Carrier 19XRT User Manual

5 (1)

19XRT Hermetic Centrifugal Liquid Chillers

50/60 Hz with PIC II Controls and HFC-134a

Start-Up, Operation, and Maintenance Instructions

SAFETY CONSIDERATIONS

Centrifugal liquid chillers are designed to provide safe and reliable service when operated within design speci- ®cations. When operating this equipment, use good judgment and safety precautions to avoid damage to equipment and property or injury to personnel.

Be sure you understand and follow the procedures and safety precautions contained in the chiller instructions as well as those listed in this guide.

DO NOT VENT refrigerant relief valves within a building. Outlet from rupture disc or relief valve must be vented outdoors in accordance with the latest edition of ANSI/ASHRAE 15 (American National Standards Institute/American Society of Heating, Refrigeration, and Air Conditioning Engineers). The accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation.

PROVIDE adequate ventilation in accordance with ANSI/ASHRAE 15, especially for enclosed and low overhead spaces. Inhalation of high concentrations of vapor is harmful and may cause heart irregularities, unconsciousness, or death. Misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irritation. Decomposition products are hazardous.

DO NOT USE OXYGEN to purge lines or to pressurize a chiller for any purpose. Oxygen gas reacts violently with oil, grease, and other common substances.

NEVER EXCEED speci®ed test pressures, VERIFY the allowable test pressure by checking the instruction literature and the design pressures on the equipment nameplate.

DO NOT USE air for leak testing. Use only refrigerant or dry nitrogen.

DO NOT VALVE OFF any safety device.

BE SURE that all pressure relief devices are properly installed and functioning before operating any chiller.

DO NOT WELD OR FLAMECUT any refrigerant line or vessel until all refrigerant (liquid and vapor) has been removed from chiller. Traces of vapor should be displaced with dry air or nitrogen and the work area should be well ventilated. Refrigerant in contact with an open ¯ame produces toxic gases.

DO NOT USE eyebolts or eyebolt holes to rig chiller sections or the entire assembly.

DO NOT work on high-voltage equipment unless you are a quali- ®ed electrician.

DO NOT WORK ON electrical components, including control panels, switches, starters, or oil heater until you are sure ALL POWER IS OFF and no residual voltage can leak from capacitors or solidstate components.

LOCK OPEN AND TAG electrical circuits during servicing. IF WORK IS INTERRUPTED, con®rm that all circuits are deenergized before resuming work.

AVOID SPILLING liquid refrigerant on skin or getting it into the eyes. USE SAFETY GOGGLES. Wash any spills from the skin with soap and water. If liquid refrigerant enters the eyes, IMMEDIATELY FLUSH EYES with water and consult a physician.

NEVER APPLY an open ¯ame or live steam to a refrigerant

cylinder. Dangerous over pressure can result. When it is necessary to heat refrigerant, use only warm (110 F [43 C]) water.

DO NOT REUSE disposable (nonreturnable) cylinders or attempt to re®ll them. It is DANGEROUS AND ILLEGAL. When cylinder is emptied, evacuate remaining gas pressure, loosen the collar and unscrew and discard the valve stem. DO NOT INCINERATE.

CHECK THE REFRIGERANT TYPE before adding refrigerant to the chiller. The introduction of the wrong refrigerant can cause damage or malfunction to this chiller.

Operation of this equipment with refrigerants other than those cited herein should comply with ANSI/ASHRAE 15 (latest edition). Contact Carrier for further information on use of this chiller with other refrigerants.

DO NOT ATTEMPT TO REMOVE ®ttings, covers, etc., while chiller is under pressure or while chiller is running. Be sure pressure is at 0 psig (0 kPa) before breaking any refrigerant connection.

CAREFULLY INSPECT all relief devices, rupture discs, and other relief devices AT LEAST ONCE A YEAR. If chiller operates in a corrosive atmosphere, inspect the devices at more frequent intervals.

DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief device when corrosion or build-up of foreign material (rust, dirt, scale, etc.) is found within the valve body or mechanism. Replace the device.

DO NOT install relief devices in series or backwards.

USE CARE when working near or in line with a compressed spring. Sudden release of the spring can cause it and objects in its path to act as projectiles.

DO NOT STEP on refrigerant lines. Broken lines can whip about and release refrigerant, causing personal injury.

DO NOT climb over a chiller. Use platform, catwalk, or staging. Follow safe practices when using ladders.

USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move inspection covers or other heavy components. Even if components are light, use mechanical equipment when there is a risk of slipping or losing your balance.

BE AWARE that certain automatic start arrangements CAN ENGAGE THE STARTER, TOWER FAN, OR PUMPS. Open the disconnect ahead of the starter, tower fans, or pumps.

USE only repair or replacement parts that meet the code requirements of the original equipment.

DO NOT VENT OR DRAIN waterboxes containing industrial brines, liquid, gases, or semisolids without the permission of your process control group.

DO NOT LOOSEN waterbox cover bolts until the waterbox has been completely drained.

DOUBLE-CHECK that coupling nut wrenches, dial indicators, or other items have been removed before rotating any shafts.

DO NOT LOOSEN a packing gland nut before checking that the nut has a positive thread engagement.

PERIODICALLY INSPECT all valves, ®ttings, and piping for corrosion, rust, leaks, or damage.

PROVIDE A DRAIN connection in the vent line near each pressure relief device to prevent a build-up of condensate or rain water.

Manufacturer reserves the right to discontinue, or change at any time, speci®cations or designs without notice and without incurring obligations.

Book

2

 

PC 211

Catalog No. 531-977

Printed in U.S.A.

Form 19XRT-2SS

Pg 1

11-98

Replaces: New

Tab

5a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTENTS

Page

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1

INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

ABBREVIATIONS AND EXPLANATIONS . . . . . . . 4

CHILLER FAMILIARIZATION . . . . . . . . . . . . . . . . . 5-7

Chiller Information Plate . . . . . . . . . . . . . . . . . . . . . . 5

System Components . . . . . . . . . . . . . . . . . . . . . . . . . 5

Cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Motor-Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Turbine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Factory-Mounted Starter (Optional) . . . . . . . . . . . . 7

Storage Vessel (Optional) . . . . . . . . . . . . . . . . . . . . . 7

REFRIGERATION CYCLE . . . . . . . . . . . . . . . . . . . . . 7

MOTOR AND LUBRICATING OIL

COOLING CYCLE . . . . . . . . . . . . . . . . . . . . . . . . . . 7

LUBRICATION CYCLE . . . . . . . . . . . . . . . . . . . . . . . 7-9

Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Oil Reclaim System . . . . . . . . . . . . . . . . . . . . . . . . . . 9

·PRIMARY OIL RECOVERY MODE

·SECONDARY OIL RECOVERY MODE

STARTING EQUIPMENT . . . . . . . . . . . . . . . . . . . . 10,11

Unit-Mounted Solid-State Starter (Optional) . . . 10

Unit-Mounted Wye-Delta Starter (Optional) . . . . 11

CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-44

De®nitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

·ANALOG SIGNAL

·DISCRETE SIGNAL

General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

PIC II System Components . . . . . . . . . . . . . . . . . . 11

·CHILLER VISUAL CONTROLLER (CVC)

·INTEGRATED STARTER MODULE (ISM)

·CHILLER CONTROL MODULE (CCM)

·OIL HEATER CONTACTOR (1C)

·OIL PUMP CONTACTOR (2C)

·HOT GAS BYPASS CONTACTOR RELAY (3C) (Optional)

·CONTROL TRANSFORMERS (T1, T2)

CVC Operation and Menus . . . . . . . . . . . . . . . . . . 15

·GENERAL

·ALARMS AND ALERTS

·CVC MENU ITEMS

·BASIC CVC OPERATIONS (Using the Softkeys)

·TO VIEW STATUS

·OVERRIDE OPERATIONS

·TIME SCHEDULE OPERATION

·TO VIEW AND CHANGE SET POINTS

·SERVICE OPERATION

PIC II System Functions . . . . . . . . . . . . . . . . . . . . . 33

·CAPACITY CONTROL

·ECW CONTROL OPTION

·CONTROL POINT DEADBAND

·PROPORTIONAL BANDS AND GAIN

·CHILLER TIMERS

·OCCUPANCY SCHEDULE

Safety Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Shunt Trip (Option) . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Default Screen Freeze . . . . . . . . . . . . . . . . . . . . . . . 36

Ramp Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Page

Capacity Override . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

High Discharge Temperature Control . . . . . . . . . 36

Oil Sump Temperature Control . . . . . . . . . . . . . . . 36

Oil Cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Remote Start/Stop Controls . . . . . . . . . . . . . . . . . . 37

Spare Safety Inputs . . . . . . . . . . . . . . . . . . . . . . . . . 37

Spare Safety Alarm Contacts . . . . . . . . . . . . . . . . 37

Refrigerant Leak Detector . . . . . . . . . . . . . . . . . . . 37

Condenser Pump Control . . . . . . . . . . . . . . . . . . . . 37

Condenser Freeze Prevention . . . . . . . . . . . . . . . . 38

Tower-Fan Relay Low and High . . . . . . . . . . . . . . 38

Auto. Restart After Power Failure . . . . . . . . . . . . 38

Water/Brine Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

·RESET TYPE 1

·RESET TYPE 2

·RESET TYPE 3

Demand Limit Control Option . . . . . . . . . . . . . . . . 39

Surge Prevention Algorithm . . . . . . . . . . . . . . . . . 39

Surge Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Lead/Lag Control . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

·COMMON POINT SENSOR INSTALLATION

·CHILLER COMMUNICATION WIRING

·LEAD/LAG OPERATION

·FAULTED CHILLER OPERATION

·LOAD BALANCING

·AUTO. RESTART AFTER POWER FAILURE

Ice Build Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

·ICE BUILD INITIATION

·START-UP/RECYCLE OPERATION

·TEMPERATURE CONTROL DURING ICE BUILD

·TERMINATION OF ICE BUILD

·RETURN TO NON-ICE BUILD OPERATIONS

Attach to Network Device Control . . . . . . . . . . . . 43 · ATTACHING TO OTHER CCN MODULES

Service Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

·TO ACCESS THE SERVICE SCREENS

·TO LOG OUT OF NETWORK DEVICE

·HOLIDAY SCHEDULING

START-UP/SHUTDOWN/RECYCLE

SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45,46

Local Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Shutdown Sequence . . . . . . . . . . . . . . . . . . . . . . . . 46

Automatic Soft Stop Amps Threshold . . . . . . . . 46

Chilled Water Recycle Mode . . . . . . . . . . . . . . . . . 46

Safety Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

BEFORE INITIAL START-UP . . . . . . . . . . . . . . . . 47-59

Job Data Required . . . . . . . . . . . . . . . . . . . . . . . . . . 47

Equipment Required . . . . . . . . . . . . . . . . . . . . . . . . 47

Using the Optional Storage Tank

and Pumpout System . . . . . . . . . . . . . . . . . . . . . 47

Remove Shipping Packaging . . . . . . . . . . . . . . . . 47

Open Oil Circuit Valves . . . . . . . . . . . . . . . . . . . . . . 47

Tighten All Gasketed Joints and

Guide Vane Shaft Packing . . . . . . . . . . . . . . . . 47

Check Chiller Tightness . . . . . . . . . . . . . . . . . . . . . 47

Refrigerant Tracer . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

Leak Test Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

Standing Vacuum Test . . . . . . . . . . . . . . . . . . . . . . 49

Chiller Dehydration . . . . . . . . . . . . . . . . . . . . . . . . . 52

Inspect Water Piping . . . . . . . . . . . . . . . . . . . . . . . . 52

Check Optional Pumpout Compressor

Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Check Relief Valves . . . . . . . . . . . . . . . . . . . . . . . . . 52

Inspect Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

2

CONTENTS (cont)

Page

Carrier Comfort Network Interface . . . . . . . . . . . 53

Check Starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

·MECHANICAL STARTER

·BENSHAW, INC. REDISTART MICRO SOLID-STATE STARTER

Oil Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

54

Power Up the Controls and

 

Check the Oil Heater . . . . . . . . . . . . . . . . . . . . . .

54

· SOFTWARE VERSION

 

Software Con®guration . . . . . . . . . . . . . . . . . . . . . .

54

Input the Design Set Points . . . . . . . . . . . . . . . . . .

54

Input the Local Occupied Schedule

 

(OCCPC01S) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

54

Input Service Con®gurations . . . . . . . . . . . . . . . .

