Cisco Systems 6509-NEB User Manual

Size:
1.54 Mb
Download

Catalyst 6509-NEBSwitch and CiscoOSR-7609

Router Upgrade Note

Note

Note

Product Number: WS-6509-NEB-UPGRD=

This publication describes how to upgrade your Catalyst 6509-NEBswitch or CiscoOSR-7609Router to use the Supervisor Engine 720 and the Supervisor Engine 32.

AC-Input Systems—Ifyour switch or router is using anAC-inputpower supply, you are required to install theWS-CAC-3000Wpower supply. The 3000 WAC-inputprovides a power output to power the fan tray.

DC-Input Systems—Ifyour switch or router is using aDC-inputpower supply, you are required to install theWS-CDC-2500WorPWR-4000-DCpower supply. You must provide a separate, direct connection to power the fan tray. Each input of the fan tray is rated 10 A @-40to-60VDC.

Caution It is important that you follow the steps in this document in the order they are presented.

Corporate Headquarters:

Cisco Systems, Inc., 170 West Tasman Drive, San Jose, CA 95134-1706USA

Copyright © 2004–2006Cisco Systems, Inc. All rights reserved.

Contents

Contents

This publication consists of the following sections:

Safety Overview, page 2

Parts List, page 3

Required Tools, page 3

Installation Guidelines, page 4

Shutting Down the System, page 4

Replacing the Panel Safety Cover, page 5

Replacing the Fan Tray, page 7

Replacing the Power Supply, page 10

Connecting Power to the Fan Tray, page 13

Replacing the Supervisor Engine, page 17

Powering Up the System, page 21

Verifying Installation, page 22

Related Documentation, page 23

Obtaining Documentation, page 23

Documentation Feedback, page 24

Cisco Product Security Overview, page 24

Obtaining Technical Assistance, page 25

Obtaining Additional Publications and Information, page 27

Safety Overview

Safety warnings appear throughout this publication in procedures that, if performed incorrectly, may harm you. A warning symbol precedes each warning statement.

Warning IMPORTANT SAFETY INSTRUCTIONS

This warning symbol means danger. You are in a situation that could cause bodily injury. Before you work on any equipment, be aware of the hazards involved with electrical circuitry and be familiar with standard practices for preventing accidents. Use the statement number provided at the end of each warning to locate its translation in the translated safety warnings that accompanied this device. Statement 1071

SAVE THESE INSTRUCTIONS

Warning Before performing any of the following procedures, ensure that power is removed from the DC circuit.

Statement 1003

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

2

78-16162-02

 

 

Parts List

Warning This unit might have more than one power supply connection. All connections must be removed tode-energizethe unit.Statement 1028

Warning Only trained and qualified personnel should be allowed to install, replace, or service this equipment.

Statement 1030

Warning Hazardous voltage or energy is present on the backplane when the system is operating. Use caution when servicing.Statement 1034

Warning This product requiresshort-circuit(overcurrent) protection, to be provided as part of the building installation. Install only in accordance with national and local wiring regulations.Statement 1045

Warning When installing or replacing the unit, the ground connection must always be made first and disconnected last.Statement 1046

Parts List

The following items are included in the upgrade kit:

One high speed fan tray

The high speed fan tray provides additional cooling for the Supervisor Engine 720 and the Supervisor Engine 32.

The high speed fan tray requires external power, either from the 3000 W AC-inputpower supply or from an external DC power source. The fan tray ships with power wires secured at each terminal block. Use these wires to connect the fan tray to the 3000 WAC-inputpower supply using the supplied cable, or remove them to connect to a DC power source.

One panel safety cover

The panel safety cover provides increased chassis airflow.

Two fan tray power cables (for AC-inputsystems)

The fan tray power cable provides a connection between the fan tray and the 3000 W AC-inputpower supply. Two cables are provided for systems with redundant power supplies.

Required Tools

These tools are required to perform the installation:

Number 1 Phillips-headscrewdriver

Number 2 Phillips-headscrewdriver

Flat-bladescrewdriver (forDC-inputsystems)

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

 

78-16162-02

3

 

 

 

Installation Guidelines

Installation Guidelines

Follow these guidelines when upgrading the chassis:

If your switch or router is using an AC-inputpower supply, you are required to install theWS-CAC-3000Wpower supply. The 3000 WAC-inputprovides a power output to power the fan tray.

If your switch or router is using a DC-inputpower supply, you are required to install theWS-CDC-2500WorPWR-4000-DCpower supply. You must provide a separate, direct connection to power the fan tray. Each input of the fan tray is rated 10 A @-40to-60VDC.

Observe the following cautions:

Caution It is important that you follow the steps in this document in the order they are presented.

Caution Always use an ESD wrist strap when handling modules or coming into contact with internal components.

Caution Use both hands to install and remove power supplies. Each Catalyst 6500 seriesAC-inputpower supply weighs between 22 pounds (9.9 kg) and 28 pounds (12.6 kg).

Caution Do not exert too much pressure on the ejector levers. They will bend and be damaged.

Caution In a system with dual power supplies, connect each power supply to a separate input source. In case of a power source failure, the second source will most likely still be available.

Shutting Down the System

To perform the upgrade, you must shut down the system.

Before you shut down the system, you should first upload the current configuration to a server. This saves time when bringing the module back online. You can recover the configuration by downloading it from the server to the nonvolatile memory of the supervisor engine. For more information, refer to the “Working with Configuration Files” chapter in the Catalyst 6500 Series Software Configuration Guide.

To properly shut down the system, follow these steps:

Step 1 Upload the current configuration to a server. On any modules running Cisco IOS, save the running configuration.

Warning Before working on a system that has an on/off switch, turn OFF the power and unplug the power cord.

Statement 1

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

4

78-16162-02

 

 

Replacing the Panel Safety Cover

Warning This unit might have more than one power supply connection. All connections must be removed tode-energizethe unit.Statement 1028

Step 2 Depending on how your system is powered, perform one of the two sets of substeps below.

