036-21564-002-A-0404
TECHNICAL GUIDE
J
SINGLE PACKAGE
AIR-TO-AIR
HEAT PUMPS
B3CH 036, 048 & 060 (208/230, 460V) B5CH 036 & 060 (575V), B6CH 048 3, 4 AND 5 NOMINAL TONS
(10 SEER)
SUNLINE 2000
DESCRIPTION
YORK Sunline 2000 Heat Pumps are convertible single package units with a common cabinet and common roof curb for the 3, 4 and 5 ton sizes. The units were designed for residential and light commercial applications. They can easily be installed on a roof curb, slab, roof jack or frame.
All units are self--contained and assembled on rigid full perimeter base rails allowing for 3--way fork lift access and overhead rigging. Every unit is completely charged, wired, piped and tested at the factory to provide for a quick and easy field installation.
The units are available with supplemental electric heaters as field--installed accessories.
Both down and side discharge airflows are available without having to swap panels. The installer simply removes the duct covers for the desired configuration. Economizers may be used on either side or down discharge applications with no modifications required.
All models include a 1--year limited warranty on the complete unit. Compressors and electric heater elements each carry an additional 4--year warranty.
FEATURES
CONTROLS -- These heat pumps utilize a unique time-- temperature defrost circuit which adjusts the time between defrost cycles based on the outdoor temperature to provide optimal comfort control and ensure reliable operation. The ambient--modified, time--temperature defrost control extends the time below 35°F and shortens the time above 35°F. The nominal defrost times are field adjustable to 50, 80 and 110 minutes. The defrost time is initiated and terminated by a liquid line control with a 10 minute override limit built into the defrost control.
COMMON FOOTPRINT/COMMON CABINET -- The 3, 4 and 5 ton units all share the exact same cabinet -- and therefore the same roof curb. You now have the flexibility of setting one curb and, after the internal load has been determined, placing the proper tonnage unit on that curb.
HIGH EFFICIENCY -- All units have a minimum SEER of 10, a COP of 3.0 (high) and 2.0 (low) and an HSPF as high as 7.3. These efficiencies exceed all legislated minimum levels and provide low operating costs.
CONVERTIBLE AIRFLOW DESIGN -- Both the side and bottom duct openings are covered when they leave the factory. If a side supply/side return is desired, you simply remove the two side duct covers from the outside of the unit and discard them. If a bottom supply/return is desired, you simply remove the two bottom duct covers and discard them. No panel cutting or swapping is required! Convertible airflow design allows maximum field flexibility and minimum inventory.
FACTORY--INSTALLED OPTIONS -- Economizers can be installed at the factory. They are shipped installed and wired. The outdoor air hood needs only to be field assembled and installed.
Adjustable belt--drive blowers are available on most models from the factory for complete air flow flexibility.
FIELD--INSTALLED ACCESSORIES -- Accessories were designed for quick and easy installation. The motorized damper and economizers simply slide in and electrical connections are made by modular plugs. Electric heaters mount easily and knockouts are provided in the internal partitions to connect the elements to the control box single point kit.
The motorized air damper includes a slid--in/plug--in damper assembly with a rainhood and filters. The outdoor air dampers open when the indoor fan motor is energized. The damper is capable of providing 0% through 100% of outdoor return air opening.
The manual outdoor damper provides 0% through 35% or 0% through 100% of return air opening (field adjustable). Designed for duct mounted side or bottom supply/return applications. Includes rain hood assembly and filter.
The 14" high roof curb is shipped knocked down. A roof curb deck is not required because the bottom of the unit is insulated.
WIDE RANGE OF INDOOR AIRFLOWS -- All models operate over a wide range of design conditions with a 3--speed direct-- drive fan motor. Belt--drive blowers are also available on all models.
FULL PERIMETER BASE RAILS -- The permanently attached base rails provide a solid foundation for the entire unit and protect the unit during shipment. The rails provide fork lift access from 3 sides and rigging holes are also provided so that an overhead crane can be used to place the units on a roof.
FEATURES - CONT'D.
SYSTEM PROTECTION -- Crankcase heaters and internal compressor protection are standard on all compressors. Every unit has a liquid line filter--drier, low pressure switch, high pressure switch and high temperature switch to protect all system components. A suction line freezestat is supplied on all three--phase units to protect against loss of charge and coil frosting due to low economizer outdoor air temperature while the compressor is running. All units will provide cooling at ambient temperatures down to 45°F.
UTILITY CONNECTIONS MADE EASY -- Electric utility knockouts are provided in the unit underside as well as the side of the unit. A clearly identified location is provided to mount a
036-21564-002-A-0404
field supplied electrical disconnect switch. Utility connections can be made quickly and with a minimum amount of field labor.
SIMPLE CONTROL CIRCUIT -- Mate--n--lock plug connectors are used where line and low voltage wires pass thru internal bulkheads. This allows for easier troubleshooting and component replacement. The electrical control box is not located in the compressor compartment so the access cover can be removed for troubleshooting without affecting the normal system operating pressures.
AIR FILTERS -- Units come standard with 1" throwaway filters. The unit filter racks can accommodate 1" or 2" filters without any modifications.
SUNLINE 2000 Heat Pump
DIRECT DRIVE BLOWER MOTOR (Belt-Drive Option also available on some models)
(Direct Drive Models)
TABLE OF CONTENTS
Description .......................................................................... |
1 |
Features .............................................................................. |
1 |
Ratings ................................................................................ |
3 |
Physical Data....................................................................... |
3 |
Cooling Capacities - 3 Ton................................................... |
4 |
Cooling Capacities - 4 Ton................................................... |
5 |
Cooling Capacities - 5 Ton................................................... |
6 |
Heating Capacities .............................................................. |
7 |
Supply Air Blower Perf. - 3 & 4 Ton w/Belt-Drive................. |
8 |
Supply Air Blower Perf. - 5 Ton w/Belt-Drive ....................... |
9 |
Supply Air Blower Perf. - 3, 4 & 5 Ton w/Direct-Drive.......... |
9 |
Motor and Drive Data .......................................................... |
9 |
Static Resistances ............................................................. |
10 |
Heater / CFM Limitations................................................... |
10 |
Field Wiring ....................................................................... |
10 |
Electrical Data - Basic Units (Direct-Drive) ........................ |
11 |
Elec. Data-Ht. Pump/Elec.Ht. 3 Ton (Direct-Drive) ............ |
11 |
Elec. Data-Ht. Pump/Elec.Ht. 4 & 5 Ton (Direct-Drive)...... |
12 |
Electrical Data - Basic Units (Belt-Drive) ........................... |
13 |
Elec. Data-Ht. Pump/Elec.Ht. 3 Ton (Belt-Drive) ............... |
13 |
Elec. Data-Ht. Pump/Elec.Ht. 4 & 5 Ton (Belt-Drive)......... |
14 |
Unit Dimensions ................................................................ |
15 |
Roof Curb Dimensions ...................................................... |
17 |
Factory Installed Options / Field-Installed Accessories ..... |
18 |
Typical Applications........................................................... |
19 |
2 |
Unitary Products Group |
036-21564-002-A-0404
RATINGS
CAPACITY RATINGS
|
|
|
|
|
|
ARI RATINGS (SEE NOTE 1) |
|
|
|
|
|
|
NOMINAL |
|
|||
MODEL |
|
COOLING |
|
|
SOUND |
|
HEATING CAPACITY |
ELECTRIC HEAT CAPACITY |
|||||||||
|
|
|
RATING |
|
|
|
|
|
|
|
(SEE NOTE 3) |
|
|||||
BCH |
PERFORMANCE |
|
HSPF |
47 |
° |
F |
17 |
° |
F |
|
|||||||
|
(SEE NOTE 2) |
|
KW |
|
|||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
MBH |
|
SEER |
|
EER |
|
bels |
|
MBH |
|
COP |
MBH |
|
COP |
240V |
480V |
600V |
036 |
39 |
|
10.00 |
|
9.20 |
|
8.6 |
7.3 |
39.0 |
|
3.0 |
23.0 |
|
2.1 |
5, 7, 10, 15 & 20 |
7,10,15 & 20 |
10, 15 & 20 |
048 |
48 |
|
10.20 |
|
9.25 |
|
8.6 |
6.7 |
48.0 |
|
3.0 |
26.4 |
|
2.0 |
5, 7, 10, 15 & 20 |
7,10,15 & 20 |
10, 15 & 20 |
060 |
59 |
|
10.00 |
|
9.20 |
|
8.4 |
7.0 |
59.0 |
|
3.0 |
36.0 |
|
2.1 |
5,7,10,15,20 & 30 |
7,10,15,20 & 30 |
10,15,20 & 30 |
NOTE: 1. Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.
