Carrier 38GS User Manual

0 (0)
Number One Airconditioning Mater
Syracuse New York

Air-Cooled Condensing Units

g DIAM KOS FOR CONTROL WIRING
SUCTION LINE CONN
SUCTION LINE VALVE
4'-0" OVERHEAD SPACE REQ'D FOR SERVICE AND AIR FLOW
3 -0 (BOTH SIDES)
LIQUID LINE VALVE
LIQUID LINE CONN
CONCRETE
MOUNTING

TRANSPORTATION DAMAGE

File claim with shipping company if shipment is
damaged or incomplete.
Unpackaging Unit — Move condensing unit to final
location. Open carton at end marked “compressor end.” Slide unit from carton taking special care to not damage service valves or grilles.

PRELIMINARY SURVEY

Consult local building codes and National Electrical Code (NEC) for special installation requirements.
When installing unit, allow sufficient space for air flow clearance, wiring, refrigerant piping and servicing unit. Position unit so water from roof or eaves does not flow directly on top of unit.
Install unit on a solid, level mounting pad. Unit can be attached to pad with a mastic adhesive or
by drilling holes in base pan for 1/4-in. mounting bolts. Do not block base pan water drainage holes.
38GS,CC,CE Condensing Units Connected to Carrier Matched Evaporators with Carrier Acces
sory Tubing — Check system refrigerant charge
when tubing lengths are above or below 25 feet. See Refrigerant Charging (page 10) for details.
Fig. 1 — Dimensions, Connections and Mounting Pad
38GS,CC,CE Unit
Table 1 — Installation Data
38GS
014
COND UNIT 38CC
OPER WT (lb) 130 135 UNIT DIM. (ft-in.)
Length A
Width B
Height G
REFRIG CONN.(in.)
Suction (ODF)
Liquid (ODF)
*5/8-in suction connection on 38CE002
t38CE045,005 and 38GS.CC060 are factory supplied with 3/4- to
1 1/8-in suction valve adapter (field installed) for 1 1/8-in
suction line
© Carrier Corporation 1975
38CB
- - -
- - -
'l-4
% lYsT '/b I
018
1-4
024
142|149
N4
Com
036 042
030 030 036 002* 003 004 045 005
158 191
2-10V4
1-10
1-4 1 1-4 (2-0
DOtible Fittings
%
'8
048 060t
042 048 060t
193 200
----
2-0 2-0
-----
'/4t
38GS,CC,CE Condensing Units Connected to Non­Carrier Evaporators — Check refrigerant charge
when condensing unit is added to a system in which other than a Carrier approved evaporator is being used or where the evaporator has been previously installed. Field-supplied refrigerant pip ing must be in accordance with Field-Supplied Piping Data, Table 3.
Where indicated on Table 3 for 38GS,CE units,
install a liquid line filter-drier and accessory crank case heater on condensing unit. (Filter-drier is factory supplied on CE045,005 units.) Accessory start capacitor and relay also required on 38GS
units, but not normally required on 38CE units.
See Compressor Service (page 7). All above items are standard or not required for 38CC units.
Use an evaporator coil with a bleed-type ex pansion device. If coil does not have a bleed-type expansion device it may be necessary to add an accessory start capacitor and relay to condensing unit. This would require removing compressor start
thermistor (PTC device) on units so equipped.
Form 38GS-13SI
Table 2 — Accessories
PART
NUMBER
HH01AD040 HH93AZ040
JHH51AR00J[^
HH07AT070, HH07AT074 H N93^076
HH0iAD042”
HH93AZ042 HH01YA092
HH_93_YZ094 32LT900301
(200-3 Ph) 32LT900601 (460-3 Ph)
38GS900102 38GS900212
38GS900112 38GS900292
38GS900172 38GS900182
38GC900031 10 38GC900071 10 38GC900041 38GC900081 38GS900221 38GC900091 38GC900061 35
38GC900101 38GC900191 50 % 38GC900ni
Low-Voltage Control Honeywell Deluxe Thermostat Thermostat Subbase
Comfort Control Center (Use with HH01AD040)
Low-Voltage Control — Honeywell Thermostat Thermostat Subbase (with Automatic Changeover)
Low-Voltage Control ~ Honeywell Thermostat Thermostat Subbase
Low-Voltage Control Grayson Thermostat Thermostat Subbase
Solid State Head Pressure Control
Indoor Fan Relays (^¡x HN61KJ210)
40VA Low-Voltage Control Transformers (24 V - Six 38GS900Q9])
Crankcase Heaters (Six 38GS900131)
Crankcase Heaters (Six 38GS900281) Start Capacitor and Relay Package (Six 38GS900041) Start Capacitor
Tubing Pa
Liqui d
Lgth
(ft)
18 18 25 25
35
50
(in.)
r 5/^
OD
%
% % % : %
V
D6
V
V
4
Tube End
OD (in.)
DESCRIPTION
and Relay F^ackage (Six 38GS900051
ckages
Suction*
OD
(in.)
^8 ^8
y« , % %
%
%
%
T ubeODFnd
in.)
Evap
%
^8 % 1 % % ^8 %
%
V
/4
I V4t
%
%
Cond
^41 I
%
%t
%t % % ^/4 %t
%
y —
/4 k4
38CC — (Fan motor suitable for 32LT)
38GS
V
014,018,024
4
3/ H
030,036,042,048
/4
V
014,018,024
/8
030,036,042,048 014,018,024 030,036,042,048 014,018,024
=/8
V
030,036,042,048
/4
014,018,024 -
%
030,036,042,048
USAGE
38GS,CC,CE
38GS,CC,CE 38GS,CC,CE
38GS (except 38G5014), 38CE
38GS0Ì4
38GS (except 38GSÒ42), 38CE
38GS042
UNIT
38CC
-
030,036,042,048
-
030,036,042,048
-
030,036,042,048
-
030,036,042,048
030,036,042,048
38CE
002
003,004,045,005
002
003,004,045,005
002
“0Ü3%O470457O0r^
002 003,004,045,005 002 003,004,045,005
*AII suction lines have a 90° bend at one end
tForb/8-in evaporator connection, cut off 3/4-in end