AC-InputSystems

a.Turn the power switch to the Off (0) position on each power supply. Turning the power switch off also disengages a pawl that unlocks the power supply from the chassis.

b.Disconnect the power cord from the power source.

c.Loosen the screw on the cable retention device, and disconnect the power cord from the power supply being removed.

Note The AC power cord for the 4000 W power supply is hard wired and cannot be removed from the supply.

Warning Before performing any of the following procedures, ensure that power is removed from the DC circuit.

Statement 1003

DC-InputSystems

a.Verify that power is off to the DC circuit for each power supply. As an added safety precaution, you should secure the source DC circuit breaker switch in the OFF position with electrical tape.

b.Turn the power switch to the Off (0) position on each power supply. Turning the power switch off also disengages a pawl that unlocks the power supply from the chassis.

Replacing the Panel Safety Cover

This section describes how to remove and install the panel safety cover for the Catalyst 6509-NEBswitch and CiscoOSR-7609Router. A number 1Phillips-headscrewdriver is required to perform this procedure.

Caution Always use an ESD wrist strap when handling modules or coming into contact with internal components.

Warning Hazardous voltage or energy is present on the backplane when the system is operating. Use caution when servicing.Statement 1034

To remove the panel safety cover, perform these steps:

Step 1 Use a number 1Phillips-headscrewdriver to remove the 8 panel screws, 4 each located along the top and bottom of the chassis. (SeeFigure 1.) Set the screws aside.

Step 2 Grasp the panel handle and pull the panel away from the chassis.

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

 

78-16162-02

5

 

 

 

Replacing the Panel Safety Cover

Figure 1 Removing the Panel Safety Cover

Panel handle

105072

Step 3 On the new panel safety cover, grasp the panel handle and press the panel into place, starting at the bottom of the chassis and working up. Be careful not to damage the EMI gasket.

Step 4 Use a number 1Phillips-headscrewdriver to install the 8 panel screws, 4 each located along the top and bottom of the chassis. (SeeFigure 2.)

Step 5 Proceed to the “Replacing the Fan Tray” section on page 7 to replace the fan tray.

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

6

78-16162-02

 

 

Replacing the Fan Tray

Figure 2 Installing the Panel Safety Cover

105071

Replacing the Fan Tray

This section describes how to remove and install the fan tray for the Catalyst 6509-NEBswitch and CiscoOSR-7609Router. Aflat-bladeor number 2Phillips-headscrewdriver is required to perform this procedure.

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

 

78-16162-02

7

 

 

 

Replacing the Fan Tray

Removing the Fan Tray

Warning When removing the fan tray, keep your hands and fingers away from the spinning fan blades. Let the fan blades completely stop before you remove the fan tray.Statement 258

To remove the existing fan tray, follow these steps:

Step 1 Use aflat-bladeor number 2Phillips-headscrewdriver to loosen the two captive installation screws on the fan tray by turning them counterclockwise. (SeeFigure 3.)

Figure 3 Removing the Fan Tray

Captive installation screw

FAN

STATUS

Captive installation screw

 

STATUS

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

STATUS

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

STATUS

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

STATUS

STATUS

STATUS

LINK

LINK

LINK

LINK

LINK

LINK

 

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

 

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

 

SUPERVISOR2

STATUS SYSTEM CONSOLE PWR MGMT RESET

2GE-SUP2-X6K-WS

SUPERVISOR2

STATUS SYSTEM CONSOLE PWR MGMT RESET

2GE-SUP2-X6K-WS

o

o

INPUT

FAN

OUTPUT

OK

OK

FAIL

INPUT

FAN

OUTPUT

OK

OK

FAIL

30696

Step 2 Grasp the fan tray handle with one hand and pull the fan tray outward about 1 inch; rock it gently, if necessary, to unseat the power connector from the backplane. Wait for the fans to stop spinning.

Step 3 Once the fans have stopped spinning, pull the fan tray out further and support the underside of the fan tray with the other hand.

Step 4 Pull the fan tray clear of the chassis, and put it in a safe place.

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

8

78-16162-02

 

 

Replacing the Fan Tray

Installing the High Speed Fan Tray

To install the high speed fan tray, follow these steps:

Step 1 Hold the fan tray with the fans facing down and the FAN FAIL LED on the right. (SeeFigure 4.)

Figure 4 Installing the High Speed Fan Tray

Captive installation screw

48V INPUT 1

INPOUT POWER

GOOD

RTN -48VDCGND

WS-C6500-NEB-FAN2

Captive installation screw

 

HIGH SPEED FAN

 

STATUS

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

STATUS

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

STATUS

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

 

48V INPUT 2

SUPERVISOR2

 

2GE-SUP2-X6K-WS

SUPERVISOR2

SYSTEM

2GE-SUP2-X6K-WS

 

 

 

 

 

STATUS

 

 

STATUS

 

 

 

 

 

 

SYSTEM

 

 

 

 

FAN FAIL

STATUS

 

STATUS

STATUS

CONSOLE

 

 

CONSOLE

 

INPOUT POWER

 

PWR

 

 

 

 

GOOD

 

 

 

MGMT

 

 

PWR

 

 

 

 

 

 

RESET

 

 

MGMT

 

 

RTN

-48VDC

GND

 

 

 

 

RESET

 

LINK

 

 

 

 

 

 

 

 

LINK

 

LINK

 

 

 

 

 

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

 

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

LINK

 

LINK

LINK

LINK

o

o

INPUT

FAN

OUTPUT

OK

OK

FAIL

INPUT

FAN

OUTPUT

OK

OK

FAIL

105068

Step 2 Place the fan tray into the front chassis cavity so that it rests on the chassis, and then lift the fan tray up slightly, aligning the top and bottom chassis guides.

Step 3 Push the fan tray into the chassis until the power connector seats in the backplane and the captive installation screws make contact with the chassis.

Step 4 Use aflat-bladeor number 2Phillips-headscrewdriver to tighten the captive installation screws.

Step 5 Proceed to the “Replacing the Power Supply” section on page 10 to replace the power supply.

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

 

78-16162-02

9

 

 

 

Replacing the Power Supply

Replacing the Power Supply

Note DC-input systems—See the “Connecting Site Power to the Fan Tray for DC-Input Systems” section on page 15 to connect site power to the high speed fan tray.