2.Rated in accordance with ARI Standard 270.
3.Heaters available as accessories - all with single point power supply.
SEER = Seasonal Energy Efficiency Ratio - the total cooling output in BTU's during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.
EER = Energy Efficiency Ratio-the cooling capacity in BTU's per hour (BTUH) divided by the power input in watts at any given set of rating conditions, expressed in BTUH per watt (BTUH/watt).
COP = Coefficient of Performance - the total heating capacity provided by the refrigeration system, including circulating fan heat but excluding supplementary resistance (BTU's per hour) divided by the total electric input (watts) x 3.412.
SOUND POWER RATINGS
|
|
ESP |
Blower |
|
|
|
|
Sound Power (dB 10-12 Watts) |
|
|
|
|||||
Unit |
CFM |
|
|
Octave Band Centerline Frequency (Hz) |
|
|
SWL |
dB(A) |
||||||||
|
|
|
|
|
|
|
||||||||||
Size |
|
|
|
|
|
|
|
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
IWG |
Speed |
KW |
63 |
125 |
|
250 |
500 |
1000 |
2000 |
|
4000 |
8000 |
dB(A) |
@ 10 ft* |
|
|
|
|
|
|
|||||||||||
038 |
1200 |
0.60 |
LOW |
0.60 |
84 |
84 |
|
74 |
67 |
69 |
62 |
|
57 |
52 |
74 |
41 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
048 |
1600 |
0.55 |
HIGH |
0.80 |
85 |
85 |
|
75 |
68 |
70 |
63 |
|
58 |
53 |
75 |
42 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
060 |
2000 |
0.45 |
HIGH |
1.00 |
86 |
86 |
|
76 |
69 |
71 |
64 |
|
59 |
54 |
76 |
43 |
*At a distance of 10 ft from the blower
NOTE: These values have been accessed using a model of sound propagation from a point source into the hemispheric free field. The dBA values provided are to be used for reference only. Calculation of dBAvalues cover matters of system design and the fan manufacturer has no way of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.
PHYSICAL DATA
BASIC UNITS
|
MODELS |
|
BCH |
|
|
|
036 |
048 |
060 |
||
|
|
||||
SUPPLY AIR |
CENTRIFUGAL BLOWER (Dia. x Wd. in.) |
12 x 10 |
12 x 10 |
12 x 10 |
|
FAN MOTOR HP (DIRECT-DRIVE) |
12 |
3 4 |
1 |
||
BLOWER |
|||||
FAN MOTOR HP (BELT-DRIVE) |
1.5 |
1.5 |
1.5 |
||
|
|||||
INDOOR |
ROWS DEEP |
4 |
3 |
3 |
|
FINS PER INCH |
16 |
15 |
15 |
||
COIL |
|||||
FACE AREA (Sq. Ft.) |
4.3 |
5.1 |
5.1 |
||
|
|||||
OUTDOOR |
PROPELLER DIA. (in.) |
22 |
22 |
24 |
|
FAN MOTOR HP |
13 |
12 |
12 |
||
FAN |
|||||
NOM. CFM TOTAL |
4300 |
4200 |
4500 |
||
|
|||||
OUTDOOR |
ROWS DEEP |
1 |
1 |
1 |
|
FINS PER INCH |
20 |
20 |
20 |
||
COIL |
|||||
FACE AREA (Sq. Ft.) |
17.1 |
17.1 |
17.1 |
||
|
|||||
AIR |
QUANTITY PER UNIT (15" x 20" x 1") |
2 |
2 |
2 |
|
FILTERS |
QUANTITY PER UNIT (14" X 25" X 1") |
1 |
1 |
1 |
|
(SEE NOTE) |
TOTAL FACE AREA (sq. ft.) |
6.6 |
6.6 |
6.6 |
|
CHARGE |
REFRIGERANT 22 (lbs./oz.) |
7/12 |
9/2 |
8/4 |
|
COMPRESSOR |
HERMETIC, RECIPROCATING (Qty) |
1 |
1 |
1 |
NOTE: Filter racks can accommodate 1" or 2" thick filters.
Unitary Products Group |
3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
036-21564-002-A-0404 |
|||
COOLING CAPACITIES - 3 TON (BCH036) |
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Air On |
|
|
|
|
|
|
Temperature of Air on Outdoor Coil |
|
|
|
|
|
|
|
|
|||||||||
|
|
Indoor |
|
|
|
85 °F |
|
|
|
|
|
|
|
|
|
|
95 °F |
|
|
|
|
|
||||
|
|
Coil |
|
Total |
Power |
|
Sensible Capacity1, MBH |
|
Total |
Power |
|
|
Sensible Capacity1, MBH |
|
|
|||||||||||
|
|
CFM |
|
WB |
Cap.1 |
Input2 |
|
Entering Dry Bulb, °F |
|
Cap.1 |
Input2 |
|
|
Entering Dry Bulb, °F |
|
|
||||||||||
|
|
|
°F |
MBH |
KW |
86 |
83 |
80 |
77 |
|
74 |
71 |
|
68 |
MBH |
KW |
|
86 |
83 |
80 |
77 |
74 |
71 |
68 |
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||
|
|
|
|
72 |
51 |
3.4 |
37 |
32 |
28 |
24 |
|
19 |
- |
|
- |
47 |
3.7 |
|
34 |
29 |
25 |
22 |
17 |
- |
- |
|
1750 |
|
67 |
46 |
3.4 |
40 |
40 |
36 |
31 |
|
26 |
21 |
|
16 |
44 |
3.7 |
|
38 |
38 |
34 |
29 |
24 |
20 |
15 |
|
||
|
62 |
42 |
3.3 |
42 |
42 |
41 |
39 |
|
34 |
29 |
|
24 |
38 |
3.6 |
|
38 |
38 |
37 |
35 |
30 |
26 |
21 |
|
|||
|
|
|
|
|
|
|
|
|||||||||||||||||||
|
|
|
|
57 |
42 |
3.3 |
42 |
42 |
42 |
40 |
|
35 |
30 |
|
25 |
37 |
3.6 |
|
37 |
37 |
37 |
35 |
30 |
26 |
22 |
|
|
|
|
|
72 |
49 |
3.4 |
35 |
30 |
26 |
22 |
|
18 |
- |
|
- |
46 |
3.7 |
|
32 |
28 |
24 |
20 |
16 |
- |
- |
|
1500 |
|
67 |
45 |
3.4 |
39 |
37 |
33 |
29 |
|
24 |
20 |
|
15 |
42 |
3.7 |
|
36 |
34 |
30 |
27 |
22 |
18 |
14 |
|
||
|
62 |
41 |
3.3 |
41 |
41 |
40 |
37 |
|
32 |
28 |
|
24 |
37 |
3.6 |
|
37 |
37 |
36 |
33 |
28 |
25 |
21 |
|
|||
|
|
|
|
|
|
|
|
|||||||||||||||||||
|
|
|
|
57 |
41 |
3.3 |
41 |
41 |
41 |
38 |
|
34 |
29 |
|
25 |
36 |
3.6 |
|
36 |
36 |
36 |
33 |
29 |
25 |
21 |
|
|
|
|
|
72 |
48 |
3.4 |
33 |
29 |
24 |
20 |
|
16 |
- |
|
- |
45 |
3.7 |
|
30 |
27 |
22 |
18 |
15 |
- |
- |
|
1400 |
|
67 |
44 |
