast-iron
pipe. Check local utility for recommendations con
cerning existing lines. Choose a supply pipe that is large enough to keep pressure loss as low as prac tical. Never use pipe smaller than the 112-in. FPT
gas inlet on unit manual shutoff.
When installing gas supply line, observe local codes pertaining to gas pipe installations. Refer to National Fuel Gas Code, NFPA 54-1980/ANSI Z223.1-1980 in absence of local building codes. Adhere to following pertinent recommendations:
1
Control Transformer 9
2
Compressor Contactor 10
3
Ground Lug
4
Dual Run Capacitor 11 (for compressor and 12 condenser fan motor) 13
5
Gas Valve
6
1/2-in Nipple 14
7
Gas Pipe Entrance Hole 15 Gas Inlet 16 Pressure Tap 17
Manual Shutoff Regulator, Adjustment Cover Screw Electronic Control Head Secondary-Air Shield Low-Voltage Pigtail Leads Blower Motor Run Capacitor Heating Relay Cooling Relay Combustion Air Shroud
Fig. 6 — Model 48KLA036 — Side View
(Partial) with Access Doors Removed
1. Avoid low spots in long runs of pipe. Grade all pipe I /4 in. in every 15 ft to prevent traps. Grade all horizontal runs downward to risers. Use risers to connect to heating section and to meter.
2. Protect all segments of piping system against physical and thermal damage. Support all piping with appropriate hangers, etc. Use a minimum of one hanger in every 6 feet. For pipe sizes larger than 1 / 2 in., follow recommendations of national
codes.
3. Apply joint compound (pipe dope) sparingly and only to male threads of joint when making pipe connections. Use only pipe dope that is resistant to action of liquefied petroleum gases as speci fied by local and/or national codes. Never use
pipe thread tape.
4. Install a sediment trap in riser leading to the heat ing section. See Fig. 7. This drip leg functions as a trap for dirt and condensate. Install trap where condensate cannot freeze. Install this sediment trap by connecting a piping tee to riser leading to heating section, so that straight-through section of tee is vertical. Then, connect capped nipple
into lower end of tee. Extend capped nipple below level of gas controls.
Fig. 7 — Sediment Trap
Step 3 — Make Duct Connections — Model
48KHA,KLA has duct flanges on the supply-and return-air openings on side of unit. See Fig. 4 for connection sizes and locations.
5. Install an accessible, external, manual shutoff valve in gas supply pipe within 6 ft of heating section.
NOTE: The unit manual shutoff valve has a
1/8-in. tapping on the inlet side of this shutoff
for measuring gas input pressure.
6. Install ground-joint union close to heating sec
tion between unit manual shutoff and external
manual main shutoff valve.
7. Pressure-test all gas piping in accordance with local and national plumbing and gas codes before eonnecting piping to unit.
NOTE: When pressure-testing the gas supply system after the gas supply piping has been con nected to the unit gas valve, the supply piping must be disconnected from the gas valve during any pressure testing of the piping systems at test pressure in excess of 0.5 in. psig. When pressure testing the gas supply piping system at test pres sures equal to or less than 0.5 in. psig, the unit heating section must be isolated from the gas piping system by closing the external main manual shutoff valve and slightly opening
ground-joint union.
8. Where permitted by local codes, use an approved corrugated metal tubing gas connector between rigid gas piping and unit manual shutoff.
9. Check for gas leaks at all field-installed and factory-installed gas lines after all piping connec tions have been completed. Use soap-and-water solution (or method specified by local codes and/ or regulations).
Adhere to the following requirements when se
lecting, sizing and installing duct system:
1. Select and size ductwork, supply-air registers and return-air grilles according to ASHRAE recom mendations and as presented in Carrier System
Design Manual, Part 2.
2. Use a flexible transition between rigid ductwork and unit to prevent transmission of vibration. The transition may be screwed or bolted to duct flanges. Use suitable gaskets to ensure a weather­tight and airtight seal.