This section describes how to remove and install AC-inputpower supplies for the Catalyst6509-NEBswitch and CiscoOSR-7609router.

Removing an AC-InputPower Supply

Warning Hazardous voltage or energy is present on the backplane when the system is operating. Use caution when servicing.Statement 1034

To remove an AC-inputpower supply, follow these steps:

Step 1 Loosen the captive installation screw. (SeeFigure 5.)

Caution Use both hands to install and remove power supplies. Each Catalyst 6500 seriesAC-inputpower supply weighs between 22 pounds (9.9 kg) and 28 pounds (12.6 kg).

Step 2 Grasp the power supply handle with one hand, and slide the power supply part of the way out of the chassis. Place your other hand underneath the power supply, as shown inFigure 6, and slide the power supply completely out of the chassis.

Figure 5 AC-InputPower Supply Front Panel

AC power connection

Cable retention

device

16029

I

0

Power switch

INPUT

FAN

OUTPUT

OK

OK

FAIL

 

Status LEDs

Captive installation screw

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

10

78-16162-02

 

 

Replacing the Power Supply

Figure 6 Removing an AC-InputPower Supply

 

48V INPUT 1

 

 

 

FAN

 

 

 

 

 

 

STATUS

 

 

 

 

 

 

 

 

 

INPOUT POWER

 

 

RTN

 

GOOD

 

 

 

-48VDCGND

 

 

 

WS-C6500-NEB-FAN2

 

 

 

STATUS

 

STATUS

STATUS

 

 

 

 

 

 

 

2

 

1

2

1

 

 

 

 

 

 

 

2

1

LINK

 

 

LINK

 

 

 

1

 

 

 

LINK1

 

 

 

 

1

 

 

2

 

 

2

 

 

 

LINK

 

 

LINK

 

LINK2

 

 

 

 

 

 

 

4

 

3

4

 

 

 

 

 

 

3

4

3

LINK

 

 

LINK

 

LINK3

 

3

 

 

3

 

 

4

 

 

4

 

 

 

LINK

 

 

LINK

 

LINK4

 

 

 

 

 

 

 

RESET

ALARMCARRIER

RESET

ALARMCARRIER

RESET

 

 

 

LINK

 

LINK

 

 

 

 

 

 

 

ALARMCARRIER

 

 

1

 

1

 

 

ACTIVE

 

 

 

 

 

 

 

2

 

2

 

RX

TX

 

 

 

 

 

PORT1

RX

 

3

 

3

 

 

 

 

 

 

 

ALARMCARRIER

TX

 

4

 

4

 

 

 

5

 

 

 

 

ACTIVE

 

 

5

 

 

 

 

 

 

 

 

RX

TX

 

6

 

6

 

PORT2

RX

 

 

 

 

 

 

 

7

 

7

 

 

TX

 

 

 

 

 

ALARMCARRIER

 

 

8

 

8

 

 

ACTIVE

 

 

 

 

 

 

 

 

 

 

 

RX

TX

 

 

 

 

 

 

RX

 

 

 

 

 

PORT3

 

 

 

 

 

 

 

TX

 

 

 

 

 

ALARMCARRIER

 

 

 

 

 

 

 

ACTIVE

 

 

 

 

 

RX

TX

 

 

 

 

 

 

RX

 

 

 

 

 

 

TX

STATUS

ACTIVE

NEXT

SELECT

HIGH SPEED FAN

48V INPUT 2

STATUS

ACTIVE

NEXT

SELECT

STATUS

 

STATUS

 

2

1

2

1

LINK

 

LINK1

 

1

 

 

LINK

 

LINK2

 

2

 

 

4

3

4

3

LINK

 

LINK3

 

3

 

 

LINK

 

LINK4

 

4

 

 

RESET

 

RESET

 

ALARMCARRIER

 

ALARMCARRIER

 

 

ACTIVE

 

ACTIVE

RX

TX

RX

TX

PORT

RX

 

RX

1

 

PORT1

 

 

TX

 

TX

ALARMCARRIER

 

ALARMCARRIER

 

 

ACTIVE

 

ACTIVE

RX

TX

RX

TX

PORT

RX

 

RX

2

 

PORT2

 

 

TX

 

TX

ALARMCARRIER

 

ALARMCARRIER

 

 

ACTIVE

 

ACTIVE

RX

TX

RX

TX

PORT

RX

 

RX

 

PORT3

 

3

 

 

 

TX

 

TX

ALARMCARRIER

 

ALARMCARRIER

 

 

ACTIVE

 

ACTIVE

RX

TX

RX

TX

 

RX

 

RX

 

TX

 

TX

SUPERVISOR2

FAN FAIL INPOUT POWER

 

 

 

GOOD

 

 

 

 

RTN

-48VDCGND

STATUS

WS

SUPERVISOR2

STATUS

SUP2-

-

 

-

 

 

WS-

 

X6K

 

 

X6K-

 

-

 

 

 

SUP2

 

 

 

SYSTEM

2GE

 

SYSTEM

2GE

CONSOLE

 

 

CONSOLE

 

PWR

 

 

PWR

 

MGMT

 

 

RESETMGMT

 

RESET

 

 

 

105074

OUTPUT

FAIL

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

 

78-16162-02

11

 

 

 

Replacing the Power Supply

Installing the 3000 W AC-InputPower Supply

Caution Use both hands to install and remove power supplies. Each Catalyst 6500 seriesAC-inputpower supply weighs between 22 pounds (9.9 kg) and 28 pounds (12.6 kg).

To install the 3000 W AC-inputpower supply, follow these steps:

Step 1 Ensure that the system (earth) ground connection has been made. For ground connection instructions, refer to the installation guide for your hardware platform.

Step 2 Verify that the power switch is in the Off (0) position on the power supply you are installing. (SeeFigure 7.)