54

·PASSWORD

·INPUT TIME AND DATE

·CHANGE CVC CONFIGURATION IF NECESSARY

·TO CHANGE THE PASSWORD

·TO CHANGE THE CVC DISPLAY FROM ENGLISH TO METRIC UNITS

·MODIFY CONTROLLER IDENTIFICATION IF NECESSARY

·INPUT EQUIPMENT SERVICE PARAMETERS IF NECESSARY

·MODIFY EQUIPMENT CONFIGURATION IF NECESSARY

Perform A Control Test . . . . . . . . . . . . . . . . . . . . . . 57

·COOLER AND CONDENSER PRESSURE TRANSDUCER AND WATERSIDE FLOW DEVICE CALIBRATION

Check Optional Pumpout System

Controls and Compressor . . . . . . . . . . . . . . . . . 57

High Altitude Locations . . . . . . . . . . . . . . . . . . . . . 57

Charge Refrigerant Into Chiller . . . . . . . . . . . . . . . 58

·CHILLER EQUALIZATION WITHOUT PUMPOUT UNIT

·CHILLER EQUALIZATION WITH PUMPOUT UNIT

·TRIMMING REFRIGERANT CHARGE

INITIAL START-UP . . . . . . . . . . . . . . . . . . . . . . . . . 59,60 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

Dry Run to Test Start-Up Sequence . . . . . . . . . . 59

Check Motor Rotation . . . . . . . . . . . . . . . . . . . . . . . 59

·IF THE MOTOR ROTATION IS CLOCKWISE

·IF THE MOTOR ROTATION IS NOT CLOCKWISE

Check Oil Pressure and Compressor Stop . . . . 60 To Prevent Accidental Start-Up . . . . . . . . . . . . . . 60 Check Chiller Operating Condition . . . . . . . . . . . 60 Instruct the Customer Operator . . . . . . . . . . . . . . 60

·COOLER-CONDENSER

·OPTIONAL STORAGE TANK AND PUMPOUT SYSTEM

·MOTOR COMPRESSOR ASSEMBLY

·MOTOR COMPRESSOR LUBRICATION SYSTEM

·CONTROL SYSTEM

·AUXILIARY EQUIPMENT

·DESCRIBE CHILLER CYCLES

·REVIEW MAINTENANCE

·SAFETY DEVICES AND PROCEDURES

·CHECK OPERATOR KNOWLEDGE

·REVIEW THE START-UP, OPERATION, AND MAINTENANCE MANUAL

OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . 60-62

Operator Duties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

Prepare the Chiller for Start-Up . . . . . . . . . . . . . . 60

To Start the Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . 60

Check the Running System . . . . . . . . . . . . . . . . . . 60

To Stop the Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . 61 After Limited Shutdown . . . . . . . . . . . . . . . . . . . . . 61

Page

Preparation for Extended Shutdown . . . . . . . . . . 61 After Extended Shutdown . . . . . . . . . . . . . . . . . . . 61

Cold Weather Operation . . . . . . . . . . . . . . . . . . . . . 61

Manual Guide Vane Operation . . . . . . . . . . . . . . . 61

Refrigeration Log . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

PUMPOUT AND REFRIGERANT TRANSFER PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . 63-65

Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

Operating the Optional Pumpout

Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 · TO READ REFRIGERANT PRESSURES

Chillers with Storage Tanks . . . . . . . . . . . . . . . . . . 64

·TRANSFER REFRIGERANT FROM PUMPOUT STORAGE TANK TO CHILLER

·TRANSFER THE REFRIGERANT FROM CHILLER TO PUMPOUT STORAGE TANK

Chillers with Isolation Valves . . . . . . . . . . . . . . . . 65

·TRANSFER ALL REFRIGERANT TO CHILLER CONDENSER VESSEL

·TRANSFER ALL REFRIGERANT TO CHILLER COOLER VESSEL

·RETURN REFRIGERANT TO NORMAL OPERATING CONDITIONS

GENERAL MAINTENANCE . . . . . . . . . . . . . . . . . 66,67 Refrigerant Properties . . . . . . . . . . . . . . . . . . . . . . . 66 Adding Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Removing Refrigerant . . . . . . . . . . . . . . . . . . . . . . . 66

Adjusting the Refrigerant Charge . . . . . . . . . . . . 66 Refrigerant Leak Testing . . . . . . . . . . . . . . . . . . . . 66

Leak Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

Test After Service, Repair, or Major Leak . . . . . 66

·REFRIGERANT TRACER

·TO PRESSURIZE WITH DRY NITROGEN

Repair the Leak, Retest, and Apply

Standing Vacuum Test . . . . . . . . . . . . . . . . . . . . 66

Checking Guide Vane Linkage . . . . . . . . . . . . . . . 66

Trim Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . 66

WEEKLY MAINTENANCE . . . . . . . . . . . . . . . . . . . . 67

Check the Lubrication System . . . . . . . . . . . . . . . 67

SCHEDULED MAINTENANCE . . . . . . . . . . . . . .

67-71

Service Ontime . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 67

Inspect the Control Panel . . . . . . . . . . . . . . . . . . .

. 67

Check Safety and Operating Controls

 

Monthly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 67

Changing Oil Filter . . . . . . . . . . . . . . . . . . . . . . . . .

. 67

Oil Speci®cation . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 68

Oil Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 68

· TO CHANGE THE OIL

 

Refrigerant Filter . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 68

Oil Reclaim Filter . . . . . . . . . . . . . . . . . . . . . . . . . .

. 68

Inspect Refrigerant Float System . . . . . . . . . . .

. 68

Inspect Relief Valves and Piping . . . . . . . . . . . .

. 68

Turbine Strainer . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 68

Turbine Maintenance . . . . . . . . . . . . . . . . . . . . . . .

. 68

Compressor Bearing and Gear Maintenance .

. 68

Inspect the Heat Exchanger Tubes and Flow

 

Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 70

· COOLER AND FLOW DEVICES

 

· CONDENSER AND FLOW DEVICES

 

Water Leaks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70

Water Treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70

Inspect the Starting Equipment . . . . . . . . . . . . . . 70

Check Pressure Transducers . . . . . . . . . . . . . . . . 70

Optional Pumpout System Maintenance . . . . . . 70

·OPTIONAL PUMPOUT COMPRESSOR OIL CHARGE

·OPTIONAL PUMPOUT SAFETY CONTROL SETTINGS

3

CONTENTS (cont)

Page

Ordering Replacement Chiller Parts . . . . . . . . . . 71

TROUBLESHOOTING GUIDE . . . . . . . . . . . . . . . 71-97

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

Checking the Display Messages . . . . . . . . . . . . . 71

Checking Temperature Sensors . . . . . . . . . . . . . . 71

·RESISTANCE CHECK

·VOLTAGE DROP

·CHECK SENSOR ACCURACY

·DUAL TEMPERATURE SENSORS

Checking Pressure Transducers . . . . . . . . . . . . . 72

· TRANSDUCER REPLACEMENT

Control Algorithms Checkout Procedure . . . . . 72

Control Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

Control Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82

·RED LED (Labeled as STAT)

·GREEN LED (Labeled as COM)

Notes on Module Operation . . . . . . . . . . . . . . . . . . 82

Page

Chiller Control Module (CCM) . . . . . . . . . . . . . . . . 83

·INPUTS

·OUTPUTS

Integrated Starter Module (ISM) . . . . . . . . . . . . . . 83

·INPUTS

·OUTPUTS

Replacing Defective Processor Modules . . . . . . 83

· INSTALLATION

Solid-State Starters . . . . . . . . . . . . . . . . . . . . . . . . . 83

·TESTING SILICON CONTROL RECTIFIERS IN BENSHAW, INC., SOLID-STATE STARTERS

·SCR REMOVAL/INSTALLATION

Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98

INITIAL START-UP CHECKLIST FOR 19XRT HERMETIC CENTRIFUGAL

LIQUID CHILLER . . . . . . . . . . . . . . . . . CL-1 to CL-12

INTRODUCTION

ABBREVIATIONS AND EXPLANATIONS

Prior to initial start-up of the 19XRT chiller, those involved in the start-up, operation, and maintenance should be thoroughly familiar with these instructions and other necessary job data. This book is outlined to familiarize those involved in the start-up, operation and maintenance of the unit with the control system before performing start-up procedures. Procedures in this manual are arranged in the sequence required for proper chiller start-up and operation.

This unit uses a microprocessor control system. Do not short or jumper between terminations on circuit boards or modules. Control or board failure may result.

Be aware of electrostatic discharge (static electricity) when handling or making contact with circuit boards or module connections. Always touch a chassis (grounded) part to dissipate body electrostatic charge before working inside control center.

Use extreme care when handling tools near circuit boards and when connecting or disconnecting terminal plugs. Circuit boards can be damaged easily. Always hold boards by the edges, and avoid touching components and connections.

This equipment uses, and can radiate, radio frequency energy. If not installed and used in accordance with the instruction manual, it may interfere with radio communications. This equipment has been tested and found to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user, at his own expense, will be required to take whatever measures may be required to correct the interference.

Always store and transport replacement or defective boards in an anti-static shipping bag.

Frequently used abbreviations in this manual include:

CCM

Ð

Chiller Control Module

CCN

Ð

Carrier Comfort Network

CVC

Ð

Chiller Visual Control

CCW

Ð

Counterclockwise

CW

Ð Clockwise

ECDW

Ð

Entering Condenser Water

ECW

Ð

Entering Chilled Water

EMS

Ð

Energy Management System

HGBP

Ð Hot Gas Bypass

I/O

Ð

Input/Output

ISM

Ð

Integrated Starter Module

LCD

Ð

Liquid Crystal Display

LCDW

Ð

Leaving Condenser Water

LCW

Ð

Leaving Chilled Water

LED

Ð

Light-Emitting Diode

OLTA

Ð

Overload Trip Amps

PIC II

Ð

Product Integrated Control II

RLA

Ð Rated Load Amps

SCR

Ð

Silicon Controlled Recti®er

SI

Ð

International System of Units

TXV

Ð

Thermostatic Expansion Valve

Words printed in all capital letters or in italics may be viewed on the Chiller Visual Control (CVC) (e.g., LOCAL, CCN, ALARM, etc.).

Words printed in both all capital letters and italics can also be viewed on the CVC and are parameters (e.g., CONTROL MODE, COMPRESSOR START RELAY, ICE BUILD OPTION, etc.) with associated values (e.g., modes, temperatures, percentages, pressures, on, off, etc.).

Words printed in all capital letters and in a box represent

softkeys

on the CVC

control panel (e.g.,

ENTER

,

 

,

 

,

 

, etc.).

EXIT

INCREASE

QUIT

Factory-installed additional components are referred to as options in this manual; factory-supplied but ®eld-installed additional components are referred to as accessories.

The chiller software part number of the 19XRT unit is located on the back of the CVC.

4

CHILLER FAMILIARIZATION (Fig. 1 and 2)

Chiller Information Plate Ð The information plate is located on the right side of the chiller control panel.

System Components Ð The components include the cooler and condenser heat exchangers in separate vessels, motor-compressor, turbine, lubrication package, control panel, and motor starter. All connections from pressure vessels have external threads to enable each component to be pressure tested with a threaded pipe cap during factory assembly.

Cooler Ð This vessel (also known as the evaporator) is located underneath the compressor. The cooler is maintained at lower temperature/pressure so evaporating refrigerant can remove heat from water ¯owing through its internal tubes.

Condenser Ð The condenser operates at a higher temperature/pressure than the cooler and has water ¯owing through its internal tubes in order to remove heat from the refrigerant.

Motor-Compressor Ð This component maintains system temperature and pressure differences and moves the heatcarrying refrigerant from the cooler to the condenser.

Turbine Ð The turbine serves 2 purposes. First, it acts as the expansion device to separate condenser pressure from cooler pressure. Second, using the pressure differential between the cooler and condenser, the turbine converts the pressure drop to energy and uses this energy to supplement the compressor motor, thereby reducing the required horsepower.

Control Panel Ð The control panel is the user interface for controlling the chiller. It regulates the chiller's capacity as required to maintain proper leaving chilled water temperature. The control panel:

·registers cooler, condenser, and lubricating system pressures

·shows chiller operating condition and alarm shutdown conditions

·records the total chiller operating hours

·sequences chiller start, stop, and recycle under microprocessor control

·displays status of motor starter

·provides access to other CCN (Carrier Comfort Network) devices

Fig. 1 Ð 19XRT Identi®cation

5

1

2

3

4

5

6

7

8

9

10 11 12 13

14

15

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Ð Turbine Housing

 

 

 

 

 

 

 

 

 

 

 

 

 

2

Ð Power Panel

 

 

 

 

 

 

 

 

 

 

 

 

 

3

Ð Motor Housing

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Ð Oil Level Sight Glasses

 

 

 

 

 

 

 

 

 

 

 

 

 

5

Ð Guide Vane Actuator

 

 

 

 

 

 

 

 

 

 

 

 

 

6

Ð Demistor Vent Line

 

 

 

 

 

 

 

 

 

 

 

 

 

7

Ð Suction Elbow

 

 

 

 

 

 

 

 

 

 

 

 

 

8

Ð Chiller Visual Control (CVC)

 

 

 

 

 

 

 

 

 

 

 

 

16

9

Ð Condenser Pumpout Connection (Hidden)

 

 

 

 

 

 

 

 

 

 

 

 

10

Ð Condenser Relief Valves

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17

11

Ð Relief Transfer Valve

 

 

 

 

 

 

 

 

 

 

 

 

12

Ð Condenser Pressure Transducer (Hidden)

 

 

 

 

 

 

 

 

 

 

 

 

16

 

 

 

 

 

 

 

 

 

 

 

 

13

Ð Cooler Relief Valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

Ð Cooler Pressure Transducer (Hidden)

 

 

 

 

 

 

 

 

 

 

 

 

 

15

Ð Cooler Pumpout Connection

 

 

 

 

 

 

 

 

 

 

 

 

 

16

Ð Cooler/Condenser Water¯ow Device

 