Table 2 — Filter Sizes (Field Supplied),
(Sq In.)*
STANDARD
MODEL 48-
KLA118310BE
KHA024310BF
KLA124310BE
KHA030310BF
KLA130310BE
KHA036310BF KHA036510CE
KHA036510CF KHA136310BE KLA036510CE KLA036610CE KLA136310BE
KHA042310BF
KHA042510CF KLA042510CE KLA142310BE
KHA048310BF
KHA048510CF 768 KLA048510CE KLA048610CE KLA148310BE 768
KHA060310BF KLA160310BE
*Required air filter areas shown are based on the ARI-rated cooling
airflow or the heating airflow at a velocity of 300 fpm depending on whichever value is larger Air filter pressure drop should not exceed 0 08 in wg
DISPOSABLE
TYPE
302 202 454 384 257
480 320 480 320
694 462 576 384 694 462 . 576 384 > 576 384 576 384 576 384
694 462 694 672 448 672 448
768 768 512
768 512
960 640 960
CLEANABLE OR HIGH CAPACITY
TYPE
303
462
512 512
512
640
L
3. Install external, field-supplied air filter(s) in return-air ductwork where it is easily accessible
for service. Recommended filter sizes are shown in Table 2.
4. Size all ductwork for maximum required airflow (either heating or cooling) for unit beinginstalled. Avoid abrupt duct size increases or decreases.
5. Adequately insulate and weatherproof all duct work located outdoors. Insulate ducts passing through an unconditioned space, and use a vapor barrier in accordance with the latest issue of SMACNA and NESCA minimum installation standards for heating and air conditioning systems. Secure all ducts to building structure.
6. Flash, weatherproof and vibration-isolate all openings in building structure in accordance with local codes and good building practices.
Step 4 — Make Wiring Connections
4. When low-voltage control wires are run in same conduit as high-voltage wires, insulate low­voltage wires for highest voltage contained within conduit.
5. Do not damage internal components when drill ing through any panel to mount electrical hardware, conduit, etc.
HIGH-VOLTAGE CONNECTIONS — Unit must have a separate electrical service with a field­supplied, waterproof, fused disconnect switch per
NEC mounted near, and within sight from, the unit.
Refer to unit rating plate for maximum fuse size and
minimum circuit amps (ampacity) for wire sizing. Table 3 shows recommended wire sizes and lengths based on rating plate data.
The field-supplied disconnect switch box may be
mounted on unit over the high-voltage inlet hole in control corner panel. See Fig. 4.
1. Make all electrical connections in accordance with National Electrical Code ANSI/NFPA 70-
1984 and local electrical codes governing such
wiring.
2. Use only copper conductor for connections between the field-supplied electrical disconnect switch and the unit. Do not use aluminum or
copper-clad aluminum wire.
3. Ensure that high-voltage power to unit is within
operating voltage range indicated on unit rating plate. On 3-phase units, ensure that phases are
balanced within 2%. Consult local power company for correction of improper voltage and/or phase balance.
Proceed as follows to complete the high-voltage
connections to unit:
1. Connect ground lead to chassis ground connec tion when using a separate ground wire.
2. Run high-voltage leads into unit control box and connect to contactor. See unit wiring label and Fig. 6 and 8.
NOTE: On 3-phase units, connect third high-voltage
lead to brown high-voltage pigtail lead. See unit wiring label and Fig. 8.
SPECIAL PROCEDURES FOR 208-V OPERATION
For operation on 208 volts, disconnect orange
transformer-primary lead from contactor. See unit wiring label and Fig. 6. Remove tape and cover from
terminal on end of red transformer-primary lead. Save cover. Connect red lead to contactor terminal from which orange lead was disconnected.
