8.1 Nominal Powers and Currents According to UL508 ...........53
8.2 Nominal Powers and Currents for Standard IP55,
IV Pole Weg Motor .............................................................53
8.3 Power Data .........................................................................54
8.4 Electronics and Programming Data ....................................54
CHAPTER 1
SAFETY INSTRUCTIONS
This Manual contains the necessary information for the correct use
of the Soft-Starter SSW-07.
It was written to be used by qualied personnel with suitable training
or technical qualications to operate this type of equipment.
1.1 SAFETY
NOTICES IN
THE MANUAL
1.2 SAFETY
NOTICES ON
THE PRODUCT
The following safety notices will be used in the text.
DANGER!
The nonobservance of the procedures recommended in this warning
can lead to death, serious injuries and considerable material damage.
ATTENTION!
Failure to observe the recommended procedures in this notice may
lead to material damage.
NOTE!
The text intents to supply important information for the correct
understanding and good operation of the product.
The following symbols may be attached to the product as a safety
notice.
English
1.3 PRELIMINARY
RECOMMENDATIONS
High Voltages.
Components are sensitive to electrostatic discharge.
Do not touch them.
Mandatory connection to ground protection (PE).
DANGER!
Only personnel with suitable qualication and familiar with the
Soft-Starter SSW-07 and associated equipment should plan or
implement the installation, start-up, operation and maintenance of
this equipment.
These personnel must follow all safety instructions in this manual
and/ or dened by local regulations.
Failure to follow these safety instructions may result in personnel
injury and/or equipment damage.
5
CHAPTER 1 - SAFETY INSTRUCTIONS
NOTE!
In this Manual, qualied personnel are those trained to:
1. Install, ground, power-up, and operate the Soft-Starter SSW-07
according to this manual and the required safety procedures;
2. Use protection equipment according to established regulations;
3. Give First Aid.
DANGER!
Always disconnect the general power supply before touching any
electrical component associated to the Soft-Starter SSW-07.
English
High voltage may be present even after the power supply is
disconnected. Wait at least 3 minutes for the total discharge of the
capacitors.
Always connect the equipment’s heatsink to the protection ground
(PE), at the proper connection point.
ATTENTION!
All electronic boards have components that are sensitive to
electrostatic discharges. Do not touch these components or
connectors directly.
If necessary, rst touch the grounded metallic heatsink or use a
suitable grounded wrist strap.
Do not apply any high voltage test on the Soft-Starter SSW-07!
If necessary, contact the manufacturer.
NOTE!
Soft-Starters SSW-07 may interfere with other electronic equipment.
Follow the measures in Chapter 3 to reduce these effects.
NOTE!
Read this manual completely before installing or operating the
Soft-Starter SSW-07.
6
GENERAL INFORMATION
Tampa para
Trifásica
Opcionais Plug-In
Ajustes e Habilitar asProteções
DIP Swith para
LED's para Indicação
Entrada de Alimentação
de Status da SSW-07
Saída para Motor
Saida a Relé(13,14/23 e 24)
CHAPTER 2
2.1 ABOUT THIS
MANUAL
2.2 ABOUT THE
SOFT-STARTER
SSW-07
This manual presents the Soft-Starter installation, how to start it up,
its main technical characteristics and how to identify and correct the
most common problems. The manuals listed next must be consulted
in order to get more information regarding the functions, accessories
and working conditions:
Programming Manual, with a detailed description of the
parameters and its functions;
RS232 / RS485 Communication Manual.
DeviceNet Communication Manual.
These manuals are supplied in electronic format on the CD-ROM
that accompanies the Soft-Starter, or can be obtained at WEG’s
web site: http://www.weg.net.
The Soft-Starter SSW-07 is a high performance product that permits
the start control of the three phase AC induction motors. Thus, it
prevents mechanical shocks on the load and current peaks in the
supply line.