3.3 |
39 |
36 |
32 |
28 |
|
23 |
20 |
|
15 |
41 |
3.7 |
|
36 |
33 |
29 |
26 |
21 |
18 |
13 |
|
||
|
62 |
40 |
3.3 |
40 |
39 |
38 |
34 |
|
30 |
26 |
|
22 |
36 |
3.6 |
|
36 |
35 |
34 |
30 |
27 |
23 |
19 |
|
|||
|
|
|
|
|
|
|
|
|||||||||||||||||||
|
|
|
|
57 |
40 |
3.3 |
40 |
40 |
39 |
35 |
|
31 |
27 |
|
23 |
36 |
3.5 |
|
36 |
36 |
35 |
31 |
27 |
24 |
20 |
|
|
|
|
|
72 |
47 |
3.4 |
31 |
27 |
24 |
20 |
|
16 |
- |
|
- |
44 |
3.7 |
|
29 |
25 |
22 |
18 |
14 |
- |
- |
|
|
1200 |
|
67 |
41 |
3.3 |
36 |
32 |
29 |
25 |
|
22 |
18 |
|
14 |
39 |
3.6 |
|
34 |
30 |
27 |
23 |
20 |
17 |
13 |
|
|
|
|
62 |
38 |
3.3 |
38 |
37 |
36 |
32 |
|
29 |
25 |
|
21 |
35 |
3.6 |
|
35 |
34 |
33 |
29 |
26 |
23 |
19 |
|
||
|
|
|
|
|
|
|
|
|||||||||||||||||||
|
|
|
|
57 |
37 |
3.3 |
37 |
37 |
36 |
33 |
|
30 |
26 |
|
22 |
35 |
3.5 |
|
35 |
35 |
34 |
31 |
28 |
24 |
20 |
|
|
|
|
|
72 |
45 |
3.3 |
28 |
25 |
22 |
19 |
|
16 |
- |
|
- |
42 |
3.6 |
|
26 |
23 |
20 |
17 |
14 |
- |
- |
|
1050 |
|
67 |
41 |
3.3 |
34 |
30 |
27 |
24 |
|
20 |
17 |
|
14 |
38 |
3.6 |
|
31 |
27 |
25 |
22 |
18 |
15 |
12 |
|
||
|
62 |
36 |
3.3 |
36 |
35 |
33 |
30 |
|
27 |
24 |
|
21 |
34 |
3.5 |
|
34 |
33 |
31 |
28 |
25 |
22 |
19 |
|
|||
|
|
|
|
|
|
|
|
|||||||||||||||||||
|
|
|
|
57 |
36 |
3.3 |
36 |
36 |
34 |
31 |
|
28 |
25 |
|
22 |
33 |
3.5 |
|
33 |
33 |
31 |
28 |
25 |
22 |
20 |
|
|
|
|
|
72 |
45 |
3.3 |
26 |
24 |
20 |
17 |
|
15 |
- |
|
- |
40 |
3.6 |
|
23 |
21 |
17 |
15 |
13 |
- |
- |
|
900 |
|
67 |
39 |
3.3 |
31 |
28 |
25 |
22 |
|
19 |
17 |
|
14 |
35 |
3.6 |
|
27 |
25 |
22 |
19 |
17 |
15 |
12 |
|
||
|
62 |
35 |
3.2 |
35 |
34 |
32 |
29 |
|
25 |
23 |
|
20 |
32 |
3.5 |
|
32 |
30 |
28 |
25 |
22 |
20 |
17 |
|
|||
|
|
|
|
|
|
|
|
|||||||||||||||||||
|
|
|
|
57 |
35 |
3.2 |
35 |
35 |
32 |
30 |
|
26 |
24 |
|
21 |
31 |
3.5 |
|
31 |
31 |
28 |
26 |
23 |
21 |
18 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
Air On |
|
|
|
|
|
|
Temperature of Air on Outdoor Coil |
|
|
|
|
|
|
|
|
|||||||||
|
|
Indoor |
|
|
|
105 °F |
|
|
|
|
|
|
|
|
|
|
115 °F |
|
|
|
|
|
||||
|
|
Coil |
|
Total |
Power |
|
Sensible Capacity1, MBH |
|
Total |
Power |
|
|
Sensible Capacity1, MBH |
|
|
|||||||||||
|
|
CFM |
|
WB |
Cap.1 |
Input2 |
|
Entering Dry Bulb, °F |
|
Cap.1 |
Input2 |
|
|
Entering Dry Bulb, °F |
|
|
||||||||||
|
|
|
°F |
MBH |
KW |
86 |
83 |
80 |
77 |
|
74 |
71 |
|
68 |
MBH |
KW |
|
86 |
83 |
80 |
77 |
74 |
71 |
68 |
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||
|
|
|
|
72 |
44 |
4.0 |
31 |
27 |
24 |
20 |
|
16 |
- |
|
- |
42 |
4.2 |
|
30 |
26 |
23 |
19 |
15 |
- |
- |
|
1750 |
|
67 |
40 |
4.0 |
34 |
34 |
31 |
26 |
|
22 |
18 |
|
13 |
36 |
4.1 |
|
31 |
31 |
28 |
24 |
20 |
16 |
12 |
|
||
|
62 |
35 |
3.9 |
35 |
35 |
34 |
32 |
|
28 |
24 |
|
20 |
34 |
4.1 |
|
34 |
34 |
33 |
31 |
27 |
23 |
19 |
|
|||
|
|
|
|
|
|
|
|
|||||||||||||||||||
|
|
|
|
57 |
35 |
3.9 |
35 |
35 |
35 |
33 |
|
29 |
25 |
|
20 |
33 |
4.1 |
|
33 |
33 |
33 |
31 |
27 |
23 |
19 |
|
|
|
|
|
72 |
43 |
4.0 |
30 |
26 |
22 |
19 |
|
15 |
- |
|
- |
41 |
4.2 |
|
29 |
25 |
21 |
18 |
15 |
- |
- |
|
1500 |
|
67 |
38 |
4.0 |
32 |
31 |
27 |
24 |
|
20 |
16 |
|
12 |
35 |
4.1 |
|
30 |
28 |
25 |
22 |
18 |
15 |
11 |
|
||
|
62 |
34 |
3.9 |
34 |
34 |
33 |
30 |
|
26 |
23 |
|
19 |
33 |
4.1 |
|
33 |
33 |
32 |
29 |
25 |
22 |
19 |
|
|||
|
|
|
|
|
|
|
|
|||||||||||||||||||
|
|
|
|
57 |
34 |
3.9 |
34 |
34 |
34 |
31 |
|
28 |
24 |
|
20 |
32 |
4.1 |
|
32 |
32 |
32 |
29 |
26 |
22 |
19 |
|
|
|
|
|
72 |
42 |
4.0 |
28 |
25 |
21 |
17 |
|
14 |
- |
|
- |
39 |
4.2 |
|
26 |
23 |
19 |
16 |
13 |
- |
- |
|
1400 |
|
67 |
37 |
4.0 |
32 |
30 |
26 |
23 |
|
19 |
16 |
|
12 |
34 |
4.1 |
|
30 |
27 |
24 |
21 |
17 |
15 |
11 |
|
||
|
62 |
33 |
3.9 |
33 |
32 |
31 |
28 |
|
24 |
21 |
|
18 |
32 |
4.1 |
|
32 |
31 |
30 |
27 |
24 |
20 |
17 |
|
|||
|
|
|
|
|
|
|
|
|||||||||||||||||||
|
|
|
|
57 |
32 |
3.8 |
32 |
32 |
31 |
28 |
|
24 |
21 |
|
18 |
32 |
4.0 |
|
32 |
32 |
31 |
28 |
24 |
21 |
18 |
|
|
|
|
|
72 |
41 |
4.0 |
27 |
23 |
20 |
17 |
|
13 |
- |
|
- |
37 |
4.2 |
|
24 |
21 |
18 |
15 |
12 |
- |
- |
|
1200 |
|
67 |
35 |
3.9 |
30 |
27 |
24 |
21 |
|
18 |
15 |
|
11 |
32 |
4.1 |
|
28 |
24 |
22 |
19 |
17 |
14 |
10 |
|
||
|
62 |
32 |
3.9 |
32 |
31 |
30 |
26 |
|
24 |
21 |
|
17 |
30 |
4.1 |
|
30 |
29 |
28 |
25 |
22 |
19 |
16 |
|
|||
|
|
|
|
|
|
|
|
|||||||||||||||||||
|
|
|
|
57 |
31 |
3.8 |
31 |
31 |
31 |
27 |
|
25 |
21 |
|
18 |
29 |
4.0 |
|
29 |
29 |
29 |
25 |
23 |
20 |
17 |
|
|
|
|
|
72 |
40 |
3.9 |
24 |
22 |
19 |
16 |
|
14 |
- |
|
- |
35 |
4.1 |
|
21 |
19 |
17 |
14 |
12 |
- |
- |
|
1050 |
|
67 |
34 |
3.9 |
28 |
24 |
22 |
19 |
|
16 |
14 |
|
11 |
31 |
4.0 |
|
25 |
22 |
20 |
18 |
15 |
12 |
10 |
|
||
|
62 |
30 |
3.8 |
30 |
29 |
27 |
25 |
|
22 |
20 |
|
17 |
29 |
4.0 |
|
29 |
28 |
26 |
24 |
21 |
19 |
16 |
|
|||
|
|
|
|
|
|
|
|
