Yaskawa iQpump Drive User Manual

iQpump Drive
User Manual
Document Number: TM.iQp.01
Quick Reference for iQpump (P7U) <0033>
Parameter
Factory Setting
User
Setting
Parameter
Number
Factory Setting
User
Setting
Parameter
Number
Factory Setting
User
Setting
Parameter
Number
Factory Setting
User
Setting
Parameter
A1-00 0 C6-05 0 H4-04 8 n3-03 1.0 P2-12 15 RPM
A1-01 2 d1-01 00145 H4-05 50.0% n3-04 40 s P2-13 5.0 s
A1-03 0 d1-02 00145 H4-06 0.0% o1-01 6 P2-14 5.0 s
A1-04 0 d1-03 00145 H4-07 0 o1-02 1**
A1-05 0 d1-04 00145 H4-08 0 o1-05 3
b1-01 0 d1-17 0.00 to 6.00 Hz H5-01 1F o1-06 1**
b1-02 1 d2-01 100.0% H5-02 3 o1-07 2**
P2-15
P2-16
0.0 (system
units P1-02)
1.5 (system
units P1-02)
b1-03 0 d2-02 0.0% H5-03 0 o1-08 91** P2-17 2.0 s
b1-08 0 d2-03 0.0% H5-04 3 o2-01 1** P2-18 2.0 s
b1-11 0 s d3-01 0.0 Hz H5-05 1 o2-02 1 P2-19 0
b2-01 0.5 Hz d3-02 0.0 Hz H5-06 5 ms o2-03 0 P2-20 0.0 Hz
b2-02 50% d3-03 0.0 Hz H5-07 1 o2-04 kVA Dep. P3-01 0
b2-03 0.00 s d3-04 1.0 Hz H5-09 2.0 s o2-05 0 P3-02 59.0 Hz
b2-04 0.50 s
b2-09 0% L1-02 8.0 min o2-07 0 H
E1-01
240.0 V
486.0 V
L1-01 1 o2-06 1
P3-03
0.0 (system
units P1-02)
b3-01 2 E1-03 F L1-03 3 o2-08 1 P3-04 59.0 Hz
b3-02 120% E1-04 60.0 Hz L1-04 1 o2-10 0 H
b3-03 2.0 s
b3-05 0.2 s L2-01 2 o2-14 0 P3-06 5 s
E1-05
240.0 V
486.0 V
L1-05 0.20 s o2-12 0
b3-14 1 E1-06 60.0 Hz L2-02 kVA Dep o3-01 0
b4-01 0.0 s E1-07 3.0 Hz L2-03 kVA Dep o3-02 0
b4-02 0.0 s
b5-01 1 L2-05 Voltage Class Dep. P1-02 1
E1-08
17.2 Vac
33.6 Vac
L2-04 kVA Dep P1-01 0
P3-05
P3-07
P3-08
0.0 (system
units P1-02)
0.0 (system
units P1-02)
0.0 (system
units P1-02)
b5-02 2.00 E1-09 1.5 Hz L3-01 1 P1-03 00145 P3-09 35.0 Hz
b5-03 5.0 s E1-10 10.3 Vac L3-02 120%
b5-04 100.0% E1-11 0.0 Hz L3-04 1 P3-11 2 s
P1-04
0.0 (system
units P1-02)
b5-06 100.0% E1-12 0.0 Vac L3-05 1 P1-05 0 s
b5-07 0.0% E1-13 0.0 Vac L3-06 120% P1-06 35.0 Hz
b5-08 0.00 s E2-01 kVA Dep L4-01 0.0 Hz
b5-09 0 E2-03 kVA Dep L4-02 2.0 Hz
P1-07
0.0 (system
units P1-02)
b5-10 1.0 E2-04 2 L4-05 0 P1-08 5 s
b5-12 0 E2-05 kVA Dep L4-06 80%
b5-13 0% F6-01 1 L5-01 0
P1-09
155.0 (system units P1-02)
P3-10 35.0 Hz
P3-12
0.0 (system
units P1-02)
P3-13 0.0 Hz
P3-14
P4-01
0.0 (system
units P1-02)
0.0 (system
units P1-02)
b5-14 1.0 s F6-02 0 L5-02 0 P1-10 2 s P4-02 0.0 Hz
b5-17 0.0 s F6-03 1 L5-03 180.0 s
b8-01 0 F6-05 0 L6-01 0 P4-04 2.0 s
P1-11
0.0 (system
units P1-02)
P4-03 0.0 min
b8-04 kVA Dep. H1-01 24 L6-02 15% P1-12 60 s P4-05 0.0 Hz
b8-05 2 0 ms H1-02 14 L6-03 10.0 s
b8-06 0%
C1-01 25.0 s L8-02 95º C P1-14 0.0 A P4-08 0
H1-03
3: 2 - Wire 0: 3 - Wire
L8-01 0 P4-07 0
P1-13
0.0 (system
units P1-02)
P4-06 1.0 s
C1-02 25.0 s H1-04 80 L8-03 4 P1-15 0 P4-09 0.2 min
C1-03 10.0 s H1-05 84 L8-05 1 P2-01 0 P4-10 0
C1-04 10.0 s H2-01 40 L8-06 5.0% P2-02 0.0 P5-01 1
C1-05 50.0 s H2-02 41 L8-07 1 P2-03 10 s P5-02 0.0 Hz
C1-06 50.0 s H3-02 100.0% L8-09 1
C1-09 10.0 s H3-03 0.0% L8-10 0 P5-04 1
P2-04
0.0 (system
units P1-02)
P5-03 1
C1-11 0.0 Hz H3-08 2 L8-11 300 s P2-05 10 s T1-02 kVA Dep.
C2-01 0.20 s H3-09 B* L8-12 45º C P2-06 0 T1-04 kVA Dep.
C2-02 0.20 s H3-10 100.0% L8-15 1 P2-07 300 s
C4-01 1.00 H3-11 0.0% L8-18 1 P2-08 0
C4-02 200 ms H3-12 0.30 s L8-19 20.0%
C6-01 2 H3-13 0 n1-01 1
C6-02 kVA Dep H4-01 2 n1-02 1.00
C6-03 kVA Dep H4-02 100.0% n3-01 5%
P2-09
P2-10
0.0 (system
units P1-02)
0.0 (system
units P1-02)
C6-04 kVA Dep H4-03 0.0% n3-02 150% P2-11 0 RPM
* Factory setting changes to “B” when b5-01=1. ** Factory setting changes to “B” when b5-01=1 as follows: o1-06=1, o1-07=38, o1=08=24
Factory Setting
User
Setting
2 YAS K AWA TM.iQp.01 iQpump Drive User Manual
Table of Contents
Warnings and Cautions ............................................................. 7
Introduction ................................................................................ 9
Physical Installation................................................................. 11
iQpump Model Number and Enclosure Style ................................................ 12
Confirmations Upon Delivery ........................................................................ 13
Component Names ....................................................................................... 15
Exterior and Mounting Dimensions ............................................................... 17
Heat Loss Data ............................................................................................. 21
Checking and Controlling the Installation Site............................................... 22
Installation Orientation and Clearances ........................................................ 23
Removing and Attaching the Terminal Cover................................................ 24
Removing/Attaching the Digital Operator and Front Cover........................... 25
Electrical Installation ............................................................... 29
Terminal Block Configuration ........................................................................ 30
Wiring Main Circuit Terminals........................................................................ 31
Control Wiring ............................................................................................... 40
Digital Operator ........................................................................ 51
Digital Operator Display ................................................................................ 52
Digital Operator Keys.................................................................................... 53
Drive Mode Indicators ................................................................................... 54
Drive Main Menu........................................................................................... 55
Pump Quick Setup Menu (-QUICK-) <0032>................................................ 60
Programming Menu (-ADV-).......................................................................... 61
Example of Changing a Parameter............................................................... 63
YASKAWA TM.iQp.01 iQpump Drive User Manual 3
Start Up ..................................................................................... 65
Start Up ......................................................................................................... 66
iQpump Drive Start Up Procedures............................................................... 69
Pump System Start/Stop ............................................................................... 73
Pump Basics ................................................................................................. 75
Use Feedback Level to Start iQpump Controller........................................... 77
Low Feedback Level Alarm and Fault Setup ................................................ 79
High Feedback Level Alarm and Fault Setup................................................ 81
Feedback Loss Detection.............................................................................. 83
Basic Pump Protection.................................................................................. 84
Basic Programming ................................................................. 87
iQpump Basic Programming Parameters...................................................... 88
Pump Basic................................................................................................. 127
Pump Protection.......................................................................................... 130
T1 Auto-Tuning ........................................................................................... 134
Diagnostics & Troubleshooting ............................................ 135
Fault Detection............................................................................................ 136
iQpump Keypad Messages......................................................................... 141
Alarm Detection........................................................................................... 143
Operator Programming Errors (OPE).......................................................... 146
Auto-Tuning Faults...................................................................................... 147
Digital Operator COPY Function Faults ...................................................... 148
Troubleshooting .......................................................................................... 149
Main Circuit Test Procedure ........................................................................ 153
Drive Date Stamp Information ..................................................................... 157
Maintenance............................................................................ 159
Periodic Inspection...................................................................................... 160
Preventive Maintenance.............................................................................. 161
Heatsink Cooling Fan Replacement............................................................ 162
Removing and Mounting the Terminal Card................................................ 164
Parameters.............................................................................. 165
Parameter List............................................................................................. 166
Monitor List.................................................................................................. 190
Fault Trace List ........................................................................................... 193
Fault History List ......................................................................................... 194
4 YASKAWA TM.iQp.01 iQpump Drive User Manual
Capacity Related Parameters................................................ 197
Drive Capacity............................................................................................. 198
Parameters Affected by o2-04 .................................................................... 199
Capacity Related Parameter Values ........................................................... 200
Specifications ......................................................................... 203
Standard iQpump Drive Specifications........................................................ 204
Communication ...................................................................... 207
Using Modbus Communication ................................................................... 208
Modbus Function Code Details................................................................... 212
Modbus Data Tables ................................................................................... 214
Modbus Self-Diagnosis ............................................................................... 219
Peripheral Devices ................................................................. 221
Branch Circuit Short Circuit Protection........................................................ 222
Branch Circuit Overload Protection............................................................. 224
Peripheral Devices...................................................................................... 224
Third Party Serial Communication Converters
RS232-RS485 / USB - RS485 Converters.................................................. 225
PumpScada Software ................................................................................. 227
Energy Savings Estimation Software.......................................................... 227
EMC Compatibility.................................................................. 229
EMC Compatibility....................................................................................... 230
Electromagnetic Compatibility (EMC) ........................................................ 231
YASKAWA TM.iQp.01 iQpump Drive User Manual 5
6 YASKAWA TM.iQp.01 iQpump Drive User Manual

