Blodgett MG3270 Installation Manual

4.5 (4)
Blodgett MG3270 Installation Manual

BLODGETT CONVEYOR

STARTUP AND CALIBRATION GUIDE

BLODGETT OVEN COMPANY

www.blodgettcorp.com

50 Lakeside Avenue, Box 586, Burlington, Vermont 05402 USA Telephone (800) 331-5842, (802) 860-3700 Fax: (802)864-0183

PN M9437 Rev E (6/01)

E 2000 --- G.S. Blodgett Corporation

Table of Contents

Introduction

Pre-Startup Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Manual Control Startup

Control Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Gas Pressure Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Temperature Control Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Temperature Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Motor Control Board Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Belt Speed Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Closed Loop --- Dart Microdrive MDP . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Open Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Convection Blowers and Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Computer Control Startup

Control Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Gas Pressure Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Convection Blowers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Computer Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Temperature Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Belt Speed Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Closed Loop Single Belt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Open Loop Twin Belt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Motor Control Board Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

PLC Control Startup

Control Identification and Registration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Gas Pressure Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Convection Blowers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Temperature Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Belt Speed Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Introduction

Pre-Startup Requirements

OWNER’S RESPONSIBILITIES

A minimum of 5 to 7 working days are needed to schedule a start-up procedure.

Before a factory representative, or a factory trained representative, arrives to perform a startup procedure, the owner MUST ALREADY have satisfied the following requirements:

1.Gas Models: Installation of an adequate mechanically driven ventilation system for the unit. The ventilation system should replace 80% of the exhaust volume with fresh make up air. The table below can be used as a guideline.

2.Electric supplies installed by a certified professional.

NOTE: Refer to the Owner’s manual provided with the oven for electrical specifications.

3.Gas Models: Gas supplies installed by a certified professional.

NOTE: Refer to the Owner’s manual provided with the oven for gas specifications.

Be sure to size the meter for all gas models as follows:

U.S. installations

a.) Add the total BTU’s/hr of all the gas appliances on the line.

b.) Convert BTU’s to cubic ft/hr using the formula Cu Ft/Hr = 1000 BTU/Hr.

c.) Size the meter accordingly.

General export and Canadian installations

a.) Add the total M3/min of all the appliances on the line.

b.) Size the meter accordingly.

NOTE: Refer to the Owner’s manual provided with

the oven for additional information on utility installation requirements.

SERVICE AGENCY’S RESPONSIBILITIES

Before performing a start-up procedure, the service agency MUST ALREADY have satisfied the following requirements:

1.Assembly of the oven(s).

NOTE: Refer to the Owner’s manual provided with the oven for assembly.

2.Conversion of ovens to other types of gas when required.

Oven

Exhaust Volume -- CFM (M3/min)

Supply Requirements -- CFM (M3/min)

Model

 

 

 

 

 

 

Single

Double

Triple

Single

Double

Triple

 

MT1828G

400-500

800-1000

1200-1500

320-400

640-800

960-1200

 

(14-17)

(23-28)

(34-43)

(12-14)

(18-23)

(27-34)

SG2136G or

400-500

800-1000

1200-1500

320-400

640-800

960-1200

MT2136G

(14-17)

(23-28)

(34-43)

(12-14)

(18-23)

(27-34)

 

 

 

 

 

 

 

SG3240G or

800-1000

1200-1600

2000-2400

640-800

960-1280

1600-1920

MT3240G

(23-28)

(34-46)

(57-68)

(18-23)

(27-36)

(46-54)

 

 

 

 

 

 

 

MT3255G

1000-1400

2000-2800

3000-4100

800-1120

1600-2240

2400-3300

 

(28-40)

(57-79)

(85-116)

(23-32)

(46-64)

(68-93)

MT3270

1200-1650

2400-3300

3600-5000

960-1320

1920-2640

2880-4000

 

(34-47)

(68-93)

(102-142)

(27-37)

(54-75)

(82-113)

MG3270

1200-1650

2400-3300

3600-5000

960-1320

1920-2640

2880-4000

 

(34-47)

(68-93)

(102-142)

(27-37)

(54-75)

(82-113)

MT3855

1000-1400

2400-3300

3600-5000

800-1120

1920-2640

2880-4000

 

(28-40)

(68-93)

(102-142)

(23-32)

(54-75)

(82-113)

 

 

 

 

 

 

 

MT3870

1200-1650

2400-3300

3600-5000

960-1320

1920-2640

2880-4000

 

(34-47)

(68-93)

(102-142)

(27-37)

(54-75)

(82-113)

2

Manual Control Startup

Control Identification

The following instructions are for the standard manual control. See Figure 1 for control identification.