Figure 7 3000 Watt AC-InputPower Supply Front Panel

AC power connection

Cable

etention

 

 

 

 

 

 

 

 

device

 

 

 

 

 

 

 

 

 

 

110-120V- 15A

 

 

 

 

 

200-240V- 15A

 

 

 

 

 

60/50HZ

 

 

 

 

 

T

 

L

I

 

 

 

 

 

 

L

 

 

 

 

 

S

A

N

 

 

 

 

 

 

 

 

 

 

 

N

 

 

U

 

 

 

Power

I

 

 

R

 

 

 

O

 

 

 

 

 

 

OUTPUT 42V /17A

switch

 

 

 

 

OK

OK OUTPUT

42V /17A

 

 

 

 

 

OK

 

 

 

 

 

 

INPUT FAN

+

 

 

 

 

 

 

 

FAIL

105069

 

 

 

 

External power

 

 

 

 

Captive installation

Status LEDs (3)

connector cover

screw

 

 

 

Step 3 Grasp the power supply handle with one hand. Place your other hand underneath the power supply, as shown inFigure 8. Slide the power supply into the power supply bay. Make sure that the power supply is fully seated in the bay.

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

12

78-16162-02

 

 

Connecting Power to the Fan Tray

Figure 8 Installing the 3000 W Power Supply

 

48V INPUT 1

 

 

 

FAN

 

 

 

 

 

 

STATUS

 

 

 

 

 

 

 

 

 

INPOUT POWER

 

 

RTN

 

GOOD

 

 

 

-48VDCGND

 

 

 

WS-C6500-NEB-FAN2

 

 

 

STATUS

 

STATUS

STATUS

 

 

 

 

 

 

 

2

 

1

2

1

 

 

 

 

 

 

 

2

1

LINK

 

 

LINK

 

 

 

1

 

 

 

LINK1

 

 

 

 

1

 

 

2

 

 

2

 

 

 

LINK

 

 

LINK

 

LINK2

 

 

 

 

 

 

 

4

 

3

4

 

 

 

 

 

 

3

4

3

LINK

 

 

LINK

 

LINK3

 

3

 

 

3

 

 

4

 

 

4

 

 

 

LINK

 

 

LINK

 

LINK4

 

 

 

 

 

 

 

RESET

ALARMCARRIER

RESET

ALARMCARRIER

RESET

 

 

 

LINK

 

LINK

 

 

 

 

 

 

 

ALARMCARRIER

 

 

1

 

1

 

 

ACTIVE

 

 

 

 

 

 

 

2

 

2

 

RX

TX

 

 

 

 

 

PORT1

RX

 

3

 

3

 

 

 

 

 

 

 

ALARMCARRIER

TX

 

4

 

4

 

 

 

5

 

 

 

 

ACTIVE

 

 

5

 

 

 

 

 

 

 

 

RX

TX

 

6

 

6

 

PORT2

RX

 

 

 

 

 

 

 

7

 

7

 

 

TX

 

 

 

 

 

ALARMCARRIER

 

 

8

 

8

 

 

ACTIVE

 

 

 

 

 

 

 

 

 

 

 

RX

TX

 

 

 

 

 

 

RX

 

 

 

 

 

PORT3

 

 

 

 

 

 

 

TX

 

 

 

 

 

ALARMCARRIER

 

 

 

 

 

 

 

ACTIVE

 

 

 

 

 

RX

TX

 

 

 

 

 

 

RX

 

 

 

 

 

 

TX

STATUS

ACTIVE

NEXT

SELECT

HIGH SPEED FAN

48V INPUT 2

STATUS

ACTIVE

NEXT

SELECT

STATUS

 

STATUS

 

2

1

2

1

LINK

 

LINK1

 

1

 

 

LINK

 

LINK2

 

2

 

 

4

3

4

3

LINK

 

LINK3

 

3

 

 

LINK

 

LINK4

 

4

 

 

RESET

 

RESET

 

ALARMCARRIER

 

ALARMCARRIER

 

 

ACTIVE

 

ACTIVE

RX

TX

RX

TX

PORT

RX

 

RX

1

 

PORT1

 

 

TX

 

TX

ALARMCARRIER

 

ALARMCARRIER

 

 

ACTIVE

 

ACTIVE

RX

TX

RX

TX

PORT

RX

 

RX

2

 

PORT2

 

 

TX

 

TX

ALARMCARRIER

 

ALARMCARRIER

 

 

ACTIVE

 

ACTIVE

RX

TX

RX

TX

PORT

RX

 

RX

 

PORT3

 

3

 

 

 

TX

 

TX

ALARMCARRIER

 

ALARMCARRIER

 

 

ACTIVE

 

ACTIVE

RX

TX

RX

TX

 

RX

 

RX

 

TX

 

TX

SUPERVISOR2

FAN FAIL INPOUT POWER

 

 

 

GOOD

 

 

 

 

RTN

-48VDCGND

STATUS

WS

SUPERVISOR2

STATUS

SUP2-

-

 

-

 

 

WS-

 

X6K

 

 

X6K-

 

-

 

 

 

SUP2

 

 

 

SYSTEM

2GE

 

SYSTEM

2GE

CONSOLE

 

 

CONSOLE

 

PWR

 

 

PWR

 

MGMT

 

 

RESETMGMT

 

RESET

 

 

 

OUTPUT 42V

105070

/

 

 

42V

INPUT

 

OK

FAN OUTPUT

OK

OK

FAIL

+

Step 4 Tighten the power supply captive installation screw. (SeeFigure 7.)

Step 5 If you have a redundant power supply, install it now following the steps in this section.

Step 6 Proceed to the“Connecting Power to the Fan Tray” section on page 13 to connect power to the high speed fan tray.

Connecting Power to the Fan Tray

The high-speedfan tray requires external power, either from the 3000 WAC-inputpower supply or from an external DC power source. The fan tray ships with power wires secured at each terminal block.

If you are using the 3000 W AC-inputpower supply, use the supplied cables to connect the fan tray wires to the power supply.

If you are using a DC-inputpower supply, remove the wires from the fan tray and connect directly to a DC power source.