|||||||||||||||||||
|
|
|
|
57 |
30 |
3.8 |
30 |
30 |
28 |
25 |
|
23 |
20 |
|
18 |
28 |
4.0 |
|
28 |
28 |
26 |
24 |
21 |
19 |
17 |
|
|
|
|
|
72 |
38 |
3.9 |
21 |
20 |
16 |
14 |
|
12 |
- |
|
- |
34 |
4.1 |
|
19 |
18 |
15 |
12 |
11 |
- |
- |
|
900 |
|
67 |
32 |
3.9 |
25 |
22 |
20 |
18 |
|
15 |
13 |
|
11 |
29 |
4.0 |
|
23 |
20 |
18 |
16 |
14 |
12 |
10 |
|
||
|
62 |
29 |
3.8 |
29 |
27 |
25 |
23 |
|
20 |
18 |
|
16 |
27 |
4.0 |
|
27 |
25 |
24 |
21 |
18 |
17 |
15 |
|
|||
|
|
|
|
|
|
|
|
|||||||||||||||||||
|
|
|
|
57 |
29 |
3.8 |
29 |
29 |
26 |
24 |
|
21 |
19 |
|
17 |
26 |
4.0 |
|
26 |
26 |
23 |
22 |
19 |
17 |
15 |
|
|
1These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply this value by |
|||||||||||||||||||||||||
|
3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit. |
|
|
|
|
|
|
|
|
|||||||||||||||||
|
2These ratings include the compressor and the outdoor fan motors but not the supply air blower motor. The total outdoor fan motor power input is 0.35 KW. |
|
|
|||||||||||||||||||||||
|
Refer to the Blower Performance Table for the KW of the supply air blower motor. |
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||
|
|
|
|
NOMINAL RATING |
|
|
|
|
|
|
|
|
ALL SENSIBLE CAPACITY |
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4 |
Unitary Products Group |
036-21564-002-A-0404
COOLING CAPACITIES - 4 TON (BCH048)
Air On |
|
|
|
|
|
|
Temperature of Air on Outdoor Coil |
|
|
|
|
|
|
|
||||||||
Indoor |
|
|
|
85 °F |
|
|
|
|
|
|
|
|
|
95 °F |
|
|
|
|
||||
Coil |
|
Total |
Power |
|
Sensible Capacity1, MBH |
|
Total |
Power |
|
|
Sensible Capacity1, MBH |
|
||||||||||
CFM |
|
WB |
Cap.1 |
Input2 |
|
Entering Dry Bulb, °F |
|
Cap.1 |
Input2 |
|
|
Entering Dry Bulb, °F |
|
|||||||||
|
°F |
MBH |
KW |
86 |
83 |
80 |
77 |
|
74 |
71 |
68 |
MBH |
KW |
|
86 |
83 |
80 |
77 |
74 |
71 |
68 |
|
|
|
|
|
|||||||||||||||||||
|
|
72 |
56 |
4.1 |
42 |
36 |
31 |
26 |
|
- |
- |
- |
53 |
4.5 |
|
40 |
35 |
29 |
24 |
- |
- |
- |
2000 |
|
67 |
53 |
4.0 |
48 |
47 |
41 |
36 |
|
30 |
25 |
- |
51 |
4.4 |
|
46 |
45 |
41 |
35 |
30 |
24 |
- |
|
62 |
49 |
4.0 |
49 |
49 |
48 |
44 |
|
38 |
33 |
28 |
46 |
4.3 |
|
46 |
46 |
45 |
41 |
35 |
30 |
24 |
|
|
|
|
|
|||||||||||||||||||
|
|
57 |
49 |
3.9 |
49 |
49 |
49 |
44 |
|
38 |
33 |
28 |
46 |
4.3 |
|
46 |
46 |
46 |
41 |
35 |
30 |
24 |
|
|
72 |
55 |
4.0 |
40 |
35 |
30 |
25 |
|
- |
- |
- |
53 |
4.4 |
|
38 |
33 |
28 |
23 |
- |
- |
- |
1800 |
|
67 |
52 |
4.0 |
47 |
44 |
39 |
34 |
|
29 |
24 |
- |
51 |
4.4 |
|
44 |
44 |
39 |
34 |
29 |
24 |
- |
|
62 |
48 |
3.9 |
48 |
48 |
47 |
43 |
|
38 |
33 |
28 |
47 |
4.3 |
|
47 |
47 |
45 |
40 |
36 |
31 |
26 |
|
|
|
|
|
|||||||||||||||||||
|
|
57 |
48 |
3.9 |
48 |
48 |
48 |
43 |
|
38 |
33 |
28 |
45 |
4.2 |
|
45 |
45 |
45 |
40 |
35 |
30 |
25 |
|
|
72 |
53 |
4.0 |
37 |
33 |
28 |
24 |
|
- |
- |
- |
52 |
4.4 |
|
36 |
32 |
27 |
23 |
- |
- |
- |
1600 |
|
67 |
51 |
4.0 |
46 |
42 |
37 |
33 |
|
28 |
24 |
- |
50 |
4.3 |
|
44 |
43 |
38 |
34 |
29 |
25 |
- |
|
62 |
47 |
3.9 |
47 |
47 |
46 |
41 |
|
37 |
32 |
28 |
45 |
4.2 |
|
45 |
45 |
44 |
40 |
36 |
31 |
27 |
|
|
|
|
|
|||||||||||||||||||
|
|
57 |
47 |
3.9 |
47 |
47 |
47 |
42 |
|
38 |
33 |
29 |
44 |
4.1 |
|
44 |
44 |
44 |
40 |
36 |
31 |
27 |
|
|
72 |
52 |
4.0 |
34 |
30 |
26 |
22 |
|
- |
- |
- |
49 |
4.3 |
|
33 |
29 |
25 |
21 |
- |
- |
- |
1400 |
|
67 |
49 |
3.9 |
42 |
38 |
34 |
30 |
|
26 |
22 |
- |
47 |
4.2 |
|
42 |
38 |
34 |
30 |
26 |
22 |
- |
|
62 |
46 |
3.8 |
46 |
45 |
42 |
38 |
|
34 |
30 |
26 |
43 |
4.1 |
|
43 |
42 |
40 |
36 |
32 |
28 |
24 |
|
|
|
|
|
|||||||||||||||||||
|
|
57 |
45 |
3.8 |
45 |
45 |
43 |
39 |
|
35 |
31 |
27 |
42 |
4.1 |
|
42 |
42 |
40 |
36 |
32 |
28 |
24 |
|
|
72 |
50 |
3.9 |
31 |
27 |
24 |
20 |
|
- |
- |
- |
47 |
4.2 |
|
29 |
25 |
22 |
18 |
- |
- |
- |
1200 |
|
67 |
47 |
3.9 |
38 |
35 |
31 |
28 |
|
24 |
21 |
- |
45 |
4.2 |
|
37 |
34 |
30 |
27 |
23 |
20 |
- |
|
62 |
44 |
3.8 |
44 |
42 |
39 |
35 |
|
32 |
28 |
25 |
40 |
4.1 |
|
40 |
39 |
36 |
32 |
29 |
25 |
22 |
|
|
|
|
|
|||||||||||||||||||
|
|
57 |
44 |
3.7 |
44 |
43 |
39 |
36 |
|
32 |
29 |
25 |
40 |
4.0 |
|
40 |
39 |
36 |
32 |
29 |
25 |
22 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||
Air On |
|
|
|
|
|
|
Temperature of Air on Outdoor Coil |
|
|
|
|
|
|
|
||||||||
Indoor |
|
|
|
105 °F |
|
|
|
|
|
|
|
|
|
115 °F |
|
|
|
|
||||
Coil |
|
Total |
Power |
|
Sensible Capacity1, MBH |
|
Total |
Power |
|
|
Sensible Capacity1, MBH |
|
||||||||||
CFM |
|
WB |
Cap.1 |
Input2 |
|
Entering Dry Bulb, °F |
|
Cap.1 |
Input2 |
|
|
Entering Dry Bulb, °F |
|
|||||||||
|
°F |
MBH |
KW |
86 |
83 |
80 |
77 |
|
74 |
71 |
68 |
MBH |
KW |
|
86 |
83 |
80 |
77 |
74 |
71 |
68 |
|
|
|
|
|
|||||||||||||||||||
|
|
72 |
51 |
4.9 |
40 |
35 |
29 |
24 |
|
- |
- |
- |
49 |
5.2 |
|
39 |
34 |
29 |
23 |
- |