COOK TIME

ON OFF

ACTUAL

SETPOINT

HEAT

 

TEMPERATURE

 

ON

OFF

ON

OFF

 

HEAT

 

BLOWER

CONVEYOR

Figure 1

3

Manual Control Startup

Gas Pressure Adjustments

THE FOLLOWING STARTUP PROCEDURES MUST BE PERFORMED BY A QUALIFIED TECHNICIAN

ONLY.

REGULATED GAS PRESSURE

NOTE: Gas models only.

Incoming static gas pressure to the unit, with all the gas appliances drawing from the supply, should be a minimum of 5.5” W.C. (13.7 mbar) for natural gas and 11” W.C. (28 mbar) for propane gas.

The manifold pressure, if measured after the regulator located inside the control box, must be 3.5” W.C. (9 mbar) for natural gas and 10” W.C. (25 mbar) for propane gas.

The pressure can be checked at the tap on either the dual regulated gas valve or the solenoid valve.

Turn the adjusting screw on the left front side of the dual regulated valve to adjust the gas pressure. Turn the screw clockwise to raise the gas pressure and counter-clockwise to lower it.

PRIMARY AIR ADJUSTMENT

NOTE: Gas models only.

The air shutter disc on the burner blower motor, located inside the control box at the top of the assembly, is factory adjusted to provide the most efficient blue flame possible at sea level.

1.Visually examine the quality of the flame.

2.If it needs adjusting, increase or decrease the air mixture to attain the best flame quality.

Regulator

Cap

Pressure Tap

Regulator

Adjustment

Figure 2

4

Manual Control Startup

Temperature Control Configuration

CONFIGURATION PROCEDURES

NOTE: Follow these configuration procedures to change the factory settings.

To enter the Configuration Menus

1.Press and hold the actual temperature key for approximately 10 seconds. When the menu system has been accessed, the display toggles between dEF and either SP or Act.

Setting the Default Display

The default display determines whether the controller displays the actual or setpoint temperature.

1.Use the arrow keys to select the desired display default.

NOTE: We recommend using the setpoint display default.

2.Press the actual temperature key to enter the selected display default. The display toggles between HYS and a numerical value.

Setting the Control Hysteresis

The control hysteresis, or burner cycle is used to prevent rapid cycling around the setpoint. The hysteresis is adjustable from 2_F to 252_F (1_C to 122_C).

1.Use the arrow keys to select the desired control hysteresis.

NOTE: We recommend 5_F (3_C) initially.

2.Press the actual temperature key to enter the selected hysteresis value. The display toggles between OFF and a numerical value.

Setting the Display Offset

The display offset adjusts the displayed temperature if the actual temperature differs from the temperature seen by the thermocouple. If the actual temperature is lower a positive offset is needed. If the actual temperature is higher a negative offset is needed. The display offset is adjustable from -126_F to +126_F (-87_C to +52_C).

1.Use the arrow keys to select the desired display offset.

2.Press the actual temperature key to enter the selected offset value. The display toggles between ALr and a numerical value.

Setting the Deviation Band Alarm

The deviation band alarm causes the display to flash when the actual temperature varies (in either direction) from the setpoint. The deviation band alarm is adjustable to off or values from 1_F to 252_F (0.5_C to 122_C).

1.Use the arrow keys to select the desired deviation band alarm.

NOTE: We recommend 20_F (11_C).

2.Press the actual temperature key to enter the selected alarm value.

To exit the Configuration Menus

1.Push and hold the actual temperature key for approximately 3 seconds.