 

 

 

 

 

 

 

 

 

 

 

 

17

Ð Condenser In/Out Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermistors

 

 

 

 

 

 

 

 

 

 

 

 

 

18

Ð Cooler In/Out Temperature Thermistors

 

 

 

 

 

 

 

 

 

 

 

 

 

19

Ð Chiller Identi®cation Nameplate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Location

 

 

 

 

 

 

 

 

 

 

 

 

 

20

Ð Float Chamber

 

 

22

 

21

 

20

 

 

19

 

18 17

 

21

Ð Refrigerant Charging Valve

 

 

 

RIGHT END VIEW

 

 

 

 

 

22

Ð Oil Drain Charging Valve

 

 

 

 

 

 

 

 

 

 

23

24

25

 

 

 

 

 

 

26 27

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

 

23

Ð Take-Apart, Connector (Upper)

 

 

 

 

 

 

 

 

 

 

 

 

 

24

Ð Waterbox Vent Connection (Typical)

 

 

 

 

 

 

 

 

 

 

 

 

 

25

Ð Cooler Liquid Return Line

 

 

 

 

 

 

 

 

 

 

 

 

 

26

Ð Oil Filter Access Cover

 

 

 

 

 

 

 

 

 

 

 

 

 

27

Ð Refrigerant Oil Cooler

 

 

 

 

 

 

 

 

 

 

 

 

 

28

Ð Take-Apart, Rabbet-Fit Connector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Lower)

 

 

 

 

 

 

 

 

 

 

 

 

 

29

Ð Cooler Return-End Waterbox Cover

 

 

 

 

 

 

 

 

 

 

 

 

 

30

Ð Waterbox Drain Port (Typical)

 

 

 

 

 

 

 

 

 

 

 

 

 

31

Ð Condenser Return-End Waterbox Cover

31

 

30

29

 

 

28

 

 

 

LEFT END VIEW

 

 

 

 

 

2

 

4

5

6

7

LEGEND

 

3

Ð Turbine Suction

 

 

 

 

 

1

 

 

 

 

1

 

 

 

 

 

2

Ð Nozzle (Typical, 1 of 6 Shown)

 

 

 

 

 

 

3

Ð Nozzle Block

 

 

 

 

 

 

4

Ð High Efficiency Motor

 

 

 

 

 

 

5

Ð Transmission

 

 

 

 

 

 

6

Ð Compressor Base

 

 

 

 

 

 

7

Ð Guide Vane Actuator

 

 

 

 

 

 

8

Ð Oil Filter Housing

 

 

 

 

 

 

9

Ð Turbine Wheel

12

 

 

 

 

 

10

Ð Turbine Housing

 

 

 

 

 

11

Ð Turbine Discharge

 

 

 

 

 

 

12

Ð Turbine Sight Glass

11

10

9

8

 

 

 

 

TURBINE COMPONENTS

Fig. 2 Ð Typical 19XRT Components

6

Factory-Mounted Starter (Optional) Ð The starter allows for the proper start and disconnect of electrical energy for the compressor-motor, oil pump, oil heater, and control panel.

Storage Vessel (Optional) Ð There are 2 sizes of storage vessels available. The vessels have double relief valves, a magnetically-coupled dial-type refrigerant level gage, a one-inch FPT drain valve, and a 1¤2-in. male ¯are vapor connection for the pumpout unit.

NOTE: If a storage vessel is not used at the jobsite, factoryinstalled isolation valves on the chiller may be used to isolate the chiller charge in either the cooler or condenser. An optional pumpout system is used to transfer refrigerant from vessel to vessel.

REFRIGERATION CYCLE

The compressor continuously draws refrigerant vapor from the cooler, at a rate set by the amount of guide vane opening (Fig. 3). As the compressor suction reduces the pressure in the cooler, the remaining refrigerant boils at a fairly low temperature (typically 38 to 42 F [3 to 6 C]). The energy required for boiling is obtained from the water ¯owing through the cooler tubes. With heat energy removed, the water becomes cold enough for use in an air conditioning circuit or process liquid cooling.

After taking heat from the water, the refrigerant vapor is compressed. Compression adds still more heat energy and the refrigerant is quite warm (typically 98 to 102 F [37 to 40 C]) when it is discharged from the compressor into the condenser.

Relatively cool (typically 65 to 90 F [18 to 32 C]) water ¯owing through the condenser tubes removes heat from the refrigerant, and the vapor condenses to a liquid. Further removal of heat from the refrigerant occurs in the lower chamber of the condenser, which is called the sensible subcooler. At this point, the liquid refrigerant is subcooled by contact with the coolest (entering water) condenser tubes.

After leaving the sensible subcooler section of the condenser, the liquid refrigerant enters the ¯oat valve chamber. The main ¯oat valve maintains a liquid level in the subcooler to prevent hot gas bypass from the condenser to the cooler at part load conditions. A second valve in the ¯oat valve chamber opens at part load conditions when the liquid level increases in the condenser to bypass liquid from the ¯oat chamber directly to the cooler inlet. The liquid refrigerant from the main ¯oat valve then ¯ows into the turbine housing chamber on the compressor. The liquid refrigerant passes through the turbine nozzles and impacts the turbine blades where energy is reclaimed as the refrigerant expands through the turbine to the lower cooler pressure. The turbine wheel is attached to the motor shaft which allows the turbine to supplement and reduce motor power requirements. At this point the refrigerant ¯ashes to a mixture of gas and liquid which removes heat from the remaining liquid. This mixture ¯ows back to the cooler where it is now at the same temperature and pressure at which the cycle began.

MOTOR AND LUBRICATING OIL

COOLING CYCLE

The motor and the lubricating oil are cooled by liquid refrigerant taken from the bottom of the condenser vessel (Fig. 3). Refrigerant ¯ow is maintained by the pressure

differential that exists due to compressor operation. After the refrigerant ¯ows past an isolation valve, an in-line ®lter, and a sight glass/moisture indicator, the ¯ow is split between the motor cooling and oil cooling systems.

Flow to the motor cooling system passes through an ori- ®ce and into the motor. Once past the ori®ce, the refrigerant is directed over the motor by a spray nozzle. The refrigerant collects in the bottom of the motor casing and is then drained back into the cooler through the motor refrigerant drain line. The refrigerant outlet from the motor casing is sized to act as an ori®ce to maintain a higher pressure in the motor shell than in the cooler/oil sump. The motor is protected by a temperature sensor imbedded in the stator windings. An increase in motor winding temperature past the motor override set point overrides the temperature capacity control to hold, and if the motor temperature rises 10° F (5.5° C) above this set point, closes the inlet guide vanes. If the temperature rises above the safety limit, the compressor shuts down.

Refrigerant that ¯ows to the oil cooling system is regulated by thermostatic expansion valves (TXVs). The TXVs regulate ¯ow into the oil/refrigerant plate and frame-type heat exchanger (the oil cooler in Fig. 3). The expansion valve bulbs control oil temperature to the bearings. The refrigerant leaving the oil cooler heat exchanger then returns to the chiller cooler.

LUBRICATION CYCLE

Summary Ð The oil pump, oil ®lter, and oil cooler make up a package located partially in the transmission casting of the compressor-motor-turbine assembly. The oil is pumped into a ®lter assembly to remove foreign particles and is then forced into an oil cooler heat exchanger where the oil is cooled to proper operational temperatures. After the oil cooler, part of the ¯ow is directed to the gears and the high speed shaft bearings; the remaining ¯ow is directed to the motor shaft bearings. Oil drains into the transmission oil sump to complete the cycle (Fig. 4).

Details Ð Oil is charged into the lubrication system through a hand valve. Two sight glasses in the oil reservoir permit oil level observation. Normal oil level is between the middle of the upper sight glass and the top of the lower sight glass when the compressor is shut down. The oil level should be visible in at least one of the 2 sight glasses during operation. Oil sump temperature is displayed on the CVC (Chiller Visual Control) default screen. During compressor operation, the oil sump temperature ranges between 125 to 150 F (52 to 66 C).

The oil pump suction is fed from the oil reservoir. An oil pressure relief valve maintains 18 to 25 psid (124 to 172 kPad) differential pressure in the system at the pump discharge. This differential pressure can be read directly from the CVC default screen. The oil pump discharges oil to the oil ®lter assembly. This ®lter can be closed to permit removal of the ®lter without draining the entire oil system (see Maintenance sections, pages 66-71, for details). The oil is then piped to the oil cooler heat exchanger. The oil cooler uses refrigerant from the condenser as the coolant. The refrigerant cools the oil to a temperature between 120 and 140 F (49 to 60 C).

7

Carrier 19XRT User Manual

8

LEGEND

1Ð Condenser Tubes

2Ð Filter/Drier

3Ð Moisture Indicator

4Ð Refrigerant Cooling Isolation Valves

5Ð Main Condenser Liquid Drain Line

6Ð Float Chamber Vent

7Ð Subcooler

8Ð Discharge Isolation Valve (Optional)

9Ð High Condenser Level Drain

10Ð Condenser Side Refrigerant Charging Valve

11Ð Stator

12Ð Transmission

13Ð Diffuser

14Ð Impeller

15Ð Inlet Guide Vanes

16Ð Cooler Distribution Pipe

17Ð Refrigerant Cooling Drain Lines

18Ð Oil Pump

19Ð Oil Filter

20Ð Rotor

21Ð Oil Cooler

22Ð Ori®ced Fitting

23Ð Thermal Expansion Valve for

Oil Cooling

24Ð Cooler Refrigerant Supply Line

25Ð Turbine Suction Line Strainer

26Ð Cooler Suction Line

27Ð Cooler Refrigerant Charging Valve

28Ð Turbine Bypass Line Isolation Valve

29Ð Turbine Bypass Line

30Ð Pilot Drain Line From Turbine Bypass

31Ð Float Chamber

32Ð Turbine Float Valve

33Ð Turbine Bypass Float Valve

34Ð Turbine Suction Isolation Valve (Optional)

35Ð Motor Back Pressure Ori®ce

Fig. 3 Ð Refrigerant, Motor Cooling, and Oil Cooling Cycles

JOURNAL

BEARINGS

REAR PINION

BEARING

 

 

THRUST

 

 

THRUST

 

FILTER

 

 

ISOLATION

SIGHT

 

VALVE

OIL

GLASSES

 

 

 

SUPPLY

FILTER

STRAINER

LINE

 

 

OIL DRAIN

CHECK

 

 

VALVE

 

 

ISOLATION

 

 

VALVE

THERMAL

OIL SUPPLY

ISOLATION

OIL

SIGHT

CHARGE

GLASS

EXPANSION

PRESSURE

VALVE

VALVE

FILTER

VALVE BULB

TRANSDUCER

OIL

 

 

 

EDUCTOR STRAINER

 

 

 

COOLER

ISOLATION

 

 

OIL PUMP

OIL PRESSURE

VALVE

 

 

AND MOTOR

RELIEF VALVE

COOLER

 

 

 

 

 

 

 

 

OIL

 

 

 

 

RECLAIM

 

 

 

 

LINE

Fig. 4 Ð Lubrication System

As the oil leaves the oil cooler, it passes the oil pressure transducer and the thermal bulb for the refrigerant expansion valve on the oil cooler. The oil is then divided. Part of the oil ¯ows to the thrust bearing, forward pinion bearing, and gear spray. The rest of the oil lubricates the motor shaft bearings and the rear pinion bearing. The oil temperature is measured in the bearing housing as it leaves the thrust and forward journal bearings. The oil then drains into the oil reservoir at the base of the compressor. The PIC II (Product Integrated Control II) measures the temperature of the oil in the sump and maintains the temperature during shutdown (see Oil Sump Temperature Control section, page 36). This temperature is read on the CVC default screen.

During the chiller start-up, the PIC II energizes the oil pump and provides 45 seconds of prelubrication to the bearings after pressure is veri®ed before starting the compressor. During shutdown, the oil pump will run for 60 seconds to post-lubricate after the compressor shuts down. The oil pump can also be energized for testing purposes during a Control Test.

Ramp loading can slow the rate of guide vane opening to minimize oil foaming at start-up. If the guide vanes open quickly, the sudden drop in suction pressure can cause any refrigerant in the oil to ¯ash. The resulting oil foam cannot be pumped efficiently; therefore, oil pressure falls off and lubrication is poor. If oil pressure falls below 15 psid (103 kPad) differential, the PIC II will shut down the compressor.

If the controls are subject to a power failure that lasts more than 3 hours, the oil pump will be energized periodically when the power is restored. This helps to eliminate refrigerant that has migrated to the oil sump during the power failure. The controls energize the pump for 60 seconds every 30 minutes until the chiller is started.

Oil Reclaim System Ð The oil reclaim system returns oil lost from the compressor housing back to the oil reservoir by recovering the oil from 2 areas on the chiller. The guide vane housing is the primary area of recovery. Oil is also recovered by skimming it from the operating refrigerant level in the cooler vessel.

PRIMARY OIL RECOVERY MODE Ð Oil is normally recovered through the guide vane housing on the chiller. This is possible because oil is normally entrained with refrigerant in the chiller. As the compressor pulls the refrigerant up from the cooler into the guide vane housing to be compressed, the oil normally drops out at this point and falls to the bottom of the guide vane housing where it accumulates. Using discharge gas pressure to power an eductor, the oil is drawn from the housing and is discharged into the oil reservoir.