- |
- |
2000 |
|
67 |
46 |
4.7 |
42 |
42 |
39 |
34 |
|
28 |
23 |
- |
41 |
5.0 |
|
40 |
40 |
37 |
32 |
26 |
21 |
- |
|
62 |
43 |
4.6 |
43 |
43 |
42 |
37 |
|
32 |
27 |
21 |
40 |
4.9 |
|
40 |
40 |
39 |
34 |
29 |
23 |
18 |
|
|
|
|
|
|||||||||||||||||||
|
|
57 |
43 |
4.6 |
43 |
43 |
43 |
38 |
|
32 |
28 |
22 |
40 |
4.8 |
|
40 |
40 |
40 |
34 |
30 |
24 |
19 |
|
|
72 |
50 |
4.8 |
38 |
33 |
28 |
23 |
|
- |
- |
- |
47 |
5.1 |
|
37 |
32 |
27 |
22 |
- |
- |
- |
1800 |
|
67 |
45 |
4.7 |
41 |
41 |
37 |
32 |
|
27 |
22 |
- |
40 |
4.9 |
|
37 |
36 |
35 |
30 |
25 |
20 |
- |
|
62 |
42 |
4.6 |
42 |
42 |
41 |
37 |
|
32 |
27 |
22 |
39 |
4.8 |
|
39 |
39 |
37 |
34 |
29 |
24 |
19 |
|
|
|
|
|
|||||||||||||||||||
|
|
57 |
42 |
4.5 |
42 |
42 |
42 |
37 |
|
33 |
27 |
23 |
38 |
4.7 |
|
38 |
38 |
38 |
33 |
30 |
25 |
20 |
|
|
72 |
49 |
4.8 |
35 |
31 |
26 |
22 |
|
- |
- |
- |
46 |
5.1 |
|
34 |
29 |
25 |
20 |
- |
- |
- |
1600 |
|
67 |
44 |
4.6 |
40 |
40 |
35 |
31 |
|
26 |
22 |
- |
39 |
4.9 |
|
36 |
36 |
32 |
28 |
23 |
19 |
- |
|
62 |
41 |
4.5 |
41 |
41 |
40 |
35 |
|
32 |
27 |
23 |
37 |
4.7 |
|
37 |
37 |
36 |
33 |
28 |
24 |
19 |
|
|
|
|
|
|||||||||||||||||||
|
|
57 |
41 |
4.4 |
41 |
41 |
41 |
36 |
|
32 |
28 |
23 |
37 |
4.7 |
|
37 |
37 |
37 |
34 |
28 |
25 |
20 |
|
|
72 |
47 |
4.7 |
32 |
28 |
24 |
20 |
|
- |
- |
- |
44 |
5.0 |
|
31 |
27 |
23 |
19 |
- |
- |
- |
1400 |
|
67 |
42 |
4.5 |
38 |
36 |
32 |
28 |
|
24 |
20 |
- |
37 |
4.8 |
|
36 |
34 |
30 |
26 |
21 |
17 |
- |
|
62 |
39 |
4.4 |
39 |
38 |
37 |
33 |
|
28 |
25 |
20 |
36 |
4.7 |
|
36 |
35 |
34 |
30 |
26 |
22 |
18 |
|
|
|
|
|
|||||||||||||||||||
|
|
57 |
39 |
4.4 |
39 |
39 |
37 |
33 |
|
29 |
25 |
21 |
36 |
4.6 |
|
36 |
36 |
34 |
31 |
26 |
23 |
19 |
|
|
72 |
44 |
4.6 |
28 |
25 |
21 |
18 |
|
- |
- |
- |
42 |
4.9 |
|
28 |
24 |
21 |
17 |
- |
- |
- |
1200 |
|
67 |
40 |
4.5 |
36 |
32 |
29 |
25 |
|
22 |
18 |
- |
36 |
4.7 |
|
34 |
31 |
27 |
24 |
20 |
17 |
- |
|
62 |
38 |
4.4 |
38 |
36 |
34 |
29 |
|
27 |
22 |
20 |
35 |
4.6 |
|
35 |
34 |
30 |
28 |
24 |
20 |
17 |
|
|
|
|
|
|||||||||||||||||||
|
|
57 |
37 |
4.3 |
37 |
37 |
34 |
30 |
|
27 |
23 |
20 |
35 |
4.6 |
|
35 |
35 |
31 |
29 |
24 |
21 |
18 |
1These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply this value by 3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2These ratings include the compressor and the outdoor fan motors but not the supply air blower motor. The total outdoor fan motor power input is 0.35 KW. Refer to the Blower Performance Table for the KW of the supply air blower motor.
|
NOMINAL RATING |
|
ALL SENSIBLE CAPACITY |
Unitary Products Group |
5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
036-21564-002-A-0404 |
|||
COOLING CAPACITIES - 5 TON (BCH060) |
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Air On |
|
|
|
|
|
|
Temperature of Air on Outdoor Coil |
|
|
|
|
|
|
|
|
|||||||||
|
|
Indoor |
|
|
|
85 °F |
|
|
|
|
|
|
|
|
|
|
|
95 °F |
|
|
|
|
|
|||
|
|
Coil |
|
Total |
Power |
|
Sensible Capacity1, MBH |
|
Total |
Power |
|
|
Sensible Capacity1, MBH |
|
|
|||||||||||
|
|
CFM |
WB |
Cap.1 |
Input2 |
|
Entering Dry Bulb, °F |
|
Cap.1 |
Input2 |
|
|
Entering Dry Bulb, °F |
|
|
|||||||||||
|
|
°F |
MBH |
KW |
86 |
83 |
80 |
77 |
|
74 |
71 |
|
68 |
MBH |
KW |
|
86 |
83 |
80 |
77 |
74 |
71 |
68 |
|
||
|
|
|
|
|
|
|
||||||||||||||||||||
|
|
|
72 |
68 |
5.7 |
51 |
44 |
38 |
31 |
|
- |
- |
|
- |
67 |
6.0 |
|
51 |
45 |
38 |
31 |
- |
- |
- |
|
|
2500 |
67 |
65 |
5.6 |
58 |
56 |
50 |
43 |
|
37 |
30 |
|
- |
64 |
5.9 |
|
56 |
56 |
50 |
43 |
37 |
30 |
- |
|
|||
62 |
61 |
5.6 |
61 |
61 |
59 |
53 |
|
46 |
39 |
|
33 |
59 |
5.9 |
|
59 |
59 |
57 |
50 |
44 |
38 |
31 |
|
||||
|
|
|
|
|
|
|
||||||||||||||||||||
|
|
|
57 |
60 |
5.5 |
60 |
60 |
59 |
53 |
|
47 |
40 |
|
33 |
58 |
5.8 |
|
58 |
58 |
57 |
51 |
44 |
39 |
32 |
|
|
|
|
|
72 |
67 |
5.6 |
48 |
42 |
36 |
30 |
|
- |
- |
|
- |
66 |
5.9 |
|
48 |
42 |
36 |
30 |
- |
- |
- |
|
|
2250 |
67 |
64 |
5.6 |
57 |
54 |
48 |
42 |
|
36 |
30 |
|
- |
63 |
5.9 |
|
55 |
54 |
48 |
42 |
35 |
29 |
- |
|
|||
62 |
60 |
5.5 |
60 |
60 |
57 |
51 |
|
45 |
39 |
|
33 |
57 |
5.8 |
|
57 |
57 |
55 |
50 |
44 |
38 |
32 |
|
||||
|
|
|
|
|
|
|
||||||||||||||||||||
|
|
|
57 |
59 |
5.5 |
59 |
59 |
58 |
52 |
|
46 |
40 |
|
34 |
57 |
5.8 |
|
57 |
57 |
56 |
50 |
45 |
39 |
33 |
|
|
|
|
|
72 |
66 |
5.6 |
45 |
40 |
34 |
29 |
|
- |
- |
|
- |
65 |
5.9 |
|
45 |
40 |
34 |
29 |
- |
- |
- |
|
|
|
2000 |
67 |
63 |
5.5 |
56 |
51 |
45 |
40 |
|
35 |
29 |
|
- |
61 |
5.9 |
|
55 |
51 |
45 |
40 |
34 |
29 |
- |
|
||
|
62 |
59 |
5.4 |
59 |
59 |
55 |
50 |
|
44 |
39 |
|
33 |
56 |
5.8 |
|
56 |
56 |
54 |
49 |
44 |
38 |
33 |
|
|||
|
|
|
|
|
|
|
||||||||||||||||||||
|
|
|
57 |
58 |
5.4 |
58 |
58 |
57 |
52 |
|
46 |
41 |
|
36 |
56 |
5.7 |
|
56 |
56 |
55 |
50 |
44 |
39 |
34 |
|
|
|
|