Three-phase
Power Supply
English
Trimpots to adjust
DIP switch to adjust
the Thermal Class
Electronic Power Supply
(A1 and A2)/
Start/Stop Command
of the Motor (D1) and
Reset (DI2 and DI3)
Figure 2.1 - Frontal view of the SSW-07
DIP Switch for
Soft-Starter adjustment
and protection enabling
Status Indication LEDs
of the SSW-07
Lid for optional Plug-in
Modules
Relay Output
(13, 14/23 and 24)
Motor Output
7
CHAPTER 2 - GENERAL INFORMATION
English
Three-Phase
Power Supply
RS
U
VW
Three-Phase Motor
Programmable
Digital Inputs
Dl1
Dl2
Dl3
T
Control
Power Supply
A1
A2
3 x
Digital Signal
2 x
Processor
DSP
PE
Figure 2.2 - Soft-Starter SSW-07 block diagram
Programmable Digital
Outputs
13
14/2324
RL1
RL2
2.3 SOFT-STARTER SSW-07 IDENTIFICATION PLATE
WEG Stock
SSW-07 Model
Input Data (Voltage,
Number of Phases,
Current and Frequency)
Position of the Identication Plate on the Soft-Starter SSW-07:
FRONTAL VIEW X VIEW
English
X
Figure 2.4 - Location of the labels
9
CHAPTER 2 - GENERAL INFORMATION
End of
Code
Special
Software
Blank =
Standard
S1 = Special
Software
English
Special
Hardware
Blank =
Degree of
Protection
Blank =
S = Standard
O = with
220-575 VacOptional:
(2)
Standard
H1 = Electronics
supply: 110 to
130 Vac
H2 = Electronics
(1)
Standard
IP=IP20
Optional
(2)
supply: 208 to
240 Vac
10
HOW TO SPECIFY THE SSW-07 MODEL:
Three-
Phase
SSW-07
Nominal Current
WEG Soft-
Starter
EXSSW-070017T5S_ __ __ _Z
Market
Power
Supply
0017 = 17 A
0024 = 24 A
0030 = 30 A
Series
SSW-07
BR = Brazil
EX = Export
0045 = 45 A
0061 = 61 A
0085 = 85 A
0130 = 130 A
0171 = 171 A
0200 = 200 A
0255 = 255 A
0312 = 312 A
0365 = 365 A
0412 = 412 A
(1) Only for models 130 A to 412 A.
(2) Only for the 255 A to 412 A models.
NOTE!
The option eld (S or O) denes if the Soft-Starter SSW-07 will be a standard version or if it will include any optional. If standard, the
code ends here.
Always put the letter Z at the end. For example:
EXSSW070017T5SZ = Standard Soft-Starter SSW-07 with 17 A and 220 V to 575 V to three-phase input with the User’s Guide in
English, Spanish and Portuguese.
If there is any optional, the elds must be lled out in the correct sequence until the code is completed with the letter Z.
The standard product as dened by this code is described as:
Degree of Protection: IP20 from 17 A to 85 A and IP00 from 130 A to 412 A.
CHAPTER 2 - GENERAL INFORMATION
2.4 RECEIVING
AND STORAGE
The Soft-Starter SSW-07 is supplied in a cardboard box. On the
outside of the package there is an identication plate which is
identical to the one placed on the Soft-Starter SSW-07.
To open the package:
1- Put it on a table;
2- Open the package;
3- Take out the Soft-Starter.
Check if:
The Identication plate of the Soft-Starter SSW-07 matches the
model purchased:
Damage has occurred during transport. If so, contact the carrier
immediately.
If the Soft-Starter SSW-07 is not installed immediately, store it in
its package in a clean and dry place with temperature between
-25 °C (-13 °F) and 65 °C (149 °F). 1 hour at -40 °C (-40 °F) is
permitted.
English
SSW-07
Model
17 A
24 A
30 A
45 A
61 A
85 A
130 A
171 A
200 A
255 A
312 A
365 A
412 A
Height
H
mm
(in)
221
(8.70)
260
(10.24)
356
(14.02)
415
(16.34)
Table 2.1 - Dimensions of the package in mm (in)
Width
L
mm
(in)
180
(7.09)
198
(7.80)
273
(10.75)
265
(10.43)
Depth
P
mm
(in)
145
(5.71)
245
(9.65)
295
(11.61)
320
(12.6)
Volume
3
cm
(in3)
5768
(352.2)
12613
(770.8)
28670
(1750)
35192
(2147)
Weight
kg
(lb)
1.65
(3.64)
3.82
(8.42)
8.36
(18.43)
12.8
(28.2)
Figure 2.5 - Dimensions of the package
11
C
A
B
P
L
3.1 MECHANICAL
INSTALLATION
CHAPTER 3
INSTALLATION AND CONNECTION
This chapter describes the procedures for the electrical and
mechanical installation of the Soft-Starter SSW-07. The guidelines
and suggestions must be followed for the correct operation of the
Soft-Starter SSW-07.