SECONDARY OIL RECOVERY MODE Ð The secondary method of oil recovery is signi®cant under light load conditions, when the refrigerant going up to the compressor suction does not have enough velocity in which to bring oil along. Under these conditions, oil collects in a greater concentration at the top level of the refrigerant in the cooler. This oil and refrigerant mixture is skimmed from the side of the cooler and is then drawn up to the guide vane housing. There is a ®lter in this line. Because the guide vane housing pressure is much lower than the cooler pressure, the refrigerant boils off, leaving the oil behind to be collected by the primary oil recovery method.

9

STARTING EQUIPMENT

The 19XRT requires a motor starter to operate the centrifugal hermetic compressor motor, the oil pump, and various auxiliary equipment. The starter is the main ®eld wiring interface for the contractor.

See Carrier Speci®cation Z-415 for speci®c starter requirements. All starters must meet these speci®cations in order to properly start and satisfy mechanical safety requirements. Starters may be supplied as separate, free-standing units or may be mounted directly on the chiller (unit mounted) for low-voltage units only.

Three separate circuit breakers are inside the starter. Circuit breaker CB1 is the compressor motor circuit breaker. The disconnect switch on the starter front cover is connected to this breaker. Circuit breaker CB1 supplies power to the compressor motor.

The main circuit breaker (CB1) on the front of the starter disconnects the main motor current only. Power is still energized for the other circuits. Two more circuit breakers inside the starter must be turned off to disconnect power to the oil pump, PIC II controls, and oil heater.

Circuit breaker CB2 supplies power to the control panel, oil heater, and portions of the starter controls.

Circuit breaker CB3 supplies power to the oil pump. Both CB2 and CB3 are wired in parallel with CB1 so that power is supplied to them if the CB1 disconnect is open.

All starters must include a Carrier control module called the Integrated Starter Module (ISM), excluding the Benshaw solid-state starters. This module controls and monitors all aspects of the starter. See the Controls section on page 11 for additional ISM information. All starter replacement parts are supplied by the starter manufacturer excluding the ISM (contact Carrier's Replacement Component Division [RCD]).

Unit-Mounted Solid-State Starter (Optional) Ð The 19XRT chiller may be equipped with a solid-state, reduced-voltage starter (Fig. 5 and 6). This starter's primary function is to provide on-off control of the compressor motor. This type of starter reduces the peak starting torque, reduces the motor inrush current, and decreases mechanical shock. This capability is summed up by the phrase ``soft starting.'' The solid-state starter is available as a 19XRT option (factory supplied and installed). The solid-state starters manufacturer name is located inside the starter access door.

A solid-state, reduced-voltage starter operates by reducing the starting voltage. The starting torque of a motor at full voltage is typically 125% to 175% of the running torque. When the voltage and the current are reduced at start-up, the starting torque is reduced as well. The object is to reduce the starting voltage to just the voltage necessary to develop the torque required to get the motor moving. The voltage is reduced by silicon controlled recti®ers (SCRs). The voltage and current are then ramped up in a desired period of time. Once full voltage is reached, a bypass contactor is energized to bypass the SCRs.

When voltage is supplied to the solid-state circuitry, the heat sinks in the starter as well as the wires leading to the motor and the motor terminal are at line voltage. Do not touch the heat sinks, power wiring, or motor terminals while voltage is present or serious injury will result.

There is a display on the front of the Benshaw, Inc., solidstate starters that is useful for troubleshooting and starter checkout. The display indicates:

·voltage to the SCRs

·SCR control voltage

·power indication

·proper phasing for rotation

·start circuit energized

·over-temperature

·ground fault

·current unbalance

·run state

·software con®guration

The starter is further explained in the Check Starter and Troubleshooting Guide sections, pages 53 and 71.

6

1

2

3

5

4

LEGEND

1Ð Ready-Start Micro Input/Output Card

2Ð Circuit Breaker 2 (CB2):

Machine Control and Heater Power

3Ð Circuit Breaker 3 (CB3): Oil Pump Power

4Ð Ready-Start Micro Central Processing Unit Card (CPU)

5Ð Restart Micro Power Card (hidden, not depicted)

6Ð Restart Micro Bypass Card (hidden, not depicted)

Fig. 5 Ð Solid-State Starter Box,

Internal View

10

Fig. 6 Ð Typical Starter External View

(Solid-State Starter Shown)

Unit-Mounted Wye-Delta Starter (Optional)

Ð The 19XRT chiller may be equipped with a wye-delta starter mounted on the unit. This starter is intended for use with low-voltage motors (under 600 v). It reduces the starting current inrush by connecting each phase of the motor windings into a wye con®guration. This occurs during the starting period when the motor is accelerating up to speed. Once the motor is up to speed, the starter automatically connects the phase windings into a delta con®guration. Starter control, monitoring, and motor protection is provided by Carrier's Integrated Starter Module (ISM).

CONTROLS

De®nitions

ANALOG SIGNAL Ð An analog signal varies in proportion to the monitored source. It quanti®es values between operating limits. (Example: A temperature sensor is an analog device because its resistance changes in proportion to the temperature, generating many values.)

DISCRETE SIGNAL Ð A discrete signal is a 2-position representation of the value of a monitored source. (Example: A switch produces a discrete signal indicating whether a value is above or below a set point or boundary by generating an on/off, high/low, or open/closed signal.)

General Ð The 19XRT hermetic centrifugal liquid chiller contains a microprocessor-based control center that monitors and controls all operations of the chiller (see Fig. 7). The microprocessor control system matches the cooling capacity of the chiller to the cooling load while providing state-of-the-art chiller protection. The system controls cooling load within the set point plus the deadband by sensing the leaving chilled water or brine temperature and regulating the inlet guide vane via a mechanically-linked actuator motor. The guide vane is a variable ¯ow pre-whirl assembly that controls the refrigeration effect in the cooler by regulating the amount of refrigerant vapor ¯ow into the compressor. An increase in guide vane opening increases capacity. A decrease in guide vane opening decreases capacity. The microprocessor-based control center protects the chiller by monitoring the digital and analog inputs and executing capacity overrides or safety shutdowns, if required.

PIC II System Components Ð The chiller control system is called PIC II (Product Integrated Control II). See Table 1. The PIC II controls the operation of the chiller by monitoring all operating conditions. The PIC II can diagnose a problem and let the operator know what the problem is and what to check. It promptly positions the guide vanes to maintain leaving chilled water temperature. It can interface with auxiliary equipment such as pumps and cooling tower fans to turn them on when required. It continually checks all safeties to prevent any unsafe operating condition. It also regulates the oil heater while the compressor is off and regulates the hot gas bypass valve, if installed. The PIC II controls provide critical protection for the compressor motor and controls the motor starter.

The PIC II can interface with the Carrier Comfort Network (CCN) if desired. It can communicate with other PIC I or PIC II equipped chillers and other CCN devices.

The PIC II consists of 3 modules housed inside 3 major components. The component names and corresponding control voltages are listed below (also see Table 1):

·control panel

Ðall extra low-voltage wiring (24 v or less)

·power panel

Ð230 or 115 v control voltage (per job requirement)

Ðup to 600 v for oil pump power

·starter cabinet

Ðchiller power wiring (per job requirement)

Table 1 Ð Major PIC II Components and

Panel Locations*

PIC II COMPONENT

PANEL

LOCATION

 

Chiller Visual Controller (CVC) and Display

Control Panel

Integrated Starter Module (ISM)

Starter Cabinet

Chiller Control Module (CCM)

Control Panel

Oil Heater Contactor (1C)

Power Panel

Oil Pump Contactor (2C)

Power Panel

Hot Gas Bypass Relay (3C) (Optional)

Power Panel

Control Transformers (T1, T2)

Power Panel

Temperature Sensors

See Fig. 7.

Pressure Transducers

See Fig. 7.

 

 

*See Fig. 5 and Fig. 7-11.

 

CHILLER VISUAL CONTROLLER (CVC) Ð The CVC is the ``brain'' of the PIC II. This module contains all the operating software needed to control the chiller. The CVC is mounted to the control panel (Fig. 10) and is the input center for all local chiller set points, schedules, con®gurable functions, and options. The CVC has a stop button, an alarm light, four buttons for logic inputs, and a backlight display. The backlight will automatically turn off after 15 minutes of non-use. The functions of the four buttons or ``softkeys'' are menu driven and are shown on the display directly above the softkeys.

The viewing angle of the CVC can be adjusted for optimum viewing. Remove the 2 bolts connecting the control panel to the brackets attached to the cooler. Place them in one of the holes to pivot the control panel forward to backward to change the viewing angle. See Fig. 10. To change the contrast of the display, access the adjustment on the back of the CVC. See Fig. 10.

11

LEGEND

1Ð Condenser Temperature Sensor Connection

2Ð Condenser Pressure Transducer Connection

TOP VIEW

COMPRESSOR AREA

Fig. 7 Ð 19XRT Control and Sensor Locations

12

INTEGRATED STARTER MODULE (ISM) Ð This module is located in the starter cabinet. This module initiates commands from the CVC for starter functions such as starting and stopping the compressor, condenser, chilled water pumps, tower fan, spare alarm contacts, and the shunt trip. The ISM monitors starter inputs such as line voltage, motor current, ground fault, remote start contact, spare safety, condenser high pressure, oil pump interlock, starter 1M, and run contacts. The ISM contains logic capable of safety shutdown. It shuts down the chiller if communications with the CVC are lost.

CHILLER CONTROL MODULE (CCM) Ð This module is located in the control panel. The CCM provides the input and outputs necessary to control the chiller. This module monitors refrigerant pressure, entering and leaving water temperatures, and outputs control for the guide vane actuator, oil heaters, and oil pump. The CCM is the connection point for optional demand limit, chilled water reset, remote temperature reset, and refrigerant leak sensor.

OIL HEATER CONTACTOR (1C) Ð This contactor is located in the power panel (Fig. 11) and operates the heater at either 115 or 230 v. It is controlled by the PIC II to maintain oil temperature during chiller shutdown.

OIL PUMP CONTACTOR (2C) Ð This contactor is located in the power panel. It operates all 200 to 575-v oil pumps. The PIC II energizes the contactor to turn on the oil pump as necessary.

HOT GAS BYPASS CONTACTOR RELAY (3C) (Optional) Ð This relay, located in the power panel, controls the opening of the hot gas bypass valve. The PIC II energizes the relay during low load, high lift conditions.

CONTROL TRANSFORMERS (T1, T2) Ð These transformers convert incoming control voltage to 24 vac power for the 3 power panel contactor relays, CCM, and CVC.

Fig. 8 Ð Control Sensors (Temperature)

Fig. 9 Ð Control Sensors

(Pressure Transducers, Typical)

13

Fig. 10 Ð Control Panel

Fig. 11 Ð Power Panel

14

CVC Operation and Menus (Fig. 12-18)

GENERAL

·The CVC display automatically reverts to the default screen after 15 minutes if no softkey activity takes place and if the chiller is not in the pumpdown mode (Fig. 12).

·If a screen other than the default screen is displayed on the CVC, the name of that screen is in the upper right corner (Fig. 13).

·The CVC may be set to display either English or SI units. Use the CVC con®guration screen (accessed from the Service menu) to change the units. See the Service Operation section, page 44.

·Local Operation Ð The PIC II can be placed in local operating mode by pressing the LOCAL softkey. The PIC II then accepts commands from the CVC only and

uses the Local Time Schedule to determine chiller start and stop times.

·CCN Operation Ð The PIC II can be placed in the CCN

operating mode by pressing the CCN softkey. The

PIC II then accepts modi®cations from any CCN interface or module (with the proper authority), as well as from the CVC. The PIC II uses the CCN time schedule to determine start and stop times.

ALARMS AND ALERTS Ð An alarm shuts down the compressor. An alert does not shut down the compressor, but it noti®es the operator that an unusual condition has occurred. An alarm (*) or alert (!) is indicated on the STATUS screens on the far right ®eld of the CVC display screen.

Alarms are indicated when the control center alarm light

(!) ¯ashes. The primary alarm message is displayed on the default screen. An additional, secondary message and troubleshooting information are sent to the ALARM HISTORY table.

When an alarm is detected, the CVC default screen will freeze (stop updating) at the time of alarm. The freeze enables the operator to view the chiller conditions at the time of alarm. The STATUS tables will show the updated information. Once all alarms have been cleared (by pressing the

RESET softkey), the default CVC screen will return to nor-

mal operation.

CVC MENU ITEMS Ð To perform any of the operations described below, the PIC II must be powered up and have successfully completed its self test. The self test takes place automatically, after power-up.

Press the MENU softkey to view the list of menu struc-

tures: STATUS , SCHEDULE , SETPOINT , and

SERVICE .

·The STATUS menu allows viewing and limited calibration or modi®cation of control points and sensors, relays and contacts, and the options board.

·The SCHEDULE menu allows viewing and modi®cation of the local and CCN time schedules and Ice Build time schedules.

·The SETPOINT menu allows set point adjustments, such as the entering chilled water and leaving chilled water set points.