Warnings and Cautions

This Section provides warnings and cautions pertinent to this product, that if not heeded, may result in personal injury, fatality, or equipment damage. Yaskawa is not responsible for consequences of ignoring these instructions.
WARNING
YASKAWA manufactures component parts that can be used in a wide variety of industrial applications. The selection and application of YASKAWA products remain the responsibility of the equipment designer or end user. YASKAWA accepts no responsibility for the way its products are incorporated into the final system design. Under no circumstances should any YASKAWA product be incorporated into any product or design as the exclusive or sole safety control. Without exception, all controls should be designed to detect faults dynamically and fail safely under all circumstances. All products designed to incorporate a component part manufactured by YASKAWA must be supplied to the end user with appropriate warnings and instructions as to that part’s safe use and operation. Any warnings provided by YASKAWA must be promptly provided to the end user. YASKAWA offers an express warranty only as to the quality of its products in conforming to standards and specifications published in the YASKAWA manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS OFFERED. YASKAWA assumes no liability for any personal injury, property damage, losses, or claims arising from misapplication of its products.
YASKAWA TM.iQp.01 iQpump Drive User Manual 7
WARNING
• Read and understand this manual before installing, operating, or servicing this Drive. All warnings, cautions, and instructions must be followed. All activity must be performed by qualified personnel. The iQpump drive must be installed according to this manual and local codes.
• Do not connect or disconnect wiring while the power is on. Do not remove covers or touch circuit boards while the power is on. Do not remove or insert the digital operator while power is on.
• Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. Status indicator LEDs and Digital Operator display will be extinguished when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are OFF and measure DC bus voltage level to confirm safe level.
• Do not perform a withstand voltage test on any part of the unit. This equipment uses sensitive devices and may be damaged by high voltage.
• The iQpump drive is not suitable for circuits capable of delivering more than 100,000 RMS symmetrical amperes. Install adequate branch short circuit protection per applicable codes. Refer to the specification. Failure to do so may result in equipment damage and/or personal injury.
• Do not connect unapproved LC or RC interference suppression filters, capacitors, or overvoltage protection devices to the output of the Drive. These devices may generate peak currents that exceed iQpump drive specifications.
• To avoid unnecessary fault displays caused by contactors or output switches placed between iQpump drive and motor, auxiliary contacts must be properly integrated into the control logic circuit.
• YASKAWA is not responsible for any modification of the product made by the user; doing so will void the warranty. This product must not be modified.
• Verify that the rated voltage of the iQpump drive matches the voltage of the incoming power supply before applying power.
• To meet CE directives, proper line filters and proper installation are required.
• Some drawings in this manual may be shown with protective covers or shields removed, to describe details. These must be replaced before operation.
• Observe electrostatic discharge procedures when handling circuit cards to prevent ESD damage.
• The equipment may start unexpectedly upon application of power. Clear all personnel from the drive, motor, and machine area before applying power. Secure covers, couplings, shaft keys, and machine loads before energizing the Drive.
• Please do not connect or operate any equipment with visible damage or missing parts. The operating company is responsible for any injuries or equipment damage resulting from failure to heed the warnings in this manual.
Intended Use
Drives are intended for installation in electrical systems or machinery.
For use in the European Union, the installation in machinery and systems must conform to the following product standards of the Low Voltage Directive:
• EN 50178, 1997-10, Equipping of Power Systems with Electronic Devices
• EN 60201-1, 1997-12 Machine Safety and Equipping with Electrical Devices
• Part 1: General Requirements (IEC 60204-1:1997)
• EN 61010, 1997-11 Safety Requirements for Information Technology Equipment
• (IEC 950:1991 + A1:1992 + A2:1993 + A3:1995 + A4:1996, modified)
Other
The iQpump (P7U) Drive is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amperes, 240 Vac maximum (240 V Class) and 480 Vac maximum (480 V Class).
8 YASKAWA TM.iQp.01 iQpump Drive User Manual