PIPING CONNECTIONS

Condensing units can be connected to evap orator sections using Carrier accessory tubing package or field-supplied tubing of refrigerant grade. (Accessory tubing not available for 38GS060, 38CC060.) See Table 2 for accessory tubing sizes and Table 3 for recommended field­supplied tubing sizes. Where evaporator is 20 ft or more below condensing unit, reduce liquid line size one diameter (min 1/4-in. OD).
A capacity reduction will result if accessory tubing is used in 38CE045,005 systems. For example, when a 25 ft accessory tubing package is used, there will be a capacity reduction of 3 3/4% on 38CE045 and 5% on 38CE005 systems. For maximum capacity from these systems, use tubing sizes shown in Table 3.
When other than 25 ft of interconnecting tubing is used, follow special requirements de scribed in Refrigerant Charging. Do not use less
than 10 ft of liquid line. Do not cut 5/16-in. or
1/4-in. liquid line. Bend or coil to fit.
Do not use damaged or contaminated tubing. If accessory tubing package or evaporator section has been open for more than 15 seconds per connec tion, evacuate or purge evaporator coil and tubing system (use field-supplied refrigerant, not unit refrigerant). Always evacuate or purge if field­supplied tubing is used.
Before Connecting Unit Piping, consider the
following: 38CE045,005 AND 38CC UNITS - A filter-drier package is shipped with these units. Included with
filter-drier are 2 short length tubing assemblies that are equipped with flare and/or Compatible Fit
tings. Use tubing assemblies to install filter-drier into system liquid line at evaporator or condensing unit. See Fig. 2. Connect tubing assembly A (90°
assembly) to evaporator or condensing unit liquid line Compatible Fitting. Complete the filter-drier installation as shown.
Table 3 — Field-Supplied Piping Data
MAX COND
COND
X-
f 3 UNIT
38GS014, 38GS018
38GS024
38GS030, 38CC030, 38CE002
38GS036, 38CC036, 38CE003
38GS042, 38CC042, 38CE004
38GS048,
38CC048
38CE045
38GS06 0, 38CC060, 38CE005
Cap. Tube TXV
NOTES
REFRIG
CONTROL
TXV
Cap. Tube
or
AccuRater'*'^
TXV
Cap. Tube
AccuRater
Cap. Tube
or
AccuRater
TXV
Cap. Tube
or
AccuRater
TXV
Cap Tube
or
AccuRater
TXV
Cap Tube
or
AccuRater
TXV
Cap. Tube
or
AccuRater
L^y
Cap. Tube
or
AccuRater
Crankcase heater and liquid line filter-drier required on 38GS and 38CE units Accessory start capacitor
with relay also required on 38GS unit, but not
normally required on 38CE units See Compressor Service Reduce liquid line diameter by 1/8-in OD
(min 1/4-in OD) when evaporator is 20 ft or more
below condensing unit
■ Capillary Tube
- Thermal Expansion Valve
1 The following system modifications are required adjust
refrigerant charge on systems with over 25 ft separation
UNIT HT (ft)
Above
Evap
90
150
yo
150
150
90
150
90
150
90 ■
150
90
150
90
150
Be low
Evap
90
50
90 50 %
__
50
90
50
90
50
90
50
90
50
90
50
25- 50 51» 7S 7&~ 1
Suet Liq
V
'8 'x iiiiii lili
%
%
%
%
1%
IV»
Vs
V» T
/4
% liM
% Iliiii
REFRIGERANT LINE LENGTH (ft)
Line Diameter (in* OD)
'
IIBI
ilM
iiiiiiiiiii
wmmmmmmm
N s
T %
k
between condensing unit and evaporator (See Refrigerant Charging ) Adjust system oil charge as described in Note 2 Oil charge adjustment add 1% of nominal oil charge in system (Table 7) for each 10 ft of refrigerant line length above 50 feet Eor example, a system that has a 50-oz oil charge with 1 50 ft of interconnecting piping requires 5 oz of additional oil as shown below:
V
iÄiii
MB
ISl
*
150 ft - 50 ft = 100 ft 100 ft -E 10 ft = 10 ft
Litj 1 LEíj
iiiiii
IH
ilBi %
11»
Äiii
10x1% = 10% ( 10)
10 X 50 oz = 5 oz
Do not permit condensing unit to short cycle, particularly on applications with long vertical line lengths Correct short cycling condition immediately
m
¡Mil
Í.
..............
Connection Procedure — When making tubing
connections, be sure to provide clearance at unit for electrical connections.
Connect refrigerant liquid and suction lines to condensing unit, Fig. 1. Unit Compatible Fittings permit 2 methods of refrigerant line connection; mechanical (quick connect) or sweat connection. Make suction line connection first.
38CE045,005, 38GS060 AND 38CC060 UNITS ­Remove suction line adapter taped to compressor suction line. Connect 3/4-in. end of adapter to unit suction line Compatible Fitting. Sweat connect refrigerant suction line to 1 1/8-in. end of adapter. Connect liquid refrigerant line to unit.
MECHANICAL CONNECTION (Mate one set of connections at a time.)
1. Loosen nut on Compatible Fitting one turn. Do not remove. Remove plug and be sure 0-ring is in the groove
2.
inside the Compatible Fitting. Cut tubing to correct length.
3. Use gage on tag attached to service valve to
4. mark tube end for correct insertion depth. Insert tube into Compatible Fitting until it
bottoms. (Tube should be inserted at least as far as mark on tubing.)
Tighten nut until it bottoms on back coupling
5. flange.
c
Fig. 2 — Filter-Drier Assembly Installation (38CC, 38CE045 and 005)
SWEAT CONNECTION (Use refrigerant grade
tubing.)
1. Remove locking nut, rubber 0-ring and Schrader core from valve.
2. Cut tubing to correct length.
3. Insert tube into Compatible Fitting. Wrap top and bottom of service valves in wet cloth to prevent damage by heat. Solder with low temperature (450 F) silver alloy solder.
4. Replace Schrader core.
5. Evacuate or purge system with field-supplied refrigerant.