PRIMARY STATUS

COMPRESSOR

DATE

TIME

MESSAGE

ONTIME

 

 

 

 

SECONDARY

 

 

 

 

 

STATUS

RUNNING TEMP CONTROL

01-01-95 11:48

MESSAGE

LEAVING CHILLED WATER

28.8 HOURS

ALARM LIGHT

CHW IN

CHW OUT

EVAP REF

55.1

 

44.1

40.7

(ILLUMINATED

 

CDW IN

CDW OUT

COND REF

WHEN POWER ON)

85.0

 

95.0

98.1

BLINKS CONTINUOUSLY

 

 

 

 

 

ON FOR AN ALARM

OIL PRESS

OIL TEMP

AMPS %

BLINKS ONCE TO

21.8

132.9

 

93

CCN

LOCAL

RESET

MENU

CONFIRM A STOP

STOP BUTTON

 

 

 

 

 

HOLD FOR ONE

 

 

 

 

 

SECOND TO STOP

 

 

 

 

 

SOFT KEYS

MENU

EACH KEY'S FUNCTION IS

LINE

DEFINED BY THE MENU DESCRIPTION

ON MENU LINE ABOVE

 

Fig. 12 Ð CVC Default Screen

19XRT_II

SERVICE

ALARM HISTORY

CONTROL TEST

CONTROL ALGORITHM STATUS

EQUIPMENT CONFIGURATION

ISM (STARTER) CONFIGURATION DATA

EQUIPMENT SERVICE

TIME AND DATE

ATTACH TO NETWORK DEVICE

LOG OUT OF DEVICE

CVC CONFIGURATION

Fig. 13 Ð CVC Service Screen

·The SERVICE menu can be used to view or modify information on the Alarm History, Control Test, Control Algorithm Status, Equipment Con®guration, ISM Starter Con®guration data, Equipment Service, Time and Date, Attach to Network Device, Log Out of Network Device, and CVC Con®guration screens.

For more information on the menu structures, refer to Fig. 15.

Press the softkey that corresponds to the menu structure

to be viewed : STATUS , SCHEDULE , SETPOINT , or

SERVICE . To view or change parameters within any of

these menu structures, use the NEXT and PREVIOUS soft-

keys to scroll down to the desired item or table. Use the

SELECT softkey to select that item. The softkey choices

that then appear depend on the selected table or menu. The softkey choices and their functions are described below.

BASIC CVC OPERATIONS (Using the Softkeys) Ð To perform any of the operations described below, the PIC II must be powered up and have successfully completed its self test.

15

·Press QUIT to leave the selected decision or ®eld without

·Press ENTER to leave the selected decision or ®eld and save

·Press NEXT to scroll the cursor bar down in order to

highlight a point or to view more points below the current screen

· Press PREVIOUS to scroll the cursor bar up in order to

·Press SELECT to view the next screen level (high-

lighted with the cursor bar), or to override (if allowable) the

· Press

·Press INCREASE or DECREASE to change the highlighted

TO VIEW STATUS (Fig. 14) Ð The status table shows the actual value of overall chiller status such as CONTROL MODE, RUN STATUS, AUTO CHILLED WATER, RESET, and REMOTE RESET SENSOR.

1.On the menu screen, press STATUS to view the list of point status tables.

2.Press NEXT or PREVIOUS to highlight the desired status table. The list of tables is:

·MAINSTAT Ð Overall chiller status

·STARTUP Ð Status required to perform startup of chiller

·COMPRESS Ð Status of sensors related to the compressor

·HEAT_EX Ð Status of sensors related to the heat exchangers

·POWER Ð Status of motor input power

·ISM_STAT Ð Status of motor starter

·CVC_PSWD Ð Service menu password forcing access screen

3.Press SELECT to view the desired point status table.

4. On the point status table, press NEXT or

PREVIOUS until the desired point is displayed on the screen.

 

 

 

19XRT_II MAINSTAT

POINT STATUS

 

 

 

Control Mode

 

OFF

 

 

 

Run Status

 

Ready

 

 

 

Start Inhibit Timer

 

0.0 Min

 

 

 

Occupied?

 

 

NO

 

 

 

System Alert/Alarm

NORMAL

 

 

 

Chiller Start/Stop

 

STOP

 

 

 

 

 

 

 

Remote Start Contact

 

Open

 

 

 

Temperature Reset

 

0.0 F

 

 

 

Control Point

 

44.0 F

 

 

 

Chilled Water Temp

 

44.6 F

 

 

 

Active Demand Limit

100%

 

 

 

Average Line Current

0.0%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 14 Ð Example of Status Screen

OVERRIDE OPERATIONS

To Override a Value or Status

1. From any point status screen, press NEXT or

16

 

 

 

 

 

 

DEFAULT SCREEN

 

 

 

 

 

 

 

 

 

CCN

 

LOCAL

 

RESET

 

MENU

 

(SOFTKEYS)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Start Chiller In CCN Control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Start Chiller in Local Control

 

 

 

 

 

 

 

 

 

Clear Alarms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Access Main Menu

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STATUS

 

 

SCHEDULE

 

SETPOINT

 

SERVICE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 1 1 1

(ENTER A 4-DIGIT PASSWORD)

 

 

List the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Status Tables

 

 

 

 

 

 

 

 

 

 

List the Service Tables

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Display The Setpoint Table

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAINSTAT

STARTUP

• COMPRESS

List the Schedules

• HEAT_EX

 

• Base Demand Limit

 

• LCW Setpoint

• POWER

 

 

• ECW Setpoint

• ISM_STAT

 

 

• Ice Build Setpoint

• CVC_PSWD

 

 

• Tower Fan High Setpoint

Select a Status Table

 

 

Select the Setpoint

NEXT

PREVIOUS

SELECT

EXIT

NEXT

PREVIOUS

SELECT

EXIT

Select a Modification Point

 

 

Modify the Setpoint

 

 

 

 

INCREASE

DECREASE

QUIT

ENTER

NEXT

PREVIOUS

SELECT

EXIT

 

 

 

 

Modify a Discrete Point

 

 

 

 

 

 

START

STOP

RELEASE

ENTER

 

 

 

 

ON

OFF

 

 

 

 

 

 

Modify an Analog Point

 

 

• OCCPC01S – LOCAL TIME SCHEDULE

 

 

INCREASE

DECREASE

RELEASE

ENTER

 

 

• OCCPC02S – ICE BUILD TIME SCHEDULE

 

 

 

 

 

 

 

 

Modify Control Options

 

 

• OCCPC03S – CCN TIME SCHEDULE

 

 

 

ENABLE

DISABLE

QUIT

ENTER

Select a Schedule

 

 

 

 

 

 

 

NEXT

PREVIOUS

SELECT

EXIT

1

2

3

4

5

6

7

8 Override

Select a Time Period/Override

NEXT

PREVIOUS

Modify a Schedule Time

INCREASE

DECREASE

Add/Eliminate a Day

ENABLE

DISABLE

SELECT

 

EXIT

 

 

 

(ANALOG VALUES)

ENTER

 

EXIT

 

 

 

(DISCRETE VALUES)

ENTER

 

EXIT

ALARM HISTORY

CONTROL TEST

CONTROL ALGORITHM STATUS

EQUIPMENT CONFIGURATION

ISM (STARTER) CONFIG DATA

EQUIPMENT SERVICE

TIME AND DATE

ATTACH TO NETWORK DEVICE

LOG OUT OF DEVICE

CVC CONFIGURATION

NEXT

 

PREVIOUS

 

SELECT

 

EXIT

SEE FIGURE 16

Fig. 15 Ð 19XRT CVC Menu Structure

17

SERVICE TABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NEXT

 

 

PREVIOUS

 

 

SELECT

 

 

 

EXIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALARM HISTORY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Display Alarm History

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(The table holds up to 25 alarms and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

alerts with the most recent alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

at the top of the screen.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTROL TEST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

List the Control Tests

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CCM Thermistors

 

 

CONTROL ALGORITHM STATUS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CCM Pressure Transducers

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pumps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Discrete Outputs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

List the Control Algorithm Status Tables

 

 

 

 

 

 

 

 

 

 

 

 

 

Guide Vane Actuator

 

 

 

 

 

 

 

CAPACITY (Capacity Control)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Diffuser Actuator

 

 

 

 

 

 

 

OVERRIDE (Override Status)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pumpdown/Lockout

 

 

 

 

 

 

 

LL_MAINT (Lead Lag Status)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminate Lockout

 

 

 

 

 

 

 

• ISM_HIST (ISM Alarm History)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Select a Test

Guide Vane Calibration

 

 

 

 

 

 

 

• LOADSHED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WSMDEFME (Water System Manager Control Status)

 

 

 

 

 

 

NEXT

 

 

PREVIOUS

 

 

SELECT

 

EXIT

 

 

 

 

 

 

OCCDEFCM (Time Schedule Status)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Select a Table

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NEXT

 

PREVIOUS

 

 

SELECT

 

 

 

 

EXIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OCCDEFM (Time

 

 

Schedule Status)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAPACITY (Capacity Control Algorithm)

 

 

 

 

 

 

Data Select Table

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OVERRIDE (Override Status)

 

 

 

 

 

 

 

 

 

 

 

 

NEXT

 

 

PREVIOUS

 

 

 

SELECT

 

 

EXIT

 

 

LL_MAINT (LEADLAG Status)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WSMDEFM2 (Water System Manager Control Status)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OCCPC01S (Local Status)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OCCPC02S (CCN, ICE BUILD Status)

 

Maintenance Table Data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OCCPC03S (CCN Status)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EQUIPMENT CONFIGURATION

 

List the Equipment Configuration Tables

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NET_OPT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BRODEF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OCCEFCS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HOLIDAYS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONSUME

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RUNTIME

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Select a Table

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NEXT

 

PREVIOUS

 

 

SELECT

 

 

EXIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Select a Parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NEXT

 

 

PREVIOUS

 

 

SELECT

 

 

EXIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Modify a Parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INCREASE

 

DECREASE

 

 

QUIT

 

 

 

ENTER

 

(ANALOG VALUES)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ENABLE

 

 

DISABLE

 

 

QUIT

 

 

 

ENTER

 

(DISCRETE VALUES)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTINUED

ON NEXT PAGE

Fig. 16 Ð 19XRT Service Menu Structure

18

SERVICE MENU CONTINUED

FROM PREVIOUS PAGE

 

 

ISM (STARTER CONFIG DATA)

 

 

 

 

EQUIPMENT SERVICE

 

 

 

 

4 4 4 4 (ENTER A 4-DIGIT PASSWORD)

 

 

 

 

 

 

 

Service Tables:

 

 

 

 

 

 

 

OPTIONS

 

 

 

Service Tables:

 

 

 

SETUP1

 

 

 

 

 

 

 

 

 

ISM (STARTER) CONFIG PASSWORD

 

 

SETUP2

 

 

 

 

 

 

 

 

• ISM_CONF

 

 

 

• LEADLAG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• RAMP_DEM

 

 

 

 

 

 

 

• TEMP_CTL

 

 

 

 

 

 

Select a Service Table

 

 

 

 

 

 

 

NEXT

PREVIOUS

SELECT

EXIT

 

 

 

 

 

Select a Service Table Parameter

 

 

 

 

 

 

NEXT

PREVIOUS

SELECT

EXIT

 

 

 

 

 

Modify a Service Table Parameter

 

 

 

 

 

 

INCREASE

DECREASE

QUIT

ENTER

(ANALOG VALUES)

 

 

 

ENABLE

DISABLE

QUIT

ENTER

(DISCRETE VALUES)

 

 

 

TIME AND DATE

 

 

 

 

 

 

 

 

 

 

 

Display Time and Date Table:

 

 

 

 

 

 

To Modify — Current Time

— Day of Week

ATTACH TO NETWORK DEVICE

 

 

— Current Date

— Holiday Today

 

 

 

 

INCREASE

DECREASE

ENTER

EXIT

(ANALOG VALUES)

 

List Network Devices

 

YES

NO

ENTER

EXIT

(DISCRETE VALUES)

 

Local

• Device 6

 

 

• Device 1 • Device 7

 

 

 

 

 

 

 

• Device 2 • Device 8

 

 

 

 

 

 

 

• Device 3 • Device 9

 

 

 

 

 

 

 

• Device 4 • Attach To Any Device

 

 

 

 

 

 

• Device 5

 

 

 

 

 

 

 

Select a Device

 

 

 

 

 

 

 

NEXT

PREVIOUS

SELECT

ATTACH

 

 

 

 

 

Modify Device Address

 

 

 

 

 

 

 

INCREASE

DECREASE

ENTER

EXIT

 

 

 

 

 

Use to attach CVC to another CCN network or device

 

 

 

 

 

Attach to "LOCAL" to enter this machine

 

 

 

 

 

 

To upload new tables

 

 

 

 

 

 

 

LOG OUT OF DEVICE

 

 

 

 

 

 

 

 

 

 

Default Screen

 

 

 

 

 

 

 

CCN

LOCAL

RESET

MENU

 

 

CVC CONFIGURATION

CVC Configuration Table

 

 

 

 

 

 

 

INCREASE

 

DECREASE

 

ENTER

 

 

EXIT

 

 

To Modify — CVC CCN Address

To View — CVC Software Version

 

— English (US IMP) or S.I. Metric Units

 

(last 2 digits of part number

 

— Password

 

 

 

 

 

indicate software version)

 

LEGEND

CCN

Ð Carrier Comfort Network

CVC

Ð Chiller Visual Control

IMP

Ð Imperial

ISM

Ð Integrated Starter Module

PIC II

Ð Product Integrated Control II

Fig. 16 Ð 19XRT Service Menu Structure (cont)

19

3. Press

For Discrete Points Ð Press YES or NO to select the desired state.