The following sections describe how to connect power to the fan tray:

Installing the Fan Tray Power Cable for AC-Input Systems, page 14

Connecting Site Power to the Fan Tray for DC-Input Systems, page 15

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

 

78-16162-02

13

 

 

 

Connecting Power to the Fan Tray

Installing the Fan Tray Power Cable for AC-InputSystems

Note The fan tray ships with power wires secured at each terminal block. Use these wires to connect the fan tray to the 3000 WAC-inputpower supply using the supplied cables. If you have redundant power supplies, repeat the steps in this section for the redundant power supply.

To connect the high speed fan tray to the 3000 W AC-inputpower supply, follow these steps:

Step 1 Connect the female end of the supplied power cable (seeFigure 9) to the fan tray wire connector. Press the two ends together until you hear a click.

Figure 9 Cable Connectors

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To fan cable

 

 

 

 

 

 

To power supply

 

105076

Step 2 On the power supply, loosen the thumb screw on the external power connector cover and lift up the cover. (SeeFigure 10.)

Figure 10

External Power Connector Cover

 

 

1

OUTPUT 42V /17A

 

OUTPUT 42V /17A

42V

2

 

 

 

/17A

42V

/17A

 

 

 

OK

+

105083

Step 3 Connect the male end of the supplied power cable to the female end of the external power connector on the power supply until you hear a click.

Step 4 If you have redundant power supplies, repeat the steps in this section for the redundant power supply.

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

14

78-16162-02

 

 

Connecting Power to the Fan Tray

Connecting Site Power to the Fan Tray for DC-InputSystems

Note To provide redundancy, you may choose to connect each fan terminal block to a separate power source.

Note Each input of the fan tray is rated 10 A @-40to-60VDC.

Warning This product requiresshort-circuit(overcurrent) protection, to be provided as part of the building installation. Install only in accordance with national and local wiring regulations.Statement 1045

Warning Before performing any of the following procedures, ensure that power is removed from the DC circuit.

Statement 1003

To connect the high speed fan tray to an external DC power source, follow these steps:

Step 1 Locate the terminal block covers on the fan tray. (SeeFigure 11.)

Figure 11 Terminal Block Covers on Fan Tray

Terminal block covers

48V INPUT 1

 

HIGH SPEED FAN

 

INPUT POWER

 

GOOD

RTN

-48VDCGND

WS-C6500-NEB-FAN2

48V INPUT 2

FAN FAIL INPUT POWER

GOOD

RTN -48VDCGND

105081

Step 2 The terminal block cover is held in place by two clips inserted into the fan tray front panel. Press the bottom of the terminal block cover, lift the cover up, and remove the cover. (SeeFigure 12.)

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

 

78-16162-02

15

 

 

 

Connecting Power to the Fan Tray

Figure 12 Removing the Terminal Block Cover

Terminal block cover

105082

Step 3 With a flat blade screwdriver, disconnect the input wires from the terminal block. (SeeFigure 13.)

Figure 13 Input Wire Connections on the Terminal Block

48V INPUT 1

+

GND

INPUT POWER

GOOD

RTN

-48vdcGND

105084

Step 4 Connect theDC-inputwires to the terminal block (seeFigure 14) in this order:

Ground

Negative (-)

Positive (+)

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

16

78-16162-02

 

 

Replacing the Supervisor Engine

Figure 14 DC-InputWire Connections on the Terminal Block

48V INPUT 1

+

GND

INPUT POWER

GOOD

RTN

-48vdcGND

 

 

 

105085

 

 

 

 

 

 

 

 

Warning

When installing or replacing the unit, the ground connection must always be made first and

 

 

 

disconnected last. Statement 1046

 

 

Step 5

After ensuring that all wire connections are secure, reinstall the terminal block cover.

 

 

 

 

Replacing the Supervisor Engine

Before you can power up the system, you need to remove the supervisor engine from slot 1 (if a redundant supervisor engine is present, remove it from slot 2) and install the Supervisor Engine 720 or the Supervisor Engine 32 in slot 5 or 6.

Removing the Supervisor Engine

This section describes how to remove an existing supervisor engine from a chassis slot.

To remove a supervisor engine from the chassis, perform these steps:

Step 1 Disconnect any network interface cables attached to the supervisor engine.

Step 2 Verify that the captive installation screws on all of the modules in the chassis are tight. This step assures that the space created by the removed supervisor engine is maintained.

Note If the captive installation screws are loose, the electromagnetic interference (EMI) gaskets on the installed modules will push the modules toward the open slot, reducing the opening size and making it difficult to install the replacement module.

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

 

78-16162-02

17

 

 

 

Replacing the Supervisor Engine

Step 3 Loosen the two captive installation screws on the supervisor engine.

Step 4 Place your thumbs on the ejector levers located at the top and bottom of the supervisor engine, and simultaneously rotate the levers outward to unseat the supervisor engine from the backplane connector.

Step 5 Grasp the edges of the supervisor engine, and slide the supervisor engine straight out of the slot. Do not touch the module circuitry.

Step 6 Place the supervisor engine on an antistatic mat or antistatic foam.

Step 7 If the slot is to remain empty, install a module filler plate to keep dust out of the chassis and to maintain proper airflow through the chassis.

Installing the Supervisor Engine

This section describes how to install the Supervisor Engine 720 or the Supervisor Engine 32 in the Catalyst 6509-NEBswitch and the CiscoOSR-7609Router.

Caution To prevent ESD damage, handle modules by the carrier edges only.

Note The Supervisor Engine 720 or Supervisor Engine 32 must be installed in slot 5 or 6 of the Catalyst 6509NEB or Cisco OSR7609 chassis.

To install the supervisor engine in the chassis, perform these steps:

Step 1 Choose a slot for the supervisor engine.

Step 2 Verify that there is enough clearance to accommodate any interface equipment that you will connect directly to the supervisor engine ports. If possible, place modules between empty slots that contain only module filler plates.

Step 3 Verify that the captive installation screws are tightened on all modules installed in the chassis. This assures that the EMI gaskets on all modules are fully compressed in order to maximize the opening space for the new module or the replacement module.

Note If the captive installation screws are loose, the EMI gaskets on the installed modules will push adjacent modules toward the open slot, reducing the opening size and making it difficult to install the replacement module.

Step 4 Remove the module filler plate by removing the two Phillipspan-headscrews from the filler plate. To remove a module, see the“Removing the Supervisor Engine” section on page 17.