NOTE: The unit exits the configuration menus if

the controller is not touched for 1 minute at any time during programming.

SETTING THE DISPLAY UNITS

1.Press and hold the actual temperature key for approximately 10 seconds until the display reads unt and flashes F or c. Press the up or down arrow key to toggle between _F and _C.

2.Press and hold the actual temperature key until the control exits the programming mode.

ACTUAL

SETPOINT

HEAT

Figure 3

5

Manual Control Startup

Temperature Calibration

Low Limit Adjustment

1.Bring the oven to 200_F (93_C).

2.Turn the blower and heat switches to OFF. The blower should continue to run.

3.Monitor the digital temperature control display. The blower motors should shut off within the range of 170-135_F(77-57_C).

4.To adjust the temperature, turn the low-limit potentiometer. A clockwise rotation increases the setting, counter-clockwise decreases it. See Figure 4.

High Limit Adjustment

NOTE: Refer to the wiring diagram shipped with the oven for terminal locations.

1.Remove the wires from the common and N.O. terminals. Touch the wires together to energize the heat circuit. This enables the oven to heat above the highest temperature allowed by the controller.

2.When the display reads 600_F (316_C), the burner blower motor should shut off. If the temperature rises above 600_F (316_C), adjust the hi-limit pot (Figure 4) so the burner shuts off at 600_F (316_C). A clockwise rotation of the high-limit pot increases the temperature, counter-clockwise decreases it.

 

 

 

 

 

 

 

 

P2

 

P1

 

 

P3

 

 

 

 

 

 

 

 

 

 

 

INCREASE

INCREASE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9 T/C 10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

+

 

 

DECREASE

 

 

 

INCREASE

DECREASE DECREASE

 

 

 

 

 

 

 

 

 

LOW LIMIT

HI LIMIT

 

 

 

 

ACTUAL

SETPOINT

HEAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INCREASE

 

 

 

DECREASE

 

 

 

 

 

 

 

 

 

 

HI LIMIT

 

 

 

LOW LIMIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ZYTRON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SERIES 300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Athena Temperature Controller

 

 

 

 

 

 

 

1

3

2

6

5

 

4

7

8

 

 

1

2

3

4

5

6

7

8

115

NO

 

C

NC

NO

C

 

 

 

230 115

NC

C

NO

NO

C

230

 

OUTPUT 1

OUTPUT 2

 

 

 

United Electric Board

 

 

Zytron Board

 

 

 

 

Figure 4

6

Manual Control Startup

Motor Control Board Adjustment

High/low speed motor control board adjustment for 180 and 130 VDC motors

NOTE: This procedure does not apply to Dart Microdrive systems or cooking computers.

NOTE: The motor control board is located on the slide out control panel.

High Speed Motor Adjustment:

1.Turn the cook time control knob on the front panel fully clockwise to decrease the cook time and turn the conveyor belt on.

2.With the motor connected (make no open circuit voltage readings) measure the voltage at the motor leads (A1 & A2 in Figure 5) on the DC control board. If the voltage is not within 3 VDC of the specified voltage continue with step 3.

3.Turn the MAX trim pot counter-clockwise to lower and clockwise to raise the voltage until it is within 3 VDC of the specified voltage.

Low Speed Motor Adjustment:

1.Turn the cook time control knob on the front panel fully counter-clockwise to increase the cook time.

2.With the motor connected (make no open circuit voltage readings) measure the voltage at the motor leads on the DC control board (A1 & A2 in Figure 5). If the voltage is not within 1 VDC of the specified voltage, continue with step 3.

3.Turn the MIN SPEED pot clockwise to lower the voltage and counter-clockwise to raise the voltage.