Introduction

This Section describes the applicability of the Manual.
The iQpump (P7U) is a Pulse Width Modulated Drive for 3-Phase AC induction motors. This type of Drive is also known as an Adjustable Frequency Drive, Variable Frequency Drive, AC Drive, AFD, ASD, VFD, and Inverter.
The iQpump (P7U) is a variable torque AC drive, designed specifically for Simplex and Multiplex pumping applications. The pump applications include Booster Systems, Submersible Deep Well, Fluid Storage Tanks, Metering Pumps, Commercial and Residential Irrigation Systems.
The iQpump (P7U) sets a new benchmark for size, cost, performance, ease-of-use benefits, comprehensive pump and motor protection features, and quality. The iQpump (P7U) includes numerous built-in features such as H/O/A Operation, Selectable Pump Control Engineering Units, PI Control, Pump Basic Control, Pump Protection, Multi­Pump Control (Lead/Lag), and Pump Messaging Terminology.
The LCD keypad/operator is equipped with Hand/Off/Auto functions, copy feature, and 5 lines of display with 16 characters per line.
Built-in PI and pump specific functions and parameters allow the operator to setup specific control values for a wide range of applications. The iQpump (P7U) will optimize the pump performance by automatically adjusting the pump controller based on operating conditions of the pump; such as, process variable changes and pump protection requirements. The P Group programming parameters are dedicated for pumping applications and provide for ease of setup.
The iQpump (P7U) drive offers energy savings by controlling the flow rate and the number of operating pumps on the system. The iQpump (P7U) can be configured using the most popular system control configurations including Simplex, Duplex, and Triplex pumps systems. The iQpump (P7U) is the master controller with the ability to add additional pumps on-line by controlling the digital I/O to each individual motor starter.
The iQpump (P7U) has an optional feature to replace the motors starters with additional drives for a more precise pump control system.
This manual is applicable to the iQpump (P7U) Drives defined by models CIMR-P7U-107. This manual is subject to change as product improvements occur. The latest version of the manual can be obtained from the Yaskawa. The date shown on the rear cover is changed when revisions are made.
This manual may describe trademarked equipment, which is the property of other companies. These trademarks are the property of the registered owner companies and may include the following:
• Modbus
Other Documents and Manuals are available to support special use or installation of this product. These documents may be provided with the product or upon request. Contact Yaskawa Electric America, Inc. as required. Documents may include the following:
• TM.iQp.02 Programming Manual
• TM.iQp.11 Modbus Manual
• PumpScada Software and Manual included on CD ROM with product
• Option Instructions included on CD ROM with product
YASKAWA TM.iQp.01 iQpump Drive User Manual 9
®
, trademark of Schneider Automation, Inc.
Conventions Used in this Manual
Software Versions
Yaskawa recognizes the need to continuously improve product quality. This drive may receive feature enhancements in the form of software or hardware changes. New functions may be added to the drive. When a new feature or function is added, the
software version <####> will be placed next to the feature or function.
EXAMPLE: This example shows that settings 2,3,4,5,6 are added to parameter A1-00 for drive software version <3020>
A1-00 Language Selection Select Language
Select the language displayed on the digital operator according to the following table:
QQQQ
Setting Description
0 English (factory default) 1 Japanese
2 Deutsche <3020>
3 Francais <3020> 4 Italiano <3020>
5 Espanol <3020>
6 Portugues <3020>
In the example above, the version note <3020> indicates that five additional languages have been added with drive software version 3020. Check the drive nameplate to determine the drive software version.
EXAMPLE:Namplate with PRG software number:
The “PRG:” number on the drive nameplate reflects the software version. The software version normally increases to a higher number with newer versions. Please consult the factory for details.
Figure 0.1
3020
Drive Software
version
Nameplate
10 YASKAWA TM.iQp.01 iQpump Drive User Manual

Physical Installation

This chapter describes the requirements for receiving and installing the iQpump drive.
1.1 iQpump Model Number and Enclosure Style . . . . . . . . . . . . . . . . 12
1.2 Confirmations Upon Delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.3 Component Names . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1.4 Exterior and Mounting Dimensions . . . . . . . . . . . . . . . . . . . . . . . . 17
1.5 Heat Loss Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
1.6 Checking and Controlling the Installation Site . . . . . . . . . . . . . . . 22
1.7 Installation Orientation and Clearances . . . . . . . . . . . . . . . . . . . . 23
1.8 Removing and Attaching the Terminal Cover . . . . . . . . . . . . . . . . 24
1.9 Removing/Attaching the Digital Operator and Front Cover. . . . . 25
1
YASKAWA TM.iQp.01 iQpump Drive User Manual 11