3.1.1 Environmental
English
Conditions
The location of the Soft-Starters SSW-07 is an important factor to
assure the correct operation and high product reliability.
Avoid:
Direct exposure to sunlight, rain, high moisture and sea air ;
Exposure to explosive or corrosive gases and liquids;
Exposure to excessive vibration, dust or any metallic and/or oil
particles in the air.
Allowed Environmental Conditions:
Surrounding air Temperature: 0 ºC to 55 ºC (32 ºF to 131 ºF) -
nominal conditions.
Relative air moisture: 5 % to 90 %, with no-condensation.
Maximum altitude: 1,000 m (3,300 ft) above sea level - nominal
conditions.
From, 1,000 m to 4,000 m (3,300 ft to 13,200 ft) above sea level -
current reduction of 1 % for each 100 m (330 ft) above 1,000 m
(3,300 ft).
From 2000 m to 4000 m (6,600 ft to 13,200 ft) above sea level -
voltage reduction of 1.1 % for each 100m (330 ft) above 2,000 m
(6,600 ft).
Pollution degree: 2 (according to the UL508).
Normally, only non conductive pollution. Condensation must not
cause conduction in the particles in the air.
3.1.2 Soft-Starter
SSW-07
Dimensions
B
D
D
C
12
The external dimensions and mounting holes are shown in gure
3.1 and table 3.1 below.
A
Figure 3.1 - SSW-07 dimensions
L
H
H
P
CHAPTER 3 - INSTALLATION AND CONNECTION
Height
SSW-07
Model
17 A
24 A
30 A
45 A
61 A
85 A
130 A
171 A
200 A
255 A
312 A
365 A
412 A
H
mm
(in)
162
(6.38)95(3.74)
208
(8.19)
276
(10.9)
331
(13.0)
* IP20 with optional.
3.1.3 Mounting
Specications
Width
L
mm
(in)
144
(5.67)
223
(8.78)
227
(8.94)
Depth
P
mm
(in)
157
(6.18)85(3.35)
203
(7.99)
220
(8.66)
242
(9.53)
A
mm
(in)
132
(5.2)
208
(8.19)
200
(7.87)
B
mm
(in)
120
(4.72)5(0.20)4(0.16)M4
148
(5.83)6(0.24)
210
(8.27)
280
(11.0)15(0.59)9(0.35)
C
mm
(in)
7.5
(0.3)
D
Mounting
mm
(in)
3.4
(0.13)M4
5
(0.2)M5
Screw
M8
Weight
kg
(lb)
1.3
(2.9)IP20
3.3
(7.28)IP20
7.6
(16.8)
11.5
(25.4)
Table 3.1 - Installation data with dimensions in mm (in)
To install the Soft-Starter SSW-07 leave at least the free spaces
surrounding the Soft-Starter as in gure 3.2 below. The dimensions
of these free spaces are described in table 3.2.
Degree
of
Protection
IP00 *
English
IP00 *
SSW-07 Model
17 A
24 A
30 A
45 A
61 A
85 A
130 A
171 A
200 A
A
mm
(in)
50
(2)
80
(3.2)
100
(4)
B
mm
(in)
50
(2)
80
(3.2)
100
(4)
C
mm
(in)
30
(1.2)
30
(1.2)
30
(1.2)
255 A
312 A
365 A
150
(6)
150
(6)
30
(1.2)
412 A
Table 3.2 - Recommended free spaces
Install the Soft-Starter SSW-07 in the vertical position according to
the following recommendations:
1) Install on a reasonably at surface;
2) Do not put heat sensitive components immediately above the
Soft-Starter SSW-07.