|
72 |
64 |
5.5 |
42 |
37 |
32 |
27 |
|
- |
- |
|
- |
62 |
5.9 |
|
43 |
38 |
33 |
28 |
- |
- |
- |
|
|
1750 |
67 |
61 |
5.5 |
52 |
47 |
42 |
37 |
|
33 |
28 |
|
- |
59 |
5.8 |
|
53 |
48 |
44 |
39 |
34 |
29 |
- |
|
|||
62 |
57 |
5.4 |
57 |
56 |
51 |
46 |
|
41 |
37 |
|
32 |
54 |
5.7 |
|
54 |
54 |
52 |
48 |
43 |
38 |
33 |
|
||||
|
|
|
|
|
|
|
||||||||||||||||||||
|
|
|
57 |
57 |
5.4 |
57 |
57 |
53 |
48 |
|
44 |
39 |
|
34 |
54 |
5.7 |
|
54 |
54 |
53 |
49 |
43 |
39 |
34 |
|
|
|
|
|
72 |
62 |
5.5 |
38 |
34 |
30 |
25 |
|
- |
- |
|
- |
60 |
5.8 |
|
41 |
36 |
32 |
28 |
- |
- |
- |
|
|
1500 |
67 |
59 |
5.5 |
48 |
43 |
39 |
35 |
|
31 |
26 |
|
- |
57 |
5.8 |
|
51 |
46 |
42 |
38 |
34 |
29 |
- |
|
|||
62 |
55 |
5.4 |
55 |
52 |
47 |
43 |
|
39 |
35 |
|
30 |
52 |
5.7 |
|
52 |
52 |
50 |
46 |
42 |
38 |
34 |
|
||||
|
|
|
|
|
|
|
||||||||||||||||||||
|
|
|
57 |
55 |
5.3 |
55 |
54 |
49 |
45 |
|
41 |
37 |
|
32 |
52 |
5.6 |
|
52 |
52 |
51 |
47 |
42 |
39 |
35 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
Air On |
|
|
|
|
|
|
Temperature of Air on Outdoor Coil |
|
|
|
|
|
|
|
|
|||||||||
|
|
Indoor |
|
|
|
105 °F |
|
|
|
|
|
|
|
|
|
|
|
115 °F |
|
|
|
|
|
|||
|
|
Coil |
|
Total |
Power |
|
Sensible Capacity1, MBH |
|
Total |
Power |
|
|
Sensible Capacity1, MBH |
|
|
|||||||||||
|
|
CFM |
WB |
Cap.1 |
Input2 |
|
Entering Dry Bulb, °F |
|
Cap.1 |
Input2 |
|
|
Entering Dry Bulb, °F |
|
|
|||||||||||
|
|
°F |
MBH |
KW |
86 |
83 |
80 |
77 |
|
74 |
71 |
|
68 |
MBH |
KW |
|
86 |
83 |
80 |
77 |
74 |
71 |
68 |
|
||
|
|
|
|
|
|
|
||||||||||||||||||||
|
|
|
72 |
64 |
6.0 |
51 |
44 |
38 |
31 |
|
- |
- |
|
- |
60 |
6.9 |
|
50 |
43 |
37 |
30 |
- |
- |
- |
|
|
2500 |
67 |
59 |
5.9 |
51 |
51 |
49 |
42 |
|
36 |
29 |
|
- |
54 |
6.6 |
|
54 |
53 |
47 |
41 |
34 |
27 |
- |
|
|||
62 |
54 |
5.9 |
54 |
54 |
51 |
46 |
|
40 |
33 |
|
26 |
49 |
6.5 |
|
49 |
49 |
48 |
42 |
35 |
28 |
22 |
|
||||
|
|
|
|
|
|
|
||||||||||||||||||||
|
|
|
57 |
54 |
5.8 |
54 |
54 |
52 |
46 |
|
41 |
33 |
|
26 |
49 |
6.5 |
|
49 |
49 |
49 |
43 |
35 |
28 |
23 |
|
|
|
|
|
72 |
63 |
5.9 |
48 |
42 |
36 |
30 |
|
- |
- |
|
- |
60 |
6.8 |
|
47 |
41 |
35 |
29 |
- |
- |
- |
|
|
2250 |
67 |
58 |
5.9 |
51 |
51 |
46 |
40 |
|
34 |
28 |
|
- |
54 |
6.6 |
|
47 |
47 |
45 |
39 |
32 |
26 |
- |
|
|||
62 |
53 |
5.8 |
53 |
53 |
52 |
46 |
|
40 |
34 |
|
28 |
49 |
6.5 |
|
49 |
49 |
47 |
42 |
36 |
30 |
24 |
|
||||
|
|
|
|
|
|
|
||||||||||||||||||||
|
|
|
57 |
53 |
5.8 |
53 |
53 |
52 |
46 |
|
41 |
35 |
|
27 |
49 |
6.4 |
|
49 |
49 |
48 |
43 |
37 |
31 |
25 |
|
|
|
|
|
72 |
62 |
5.9 |
45 |
39 |
34 |
28 |
|
- |
- |
|
- |
59 |
6.8 |
|
44 |
38 |
33 |
27 |
- |
- |
- |
|
|
2000 |
67 |
57 |
5.9 |
51 |
49 |
44 |
38 |
|
33 |
27 |
|
- |
53 |
6.5 |
|
45 |
45 |
42 |
36 |
31 |
26 |
- |
|
|||
62 |
52 |
5.8 |
52 |
52 |
51 |
46 |
|
40 |
35 |
|
30 |
48 |
6.4 |
|
48 |
48 |
46 |
42 |
36 |
31 |
25 |
|
||||
|
|
|
|
|
|
|
||||||||||||||||||||
|
|
|
57 |
52 |
5.7 |
52 |
52 |
51 |
46 |
|
40 |
36 |
|
31 |
47 |
6.4 |
|
47 |
47 |
46 |
43 |
36 |
32 |
25 |
|
|
|
|
|
72 |
60 |
5.9 |
41 |
37 |
32 |
27 |
|
- |
- |
|
- |
56 |
6.7 |
|
40 |
35 |
30 |
25 |
- |
- |
- |
|
|
1750 |
67 |
55 |
5.8 |
48 |
46 |
41 |
36 |
|
31 |
26 |
|
- |
51 |
6.5 |
|
43 |
43 |
38 |
33 |
29 |
24 |
- |
|
|||
62 |
50 |
5.7 |
50 |
50 |
48 |
43 |
|
39 |
34 |
|
29 |
46 |
6.4 |
|
46 |
46 |
43 |
38 |
33 |
28 |
24 |
|
||||
|
|
|
|
|
|
|
||||||||||||||||||||
|
|
|
57 |
50 |
5.7 |
50 |
50 |
48 |
43 |
|
39 |
34 |
|
30 |
45 |
6.3 |
|
45 |
45 |
43 |
38 |
33 |
28 |
25 |
|
|
|
|
|
72 |
57 |
5.8 |
38 |
34 |
30 |
25 |
|
- |
- |
|
- |
53 |
6.6 |
|
36 |
31 |
27 |
23 |
- |
- |
- |
|
|
1500 |
67 |
53 |
5.8 |
47 |
43 |
38 |
34 |
|
30 |
26 |
|
- |
48 |
6.4 |
|
41 |
39 |
35 |
30 |
26 |
22 |
- |
|
|||
62 |
48 |
5.7 |
48 |
48 |
45 |
41 |
|
37 |
32 |
|
28 |
44 |
6.3 |
|
44 |
44 |
39 |
35 |
30 |
26 |
22 |
|
||||
|
|
|
|
|
|
|
||||||||||||||||||||
|
|
|
57 |
48 |
5.6 |
48 |
48 |
45 |
41 |
|
38 |
32 |
|
28 |
43 |
6.2 |
|
43 |
43 |
40 |
36 |
30 |
26 |
23 |
|
|
|
1These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply this value by |
|||||||||||||||||||||||||
|
3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit. |
|
|
|
|
|
|
|
|
|||||||||||||||||
|
2These ratings include the compressor and the outdoor fan motors but not the supply air blower motor. The total outdoor fan motor power input is 0.35 KW. |
|
|
|||||||||||||||||||||||
|
Refer to the Blower Performance Table for the KW of the supply air blower motor. |
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||
|
|
|
NOMINAL RATING |
|
|
|
|
|
|
|
|
|
ALL SENSIBLE CAPACITY |
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6 |
Unitary Products Group |
036-21564-002-A-0404
HEATING CAPACITIES
|
|
|
|
|
BCH036 |
|
|
|
|
|
|
CFM |
RET. AIR |
CAP |
|
|