1.1 iQpump Model Number and Enclosure Style

1.1 iQpump Model Number and Enclosure Style
Table 1.1 iQpump Model Numbers and Enclosure Style
Input
Vol tag e
3-Phase
208-240 VAC
208-230 VAC
480 VAC
iQpump
Model-Number
Enclosure Style
CIMR-P7U-107
20P4 NEMA Type 1 (IP20) 3.6 0.5/0.75
20P7 NEMA Type 1 (IP20) 4.6 1
21P5 NEMA Type 1 (IP20) 7.8 1.5/2
22P2 NEMA Type 1 (IP20) 10.8 3
23P7 NEMA Type 1 (IP20) 16.8 5
25P5 NEMA Type 1 (IP20) 23.0 7.5
27P5 NEMA Type 1 (IP20) 31.0 7.5/10
2011 NEMA Type 1 (IP20) 46.2 15
2015 NEMA Type 1 (IP20) 59.4 20
2018 NEMA Type 1 (IP20) 74.8 25
2022 NEMA Type 1 (IP20) 88.0 30
2030 NEMA Type 1 (IP20) 115.0 40
2037 Open Chassis (IP00) 162.0 50/60
2045 Open Chassis (IP00) 192.0 60/75
2055 Open Chassis (IP00) 215.0 75
2075 Open Chassis (IP00) 312.0 100/125
2090 Open Chassis (IP00) 360.0 125/150
2110 Open Chassis (IP00) 415.0 150
40P4 NEMA Type 1 (IP20) 1.8 0.5/0.75
40P7 NEMA Type 1 (IP20) 2.1 1
41P5 NEMA Type 1 (IP20) 3.7 1.5/2
42P2 NEMA Type 1 (IP20) 5.3 3
43P7 NEMA Type 1 (IP20) 7.6 5
45P5 NEMA Type 1 (IP20) 12.5 7.5
47P5 NEMA Type 1 (IP20) 17.0 10
49P0 NEMA Type 1 (IP20) 21.0 15
4011 NEMA Type 1 (IP20) 27.0 20
4015 NEMA Type 1 (IP20) 34.0 25
4018 NEMA Type 1 (IP20) 40.0 30
4024 NEMA Type 1 (IP20) 52.0 40
4030 NEMA Type 1 (IP20) 67.2 50
4037 NEMA Type 1 (IP20) 77.0 60
4045 NEMA Type 1 (IP20) 96.0 75
4055 NEMA Type 1 (IP20) 125.0 100
4075 Open Chassis (IP00) 156.0 125
4090 Open Chassis (IP00) 180.0 150
4110 Open Chassis (IP00) 240.0 200
4160 Open Chassis (IP00) 304.0 250
4185 Open Chassis (IP00) 414.0 300/350
4220 Open Chassis (IP00) 515.0 400/450
4300 Open Chassis (IP00) 675.0 500+
Rated
Output
Current
Nominal
Hp
12 YASKAWA TM.iQp.01 iQpump Drive User Manual

1.2 Confirmations Upon Delivery

r
r
N
P7
1.2 Confirmations Upon Delivery
Receiving Checks
Check the following items as soon as the iQpump drive is received.
Table 1.2 Receiving Checks
Item Method
Has the correct model of iQpump drive been delivered?
Is the iQpump drive damaged in any way?
Are any screws or other components loose? Use a screwdriver or other tool to check for tightness.
If there are any irregularities in the above items, contact the shipping company, the distributor or representative who sold the iQpump drive, or a Yaskawa office immediately.
The iQpump drive is thoroughly tested at the factory. Any damages or shortages evident when the equipment is received must be reported immediately to the commercial carrier that transported the material. Shipping damage is not covered by the Yaskawa warranty. After unpacking and inspecting for damage, verify that internal wire connections have not come loose during shipment by spot checking wire terminations with a screwdriver or the appropriate tool.
iQpump drive storage must be in a clean and dry location. Maintain the factory packaging and provide covering as needed to protect the iQpump from construction site dirt, water, debris and traffic prior to and during construction.
Check the model number on the nameplate on the right side of the iQpump drive. Reconcile with packing slip and/or order information.
Inspect the entire exterior of the iQpump drive to see if there are any dents, scratches or other damage resulting from shipping.
Nameplate Information
A nameplate is attached to the right side of each iQpump drive. The following nameplate is an example for a standard iQpump drive.
ormal
P7 iQpump
Drive Model Number
Input Power Rating
Output Power Rating
Serial Number
UL File Number
Drive Model Number
Input Power Rating
Output Power Rating
Serial Number
UL File Number
MODEL:
INPUT: AC3PH 200-240V 50/60Hz 53A
OUTPUT: O/N: S/N:
FILE: E131457 TYPE 1 ENCLOSURE IP20
YEA ITEM#: CIMR-P7U20111A-107
MODEL:
INPUT: AC3PH 200-240V 50/60Hz 53A
OUTPUT: O/N: S/N:
FILE: E131457 TYPE 1 ENCLOSURE IP20
CIMR-P7U2011
AC3PH 0-240V 0-120Hz 46.2A 18kVA
1W06Z7123450001 PRG:1021
CIMR-P7U2011
AC3PH 0-240V 0-120Hz 46.2A 18kVA
1W06Z7123450001 PRG:0032
SPEC: 20111A
MASS: 7.0kg
SPEC: 20111A-U890107
MASS: 7.0kg
Drive Spec Numbe
Weight
Drive Spec Numbe
Weight
Note: The iQpump Drive Model Number and iQpump Drive Spec Number are required to completely identify an iQpump Drive.
Figure 1.1 iQpump (P7U) Drive Nameplate
YASKAWA TM.iQp.01 iQpump Drive User Manual 13
1.2 Confirmations Upon Delivery
TERMS
TERMS
Drive Model Numbers
The model number on the nameplate indicates the design specification, voltage, and rating of the iQpump drive in alphanumeric codes.
CIMR – P7 U 2 0 11*
AC Drive
iQpump Family
No.
U
Spec
UL Specification
Rating
No.
2
4
Voltage
3-phase, 208-240 VAC
3-phase, 480 VAC
* YEA Item #: CIMR-P7U20111A-107
Figure 1.2 iQpump Drive Model Number Structure
Drive Enclosure and Revision Code
The iQpump drive SPEC number on the nameplate indicates the voltage, iQpump drive rating, enclosure type, and the revision code of the iQpump drive in alphanumeric codes.
2
011 1 A U890107
TERMS
TERMS
No.
2 4
Open Chassis Type (IEC IP00)
Protected so that parts of the human body cannot reach electrically charged parts from the front when the iQpump drive is mounted in a control panel, also called (protected chassis).
Voltage
3-phase, 208 - 240 VAC
3-phase, 480 VAC
Rating
Figure 1.3 SPEC Number Structure
VAU Number
Hardware Revision
No.
0 Open chassis (IEC IP00)
1
Enclosure Type
NEMA Type 1 (IEC IP20)
TERMS
TERMS
NEMA Type 1 (IEC IP20)
The iQpump drive is shielded from the exterior, and can thus be mounted to the interior wall of a building (not necessarily enclosed in a control panel). The protective structure conforms to the standards of NEMA Type 1 in the USA. All protective covers (Fig 1.4) must be installed to conform with IEC IP20 and NEMA Type 1 requirements
14 YASKAWA TM.iQp.01 iQpump Drive User Manual