ATTENTION!
If a Soft-Starter SSW-07 is installed on top of another use the
minimum distance A + B and diverge from the top Soft-Starter the
hot air that comes from the one beneath it.
13
CHAPTER 3 - INSTALLATION AND CONNECTION
ATTENTION!
Independent conduits or cable trays must be planned for physic
separation of signal, control and power cables. (Refer to item 3.2
Electrical Installation).
For Soft-Starters SSW-07 installed in panels or closed metallic
boxes exhaustion/cooling is required so the temperature does not
exceed the maximum allowed. Refer to dissipated nominal power
in table 3.3.
Table 3.3 - Dissipated power for ventilator panel dimensioning
CHAPTER 3 - INSTALLATION AND CONNECTION
3.1.3.2 Mounting on
Surface
Figure 3.3 shows the installation of the Soft-Starter SSW-07 on the
surface of a mounting plate.
English
Figure 3.3 - Installation procedures of the Soft-Starter SSW-07 on a surface
3.2 ELECTRICAL
INSTALLATION
DANGER!
The Soft-Starter SSW-07 cannot be used as an emergency stop
device.
DANGER!
Be sure that the AC input power is disconnected before making any
terminal connection.
ATTENTION!
The information below may be used as a guide to achieve a proper
installation. Follow also the applicable local standards for electrical
installations.
ATTENTION!
If a power isolating contactor or circuit breaker with minimum voltage
coil is not used at the rst power on, then power up the electronics
rst, adjust the trimpots that are necessary to put the SSW-07 into
operation and only after this energize the power section.
15
CHAPTER 3 - INSTALLATION AND CONNECTION
Circuit-breaker
T
S
R
Line
English
Fuses
R/1L1 S/3L2 T/5L3
3.2.1 Power
Terminals
U/2T1 V/4T2 W/6T3 PE
Figure 3.4 - Standard power/grounding connections
PE
PE
The power terminal blocks vary in size and conguration, depending
on the SSW-07 soft-starter model, as can be observed at the gures
3.5 and 3.6.
Terminals:
R / 1L1, S / 3L2 and T / 5L3: AC supply line.
U / 2T1, V / 4T2 and W / 6T3: Motor connection.
16
CHAPTER 3 - INSTALLATION AND CONNECTION
R/1L1 S/3L2 T/5L3
Output Power
BORNE DE SAIDAPOTENCIA
Terminal
Models 17 A to 85 AModels 130 A to 412 A
Input
BORNE DE ENTRADA
Power Terminal
POTENCIA
SSW-07
Model
17 A
24 A
30 A
45 A
61 A
85 A
130 A
171 A
200 A
255 A
312 A
365 A
412 A
Figure 3.5 - Power terminals
Enclosure
Size
Screw/
Terminal
Size 01Terminal
Size 02Terminal
Size 03
Size 04
M8
(5/16”)
M10
(3/8”)
R/1L1
Output
BORNE DE SAIDAPOTENCIA
Power Terminal
U/2T1
S/3L2
V/4T2
Input
BORNE DE ENTRADA POTENCIA
Power Terminal
Line / MotorGrounding
Torque
Nm
Screw
(in lb)
3
(27)
5.5
(49)
19
(168)
37
(328)
M4
(5/32”)
M5
(3/16”)
M6
(1/4”)
Terminal
T/5L3
W/6T3
English
Torque
Nm
(in lb)
4.5
(40)
6
(53)
8.3
(73)
0.5
(4.5)
Table 3.4 - Maximum torque for power connection
3.2.2 Location of the Grounding, Control and Power Connections
Control
Control
CONTROLE
Control
CONTROLE
48.2
(1.90)
39.0
(1.54)
ATERRAMENTO
39.0
(1.54)
13.3
(0.52)
114
(4.48)
56.3
(2.22)
62.8
(2.48)
32.7
(1.29)
ATERRAMENTO
33.0
36.3
84,8
(3.34)
(1.30)
14.8
14.8
(0.59)
(0.59)
(1.43)
GroundingGroundingGrounding
Dimensions in mm (in).