 

130 Volt System

180 Volt System

Model

Low

 

High

Low

 

High

 

 

 

 

 

 

 

 

 

MT2136

20

 

130

26

 

180

 

 

 

 

 

 

 

MT3255

26

 

130

26

 

180

 

 

 

 

 

 

 

MT3270

26

 

130

26

 

180

 

 

 

 

 

 

 

MG3270

26

 

130

N/A

 

N/A

 

 

 

 

 

 

 

 

 

Minimum Speed Pot

 

 

 

 

 

 

 

 

 

 

 

 

Torque (current) limiting adjustment

 

 

 

 

 

 

 

 

Maximum Speed Pot

 

 

 

 

 

 

(DO NOT ADJUST)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yellow or Violet (pin 12)

ACC

MAX

MIN

TORQ

ON

 

 

Orange or Gray (pin 10)

 

 

TP1

 

 

 

 

 

 

 

 

 

 

 

Blue (pin 8)

 

 

TP2

 

 

Violet

Gray

 

J1

 

 

 

REG

Blue

 

 

 

 

 

 

 

 

 

 

 

 

FL

 

 

 

 

 

 

 

TB1

 

 

 

 

 

Speed Pot

L

N

A1

A2

FA

 

 

Line Hot (VAC)

+

Barrier Terminal Block TB1

 

Line Neutral (VAC)

-

Power Line and Motor Ground

 

PM Motor Armature

 

REMOVE RED PLUG FROM TOP OF DC MOTOR PRIOR TO OPERATING!

Warning: Circuit components are not at ground potential! Use only a non-metallic or insulated adjustment tool. Shock hazards may occur with conducting tools!

Figure 5

7

Manual Control Startup

Belt Speed Calibration

CLOSED LOOP -- DART MICRODRIVE MDP

1.Remove the top cover. The internal dip switch is located next to the transformer.

Dip Switch Detail

 

 

 

 

 

 

 

O

1

2

3

4

5

6

7

8 N

Figure 6

PROGRAMMING THE MDP CONTROL

NOTE: Any variable can be changed WITHOUT resetting the others.

To Enter the Program Mode

1.Set DIP switches 1, 2, 3, 4, 5, 6 and 8 to OFF. Set DIP switch 7 to ON. The motor stops.

2.The display reads PROG.

NOTE: In rate mode the current decimal point is also displayed.

Time or Rate Mode (Displayed Decimal Place)

This allows settings to be made in the proper units.

1.Set DIP switch 4 to ON.

2.The current decimal point (if any) will be lit. The display gives the current value of the decimal place variable. To change press the up or down arrow keys. Use 0-4 for the rate mode. Use 5 for the time mode.

NOTE: The decimal point will not be lit if the unit is currently in the time mode.

3.When finished, flip DIP switch 4 to OFF.

4.The display reads PROG.

K Constant

1.Flip DIP switch 1 to ON.

2.The display gives the current value for the constant. To change press the up or down arrow keys.

NOTE: For ovens with a 70” (178 cm) tunnel the preset constant is 5:20. For ovens

with a 55” (140 cm) tunnel the preset constant is 4:08.

3.When finished, set DIP switch 1 to OFF.

4.The display reads PROG.

NOTE: If you change the constant, the display set-

ting will be set to the slowest speed when you exit the programming mode.

Minimum Setting

1.Flip DIP switch 2 to ON.

2.The display gives the current value for the lower limit. To change press the up or down arrow keys.

3.When finished flip DIP switch 2 to OFF.

4.The display reads PROG.

Maximum Setting

1.Flip DIP switch 3 to ON.

2.The display gives the current value for the upper limit. To change press the up or down arrow keys.

3.When finished flip DIP switch 3 to OFF.

4.The display reads PROG.

To Exit the Program Mode

1.Make sure DIP switch 5 (Master/Follower Mode select) is in the desired position

(ON = Follower; OFF= Master).

NOTE: In most cases DIP switch 5 should be set to the master position (OFF).

2.Set DIP switches 1, 2, 3, 4, 6 and 8 to OFF.

3.If satisfied with programming values, set DIP switch 7 to OFF. The control operates using the new programmed variables.

CHECKING THE BELT SPEED CALIBRATION

Place a pan on the belt and start the conveyor.

1.Begin timing the belt’s speed when the trailing edge of the pan enters the oven.

2.End the timing cycle when the trailing edge of the pan exits the oven.

3.If the displayed time differs from the actual more than 5 seconds, reprogram the K constant.

8

Loading...
+ 19 hidden pages