1.3 Component Names

1.3 Component Names
Models CIMR-P7U20P4 through 2018 (25HP @ 208V/240V) and 40P4 through 4018 (30HP @ 480V)
The external appearance, component names, and terminal arrangement of the iQpump drive are shown in Figure 1.4 and Figure 1.5.
Top protective cover
Front cover
Digital Operator
Terminal cover
Figure 1.4 iQpump Drive Appearance
Mounting hole
Diecast Heat Sink
Nameplate
Bottom protective cover
Figure 1.5 Terminal Arrangement (Terminal Cover Removed)
YASKAWA TM.iQp.01 iQpump Drive User Manual 15
1.3 Component Names
Models CIMR-P7U2022 through 2110 (30HP and above @ 208V/240V) and 4030 through 4300 (40HP and above @ 480V)
The external appearance, component names, and terminal arrangement of the iQpump drive are shown in Figure 1.6 and Figure 1.7.
Mounting holes
Mounting holes
Drive cover
Drive cover
Cooling fan
Front cover
Front cover
Digital Operator
Digital Operator
Terminal cover
Terminal cover
Figure 1.6 iQpump Drive Appearance
Cooling fan
Nameplate
Nameplate
Control circuit
terminals
Main circuit
terminals
Ground terminal
Figure 1.7 Terminal Arrangement (Terminal Cover Removed)
Charge indicator
Ground terminal
16 YASKAWA TM.iQp.01 iQpump Drive User Manual