Figure 3.6 - Location of the grounding, control and power connections
CONTROLE
63.0
(2.48)
(2.48)
ATERRAMENTO
63.0
22.7
(0.89)
60.5
(2.38)
39.7
(1.56)
148
(5.81)
Grounding
ATERRAMENTO
75.5
(2.97)
Control
CONTROLE
75.5
(2.97)
25.1
(0.99)
197
(7.75)
17
CHAPTER 3 - INSTALLATION AND CONNECTION
3.2.3 Recommended
Power and
Grounding
Cables
English
The described specications in table 3.5 are valid only for the
following conditions:
Copper wires for 70 ºC (158 ºF) with PVC insulation for ambient
temperature of 40 ºC (104 ºF), installed in perforated and not
agglomerated conduits.
Naked or silver coated copper busbars with round edges with 1
mm radius with ambient temperature of 40 ºC (104 ºF) and bus
temperature of 80 °C (176 °F).
NOTE!
For correct cable dimensioning, consider the installation condition
and the maximum permitted line voltage drop.
3.2.4 Power Supply
Connection to
the Soft-Starter
SSW-07
18
Table 3.5 - Minimum cable gauge specication
DANGER!
The AC input must be compatible with the voltage range of the
Soft-Starter SSW-07.
DANGER!
Provide a power supply disconnecting switch for the Soft-Starter
SSW-07. This disconnecting switch must disconnect the AC input
voltage to the Soft-Starter SSW-07 whenever necessary (for
example: during maintenance services).
If a disconnected switch or a contactor is inserted in the motor supply
line never operate these devices with the motor running or when
the Soft-Starter SSW-07 is enabled.
ATTENTION!
The overvoltage control in the line that feeds the soft-starter must
be done using overvoltage suppressors with a clamping voltage of
680 Vac (phase-to-phase connection) and an energy absorption
capability of 40 joules (17 A to 200 A models) and 80 joules (255 A
to 412 A models).
CHAPTER 3 - INSTALLATION AND CONNECTION
NOTE!
Use the wire sizes and fuses recommended in tables 3.5 and 3.7.
The connector tightening torque is indicated in table 3.4. Use only
copper wires 70 °C (158 °F).
3.2.4.1 Power Supply
Capacity
The Soft-Starter SSW-07 is suitable to be used in a circuit capable
of supplying not more than X (according to table 3.6) symmetrical
rms amperes, Y maximum volts when protected by ultra-rapid fuses.
Table 3.6 - Maximum current capacity of the power supply
Y = 220-575 V
X (kA)
The SSW-07 can be installed on power supplies with a higher
fault level, if it is protected by ultra-rapid fuses with an adequate
2
interrupting current and an I
t according to item 3.2.4.2.
English
3.2.4.2 Recommended
Fuses
The fuses to be used on the input must be high speed semiconductor
fuses with l2t lower or equal to 75 % of the SCR value indicated in
2
table 3.7 (A
s). The fuse rated current should preferably be equal or
greater than the motor starting current to avoid cyclic overloads and
fuse opening in the forbidden region of the Time x Current curve.
These fuses will protect the SSW-07 in case of a short-circuit.
Normal fuses can also be used, instead of the high speed, which will protect
the installation from short-circuits, but the SSW-07 will not be protected.
For the electronic supply protection of the SSW-07 must be used
fuse type D, or circuit breaker type C as specied in table 3.7.
Power factor correction capacitors must never be installed at the
output of the Soft-Starter SSW-07. (U / 2T1, V / 4T2 and W / 6T3).
ATTENTION!
To ensure that the protections based on the current reading and
display operate correctly, for example the overload, the motor
nominal current must not be lower than 50 % of the nominal SoftStarter SSW-07 current.
NOTE!
Use the wire sizes and fuses recommended in tables 3.5, 3.6 and
3.7. The connector tightening torque is indicated in table 3.4. Use
only copper wires.
NOTE!
The Soft-Starter SSW-07 is provided with electronic protection
against motor overload. This protection must be set according to
the specic motor. When several motors are connected to the same
Soft-Starter SSW-07 use individual overload relays for each motor.