#
Table 3 — Electrical Data (60 Hz)
MODEL
48-
KLA118 KLA124 KHA024 KLA130 KHA030 KLA136 KLA036 KLA036 KHA136
KHA036 KHA036 KLA142 KLA042 KHA042 KHA042
KLA148 KLA048 KLA048
KHA048
KHA048
KLA1 60
KHA060
AWG — American Wire Gage
FLA — Full Load Amps IFM — Indoor Fan Motor LRA “ Locked Rotor Amps MCA — Maximum Circuit Ampacity OFM — Outdoor Fan Motor RLA — Rated Load Amps
SERIES
310BE 208/230-1 310BE 208/230-1 310BF 310BE 310BF 310BE 208/230-1 510CE 610CE 460-3 310BE
310BF
510CE.CF
310BE 510CE 310BF 51 DCF 208/230-3 310BE 510CE 610CE 460-3
310BF 208/230-1 510CF 310BE
310BF
VOLTS­PHASE
208/230-1 208/230-1 208/230-1
208/230-3
208/230-1 208/230-3
208/230-1 208/230-3 208/230-1
208/230-1 208/230-3 187
208/230-3
230-1 230-1
OPERATING
VOLTAGE*
Max
Min 197 197 197 197 197 197 187 253 414 506
197 187 253
197 187 197 187 197
414 197 253 187 253 207 253 207 253
253 253 253 253 253 253
253
253 253 253
253 253 253 506
COMPR FLA
RLA LRA
8 7 11 7 63 0 1 7 11 7 63 0 13 7 76.0
13.7 76 0 17 6 88 0 4 6 11 5 65 1
5 1 32 8
17 6 88 0 3 8
11.5 65.1 5.6
23.9 95.4 4.1
15 3
23.9 95.4
15.3 82.0 5.0 1.0 25.2
23.7 116.0 4.5 1.9 36.1
14 7 92 0 7 8 2 2
70 23 7
14 7 27 8 130 0 6 2 27 8 130 0
‘Voltage limits between which the unit will operate satisfactorily flf other than 75 C copper wire is used, determine size from unit ampacity and the National
Electrical code Voltage drop of wire must be less than 2% of unit rated voltage Maximum
wire length is for one way along the wiie path from unit to service panel
^Maximum dual element size
IFM
49 0 1 2
3 0 1 0 18 7
3.1 1.0 21.2
2.9 1.0
4 7
1 9 0 6 8 9
82.0 5.6 1.0
3.9 0.8 34.6
46 0
3 3 1 2
116.0 3.7 5 8
92 0
6 5
MCAt
OFM
1 0 13 1 10 9 20 14 1 0 17 4 14 4 25 12
21.0 17.6 30 1 0 27 6 1 0 20 1 17 2 25
08 26 6
1.0 21.0
0.8 34.8
25.8 21.9 35 10
28 4 24 7 35 13 3 11 5 20 14
1.9
35.3 29.3 50 8 111
2.2 26.4
42 9
1 9
1.9
43 2 36 2 60 8 99
MAX
AMPS
15 7 25 12
17.8 30
23 2 40
22 2 40 10
18.1 25 10
28.8 50 8
28.6 50 8 114
21.3 35 10 111
30.1 50
22.7 35 10 104 35 9 60 8
MAX FUSE
SIZE (Amps)t
7.6 15 14 272
MIN WIRE
SIZE (AWG)t
(75C Copper)
10 115 10 116 10 88 10 137
8 108
10 96
MAX
WIRE
LENGTHt
76 89 82
92
130 113 108
180
100
SINGLE-STAGE HEAT 6 COOL-
MANUAL CHANGEOVER
, Field Low-Voltage Wiring , Field High-Voltage Wiring . Factory Low-Voltage Wiring . Factory High-Voltage Wiring

Fig. 8 — High- and Low-Voltage Connections

SINGLE-STAGE HEAT 8 COOL-
AUTOCHANGEOVER
JUMPER-1
CONTACTOR TERMINALS
FIELD SPLICE^
G]
3
_J
>- CD
LOW-VOLTAGE
PIGTAIL LEADS
CONTROL BOX
NOTE: For manual changeover applications, use thermostat part no HH01AD042 with subbase part no HH93AZ042; or thermostat part no HH01AD040 with subbase part no. HH93AZ040
For automatic changeover, use thermostat part no HH07AT174 with subbase part no
HH93AZ096; or thermostat part no HH10AD041 with subbase part no HH93AZ041
o
3
LiJ
q:
HIGH-VOLTAGE PIGTAIL LEAD
(SEE UNIT WIRING LABEL)
--------
—■
---------
♦OHM^ —
FIELD-SUPPLIED DISCONNECT PER NEC
3-PHASE UNITS ONLY
.POWER
SUPPLY
Loading...
+ 16 hidden pages