1.4 Exterior and Mounting Dimensions

1.4 Exterior and Mounting Dimensions
Dimensions: iQpump (P7U) (NEMA 1) 208 V/240 V (3.6–74.8 AMPS) 480 V (1.8–40.0 AMPS)
FRONT VIEW
MOUNTING HOLES
RATED INPUT
208V
240V
480V
W2
CIMR-P7U  -107
FOR "A" SIZE SCREW
W1
W
MODEL
20P41
20P71
21P51
22P21
23P71
27P51
20111
20151
20181
20P41
20P71
21P51
22P21
23P71
25P51
27P51
20111
20151
20181
40P41
40P71 2.1
41P51
42P21
43P71
45P51
49P01
40111
40151
RATED
OUTPUT
CURRENT
(AMPS)
10.8
31.0
46.2
59.4
74.8 13.19 8.50 14.96 9.45 .30
10.8
16.8
23.0
31.0
46.2
59.4
74.8
3.7
5.3
7.6
12.5
21.0
27.0
34.0
40.040181
3.6
4.6
7.8
3.6
4.6
7.8
1.8
NOMINAL
1/2 3/4
7.5-10
1/2 3/4
1/2 3/4-
H2
H1
H
HP
-
1
2
3
5
15
20
25
-
1
2
3
5
7.5
10
15
20
25
1
2
3
5
7.5
1017.047P51
15
20
25
30
H1 W1
10.47
10.47
10.47
10.47
11.22
11.22
13.19
10.47
10.47
10.47
10.47
10.47
10.47
11.22
11.22
13.19
13.19 8.50 14.96 9.45 .30 1/4.47 8.27
10.47
10.47
10.47
10.47
10.47
10.47
11.22 7.32 7.8711.81 .28
11.22
13.19
13.19 8.50
FOR REFERENCE ONLY UNLESS PROPERLY ENDORSED.
IN ORDER TO ACHIEVE ADEQUATE COO LING THE DRIVE MUST BE POSITIONED TO ALLO W A MINIMUM OF FREE AIR SPACE OF 1.2 I NCHES ON SIDES AND 5 INCHES TOP AND BOTTOM
MOUNTING
4.96
4.96
4.96
4.96
4.9610.47
7.32
7.32
8.50
4.96
4.96
4.96
4.96
4.96
4.96
7.32
7.32
8.50
4.96
4.96
4.96
4.96
4.96
4.96
7.32
8.50 9.45
SIDE VIEW
11.02 5.51
11.02 5.51
11.02
11.02
11.81
12.20
13.78
11.02
11.02
11.02
11.02
11.02
11.02
11.81
12.20
13.78
11.02
11.02 5.51
11.02
11.02
11.02
11.02
11.81 7.87
13.78
AIR
AIR
D1
D
DIMENSIONS IN INCHES
WHH2
5.51
5.51
7.87
7.87
9.45
5.51
5.51
5.51
5.51
5.51
5.51
7.87
7.87
9.45
5.51
5.51
5.51
5.51
5.51
9.4513.78
W2
.28
.28
.28
.28
.28
.28
.28
.28
.28.285.5111.0216.8
.28
.28
.28
.28
.47
.30
.28
.28
.28
.28
.28
.28
.28
.28
.28
.28
.28
.28
.28
.28
.28
.28
.47
.30
.28
.28
.28
.28
.28
.28
.28
.28
.28
.28
.28
.28
.28 7.87 1/4 4.63 6.21 3.07 1.38 13.2
.28 7.87 1/4 4.63
.28
.28
.30
.47
.30
.47
1.38 DIA.
(2) HOLES SIZE "J"
.87 DIA.
C
L
B
F
BOTTOM VIEW
D1 BADCE
1.54
6.30
6.30
6.30
6.30
7.87
7.87
8.27
6.30
6.30
6.30
6.30
7.09
7.09
7.87
7.87
8.27
6.30
6.30
6.30
7.09
7.09
7.09
7.87
8.27
8.27
1.54
1.54
1.54
2.32
2.58
2.58
3.07
3.07
1.54
1.54
1.54
1.54
2.32
2.32
2.58
2.58
3.07
3.07
1.54
1.54
1.54
2.32
2.32
2.32
2.58
2.58
2.58
3.07
3.07
#10
#10
#10
#10
1/4
1/4
1/4
1/4
#10
#10
#10
#10
#10
#10
1/4
1/4
1/4
#10
#10
#10
#10
#10
#10
1/4
1/4
1/4
---
3.35
---
3.35
---
3.35
---
3.35
---
4.63
5.11
4.63
5.11
5.12
5.79
5.12.47 3.945.798.27
---
3.35
---
3.35
3.35
---
---
3.35
---
4.14
---
4.14
4.63
5.11
4.63
5.11
5.12
5.79
5.12
5.79
3.35
---
3.35
---
3.35
---
4.14
---
4.14
---
4.14
---
5.11
5.1111.22 7.32 7.8711.81 .28
4.63
5.11
5.79
5.12 6.65
5.79
5.12
F
1.97
4.73
1.97
4.73
1.97
4.73
1.97
4.73
5.52#10 1.104.14 1.977.09 8.8
3.07
6.21
6.21
3.07
6.65
3.94
6.65
4.73
1.97
4.73
1.97
4.73
1.97
1.97
4.73
1.97
5.52
1.97
5.52
3.07
6.21
6.21
3.07
6.65
3.94
6.65
3.94
4.73
1.97
4.73
1.97
4.73
1.97
5.52
1.97
5.52
1.97
5.52
1.97
6.21
3.07 1.38 13.2
6.21
3.07
3.94
6.65
3.94
E
C
J
1.10
1.10
1.10
1.10
1.38
1.38
1.73
1.73 24.2
1.10
1.10
1.10
1.10
1.10
1.10
1.38
1.38
1.73
1.73
1.10
1.10 6.6
1.10
1.10
1.10
1.10
1.38 13.2
1.732222
1.73
APPROX. WEIGHT
(LBS.)
6.6
6.6
6.6
6.6
13.2
15.4
24.2
6.6
6.6
6.6
6.6
8.8
8.8
13.2
15.4
24.2
24.2
6.6
6.6
8.8
8.8
8.8
Figure 1.8 Exterior and Mounting Dimensions
YASKAWA TM.iQp.01 iQpump Drive User Manual 17
1.4 Exterior and Mounting Dimensions
Dimensions: iQpump (P7U) (NEMA 1) 208 V/240 V (88.0–115 AMPS) 480 V (52.0–125 AMPS)
APPROX.
CURRENT
WEIGHT
(LBS.)
Figure 1.9 Exterior and Mounting Dimensions
18 YASKAWA TM.iQp.01 iQpump Drive User Manual
1.4 Exterior and Mounting Dimensions
Dimensions: iQpump (P7U) (Protected Chassis) 208–230 V (162–415 AMPS) 480 V (156–304 AMPS)
FRONT VIEW
MOUNTING HO LES FOR "A" SIZE SCREW
H2
H1
H
AIR
W2
W1
W
FOR REFERENCE ONLY UNLESS PROPERLY ENDORSED.
IN ORDER TO ACHIEVE ADEQUATE COOLING THE DRIVE MUST BE POSITIONED TO ALLOW A MINIMUM OF FREE AIR SPACE OF 1.2 INCHES ON SIDES AND 5 INCHES TOP AND BOTTOM
RATED INPUT
208V
230V
480V
MODEL
CIMR-P7U
20370
20450
20550
20750
20900
21100
20370
20450
20750
20900
40900
41100
41600
RATED OUTPUT CURRENT
(AMPS)
162
215
312
360
415
162
192
312
360
15640750
180
240
304
AIR
D1
D
NOM.
MOUNTING
HP
H1 W1
22.64
50
22.6460
27.56
75
32.28
125
33.66
150
22.64 23.629.84 14.76 .49 1253.9411.812.46 3/8
50-60
22.64 23.629.84 14.76 .49 1395.1212.992.46 3/8
75
100-125
27.56 28.5412.80 17.72 .49 1915.1213.782.46 3/8
32.28 33.4614.57 19.69 .59 2385.1214.172.56 3/8
150
125
27.56
27.56
150
32.28
200
33.66
250
DIMENSIONS IN INCHES
HWH2W2D
9.84
9.84
12.80
14.57
17.52
12.80
12.80
14.57
17.52
23.62
23.62
28.54
33.46
34.84
28.54
28.54
33.46
36.06
14.76
.49
14.76
.49
17.72
.49
19.69
.59 2.56
22.64 .59
17.72
.49
17.72
.49 196
19.69
.59
22.64
.59
2.46
2.46
12.99192
13.78
2.46
2.4617.72 .4912.8027.56 28.54100
13.78
14.17
2.56
14.96
13.78
2.46
13.78
2.46 3/8
14.17
2.56
14.96
2.56
11.81
D1 A
3.94
5.12
5.12
5.12
5.12
5.51
5.12
5.12
5.12
5.51
APPROX. WEIGHT
(LBS.)
125
3/8
139
3/8
189
3/8
191
3/8
238
3/8
330
3/8
194
3/8
224
3/8
352
3/8
Figure 1.10 Exterior and Mounting Dimensions
YASKAWA TM.iQp.01 iQpump Drive User Manual 19
1.4 Exterior and Mounting Dimensions
Dimensions: iQpump (P7U) (Protected Chassis)
MOUNTING HOLES FOR "A" SIZE SCREWS
H1
H2
AIR
H
W2
W1
W1
W
RATED INPUT
480V
CIMR-P7U
CURRENT
(AMPS)
41441850
42200
43000 58.07
300-350
675
RATED
OUTPUT
MODEL
FOR REFERENCE ONLY UNLESS PROPERLY ENDORSED.
IN ORDER TO ACHIEVE ADEQUATE COOLING THE DRIVE MUST BE POSITIONED TO ALLOW A MINIMUM OF FREE AIR OF 1.2 INCHES ON SIDES AND 5 INCHES TOP AND BOTTOM
NOM.
HP
500
MOUNTING
H1 W1
50.00
50.00400-450
56.70
HWH2W2D
51.38
10.63
10.63
14.37
51.38
27.95
27.95
36.06
.79
.79
.79
DIMENSIONS IN INCHES
16.34
3.35
16.34515
3.35
16.34
3.66
D1 A
4.94
4.94
4.94
AIR
D1
D
APPROX. WEIGHT
(LBS.)
3/8
572
3/8
616
3/8
891
Figure 1.11 Exterior and Mounting Dimensions
20 YASKAWA TM.iQp.01 iQpump Drive User Manual
1.5 Heat Loss Data