OUTDOOR AIR TEMPERATURE, °F (72% RH) |
|
|
||||
°F |
& KW |
-10 |
0 |
10 |
20 |
30 |
40 |
50 |
60 |
||
|
|||||||||||
|
55 |
MBH |
13.1 |
16.4 |
23.5 |
29.1 |
30.2 |
41.7 |
47.0 |
48.2 |
|
|
KW |
2.9 |
3.0 |
3.2 |
3.3 |
3.5 |
3.7 |
3.8 |
3.9 |
||
|
|
||||||||||
1750 |
70 |
MBH |
11.9 |
15.0 |
21.5 |
26.7 |
27.7 |
38.2 |
43.1 |
44.1 |
|
KW |
3.0 |
3.1 |
3.4 |
3.4 |
3.6 |
3.8 |
3.9 |
4.1 |
|||
|
|
||||||||||
|
80 |
MBH |
10.9 |
13.6 |
19.6 |
24.3 |
25.2 |
34.8 |
39.3 |
40.2 |
|
|
KW |
3.1 |
3.2 |
3.4 |
3.5 |
3.8 |
3.9 |
4.1 |
4.2 |
||
|
|
||||||||||
|
55 |
MBH |
12.4 |
15.5 |
22.5 |
27.7 |
28.7 |
39.6 |
44.7 |
45.8 |
|
|
KW |
2.7 |
2.9 |
3.0 |
3.1 |
3.3 |
3.5 |
3.6 |
3.7 |
||
|
|
||||||||||
1400 |
70 |
MBH |
11.4 |
14.1 |
20.3 |
25.2 |
26.1 |
36.1 |
40.7 |
41.6 |
|
KW |
2.9 |
3.0 |
3.2 |
3.3 |
3.5 |
3.7 |
3.8 |
3.9 |
|||
|
|
||||||||||
|
80 |
MBH |
10.4 |
13.1 |
18.0 |
23.2 |
24.2 |
33.3 |
37.6 |
38.5 |
|
|
KW |
3.0 |
3.1 |
3.2 |
3.4 |
3.6 |
3.8 |
3.9 |
4.0 |
||
|
|
||||||||||
|
55 |
MBH |
11.8 |
14.8 |
21.3 |
26.5 |
27.5 |
37.8 |
42.7 |
43.7 |
|
|
KW |
2.7 |
2.8 |
3.0 |
3.1 |
3.3 |
3.4 |
3.5 |
3.6 |
||
|
|
||||||||||
1200 |
70 |
MBH |
10.8 |
13.5 |
19.4 |
24.0 |
24.9 |
34.4 |
38.8 |
39.7 |
|
KW |
2.9 |
3.0 |
3.1 |
3.3 |
3.4 |
3.6 |
3.7 |
3.8 |
|||
|
|
||||||||||
|
80 |
MBH |
9.9 |
12.4 |
17.8 |
22.0 |
22.9 |
31.5 |
35.6 |
36.5 |
|
|
KW |
2.9 |
3.1 |
3.2 |
3.4 |
3.5 |
3.7 |
3.8 |
3.9 |
||
|
|
||||||||||
|
55 |
MBH |
11.2 |
14.1 |
20.3 |
25.2 |
26.1 |
35.9 |
40.6 |
41.6 |
|
|
KW |
2.6 |
2.7 |
2.9 |
3.0 |
3.3 |
3.3 |
3.5 |
3.5 |
||
|
|
||||||||||
1050 |
70 |
MBH |
10.2 |
12.8 |
18.5 |
22.8 |
23.6 |
32.7 |
36.9 |
37.8 |
|
KW |
2.8 |
2.9 |
3.0 |
3.2 |
3.3 |
3.5 |
3.6 |
3.7 |
|||
|
|
||||||||||
|
80 |
MBH |
9.3 |
11.7 |
16.7 |
20.7 |
21.5 |
29.8 |
33.6 |
34.4 |
|
|
KW |
2.8 |
3.0 |
3.1 |
3.3 |
3.4 |
3.6 |
3.7 |
3.8 |
||
|
|
||||||||||
|
|
|
|
|
BCH048 |
|
|
|
|
|
|
|
55 |
MBH |
12.3 |
17.3 |
22.5 |
28.2 |
36.3 |
44.5 |
53.8 |
61.6 |
|
|
KW |
3.4 |
3.5 |
3.6 |
3.6 |
3.8 |
4.0 |
4.6 |
5.2 |
||
|
|
||||||||||
2000 |
70 |
MBH |
11.8 |
16.6 |
21.6 |
27.1 |
34.9 |
42.8 |
51.7 |
59.2 |
|
KW |
3.5 |
3.6 |
3.8 |
3.8 |
4.0 |
4.2 |
4.8 |
5.4 |
|||
|
|
||||||||||
|
80 |
MBH |
10.9 |
15.3 |
19.9 |
24.9 |
32.1 |
39.4 |
47.6 |
54.5 |
|
|
KW |
3.6 |
3.7 |
4.0 |
4.0 |
4.1 |
4.4 |
5.0 |
5.7 |
||
|
|
||||||||||
|
55 |
MBH |
12.1 |
17.0 |
22.0 |
27.7 |
34.5 |
42.3 |
51.2 |
58.6 |
|
|
KW |
3.3 |
3.4 |
3.5 |
3.6 |
3.6 |
3.8 |
4.4 |
5.0 |
||
|
|
||||||||||
1600 |
70 |
MBH |
11.6 |
16.3 |
21.2 |
26.6 |
33.2 |
40.7 |
49.2 |
56.3 |
|
KW |
3.4 |
3.5 |
3.6 |
3.7 |
3.8 |
4.0 |
4.6 |
5.2 |
|||
|
|
||||||||||
|
80 |
MBH |
10.7 |
15.0 |
19.5 |
24.5 |
30.5 |
37.4 |
45.3 |
51.8 |
|
|
KW |
3.5 |
3.6 |
3.8 |
3.9 |
4.0 |
4.2 |
4.8 |
5.4 |
||
|
|
||||||||||
|
55 |
MBH |
10.9 |
15.3 |
19.9 |
24.9 |
31.7 |
38.9 |
47.0 |
53.8 |
|
|
KW |
3.1 |
3.2 |
3.3 |
3.4 |
3.5 |
3.7 |
4.2 |
4.8 |
||
|
|
||||||||||
1200 |
70 |
MBH |
10.5 |
14.7 |
19.1 |
24.0 |
30.5 |
37.4 |
45.2 |
51.7 |
|
KW |
3.2 |
3.3 |
3.4 |
3.5 |
3.6 |
3.8 |
4.4 |
5.0 |
|||
|
|
||||||||||
|
80 |
MBH |
9.6 |
13.5 |
17.6 |
22.0 |
28.1 |
34.4 |
41.6 |
47.6 |
|
|
KW |
3.3 |
3.4 |
3.5 |
3.6 |
3.8 |
4.0 |
4.6 |
5.2 |
||
|
|
||||||||||
|
|
|
|
|
BCH060 |
|
|
|
|
|
|
|
55 |
MBH |
18.2 |
24.7 |
31.1 |
38.4 |
45.6 |
55.4 |
64.7 |
75.6 |
|
|
KW |
5.0 |
5.1 |
5.2 |
5.3 |
5.3 |
5.6 |
5.9 |
6.5 |
||
|
|
||||||||||
2500 |
70 |
MBH |
17.5 |
23.7 |
29.9 |
37.0 |
43.9 |
53.3 |
62.2 |
72.7 |
|
KW |
5.2 |
5.3 |
5.4 |
5.5 |
5.6 |
5.9 |
6.2 |
6.8 |
|||
|
|
||||||||||
|
80 |
MBH |
16.1 |
21.8 |
27.5 |
34.0 |
40.4 |
49.0 |
57.2 |
66.9 |
|
|
KW |
5.4 |
5.6 |
5.7 |
5.8 |
5.9 |
6.0 |
6.5 |
7.2 |
||
|
|
||||||||||
|
55 |
MBH |
18.0 |
24.4 |
30.8 |
38.1 |
45.0 |
54.7 |
63.9 |
74.7 |
|
|
KW |
4.7 |
4.8 |
4.9 |
5.0 |
5.3 |
5.5 |
5.8 |
6.4 |
||
|
|
||||||||||
2000 |
70 |
MBH |
17.3 |
23.5 |
29.6 |
36.6 |
43.3 |
52.6 |
61.4 |
71.8 |
|
KW |
4.9 |
5.0 |
5.1 |
5.2 |
5.5 |
5.8 |
6.1 |
6.7 |
|||
|
|
||||||||||
|
80 |
MBH |
15.9 |
21.6 |
27.2 |
33.7 |
39.8 |
48.4 |
56.5 |
66.1 |
|
|
KW |
5.1 |
5.3 |
5.4 |
5.5 |
5.8 |
6.1 |
6.4 |
7.0 |
||
|
|
||||||||||
|
55 |
MBH |
16.2 |
22.0 |
27.8 |
34.3 |
41.4 |
50.2 |
58.7 |
68.6 |
|
|
KW |
4.5 |
4.6 |
4.7 |
4.8 |
5.0 |
5.3 |
5.5 |
6.1 |
||
|
|
||||||||||
1500 |
70 |
MBH |
15.6 |
21.2 |
26.7 |
33.0 |
39.8 |
48.3 |
56.4 |
66.0 |
|
KW |
4.7 |
4.8 |
4.9 |
5.0 |
5.2 |
5.5 |
5.8 |
6.4 |
|||
|
|
||||||||||
|
80 |
MBH |
14.4 |
19.5 |
24.6 |
30.4 |
36.6 |
44.5 |
51.9 |
60.7 |
|
|
KW |
4.9 |
5.0 |
5.1 |
5.2 |
5.5 |
5.8 |
6.1 |
6.7 |
||
|
|
Unitary Products Group |
7 |
036-21564-002-A-0404
SUPPLY AIR BLOWER PERFORMANCE - BCH036 & 048 with Belt-Drive
BCH036 - SIDE DUCT APPLICATIONS (230/460/575 VOLTS)
MODEL |
AIR FLOW |
|
|
|
|
Available External Static Pressure - IWG* |