For Analog Points Ð Press INCREASE or

4. Press

NOTE: When overriding or changing metric values, it is necessary to hold down the softkey for a few seconds in order to see a value change, especially on kilopascal values.

To Remove an Override

1. On the point status table press NEXT or

PREVIOUS

2. Press

3.Press RELEASE to remove the override and return the point

Override Indication Ð An override value is indicated by

``SUPVSR,'' ``SERVC,'' or ``BEST'' ¯ashing next to the point value on the STATUS table.

TIME SCHEDULE OPERATION (Fig. 17)

1. On

20

2.Press NEXT or PREVIOUS to highlight the desired schedule.

OCCPC01S Ð LOCAL Time Schedule OCCPC02S Ð ICE BUILD Time Schedule

3. Press

4. Press NEXT or PREVIOUS to highlight the de-

5.Press SELECT to access the highlighted period or override

6.a. Press INCREASE or DECREASE to change the time values. Override values are in one-hour incre-

Fig. 17 Ð Example of Time Schedule

Operation Screen

b.Press ENABLE to select days in the day-of-week ®elds. Press DISABLE to eliminate days from the

7. Press ENTER to register the values and to move

8. Press

9.Either return to Step 4 to select another period or override, or press EXIT again to leave the current time schedule

10.The Holiday Designation (HOLIDEF table) may be found in the Service Operation section, page 44. The month, day, and duration for the holiday must be assigned. The Broadcast function in the BRODEF table also must be enabled for holiday periods to function.

TO VIEW AND CHANGE SET POINTS (Fig. 18)

1. To view the SETPOINT table, from the MENU screen

press

 

 

 

19XR_II

SETPOINT

SETPOINT SELECT

 

 

 

Base Demand Limit

100%

 

 

 

Control Point

 

 

 

 

 

 

 

 

LCW Setpoint

 

 

50.0 F

 

 

 

ECW Setpoint

 

 

60.0 F

 

 

 

ICE BUILD Setpoint

 

 

40.0 F

 

 

 

Tower Fan High Setpoint

 

 

85.0 F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.There are 5 set points on this screen: BASE DEMAND LIMIT, LCW SETPOINT (leaving chilled water set point), ECW SETPOINT (entering chilled water set point), ICE BUILD SETPOINT, and TOWER FAN HIGH SETPOINT. Only one of the chilled water set points can be active at one time. The set point that is active is determined from the SERVICE menu. See the Service Operation section, page 44. The ice build (ICE BUILD) function is also activated and con®gured from the SERVICE menu.

3.Press NEXT or PREVIOUS to highlight the desired set

4.Press SELECT to modify the highlighted set point.

5.Press INCREASE or DECREASE to change the selected set point value.

6.Press ENTER to save the changes and return to the previous

SERVICE OPERATION Ð To view the menu-driven programs available for Service Operation, see Service Operation section, page 44. For examples of CVC display screens, see Table 2.

Fig. 18 Ð Example of Set Point Screen

21

Table 2 Ð CVC Display Data

IMPORTANT: The following notes apply to all Table 2 examples.

1.Only 12 lines of information appear on the CVC screen at any one time. Press the NEXT or PREVIOUS softkey to highlight a point or to view items below or above the current screen. Press the NEXT softkey twice to page forward; press the

PREVIOUS softkey twice to page back.

2.To access the information shown in Examples 9 through 21, enter your 4-digit password after pressing the SERVICE softkey. If

no softkeys are pressed for 15 minutes, the CVC automatically logs off (to prevent unrestricted access to PIC II controls) and reverts to the default screen. If this happens, you must reenter your password to access the tables shown in Examples 9 through 21.

3.Terms in the Description column of these tables are listed as they appear on the CVC screen.

4.The CVC may be con®gured in English or Metric (SI) units using the CVC CONFIGURATION screen. See the Service Operation section, page 44, for instructions on making this change.

5.The items in the Reference Point Name column do not appear on the CVC screen. They are data or variable names used in CCN or Building Supervisor (BS) software. They are listed in these tables as a convenience to the operator if it is necessary to cross reference CCN/BS documentation or use CCN/BS programs. For more information, see the 19XRT CCN literature.

6.Reference Point Names shown in these tables in all capital letters can be read by CCN and BS software. Of these capitalized names, those preceded by a dagger can also be changed (that is, written to) by the CCN, BS, and the CVC. Capitalized Reference Point Names preceded by two asterisks can be changed only from the CVC. Reference Point Names in lower case type can be viewed by CCN or BS only by viewing the whole table.

7.Alarms and Alerts: An asterisk in the far right ®eld of a CVC status screen indicates that the chiller is in an alarm state; an exclamation point in the far right ®eld of the CVC screen indicates an alert state. The asterisk (or exclamation point) indicates that the value on that line has exceeded (or is approaching) a limit. For more information on alarms and alerts, see the Alarms and Alerts section, page 15.

 

LEGEND

12T

Ð Motor Overload

CCN

Ð Carrier Comfort Network

CHW

Ð Chilled Water

CR

Ð Control Relay

CT

Ð Current Transformer

CVC

Ð Chiller Visual Control

ECW

Ð Entering Chilled Water

HGBP Ð Hot Gas Bypass

ISM

Ð Integrated Starter Module

LCW

Ð Leaving Chilled Water

LRA

Ð Locked Rotor Amps

mA

Ð Milliamps

P

Ð Pressure

SS

Ð Solid State

T

Ð Temperature

VFD

Ð Variable Frequency Drive

WSM

Ð Water System Manager

EXAMPLE 1 Ð CVC DEFAULT SCREEN

The following data is displayed in the CVC Default screen.

DESCRIPTION

RANGE

UNITS

REFERENCE POINT NAME

DISPLAY

(ALARM HISTORY)

 

 

 

 

(PRIMARY MESSAGE)

 

 

 

 

 

 

 

 

(SECONDARY MESSAGE)

 

 

 

 

 

 

 

 

(DATE AND TIME)

 

 

 

 

 

 

 

 

Compressor Ontime

0-500000.0

HOURS

C

 

HRS

 

Entering Chilled Water

−40-245

DEG F

ECW

 

 

 

CHW IN

Leaving Chilled Water

−40-245

DEG F

LCW

CHW OUT

Evaporator Temperature

−40-245

DEG F

ERT

EVAP REF

Entering Condenser Water

−40-245

DEG F

ECDW

CDW IN

Leaving Condenser Water

−40-245

DEG F

LCDW

CDW OUT

Condenser Temperature

−40-245

DEG F

CRT

COND REF

Oil Pressure

0-420

PSI

OILPD

OILPRESS

Oil Sump Temp

−40-245

DEG F

OILT

OIL TEMP

Average Line Current

0-999

%

AMPS %

AMPS %

 

0-1

 

CCN

 

 

 

 

0-1

 

LOCAL

 

 

0-1

 

RESET

 

NOTE: The last three entries are used to indicate operating mode to the PIC II. These values may be forced by the CVC only.

22

 

 

 

 

 

 

 

 

Table 2 Ð CVC Display Data (cont)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXAMPLE 2 Ð MAINTSTAT DISPLAY SCREEN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To access this display from the CVC default screen:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Press

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MENU

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.

Press

 

 

 

 

will be highlighted).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STATUS

(

MAINSTAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.

Press

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SELECT

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DESCRIPTION

STATUS

UNITS

 

 

 

 

POINT

 

 

Control Mode

NOTE 1

NOTE 1

CMODE

 

 

Run Status

NOTE 2

NOTE 2

RUNSTAT

 

 

Start Inhibit Timer

0-15

min

T

 

 

START

 

 

Occupied ?

0/1

NO/YES

OCC

 

 

 

 

 

 

 

 

 

 

System Alert/Alarm

0-2

NOTE 3

SYS

 

 

 

 

 

ALM

 

 

*Chiller Start/Stop

0/1

STOP/START

CHIL

 

 

 

 

 

 

S S

 

 

*Remote Start Contact

0/1

OFF/ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REMCON

 

 

Temperature Reset

−30-30

DEG F

T

 

 

RESET

 

 

*Control Point

10-120

DEG F

LCW

 

 

 

STPT

 

 

Chilled Water Temp

−40-245

DEG F

CHW

 

 

 

 

 

TMP

 

 

*Active Demand Limit

40-100

%

DEM

 

 

 

 

LIM

 

 

Average Line Current

0-999

%

AMPS

 

 

 

 

 

%

 

 

Motor Percent Kilowatts

0-999

%

KW

 

 

 

 

 

P

 

 

 

Auto Demand Limit Input

4-20

mA

AUTODEM

 

 

Auto Chilled Water Reset

4-20

mA

AUTORES

 

 

Remote Reset Sensor

−40-245

DEG F

R

 

 

 

 

 

RESET

 

 

Total Compressor Starts

0-99999

 

C

 

 

 

 

 

STARTS

 

 

Starts in 12 Hours

0-8

 

 

 

STARTS

 

 

Compressor Ontime

0-500000.0

HOURS

C

 

 

 

 

HRS

 

 

*Service Ontime

0-32767

HOURS

S

 

 

 

 

 

 

HRS

 

 

Ice Build Contact

0-1

OPEN/CLOSE

ICE

 

 

 

 

CON

 

 

Refrigerant Leak Sensor

0-20

mA

REF

 

 

 

 

 

LEAK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

1.Reset, Off, Local, CCN

2.Timeout, Ready, Recycle, Prestart, Start-up, Ramping, Running, Demand, Override, Shutdown, Trippout, Pumpdown, Lockout

3.Normal, Alert, Alarm

4.All variables with capital letter point names are available for CCN read operation. Those shown with (*) support write operations for all CCN devices.

EXAMPLE 3 Ð STARTUP DISPLAY SCREEN

To access this display from the CVC default screen: 1. Press MENU .

2.Press STATUS .

3.Scroll down to highlight STARTUP .

4.Press SELECT .

DESCRIPTION

STATUS

UNITS

 

POINT

Actual Guide Vane Pos

0-100

%

GV

 

 

 

 

 

POS

**Chilled Water Pump

0-1

OFF/ON

CHWP

 

 

 

Chilled Water Flow

0-1

NO/YES

CHW

 

 

FLOW

**Condenser Water Pump

0-1

OFF/ON

CDP

 

 

 

 

 

Condenser Water Flow

0-1

NO/YES

CDW

 

 

FLOW

Oil Pump Relay

0-1

OFF/ON

OILR

 

 

 

 

 

**Oil Pump Delta P

−6.7-200

^PSI

OILPD

Compressor Start Relay

0-1

OFF/ON

CMPR

Compressor Start Contact

0-1

OPEN/CLOSED

1M

 

 

 

AUX

Starter Trans Relay

0-1

OFF/ON

TRANS

Compressor Run Contact

0-1

OPEN/CLOSED

2M

 

AUX

**Tower Fan Relay Low

0-1

OFF/ON

TFR

 

 

 

LOW

**Tower Fan Relay High

0-1

OFF/ON

TFR

 

 

 

HIGH

Starter Fault

0-1

ALARM/NORMAL

 

 

 

STARTFLT

Spare Safety Input

0-1

ALARM/NORMAL

SAFETY

Shunt Trip Relay

0-1

OFF/ON

TRIPR

Starter Fault Status

0-255

 

ISMFLT

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation. Those shown with (**) shall support write operations for the CVC only.

23

Table 2 Ð CVC Display Data (cont)

EXAMPLE 4 Ð COMPRESS DISPLAY SCREEN

To access this display from the CVC default screen: 1. Press MENU .

2.Press STATUS .

3.Scroll down to highlight COMPRESS .

4.Press SELECT .

DESCRIPTION

STATUS

UNITS

POINT

 

Actual Guide Vane Pos

0-100

%

GV

POS

Guide Vane Delta

0-100

%

GV

 

 

 

DELTA

**Target Guide Vane Pos

0-100

%

GV

 

 

 

TRG

Oil Sump Temp

−40-245

DEG F

OILT

 

 

 

 

 

 

 

 

**Oil Pump Delta P

−6.7-200

PSI

OILPD

 

Comp Discharge Temp

−40-245

DEG F

CMPD

 

Comp Thrust Brg Temp

−40-245

DEG F

MTRB

 

Comp Motor Winding Temp

−40-245

DEG F

MTRW

 

Spare Temperature 1

−40-245

DEG F

SPARE

 

T1

Spare Temperature 2

−40-245

DEG F

SPARE

 

T2

Oil Heater Relay

0/1

OFF/ON

OILHEAT

 

 

Diffuser Actuator

0-100

%

DIFF

 

 

ACT

**Target VFD Speed

0-110

%

VFD

 

 

 

OUT

**Actual VFD Speed

0-100

%

VFD

 

 

ACT

Surge Protection Counts

0-5

 

SPC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation. Those shown with (**) shall support write operations for the CVC only.