1.5 Heat Loss Data

Table 1.3 200V Class Heat Loss Data
Drive
TYPE
CIMR-P7U-107
20P4 1.4 3.6 19 39 58 Self
20P7 1.8 4.6 26 42 68 Self
21P5 3.0 7.8 48 50 98 Self
22P2 4.1 10.8 68 59 127 Self
23P7 6.4 16.8 110 74 184 Fan
25P5 8.8 23 164 84 248 Fan
27P5 12 31 219 113 332 Fan
2011 18 46.2 357 168 524 Fan
2015 23 59.4 416 182 597 Fan
2018 29 74.8 472 208 680 Fan
2022 34 88 583 252 835 Fan
2030 44 115 883 333 1217 Fan
2037 62 162 1010 421 1430 Fan
2045 73 192 1228 499 1727 Fan
2055 82 215 1588 619 2206 Fan
2075 120 312 1956 844 2800 Fan
2090 140 360 2194 964 3157 Fan
2110 160 415 2733 1234 3967 Fan
(Inverter) Capacity
(kVA)
Rated
Output
Current
(A)
Cooling Fin Side
(W)
Internal
Unit Side (W)
Tot al
Watt Loss
(W)
Table 1.4 400V Class Heat Loss Data
Drive
TYPE
CIMR-P7U-107
40P4 1.4 1.8 14 39 53 Self
40P7 1.6 2.1 17 41 58 Self
41P5 2.8 3.7 36 48 84 Self
42P2 4.0 5.3 59 56 115 Fan
43P7 5.8 7.6 80 68 140 Fan
44P0 6.6 8.7 90 70 160 Fan
45P5 9.5 12.5 127 81 209 Fan
47P5 13 17 193 114 307 Fan
49P0 16 21 232 158 390 Fan
4011 21 27 232 158 390 Fan
4015 26 34 296 169 465 Fan
4018 30 40 389 201 590 Fan
4022 38 50.4 420 233 653 Fan
4024 40 52 691 297 989 Fan
4030 51 67.2 691 297 989 Fan
4037 59 77 801 332 1133 Fan
4045 73 96 901 386 1287 Fan
4055 95 125 1204 478 1682 Fan
4075 120 156 1285 562 1847 Fan
4090 140 180 1614 673 2287 Fan
4110 180 240 1889 847 2736 Fan
4132 200 260 2388 1005 3393 Fan
4160 230 304 2636 1144 3936 Fan
4185 315 414 2791 1328 3964 Fan
4220 390 515 3797 1712 5509 Fan
4300 510 675 5838 2482 8319 Fan
(Inverter) Capacity
(kVA)
Rated
Output
Current
(A)
Cooling Fin Side
(W)
Internal
Unit Side (W)
Tot al
Watt Loss
(W)
Cooling Method
Cooling Method
YASKAWA TM.iQp.01 iQpump Drive User Manual 21

1.6 Checking and Controlling the Installation Site

1.6 Checking and Controlling the Installation Site
Install the iQpump drive as described below and maintain optimum conditions.
WARNING
The iQpump drive heatsink temperature may exceed 158°F (70°C). Therefore, mount the iQpump drive to a surface suitable for high temperature.
Installation Site
Locate the iQpump drive as close as possible to the motor. Install the iQpump drive under the following conditions in UL Pollution Degree 1 & 2 environments. This excludes wet locations where surfaces may become conductive due to moisture and contaminant loading.
Table 1.5 Installation Site Specifications
Typ e Ambient Operating Temperature Humidity Plenum Rated
NEMA Type 1 14°F-to 104°F (-10-to 40°C) 95%-RH-or-less-(no-condensation) Yes
Open Chassis 14°F-to 113°F (-10 to +45°C) 95%-RH-or-less-(no-condensation) No
Protective covers are attached to the top and bottom of the iQpump drive. It is recommended to remove the protective covers before operating a CIMR-P7U2030/4055-107 iQpump drive and smaller in a panel to obtain the 113°F (45°C) ambient operating temperature.
Observe the following precautions when installing the iQpump drive:
• in a clean location which is free from oil mist and dust.
• in an environment where metal shavings, oil, water, or other foreign materials will not get into the iQpump drive enclosure.
• in a location free from radioactive materials.
• in a location free from harmful gasses and liquids.
• in a location free from excessive vibration.
• in a location free from chlorides.
• in a location away from direct sunlight.
• on a non-combustible surface.
Controlling the Ambient Temperature
To enhance the reliability of operation, the iQpump drive should be installed in an environment free from extreme temperature variations. If the iQpump drive is installed in an enclosure, use a cooling fan or air conditioner to maintain the internal air temperature below 113° (45°C).
Protecting the iQpump Drive from Foreign Matter
During iQpump drive installation and project construction it is possible to have foreign matter, such as metal shavings or wire clippings, fall inside the iQpump drive. To prevent foreign matter from falling into the iQpump drive, place a temporary cover over the iQpump drive.
Always remove the temporary cover from the iQpump drive before Start-Up. Otherwise, ventilation will be reduced, causing the iQpump drive to overheat.
F
22 YASKAWA TM.iQp.01 iQpump Drive User Manual

1.7 Installation Orientation and Clearances

1.7 Installation Orientation and Clearances
Install the iQpump drive vertically so as not to reduce the cooling efficiency. When installing the iQpump drive, always provide the following installation clearances to allow normal heat dissipation. For 3HP, 208V/240V (CIMR-P7U22P2-107 and below) or 2HP, 480V (CIMR-P7U41P-107 and below), ensure that the heatsink is against a closed surface to avoid diverting cooling air around the heatsink.
4.75 in (120 mm. minimum)
1.2 in
(30.5 MM.) min.
1.2 in
(30.5 mm. minimum)
4.75 in (50 mm. minimum)
Horizontal Clearance
1.2 in
(30.5 mm. minimum)
4.75 in (120 mm. minimum) Air
4.75 in (120 mm. minimum) Air
Vertical Clearance
IMPORTANT
Figure 1.12 iQpump Drive Installation Orientation and Clearance
• The same clearance is required horizontally and vertically for both Open Chassis (IP00) and NEMA Type 1 iQpump drives.
1. Always remove the top and bottom protection covers before installing a CIMR-P7U2018/4018-107 and smaller iQpump drive in a panel. Always provide enough clearance for lifting eye bolts and the main circuit wiring when installing a CIMR-P7U2022/4030-107 and larger iQpump drive in a panel.
YASKAWA TM.iQp.01 iQpump Drive User Manual 23