Step 5 Fully open both ejector levers on the supervisor engine. (SeeFigure 15.)

Step 6 Position the supervisor engine in the slot. (SeeFigure 15.) Make sure that you align the sides of the module carrier with the slot guides on the top and bottom of the slot.

Step 7 Carefully slide the supervisor engine into the slot until the EMI gasket along the right edge of the supervisor engine makes contact with the module in the slot adjacent to it and both ejector levers have closed to approximately 45 degrees with respect to the supervisor engine faceplate. (SeeFigure 16.)

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

18

78-16162-02

 

 

Replacing the Supervisor Engine

Step 8 Using the thumb and forefinger of each hand, grasp the two ejector levers and exert a slight pressure to the left, deflecting the module approximately 0.040 inches (1 mm) to create a small gap between the supervisor engine's EMI gasket and the module adjacent to it. (SeeFigure 16.)

Caution Do not exert too much pressure on the ejector levers. They will bend and be damaged.

Step 9 While pressing on the ejector levers, simultaneously close them to fully seat the supervisor engine in the backplane connector. The ejector levers are fully closed when they are flush with the supervisor engine faceplate. (SeeFigure 17.)

Step 10 Tighten the two captive installation screws on the supervisor engine.

Note Make sure the ejector levers are fully closed before tightening the captive installation screws.

Figure 15 Positioning the Supervisor Engine in the Chassis

Ejector lever fully extended

48V INPUT 1

HIGH SPEED FAN

 

 

48V INPUT 2

GOOD

 

RTN -48VDCGND

 

WS-C6500-NEB-FAN2

GOOD

 

RTN -48VDCGND

110-120V- 15A

 

 

 

 

 

 

 

 

 

200-240V- 15A

 

 

 

 

 

 

 

 

 

60/50HZ

 

 

 

 

110-120V- 15A

 

 

 

 

 

 

 

 

 

200-240V- 15A

 

 

 

 

 

 

 

 

 

60/50HZ

 

 

 

 

TALL

I

 

 

 

 

 

 

 

 

S RUN

 

 

 

 

TALL

I

 

 

 

 

 

 

 

 

 

 

 

O

 

 

 

OUTPUT 42V

S RUN

 

 

 

 

 

 

 

42V

 

 

 

 

 

 

INPUT

FAN OUTPUT

 

O

 

 

 

OUTPUT 42V

 

OK

OK

FAIL

+

 

 

 

42V

 

 

 

 

 

 

INPUT

FAN OUTPUT

 

 

 

 

 

 

 

OK

OK

FAIL

+

EMI gasket

EMI gasket

105092

Insert module between slot guides

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

 

78-16162-02

19

 

 

 

Replacing the Supervisor Engine

Figure 16 Clearing the EMI Gasket in the Chassis

Gap between the module EMI gasket and the module above it

1 mm

FABIRDSWITCH

SFM-C6500-WS

MDL

 

STATUS

ACTIVE

48V INPUT 1 HIGH SPEED FAN

GOOD

RTN -48VDCGND

WS-C6500-NEB-FAN2

48V INPUT 2

GOOD

RTN

-48VDCGND

Press left

Press left

110-120V- 15A

 

200-240V- 15A

 

60/50HZ

 

TALL

I

S RUN

 

O

 

INPUT

FAN

OUTPUT

OK

OK

FAIL

OUTPUT 42V 42V

+

 

110-120V- 15A

 

 

200-240V- 15A

 

 

60/50HZ

 

TALL

I

S

RUN

 

O

INPUT

FAN

OUTPUT

OK

OK

FAIL

OUTPUT 42V

105093

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

20

78-16162-02

 

 

Powering Up the System

Figure 17 Ejector Lever Closure in the Chassis

48V INPUT 1

 

HIGH SPEED FAN

 

INPOUT POWER

RTN

GOOD

-48VDCGND

WS-C6500-NEB-FAN2

48V INPUT 2

FAN FAIL INPOUT POWER

GOOD

RTN -48VDCGND

105094

All ejector levers flush with module faceplate

Powering Up the System

This section describes how to power up the system.

AC-Input Systems, page 21

DC-Input Systems, page 22

AC-InputSystems

To power up your AC-inputsystem, follow these steps:

Step 1 Plug the power cord into the power supply, and tighten the screw on the cable retention device.

Step 2 Connect the other end of the power cord to anAC-inputpower source.

Caution In a system with dual power supplies, connect each power supply to a separate input source. In case of a power source failure, the second source will most likely still be available.

Step 3 Turn the power switch to the On (|) position on the power supply. Switching the power switch to On also engages a pawl that locks the power supply in the bay.

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

 

78-16162-02

21

 

 

 

Verifying Installation

DC-InputSystems

To power up your DC-inputsystem, follow these steps:

Step 1 Remove the tape from the circuit breaker switch handle, and restore power by moving the circuit breaker switch handle to the On (|) position.

Step 2 Turn the power switch to the On (|) position on the power supply. Turning the power switch on also engages a pawl that locks the power supply in the chassis.

Verifying Installation

After you have powered up the switch, verify the operation of the newly installed hardware as follows:

Step 1 Verify power supply operation by checking that the power supply front panel LEDs are in these states:

INPUT OK LED is green

FAN OK LED is green

OUTPUT FAIL LED is not lit

42V LED is green

If the LEDs indicate a power problem, refer to the installation guide for your hardware platform for troubleshooting information.

Step 2 Verify the high speed fan tray operation by checking that the fan tray LEDs are in these:

INPUT POWER GOOD LED is green (there is one LED for each power input; if both inputs are used, verify both LEDs)

FAN FAIL LED is green

If the LEDs indicate a problem, refer to the installation guide for your hardware platform for troubleshooting information.

Step 3 Verify that the supervisor engine STATUS LED is lit. Check the STATUS LED periodically. If the STATUS LED changes from orange to green, the supervisor engine has successfully completed the boot process and is now online. If the STATUS LED remains orange or turns red, the supervisor engine has not successfully completed the boot process and may have encountered an error.