 

 

 

 

 

 

 

 

 

 

EXAMPLE 5 Ð HEAT

EX DISPLAY SCREEN

 

 

 

 

 

 

 

 

 

 

 

 

To access this display from the CVC default screen:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Press

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MENU

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.

Press

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STATUS

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.

Scroll down to highlight

HEAT

 

EX

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.

Press

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SELECT

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DESCRIPTION

 

STATUS

 

UNITS

 

 

POINT

 

 

**Chilled Water Delta P

 

−6.7-420

 

PSI

CHWPD

 

 

Entering Chilled Water

 

−40-245

 

DEG F

ECW

 

 

 

 

 

 

 

 

 

 

Leaving Chilled Water

 

−40-245

 

DEG F

LCW

 

 

 

 

 

 

 

 

 

 

Chilled Water Delta T

 

−6.7-420

 

^ F

CHW

 

 

 

 

 

DT

 

 

Chill Water Pulldown/Min

 

−20-20

 

^ F

CHW

 

 

 

 

 

 

PULL

 

 

Evaporator Refrig Temp

 

−40-245

 

DEG F

ERT

 

 

 

 

 

 

 

 

 

 

**Evaporator Pressure

 

−6.7-420

 

PSI

ERP

 

 

 

 

 

 

 

 

 

 

Evaporator Approach

 

0-99

 

 

^ F

EVAP

 

 

 

 

APP

 

 

**Condenser Water Delta P

 

−6.7-420

 

PSI

CDWPD

 

 

 

 

 

 

 

Entering Condenser Water

 

−40-245

 

DEG F

ECDW

 

 

 

 

 

 

Leaving Condenser Water

 

−40-245

 

DEG F

LCDW

 

 

 

 

 

 

Condenser Refrig Temp

 

−40-245

 

DEG F

CRT

 

 

 

 

 

 

 

 

 

 

**Condenser Pressure

 

−6.7-420

 

PSI

CRP

 

 

 

 

 

 

 

 

 

 

Condenser Approach

 

0-99

 

 

^ F

COND

 

 

 

 

APP

 

 

Hot Gas Bypass Relay

 

0/1

 

 

OFF/ON

HGBYPASS

 

 

Surge/HGBP Active ?

 

0/1

 

 

NO/YES

SHG

 

 

 

 

 

ACT

 

 

Active Delta P

 

0-200

 

 

PSI

DP

 

 

A

 

 

 

 

 

 

Active Delta T

 

0-200

 

 

DEG F

DT

 

 

A

 

 

 

 

 

 

Surge/HGBP Delta T

 

0-200

 

 

DEG F

DT

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation. Those shown with (**) shall support write operations for the CVC only.

24

Table 2 Ð CVC Display Data (cont)

EXAMPLE 6 Ð POWER DISPLAY SCREEN

To access this display from the CVC default screen: 1. Press MENU .

2.Press STATUS .

3.Scroll down to highlight POWER .

4.Press SELECT .

DESCRIPTION

STATUS

UNITS

 

POINT

Average Line Current

0-999

%

AMPS

%

Actual Line Current

0-99999

AMPS

AMP

 

 

 

 

A

 

Average Line Voltage

0-999

%

VOLT

 

 

 

 

 

 

 

P

Actual Line Voltage

0-99999

VOLTS

VOLT

 

 

 

 

A

Power Factor

0.0-1.0

 

POW

 

 

 

 

 

 

 

FACT

Motor Kilowatts

0-99999

kW

KW

 

 

 

 

 

 

 

 

 

Motor Kilowatt-Hours

0-99999

kWH

KWH

 

 

 

 

 

 

 

 

 

Demand Kilowatts

0-99999

kWH

DEM

 

 

 

 

 

KW

Line Current Phase 1

0-99999

AMPS

AMPS

 

 

 

 

1

Line Current Phase 2

0-99999

AMPS

AMPS

 

 

 

2

Line Current Phase 3

0-99999

AMPS

AMPS

 

 

 

3

Line Voltage Phase 1

0-99999

VOLTS

VOLT

 

1

Line Voltage Phase 2

0-99999

VOLTS

VOLT

 

 

2

Line Voltage Phase 3

0-99999

VOLTS

VOLT

 

 

3

Ground Fault Phase 1

0-999

AMPS

GF

1

 

 

 

 

 

Ground Fault Phase 2

0-999

AMPS

GF

 

2

 

 

 

 

 

Ground Fault Phase 3

0-999

AMPS

GF

 

 

3

 

 

 

 

 

Frequency

0-99

Hz

FREQ

 

 

 

 

 

 

12T Sum Heat-Phase 1

0-200

%

SUM1HEAT

12T Sum Heat-Phase 2

0-200

%

SUM2HEAT

12T Sum Heat-Phase 3

0-200

%

SUM3HEAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation.

 

 

 

 

 

 

 

 

 

 

 

EXAMPLE 7 Ð ISM

STAT SCREEN

 

 

 

 

 

 

 

 

 

 

 

 

To access this display from the CVC default screen:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Press

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MENU

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.

Press

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STATUS

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.

Scroll down to highlight

ISM

 

STAT

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.

Press

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SELECT

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DESCRIPTION

 

STATUS

UNITS

POINT

 

 

ISM Fault Status

 

0-223

 

 

ISMFLT

 

 

 

 

Single Cycle Dropout

 

0-1

 

NORMAL/ALARM

CYCLE

1

 

 

Phase Loss

 

0-1

 

NORMAL/ALARM

PH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOSS

 

 

Overvoltage

 

0-1

 

NORMAL/ALARM

OV

 

 

 

 

 

 

 

VOLT

 

 

Undervoltage

 

0-1

 

NORMAL/ALARM

UN

 

 

 

 

 

 

VOLT

 

 

Current Imbalance

 

0-1

 

NORMAL/ALARM

AMP

 

 

 

 

UNB

 

 

Voltage Imbalance

 

0-1

 

NORMAL/ALARM

VOLT

 

 

UNB

 

 

Overload Trip

 

0-1

 

NORMAL/ALARM

 

 

 

 

 

 

 

 

 

 

OVERLOAD

 

 

Locked Rotor Trip

 

0-1

 

NORMAL/ALARM

LRATRIP

 

 

Starter LRA Trip

 

0-1

 

NORMAL/ALARM

SLRATRIP

 

 

Ground Fault

 

0-1

 

NORMAL/ALARM

GRND

 

FLT

 

 

Phase Reversal

 

0-1

 

NORMAL/ALARM

PH

REV

 

 

 

 

Frequency Out of Range

 

0-1

 

NORMAL/ALARM

 

 

 

 

 

 

 

 

 

 

 

 

FREQFLT

 

 

ISM Power on Reset

 

0-1

 

NORMAL/ALARM

ISM

 

 

 

 

POR

 

 

Phase 1 Fault

 

0-1

 

NORMAL/ALARM

PHASE

 

1

 

 

Phase 2 Fault

 

0-1

 

NORMAL/ALARM

PHASE

 

2

 

 

Phase 3 Fault

 

0-1

 

NORMAL/ALARM

PHASE

 

3

 

 

ICR Start Complete

 

0-1

 

FALSE/TRUE

START

 

OK

 

 

1M Start/Run Fault

 

0-1

 

NORMAL/ALARM

1M

FLT

 

 

 

2M Start/Run Fault

 

0-1

 

NORMAL/ALARM

2M

 

 

 

FLT

 

 

Pressure Trip Contact

 

0-1

 

NORMAL/ALARM

PRS

 

 

TRIP

 

 

Starter Fault

 

0-1

 

NORMAL/ALARM

STRT

 

 

FLT

 

 

Motor Amps Not Sensed

 

0-1

 

NORMAL/ALARM

NO

 

 

 

 

 

 

 

 

 

 

AMPS

 

 

Starter Acceleration Fault

 

0-1

 

NORMAL/ALARM

ACCELFLT

 

 

High Motor Amps

 

0-1

 

NORMAL/ALARM

HIGHAMPS

 

 

1CR Stop Complete

 

0-1

 

FALSET/TRUE

STOP

 

OK

 

 

1M/2M Stop Fault

 

0-1

 

NORMAL/ALARM

1M2MSTOP

 

 

Motor Amps When Stopped

 

0-1

 

NORMAL/ALARM

AMPSTOP

 

 

Hardware Failure

 

0-1

 

NORMAL/ALARM

HARDWARE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation.

25

Table 2 Ð CVC Display Data (cont)

EXAMPLE 8 Ð SETPOINT DISPLAY SCREEN

To access this display from the CVC default screen: 1. Press MENU .

2.Press SETPOINT (Base Demand Limit will be highlighted).

3.Press SELECT .

DESCRIPTION

STATUS

UNITS

POINT

DEFAULT

Base Demand Limit

 

 

 

 

 

 

 

 

 

 

 

 

Control Point

40-100

%

DLM

 

 

 

 

100

LCW Set Point

10-120

DEG F

lcw

 

sp

50.0

ECW Set Point

15-120

DEG F

ecw

 

 

 

 

 

sp

60.0

Ice Build Set Point

15-60

DEG F

ice

 

 

 

sp

40.0

Tower Fan High Set Point

55-105

DEG F

TFH

 

 

SP

75

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: All variables are available for CCN read operation; forcing shall not be supported on set point screens.

EXAMPLE 9 Ð CAPACITY DISPLAY SCREEN

To access this display from the CVC default screen: 1. Press MENU .

2.Press SERVICE .

3.Scroll down to highlight CONTROL ALGORITHM STATUS .

4.Press SELECT .

5.Scroll down to highlight CAPACITY .

DESCRIPTION

STATUS

UNITS

POINT

Entering Chilled Water

−40-245

DEG F

ECW

 

 

 

 

Leaving Chilled Water

−40-245

DEG F

LCW

 

 

 

 

Capacity Control

 

 

 

 

 

 

 

 

 

 

 

Control Point

10-120

DEG F

ctrlpt

 

 

 

 

Control Point Error

−99-99

DEG F

cperr

 

 

 

 

ECW Delta T

−99-99

DEG F

ecwdt

 

 

 

 

ECW Reset

−99-99

DEG F

ecwres

LCW Reset

−99-99

DEG F

lcwres

Total Error + Resets

−99-99

DEG F

error

 

 

 

 

Guide Vane Delta

−2-2

%

gvd

 

 

 

 

Target Guide Vane Pos

0-100

%

GV

 

 

 

 

TRG

Actual Guide Vane Pos

0-100

%

GV

 

 

 

 

POS

Target VFD Speed

0-100

%

VFD

 

 

 

OUT

Actual VFD Speed

0-100

%

VFD

 

 

 

ACT

VFD Gain

0.1-1.5

 

VFD

 

 

 

 

CTRL

Demand Inhibit Active

0-1

NO/YES

DEM

 

 

 

 

 

INH

Amps/kW Ramp

0-100

%

DMDLIM

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance screen.

26

Table 2 Ð CVC Display Data (cont)

EXAMPLE 10 Ð OVERRIDE DISPLAY SCREEN

To access this display from the CVC default screen: 1. Press MENU .

2.Press SERVICE .

3.Scroll down to highlight CONTROL ALGORITHM STATUS .

4.Press SELECT .

5.Scroll down to highlight OVERRIDE .

DESCRIPTION

STATUS

UNITS

 

 

 

POINT

Comp Motor Winding Temp

−40-245

DEG F

MTRW

Comp Motor Temp Override

150-200

DEG F

MT

 

 

 

 

 

OVER

Condenser Pressure

0-420

PSI

CRP

 

 

 

 

 

 

Cond Press Override

90-180

PSI

CP

OVER

Evaporator Refrig Temp

−40-245

DEG F

ERT

 

 

 

 

 

 

 

 

 

Evap Ref Override Temp

2-45

DEG F

ERT

 

 

 

 

OVER

Comp Discharge Temp

−40-245

DEG F

CMPD

 

 

 

 

 

Comp Discharge Alert

125-200

DEG F

CD

 

 

ALEERT

Comp Thrust Brg Temp

−40-245

DEG F

MTRB

 

 

 

Comp Thrust Brg Alert

165-185

DEG F

TB

 

ALERT

Actual Superheat

−20-99

^ F

SUPRHEAT

Superheat Required

6-99

^ F

SUPR REQ

Condenser Refrig Temp

−40-245

DEG F

CRT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance screens.

EXAMPLE 11 Ð LL MAINT DISPLAY SCREEN

To access this display from the CVC default screen: 1. Press MENU .

2.Press SERVICE .

3.Scroll down to highlight CONTROL ALGORITHM STATUS .

4.Press SELECT .

5. Scroll down to highlight LL MAINT. .

DESCRIPTION

STATUS

UNITS

POINT

Lead Lag Control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEAD/LAG:

NOTE 1

 

leadlag

 

 

 

Con®guration Current Mode

NOTE 2

 

llmode

 

 

 

Load Balance Option

0/1

DSABLE/ENABLE

loadbal

 

 

 

LAG START TIME

2-60

MIN

lagstart

 

 

 

LAG STOP TIME

2-60

MIN

lagstop

 

 

 

PRESTART FAULT Time

2-30

MIN

pre¯t

 

 

 

Pulldown: Delta T/Min

x.xx

^ DEG

pull

 

 

dt

 

 

 

Satis®ed?