|
|
|
|
||||||
0.20 |
0.30 |
0.40 |
0.50 |
0.60 |
0.70 |
0.80 |
||||||||||
BCH |
CFM |
|||||||||||||||
RPM |
Watts |
RPM |
Watts |
RPM |
Watts |
RPM |
Watts |
RPM |
Watts |
RPM |
Watts |
RPM |
Watts |
|||
|
|
|||||||||||||||
|
2000 |
843 |
860 |
880 |
925 |
919 |
1005 |
956 |
1065 |
993 |
1145 |
1030 |
1195 |
1067 |
1235 |
|
|
1900 |
817 |
775 |
854 |
850 |
893 |
920 |
930 |
995 |
970 |
1065 |
1008 |
1125 |
1046 |
1170 |
|
|
1800 |
790 |
700 |
828 |
760 |
867 |
840 |
906 |
905 |
944 |
980 |
985 |
1040 |
1025 |
1100 |
|
|
1700 |
- |
- |
802 |
670 |
840 |
745 |
881 |
815 |
920 |
900 |
961 |
970 |
1001 |
1030 |
|
036 |
1600 |
- |
- |
- |
- |
818 |
665 |
858 |
740 |
898 |
820 |
940 |
890 |
980 |
950 |
|
|
1500 |
- |
- |
- |
- |
- |
- |
842 |
695 |
882 |
755 |
922 |
835 |
962 |
895 |
|
|
1400 |
- |
- |
- |
- |
- |
- |
833 |
650 |
867 |
705 |
904 |
765 |
942 |
820 |
|
|
1300 |
- |
- |
- |
- |
- |
- |
- |
- |
858 |
665 |
893 |
725 |
932 |
785 |
|
|
1200 |
- |
- |
- |
- |
- |
- |
- |
- |
847 |
640 |
880 |
680 |
916 |
730 |
|
|
|
|
|
|
|
|
|
|
|
|
||||||
MODEL |
AIR FLOW |
|
|
|
|
Available External Static Pressure - IWG* |
|
|
|
|
||||||
0.90 |
1.00 |
1.10 |
1.20 |
1.30 |
1.40 |
1.50 |
||||||||||
BCH |
CFM |
|||||||||||||||
RPM |
Watts |
RPM |
Watts |
RPM |
Watts |
RPM |
Watts |
RPM |
Watts |
RPM |
Watts |
RPM |
Watts |
|||
|
|
|||||||||||||||
|
2000 |
1103 |
1270 |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
|
|
1900 |
1085 |
1210 |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
|
|
1800 |
1064 |
1145 |
1102 |
1180 |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
|
|
1700 |
1040 |
1075 |
1081 |
1115 |
1121 |
1140 |
- |
- |
- |
- |
- |
- |
- |
- |
|
036 |
1600 |
1020 |
1005 |
1060 |
1050 |
1100 |
1085 |
- |
- |
- |
- |
- |
- |
- |
- |
|
|
1500 |
1003 |
945 |
1044 |
995 |
1086 |
1035 |
- |
- |
- |
- |
- |
- |
- |
- |
|
|
1400 |
982 |
880 |
1024 |
920 |
1067 |
965 |
1107 |
1000 |
- |
- |
- |
- |
- |
- |
|
|
1300 |
970 |
835 |
1010 |
870 |
1053 |
920 |
1099 |
960 |
- |
- |
- |
- |
- |
- |
|
|
1200 |
953 |
780 |
992 |
815 |
1034 |
855 |
1080 |
905 |
- |
- |
- |
- |
- |
- |
NOTE: FOR 208 VOLTS, MULTIPLY VALUES BY 0.95.
*INCLUDES ALLOWANCES FOR A WET INDOOR COIL AND 1" FILTERS. REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS.
BCH048 - SIDE DUCT APPLICATIONS (230/460/575 VOLTS)
MODEL |
AIR FLOW |
|
|
|
|
Available External Static Pressure - IWG* |
|
|
|
|
||||||
0.20 |
0.30 |
0.40 |
0.50 |
0.60 |
0.70 |
0.80 |
||||||||||
BCH |
CFM |
|||||||||||||||
RPM |
Watts |
RPM |
Watts |
RPM |
Watts |
RPM |
Watts |
RPM |
Watts |
RPM |
Watts |
RPM |
Watts |
|||
|
|
|||||||||||||||
|
2000 |
843 |
860 |
880 |
925 |
919 |
1005 |
956 |
1065 |
993 |
1145 |
1030 |
1195 |
1067 |
1235 |
|
|
1900 |
817 |
775 |
854 |
850 |
893 |
920 |
930 |
995 |
970 |
1065 |
1008 |
1125 |
1046 |
1170 |
|
|
1800 |
790 |
700 |
828 |
760 |
867 |
840 |
906 |
905 |
944 |
980 |
985 |
1040 |
1025 |
1100 |
|
|
1700 |
- |
- |
802 |
670 |
840 |
745 |
881 |
815 |
920 |
900 |
961 |
970 |
1001 |
1030 |
|
048 |
1600 |
- |
- |
- |
- |
818 |
665 |
858 |
740 |
898 |
820 |
940 |
890 |
980 |
950 |
|
|
1500 |
- |
- |
- |
- |
- |
- |
842 |
695 |
882 |
755 |
922 |
835 |
962 |
895 |
|
|
1400 |
- |
- |
- |
- |
- |
- |
833 |
650 |
867 |
705 |
904 |
765 |
942 |
820 |
|
|
1300 |
- |
- |
- |
- |
- |
- |
- |
- |
858 |
665 |
893 |
725 |
932 |
785 |
|
|
1200 |
- |
- |
- |
- |
- |
- |
- |
- |
847 |
640 |
880 |
680 |
916 |
730 |
|
|
|
|
|
|
|
|
|
|
|
|
||||||
MODEL |
AIR FLOW |
|
|
|
|
Available External Static Pressure - IWG* |
|
|
|
|
||||||
0.90 |
1.00 |
1.10 |
1.20 |
1.30 |
1.40 |
1.50 |
||||||||||
BCH |
CFM |
|||||||||||||||
RPM |
Watts |
RPM |
Watts |
RPM |
Watts |
RPM |
Watts |
RPM |
Watts |
RPM |
Watts |
RPM |
Watts |
|||
|
|
|||||||||||||||
|
2000 |
1103 |
1270 |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
|
|
1900 |
1085 |
1210 |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
|
|
1800 |
1064 |
1145 |
1102 |
1180 |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
|
|
1700 |
1040 |
1075 |
1081 |
1115 |
1121 |
1140 |
- |
- |
- |
- |
- |
- |
- |
- |
|
048 |
1600 |
1020 |
1005 |
1060 |
1050 |
1100 |
1085 |
- |
- |
- |
- |
- |
- |
- |
- |
|
|
1500 |
1003 |
945 |
1044 |
995 |
1086 |
1035 |
- |
- |
- |
- |
- |
- |
- |
- |
|
|
1400 |
982 |
880 |
1024 |
920 |
1067 |
965 |
1107 |
1000 |
- |
- |
- |
- |
- |
- |
|
|
1300 |
970 |
835 |
1010 |
870 |
1053 |
920 |
1099 |
960 |
- |
- |
- |
- |
- |
- |
|
|
1200 |
953 |
780 |
992 |
815 |
1034 |
855 |
1080 |
905 |
- |
- |
- |
- |
- |
- |
NOTE: FOR 208 VOLTS, MULTIPLY VALUES BY 0.95.
*INCLUDES ALLOWANCES FOR A WET INDOOR COIL AND 1" FILTERS. REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS.
8 |
Unitary Products Group |