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

22

78-16162-02

 

 

Related Documentation

Related Documentation

For additional information on Catalyst 6500 series switches and command-lineinterface (CLI) commands, refer to the following publications:

Regulatory Compliance and Safety Information for the Catalyst 6500 Series Switches

Regulatory Compliance and Safety Information for the Cisco 7600 Series Routers

Catalyst 6500 Series Switch Installation Guide

Cisco 7609 Router Installation Guide

Obtaining Documentation

Cisco documentation and additional literature are available on Cisco.com. Cisco also provides several ways to obtain technical assistance and other technical resources. These sections explain how to obtain technical information from Cisco Systems.

Cisco.com

You can access the most current Cisco documentation at this URL:

http://www.cisco.com/techsupport

You can access the Cisco website at this URL:

http://www.cisco.com

You can access international Cisco websites at this URL:

http://www.cisco.com/public/countries_languages.shtml

Product Documentation DVD

The Product Documentation DVD is a comprehensive library of technical product documentation on a portable medium. The DVD enables you to access multiple versions of installation, configuration, and command guides for Cisco hardware and software products. With the DVD, you have access to the same HTML documentation that is found on the Cisco website without being connected to the Internet.

Certain products also have .PDF versions of the documentation available.

The Product Documentation DVD is available as a single unit or as a subscription. Registered Cisco.com users (Cisco direct customers) can order a Product Documentation DVD (product number DOC-DOCDVD=orDOC-DOCDVD=SUB)from Cisco Marketplace at this URL:

http://www.cisco.com/go/marketplace/

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

 

78-16162-02

23

 

 

 

Documentation Feedback

Ordering Documentation

Registered Cisco.com users may order Cisco documentation at the Product Documentation Store in the Cisco Marketplace at this URL:

http://www.cisco.com/go/marketplace/

Nonregistered Cisco.com users can order technical documentation from 8:00 a.m. to 5:00 p.m. (0800 to 1700) PDT by calling 1 866 463-3487in the United States and Canada, or elsewhere by calling 011 408519-5055.You can also order documentation bye-mailat

tech-doc-store-mkpl@external.cisco.com or by fax at 1 408519-5001in the United States and Canada, or elsewhere at 011 408519-5001.

Documentation Feedback

You can rate and provide feedback about Cisco technical documents by completing the online feedback form that appears with the technical documents on Cisco.com.

You can submit comments about Cisco documentation by using the response card (if present) behind the front cover of your document or by writing to the following address:

Cisco Systems

Attn: Customer Document Ordering

170 West Tasman Drive

San Jose, CA 95134-9883

We appreciate your comments.

Cisco Product Security Overview

Cisco provides a free online Security Vulnerability Policy portal at this URL:

http://www.cisco.com/en/US/products/products_security_vulnerability_policy.html

From this site, you will find information about how to:

Report security vulnerabilities in Cisco products.

Obtain assistance with security incidents that involve Cisco products.

Register to receive security information from Cisco.

A current list of security advisories, security notices, and security responses for Cisco products is available at this URL:

http://www.cisco.com/go/psirt

To see security advisories, security notices, and security responses as they are updated in real time, you can subscribe to the Product Security Incident Response Team Really Simple Syndication (PSIRT RSS) feed. Information about how to subscribe to the PSIRT RSS feed is found at this URL:

http://www.cisco.com/en/US/products/products_psirt_rss_feed.html

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

24

78-16162-02

 

 

Obtaining Technical Assistance

Reporting Security Problems in Cisco Products

Cisco is committed to delivering secure products. We test our products internally before we release them, and we strive to correct all vulnerabilities quickly. If you think that you have identified a vulnerability in a Cisco product, contact PSIRT:

For Emergencies only — security-alert@cisco.com

An emergency is either a condition in which a system is under active attack or a condition for which a severe and urgent security vulnerability should be reported. All other conditions are considered nonemergencies.

For Nonemergencies — psirt@cisco.com

In an emergency, you can also reach PSIRT by telephone:

1 877 228-7302

1 408 525-6532

Tip We encourage you to use Pretty Good Privacy (PGP) or a compatible product (for example, GnuPG) to encrypt any sensitive information that you send to Cisco. PSIRT can work with information that has been encrypted with PGP versions 2.x through 9.x.

Never use a revoked or an expired encryption key. The correct public key to use in your correspondence with PSIRT is the one linked in the Contact Summary section of the Security Vulnerability Policy page at this URL:

http://www.cisco.com/en/US/products/products_security_vulnerability_policy.html

The link on this page has the current PGP key ID in use.

If you do not have or use PGP, contact PSIRT at the aforementioned e-mailaddresses or phone numbers before sending any sensitive material to find other means of encrypting the data.

Obtaining Technical Assistance

Cisco Technical Support provides 24-hour-a-dayaward-winningtechnical assistance. The Cisco Technical Support & Documentation website on Cisco.com features extensive online support resources. In addition, if you have a valid Cisco service contract, Cisco Technical Assistance Center (TAC) engineers provide telephone support. If you do not have a valid Cisco service contract, contact your reseller.

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

 

78-16162-02

25

 

 

 

Obtaining Technical Assistance

Cisco Technical Support & Documentation Website

The Cisco Technical Support & Documentation website provides online documents and tools for troubleshooting and resolving technical issues with Cisco products and technologies. The website is available 24 hours a day, at this URL:

http://www.cisco.com/techsupport

Access to all tools on the Cisco Technical Support & Documentation website requires a Cisco.com user ID and password. If you have a valid service contract but do not have a user ID or password, you can register at this URL:

http://tools.cisco.com/RPF/register/register.do

Note Use the Cisco Product Identification (CPI) tool to locate your product serial number before submitting a web or phone request for service. You can access the CPI tool from the Cisco Technical Support & Documentation website by clicking theTools & Resources link under Documentation & Tools. ChooseCisco Product Identification Tool from the Alphabetical Indexdrop-downlist, or click theCisco Product Identification Tool link under Alerts & RMAs. The CPI tool offers three search options: by product ID or model name; by tree view; or for certain products, by copying and pastingshow command output. Search results show an illustration of your product with the serial number label location highlighted. Locate the serial number label on your product and record the information before placing a service call.