1.8 Removing and Attaching the Terminal Cover

1.8 Removing and Attaching the Terminal Cover
Remove the terminal cover to connect cables to the control circuit and main circuit terminals.
WARNING
Prior to removing any protective cover or wiring any part of the iQpump drive, remove all power sources, including main input power and control circuit power. Wait a minimum of 5 minutes after power removal, before removing any cover. The charge lamp located within the iQpump drive should be off prior to working inside. Even if the charge lamp is off, one must measure the AC input, output, and DC Bus potential to insure safe levels prior to resuming work. Failure to adhere to this warning may result in personal injury or death.
Removing the Terminal Cover
Models CIMR-P7U20P4 through 2018 (0.5HP to 25HP @ 208V/240V) and 40P4 through 4018
(0.5HP to 30HP @ 480V)
Loosen the screw at the bottom of the terminal cover, press in on the sides of the terminal cover in the directions of arrows 1, and then lift up on the terminal in the direction of arrow 2. Refer to Figure 1.13.
Models CIMR-P7U2022 through 2110 (30HP to 150HP @ 208V/240V) and 4030 through 4300
(40HP to 500HP @ 480V)
Loosen the screws on the left and right at the top of the terminal cover, pull down the terminal cover in the direction of arrow 1 and then lift up on the terminal cover in the direction of arrow 2. Refer to Figure 1.14.
Figure 1.1
1
2
Figure 1.13 Removing the Terminal Cover Figure 1.14 Removing the Terminal Cover
Attaching the Terminal Cover
After wiring the terminal block, attach the terminal cover by reversing the removal procedure.
For Models CIMR-P7U2018/4018-107 and smaller, insert the tab on the top of the terminal cover into the groove on the iQpump drive and press in on the bottom of the terminal cover until it snaps into place.
For iQpump drives CIMR-P7U2022/4030-107 and larger, insert the tab on the top of the terminal cover into the groove on the iQpump drive, and secure the terminal cover by lifting it up toward the top of the iQpump drive.
24 YASKAWA TM.iQp.01 iQpump Drive User Manual

1.9 Removing/Attaching the Digital Operator and Front Cover

1.9 Removing/Attaching the Digital Operator and Front Cover
Models CIMR-P7U20P4 through 2018 (0.5HP to 25HP @ 208V/240V) and 40P4 through 4018 (0.5HP to 30HP @ 480V)
For Models CIMR-P7U2018/4018-107 and smaller, remove the terminal cover and then use the following procedures to remove the Digital Operator and front cover.
Removing the Digital Operator
Press on the side of the Digital Operator in the direction of arrow 1 to unlock, then lift the Digital Operator in the direction of arrow 2 to remove it as shown in Figure 1.15.
2
1
Figure 1.15 Removing the Digital Operator
Removing the Front Cover
Press the left and right sides of the front cover in the direction of arrows 1 and lift the bottom of cover in the direction of arrow 2 to remove it as shown in Figure 1.16.
1
2
Figure 1.16 Removing the Front Cover
Attaching the Front Cover
Mount the front cover to the iQpump drive by performing the steps to remove the front cover in reverse order.
1. Do not mount the front cover with the Digital Operator attached to the front cover; this may cause the Digital Operator to malfunction
due to imperfect contact.
2. Insert the tab of the upper part of the front cover into the groove of the iQpump drive and press the lower part of the front cover onto
the iQpump drive until the front cover snaps into place.
YASKAWA TM.iQp.01 iQpump Drive User Manual 25
1.9 Removing/Attaching the Digital Operator and Front Cover
Models CIMR-P7U2022 through 2110 (30HP to 150HP @ 208V/240V) and 4030 through 4300 (40HP to 500HP @ 480V)
For Models CIMR-P7U2022/4030-107 and larger, remove the terminal cover and then use the following procedures to remove the Digital Operator and front cover.
Removing the Digital Operator
Use the same procedure for Models CIMR-P7U2018/4018-107 and smaller.
Removing the Front Cover
Loosen all screws on the front cover. Lift up at the location labeled 1 at the top of the control circuit terminal card and move in the direction of arrow 2.
2
1
Figure 1.17 Removing the Front Cover
Attaching the Front Cover
Attach the front cover by reversing the procedure to remove it.
1. Confirm that the Digital Operator is not mounted on the front cover. Contact faults can occur if the cover is attached while the Digital
Operator is mounted to it.
2. Insert the tab on the top of the front cover into the slot on the iQpump drive and press in on the cover until it snaps into place on the
iQpump drive.
Attaching the Digital Operator
After attaching the front cover, mount the Digital Operator onto the iQpump drive using the following procedure.
1. Hook the Digital Operator at A (two locations) on the front cover by moving in the direction of arrow 1 as shown in the following
illustration.
2. Press the Digital Operator in the direction of arrow 2 until it snaps in place at B (two locations).
A
1
B
2
Figure 1.18 Mounting the Digital Operator
26 YASKAWA TM.iQp.01 iQpump Drive User Manual
IMPORTANT
1.9 Removing/Attaching the Digital Operator and Front Cover
• Do not remove or attach the Digital Operator or mount or remove the front cover using methods other than those described above, damage to the Digital Operator or iQpump drive may occur.
• Never attach the front cover to the iQpump drive with the Digital Operator attached to the front cover. Damage to the Digital Operator may occur. Always attach the front cover to the iQpump drive first, and then attach the Digital Operator to the front cover.
YASKAWA TM.iQp.01 iQpump Drive User Manual 27
1.9 Removing/Attaching the Digital Operator and Front Cover
THIS PAGE INTENTIONALLY LEFT BLANK.
28 YASKAWA TM.iQp.01 iQpump Drive User Manual
2

Electrical Installation

This chapter describes wiring terminals, main circuit terminal connections, main circuit terminal wiring specifications, control circuit terminals, and control circuit wiring specifications.
2.1 Terminal Block Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2.2 Wiring Main Circuit Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
2.3 Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
YASKAWA TM.iQp.01 iQpump Drive User Manual 29

2.1 Terminal Block Configuration

2.1 Terminal Block Configuration
The wiring terminals are shown in Figure 2.1.
AC MP
-V
+V
Control circuit terminals
A1
SCS+A2
SN M6
S1
S4SPS7 M4
S3
E(G) E(G)
S5
AC MA
AMS6
FM
AC
R- M5
R+RP
IG
MCMB
M3S2 S-
M2
M1
Main circuit terminals
Charge indicator
Ground terminal
Control circuit terminals
Main circuit terminals
Models CIMR-_ _ _2018 (25 HP, 208V)/ 4018 (30 HP, 480V) and smaller
AC MP
-V
R- M5FMR+RP
+V
A1
SCS+A2
SN M6
S1
E(G) E(G)
AC MA
AMS6
S5
IG
S4SPS7 M4
S3
AC
MCMB
M3S2 S-
M2
M1
Ground terminal
Charge indicator
Ground terminal
Ground terminal
Models CIMR-_ _ _2022 (30 HP, 208V)/ 4030 (40 HP, 480V) and larger
Figure 2.1 iQpump Drive Terminal Configuration
30 YASKAWA TM.iQp.01 iQpump Drive User Manual
Loading...
+ 205 hidden pages