0/1

NO/YES

pull

 

 

 

sat

LEAD CHILLER in Control

0/1

NO/YES

leadctrl

 

 

 

 

 

 

 

LAG CHILLER: Mode

NOTE 3

 

lagmode

 

 

 

Run Status

NOTE 4

 

lagstat

 

 

 

Start/Stop

NOTE 5

 

lag

 

s

 

s

Recovery Start Request

0/1

NO/YES

lag

 

 

 

 

rec

 

 

 

STANDBY CHILLER: Mode

NOTE 3

 

stdmode

 

 

 

Run Status

NOTE 4

 

stdstat

 

 

 

Start/Stop

NOTE 5

 

Std

 

 

s

 

 

 

s

Recovery Start Request

0/1

NO/YES

std

 

 

 

rec

 

 

 

Spare Temperature 1

−40-245

DEG F

SPARE

 

 

 

 

T1

Spare Temperature 2

−40-245

DEG F

SPARE

 

 

 

T2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

1.DISABLE, LEAD, LAG, STANDBY, INVALID

2.DISABLE, LEAD, LAG, STANDBY, RECOVERY, CONFIG

3.Reset, Off, Local, CCN

4.Timeout, Ready, Recycle, Prestart, Startup Ramping, Running, Demand, Override, Shutdown, Trippout, Pumpdown, Lockout

5.Stop, Start, Retain

6.All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance screens.

27

Table 2 Ð CVC Display Data (cont)

EXAMPLE 12 Ð ISM HIST DISPLAY SCREEN

To access this display from the CVC default screen: 1. Press MENU .

2.Press SERVICE .

3.Scroll down to highlight CONTROL ALGORITHM STATUS .

4.Press SELECT .

5.Scroll down to highlight ISM HIST .

DESCRIPTION

STATUS

UNITS

POINT

ISM FAULT HISTORY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Values At Last Fault:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Line Current Phase 1

0-99999

AMPS

AMPS

 

 

H1

Line Current Phase 2

0-99999

AMPS

AMPS

 

 

 

 

 

H2

Line Current Phase 3

0-99999

AMPS

AMPS

 

 

 

 

 

H3

Line Voltage Phase 1

0-99999

VOLTS

VOLTS

 

 

 

 

 

 

 

 

H1

Line Voltage Phase 2

0-99999

VOLTS

VOLTS

 

 

 

 

 

 

 

H2

Line Voltage Phase 3

0-99999

VOLTS

VOLTS

 

 

 

 

 

 

 

H3

Ground Fault Phase 1

0-999

AMPS

GRFT

 

 

H31

Ground Fault Phase 2

0-999

AMPS

GRFT

 

 

 

 

H23

Ground Fault Phase 3

0-999

AMPS

GRFT

 

 

 

 

H12

I2T Sum Heat-Phase 1

0-200

%

SUM1HT

 

 

 

 

 

 

H

I2T Sum Heat-Phase 2

0-200

%

SUM2HT

 

 

 

 

 

 

H

I2T Sum Heat-Phase 3

0-200

%

SUM3HT

 

 

 

 

 

H

Phase 1 Faulted?

0/1

NO/YES

PHASE

 

 

 

 

 

 

H1

Phase 2 Faulted?

0/1

NO/YES

PHASE

 

 

 

 

 

 

 

H2

Phase 3 Faulted?

0/1

NO/YES

PHASE

 

 

 

 

 

 

 

 

H3

Line Frequency

0-99

Hz

FREQ

 

 

 

H

 

 

ISM Fault Status

0-9999

 

ISMFLT

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance screens.

EXAMPLE 13 Ð WSMDEFME DISPLAY SCREEN

To access this display from the CVC default screen: 1. Press MENU .

2.Press SERVICE .

3.Scroll down to highlight CONTROL ALGORITHM STATUS .

4.Press SELECT .

5.Scroll down to highlight WSMDEFME .

DESCRIPTION

STATUS

UNITS

POINT

WSM Active?

0/1

NO/YES

WSMSTAT

Chilled Water Temp

0.0-99.9

DEG F

CHWTEMP

Equipment Status

0/1

OFF/ON

CHLRST

Commanded State

XXXXXXXX

TEXT

CHLRENA

CHW setpt Reset Value

0.0-25.0

DEG F

CHWRVAL

Current CHW Set Point

0.0-99.9

DEG F

CHWSTPT

 

 

 

 

NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance screens.

28

Table 2 Ð CVC Display Data (cont)

EXAMPLE 14 Ð NET OPT DISPLAY SCREEN

To access this display from the CVC default screen: 1. Press MENU .

2.Press SERVICE .

3.Scroll down to highlight EQUIPMENT CONFIGURATION .

4.Press SELECT .

5.Scroll down to highlight NET OPT .

DESCRIPTION

STATUS

UNITS

POINT

DEFAULT

Loadshed Function

 

 

 

 

 

 

Group Number

0-99

 

LDSGRPN

0

Demand Limit Decrease

0-60

%

LDSDLTA

20

Maximum Loadshed Time

0-120

MIN

MAXSHED

60

CCN Occupancy Con®g:

 

 

 

 

 

 

Schedule Number

3-99

 

OCC

 

NUM

3

Broadcast Option

0-1

DSABLE/ENABLE

OCCBRST

DSABLE

Alarm Con®guration

 

 

 

 

 

 

Re-alarm Time

0-1440

MIN

RETIME

30

Alarm Routing

0-1

 

ROUTING

10000000

 

 

 

 

 

 

 

NOTE: No variables are available for CCN read or write operation.

EXAMPLE 15 Ð ISM CONF DISPLAY SCREEN

To access this display from the CVC default screen: 1. Press MENU .

2.Press SERVICE .

3.Scroll down to highlight ISM (STARTER) CONFIG DATA .

4.Press SELECT .

5.Scroll down to highlight ISM CONF .

DESCRIPTION

STATUS

UNITS

 

 

POINT

DEFAULT

Starter Type

0-2

 

starter

1

(0 = Full, 1 = Red, 2 = SS/VFD)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor Rated Line Voltage

200-13200

VOLTS

v

 

fs

 

 

 

 

460

Volt Transformer Ratio:1

1-33

 

vt

 

 

 

 

 

rat

1

Overvoltage Threshold

105-115

%

 

 

 

overvolt

115

Undervoltage Threshold

85-95

%

undvolt

85

Over/Under Volt Time

1-10

SEC

uvuntime

5

Voltage % Imbalance

1-10

%

v

unbal

10

Voltage Imbalance Time

1-10

SEC

v

 

 

 

 

 

time

5

Motor Rated Load Amps

10-5000

AMPS

a

 

 

 

 

 

 

fs

 

 

 

 

200

Motor Locked Rotor Trip

100-60000

AMPS

 

motor

 

 

 

lr

1000

Locked Rotor Start Delay

1-10

cycles

lrdelay

 

 

 

 

5

Starter LRA Rating

100-60000

AMPS

start

 

 

 

lr

2000

Motor Current CT Ratio:1

3-1000

 

ct

 

 

 

 

turns

100

Current % Imbalance

5-40

%

c

 

 

 

 

 

 

unbal

15

Current Imbalance Time

1-10

SEC

c

 

 

 

time

5

3 Grnd Fault CT's? (1 = No)

0-1

NO/YES

gf

 

 

 

phase

YES

Ground Fault CT Ratio:1

150

 

gf

 

 

 

 

 

ctr

150

Ground Fault Current

1-25

AMPS

gf

 

 

 

 

amps

15

Ground Fault Start Delay

1-20

cycles

gf

 

 

 

 

delay

10

Ground Fault Persistence

1-10

cycles

gf

 

 

 

 

pers

5

Single Cycle Dropout

0/1

DSABLE/ENABLE

 

cycdrop

DSABLE

Frequency = 60 Hz? (No = 50)

0/1

NO/YES

freq

 

 

 

 

YES

Line Frequency Faulting

0/1

DSABLE/ENABLE

freq

en

DSABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: No variables are available for CCN read or write operation.

29

Table 2 Ð CVC Display Data (cont)

EXAMPLE 16 Ð OPTIONS DISPLAY SCREEN

To access this display from the CVC default screen: 1. Press MENU .

2.Press SERVICE .

3.Scroll down to highlight EQUIPMENT SERVICE .

4.Press SELECT .

5.Scroll down to highlight OPTIONS .

DESCRIPTION

STATUS

UNITS

POINT

DEFAULT

Auto Restart Option

0/1

DSABLE/ENABLE

ASTART

DSABLE

Remote Contacts Option

0/1

DSABLE/ENABLE

MODES

DSABLE

Soft Stop Amps Threshold

40-100

%

STRTSTOP

100

Surge/Hot Gas Bypass

 

 

 

 

 

 

 

 

 

 

 

 

Surge Limit/HGBP Option

0/1

 

srg hgbp

0

Select: Surge = 0, HGBP = 1

 

 

 

 

 

 

 

 

 

 

 

 

Min. Load Point (T1/P1)

 

 

 

 

 

 

 

 

 

 

 

 

Surge/HGBP Delta T1

0.5-20

^ F

hgb

dt1

1.5

Surge/HGBP Delta P1

30-170

PSI

hgb

 

 

 

 

dp1

50

Full Load Point (T2/P2)

 

 

 

 

 

 

 

 

 

 

 

 

Surge/HGBP Delta T2

0.5-20

^ F

hgb

dt2

10

Surge/HGBP Delta P2

50-170

PSI

hgb

 

 

 

dp2

85

Surge/HGBP Deadband

0.5-3

^ F

hgb

 

 

 

db

1

Surge Protection

 

 

 

 

 

 

 

 

 

 

 

 

Surge Delta % Amps

5-20

%

surge

 

a

10

Surge Time Period

7-10

MIN

surge

 

 

 

t

8

Ice Build Control

 

 

 

 

 

 

 

 

 

 

 

 

Ice Build Option

0/1

DSABLE/ENABLE

ibopt

 

 

 

DSABLE

Ice Build Termination

0-2

 

ibterm

0

0 = Temp, 1 = Contacts, 2 = Both

 

 

 

 

 

 

 

 

 

 

 

 

Ice Build Recycle

0/1

DSABLE/ENABLE

ibrecyc

DSABLE

Refrigerant Leak Option

0/1

DSABLE/ENABLE

LEAK

 

 

 

EN

DSABLE

Refrigerant Leak Alarm mA

4-20

mA

LEAK

 

 

 

MA

20

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: No variables are available for CCN read or write operation.

EXAMPLE 17 Ð SETUP1 DISPLAY SCREEN

To access this display from the CVC default screen: 1. Press MENU .

2.Press SERVICE .

3.Scroll down to highlight EQUIPMENT SERVICE .

4.Press SELECT .

5.Scroll down to highlight SETUP1 .

DESCRIPTION

STATUS

UNITS

 

 

 

 

 

POINT

DEFAULT

Comp Motor Temp Override

150-200

DEG F

MT

 

 

OVER

200

Cond Press Override

90-165

PSI

CP

 

 

 

 

 

OVER

125

Comp Discharge Alert

125-200

DEG F

C

 

 

 

 

 

ALERT

200

Comp Thrust Brg Alert

165-185

DEG F

 

 

 

 

 

 

ALERT

175

TB

 

Chilled Medium

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0/1

WATER/BRINE

MEDIUM

WATER

Chilled Water Deadband

.5-2.0

^F

CS

 

 

DB

 

 

 

 

 

1.0

Evap Refrig Trippoint

0.0-40.0

DEG F

ERT

 

 

 

 

 

 

 

TRIP

33

Refrig Override Delta T

2.0-5.0

^F

REF

 

 

 

 

 

 

 

OVER

3

Condenser Freeze Point

−20 - 35

DEG F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

34

CDFREEZE

Evap Flow Delta P Cutout

0.5 - 50.0

PSI

EVAP CUT

5.0

Cond Flow Delta P Cutout

0.5 - 50.0

PSI

COND

 

 

 

 

 

 

 

CUT

5.0

Water Flow Verify Time

0.5-5

MIN

WFLOW

 

 

 

 

 

 

 

T

5

Oil Press Verify Time

15-300

SEC

OILPR

 

T

 

40

Recycle Control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Recycle Restart Delta T

2.0-10.0

DEG F

RCYCR

 

 

 

DT

5

Recycle Shutdown Delta

0.5-4.0

DEG F

RCYCS

 

 

 

 

DT

1

SPARE ALERT/ALARM ENABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Disable=0, Lo=1/3,Hi=2/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Spare Temp #1 Enable

0.4

 

sp1

 

 

 

 

en

 

 

 

 

 

0

Spare Temp #1 Limit

−40-245

DEG F

sp1

 

 

 

 

 

lim

 

 

 

 

 

245

Spare Temp #2 Enable

0-4

 

sp2

 

 

 

 

 

en

 

 

 

 

 

0

Spare Temp #2 Limit

-40-245

DEG F

sp2

 

 

 

 

 

lim

 

 

 

 

 

245

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: No variables are available for CCN read operation; forcing shall not be supported on service screens.

30

Loading...
+ 82 hidden pages