ELECTRICAL DATA AND WIRING

Field wiring must comply with local and
national fire, safety and electrical codes. Voltage to unit must be within ± 10% of voltage indicated on
nameplate. Contact local power company for correction of improper line voltage.

of ifolt ois tmpro|>er Ime

When making electrical connections, provide clearance at unit for refrigerant piping connections. See Table 4 for recommended wire and fuse sizes.

Install a Branch Circuit Fused Disconnect of

adequate size to handle unit starting current. Locate disconnect within sight of and readily accessible from the unit, per section 440-14 of
National Electrical Code (NEC).
Bring Line Power Leads Into Unit — Extend leads
from fused disconnect thru hole provided in service embossment (Fig. 1) and thru 7/8-in. hole into control box.
Connect Ground Lead to a Ground Lug in Control
Box for safety. Connect power wiring. See Fig. 3.
Splice line power leads to red and violet pigtails on 38GS,CE units or to yellow pigtails (3) on 38CC
units. Use wire nuts supplied with unit. Tape each
connection. Wire nuts are suitable for copper or aluminum wire since they contain joint compound.
Control Power (24 v) wiring is brought thru hole in
service embossment and spliced to yellow pigtails on all units. See Fig. 4.
Furnace or fan-coil transformer must be used as
24-v supply for system as shown in Fig. 4 (At least
a 40-va transformer is recommended.) Current 38GS048,060 and 38CC048,060 units are equip ped with a low-voltage transformer used to power contactor thru unit control circuit. This trans former must not be used for powering the indoor thermostat control circuit.
I-PHASE CONN. TO FUSED DISCONNECT
3-PHASE
CONN. TO
FUSED
DISCONNECT
SPLICE
------------
FACTORY WIRING
------------
FIELD WIRING
p
--I3D GROUND LUG 386S,CEC0NDUNIT
-YEL-
-YEL-
-YEL-
-------I3D GROUND LUG
38CC CONO UNIT
Fig. 3 — Line Power Connections
THERMOSTAT SUBBASE
THERMOSTAT SUBBASE HH93AZ076
(COOLING ONLY)
THERMOSTAT SUBBASE HH93AZ042 OR
ONE TRANSFORMER
(COOLING AND ONE-STAGE HEATING)
^CONNECT FS TO LOW-SPEED INDOOR FAN TERMINAL
WHEN 2-SPEED FAN IS USED
IFR, FS and IFM are located in furnace on heating-cooling applications If accessory IFR is required for cooling only applications, locate (IFR) in fan coiI
ARRANGEMENT C-
ONE TRANSFORMER
(COOLING AND 2-STAGE HEATING)
^CONNECT FS TO LOW-SPEED INDOOR FAN TERMINAL
WHEN 2-SPEED FAN IS USED

Fig. 4 -- Control Circuit Connections

Control Relay (10 va) or Contactor Fan Switch Heating Control I ndoor Fan Motor I ndoor Fan Relay Transformer
Field Splice
---------------
Field Wiring
---------------- Factory Wiring
5
Loading...
+ 11 hidden pages