Submitting a Service Request

Using the online TAC Service Request Tool is the fastest way to open S3 and S4 service requests. (S3 and S4 service requests are those in which your network is minimally impaired or for which you require product information.) After you describe your situation, the TAC Service Request Tool provides recommended solutions. If your issue is not resolved using the recommended resources, your service request is assigned to a Cisco engineer. The TAC Service Request Tool is located at this URL:

http://www.cisco.com/techsupport/servicerequest

For S1 or S2 service requests, or if you do not have Internet access, contact the Cisco TAC by telephone. (S1 or S2 service requests are those in which your production network is down or severely degraded.) Cisco engineers are assigned immediately to S1 and S2 service requests to help keep your business operations running smoothly.

To open a service request by telephone, use one of the following numbers:

Asia-Pacific:+61 2 8446 7411 (Australia: 1 800 805 227)

EMEA: +32 2 704 55 55

USA: 1 800 553-2447

For a complete list of Cisco TAC contacts, go to this URL:

http://www.cisco.com/techsupport/contacts

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

26

78-16162-02

 

 

Obtaining Additional Publications and Information

Definitions of Service Request Severity

To ensure that all service requests are reported in a standard format, Cisco has established severity definitions.

Severity 1 (S1)—Anexisting network is down, or there is a critical impact to your business operations. You and Cisco will commit all necessary resources around the clock to resolve the situation.

Severity 2 (S2)—Operationof an existing network is severely degraded, or significant aspects of your business operations are negatively affected by inadequate performance of Cisco products. You and Cisco will commitfull-timeresources during normal business hours to resolve the situation.

Severity 3 (S3)—Operationalperformance of the network is impaired, while most business operations remain functional. You and Cisco will commit resources during normal business hours to restore service to satisfactory levels.

Severity 4 (S4)—Yourequire information or assistance with Cisco product capabilities, installation, or configuration. There is little or no effect on your business operations.

Obtaining Additional Publications and Information

Information about Cisco products, technologies, and network solutions is available from various online and printed sources.

The Cisco Product Quick Reference Guide is a handy, compact reference tool that includes brief product overviews, key features, sample part numbers, and abbreviated technical specifications for many Cisco products that are sold through channel partners. It is updated twice a year and includes the latest Cisco offerings. To order and find out more about the Cisco Product Quick Reference Guide, go to this URL:

http://www.cisco.com/go/guide

Cisco Marketplace provides a variety of Cisco books, reference guides, documentation, and logo merchandise. Visit Cisco Marketplace, the company store, at this URL:

http://www.cisco.com/go/marketplace/

Cisco Press publishes a wide range of general networking, training and certification titles. Both new and experienced users will benefit from these publications. For current Cisco Press titles and other information, go to Cisco Press at this URL:

http://www.ciscopress.com

Packet magazine is the Cisco Systems technical user magazine for maximizing Internet and networking investments. Each quarter, Packet delivers coverage of the latest industry trends, technology breakthroughs, and Cisco products and solutions, as well as network deployment and troubleshooting tips, configuration examples, customer case studies, certification and training information, and links to scores ofin-depthonline resources. You can access Packet magazine at this URL:

http://www.cisco.com/packet

iQ Magazine is the quarterly publication from Cisco Systems designed to help growing companies learn how they can use technology to increase revenue, streamline their business, and expand services. The publication identifies the challenges facing these companies and the technologies to help solve them, usingreal-worldcase studies and business strategies to help readers make sound technology investment decisions. You can access iQ Magazine at this URL:

http://www.cisco.com/go/iqmagazine

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

 

78-16162-02

27

 

 

 

Obtaining Additional Publications and Information

or view the digital edition at this URL:

http://ciscoiq.texterity.com/ciscoiq/sample/

Internet Protocol Journal is a quarterly journal published by Cisco Systems for engineering professionals involved in designing, developing, and operating public and private internets and intranets. You can access the Internet Protocol Journal at this URL:

http://www.cisco.com/ipj

Networking products offered by Cisco Systems, as well as customer support services, can be obtained at this URL:

http://www.cisco.com/en/US/products/index.html

Networking Professionals Connection is an interactive website for networking professionals to share questions, suggestions, and information about networking products and technologies with Cisco experts and other networking professionals. Join a discussion at this URL:

http://www.cisco.com/discuss/networking

World-classnetworking training is available from Cisco. You can view current offerings at this URL:

http://www.cisco.com/en/US/learning/index.html

This document is to be used in conjunction with the documents listed in the “Related Documentation” section.

CCVP, the Cisco logo, and the Cisco Square Bridge logo are trademarks of Cisco Systems, Inc.; Changing the Way We Work, Live, Play, and Learn is a service mark of Cisco Systems, Inc.; and Access Registrar, Aironet, BPX, Catalyst, CCDA, CCDP, CCIE, CCIP, CCNA, CCNP, CCSP, Cisco, the Cisco Certified Internetwork Expert logo, Cisco IOS, Cisco Press, Cisco Systems, Cisco Systems Capital, the Cisco Systems logo, Cisco Unity, Enterprise/Solver, EtherChannel, EtherFast, EtherSwitch, Fast Step, Follow Me Browsing, FormShare, GigaDrive, HomeLink, Internet Quotient, IOS, iPhone, IP/TV, iQ Expertise, the iQ logo, iQ Net Readiness Scorecard, iQuick Study, LightStream, Linksys, MeetingPlace, MGX, Networking Academy, Network Registrar, Packet, PIX, ProConnect, ScriptShare, SMARTnet, StackWise, The Fastest Way to Increase Your Internet Quotient, and TransPath are registered trademarks of Cisco Systems, Inc. and/or its affiliates in the United States and certain other countries.

All other trademarks mentioned in this document or Website are the property of their respective owners. The use of the word partner does not imply a partnership relationship between Cisco and any other company. (0705R)

© 2004–2006Cisco Systems, Inc. All rights reserved.

Catalyst 6509-NEBSwitch and CiscoOSR-7609Router Upgrade Note

28

78-16162-02