20
CHAPTER 3 - INSTALLATION AND CONNECTION
3.2.5.1 Standard
Three-Wire
Connection
3.2.6 Grounding
Connections
Line current of the Soft-Starter SSW-07 is equal to the motor current.
R
S
T
N
PE
R
U
1/U1
S
V
4/U2
6/W2
3/W1
T
2/V1
5/V2
Figure 3.7 - Soft-Starter SSW-07 with standard connection
R
S
T
N
PE
R
W
U
1/U1
2/V1
4/U2
S
5/V2
6/W2
T
WV
3/W1
DANGER!
The Soft-Starter must be grounded for safety purposes (PE).
The ground connection must comply with the local regulations.
Make the ground connection to a grounding bar or to the general
grounding point (resistance ≤10 ohms).
English
DANGER!
The AC input for the Soft-Starter SSW-07 must have a ground
connection.
DANGER!
Do not use the neutral conductor for grounding purpose. Use
dedicated ground conductor.
ATTENTION!
Do not share the ground wiring with other equipment that operate
with high current (for examples: high voltage motors, welding
machines, etc.). When several Soft-Starters SSW-07 are used,
observe the connections in the gure 3.8.
GROUNDING BAR
BARRA DE ATERRAMENTO
INTERNAL TO THE PANEL
INTERNAAO PAINEL
GROUNDING BAR
BARRA DE ATERRAMENTO
INTERNAL TO THE PANEL
INTERNAAO PAINEL
Figure 3.8 - Grounding connections for more than one Soft-Starter SSW-07
21
CHAPTER 3 - INSTALLATION AND CONNECTION
EMI - Electronic Interference
The Soft-Starter SSW-07 is developed to be used in industrial
systems (Class A) according to Standard EN60947-4-2.
It’s necessary to have a distance of 0.25 m (10 in) between the
Soft- Starter SSW-07 control cables and motor cables.
Example: PLC wiring, temperature controllers, thermocouple cables, etc.
Grounding of the Motor frame
Always ground the motor frame. The Soft-Starter SSW-07 output
wiring to the motor must be installed separately from the input wiring
as well as from the control and signal wiring.
English
3.2.7 Control
and Signal
Connections
TerminalDescriptionSpecications
A1
A2
TerminalFactory DefaultSpecications
DI1Starts/Stops Motor
DI2Fault reset
DI3Fault reset
13Relay 1 output - Operation
14/23Relay common point
24Relay 2 output - Full voltage
The control connections (digital inputs and relay outputs) are made
through the terminals (refer to gure 3.9).
Voltage: 110 to 240 Vac (-15 % to +10 %)
(models from 17 A to 200 A)
Electronics Supply
GroundingOnly for the 255 to 412 A models
Table 3.9 - Description of the control connector pins
110 to 130 Vac or 208 to 240 Vac
(-15 % to 10 %) (models from 255 A
to 412 A).
3 isolated digital inputs
Voltage: 110 to 240 Vac (-15 % to +10 %)
Current: 2 mA Max.
Contact capacity:
Voltage: 250 Vac
Current: 1 A
Torque Nm
(in lb)
0.5 (4.5)
22
Figure 3.9 - Control terminals of the Soft-Starter SSW-07
NOTE!
It is recommended to use shielded cables for the Dix inputs when
using long cables (above 30 m) in noisy environments. The metallic
shield and A2 must be grounded.
CHAPTER 3 - INSTALLATION AND CONNECTION
3.3 RECOMMENDED
SET-UPS
Some recommended set-ups are shown here and they can be
completely or partly used.
The main warning notes for all the recommended set-ups are
shown below and are described in the schemes by their respective
numbers.
NOTES!
The use of fuses or circuit breakers at the input circuit is
1
necessary for the entire installation protection. It is not necessary
to use ultra-fast fuses for the SSW-07 operation; however, their
use is recommended for the soft-starter complete protection.
The transformer “T1” is optional and must be used when there
2
is a difference between the line voltage and the electronic power
voltage.
In case that damage at the SSW-07 Soft-Starter power circuit
3
keeps the motor running (e.g., shorted thyristors), the motor
protection is obtained with the use of the power isolating
contactor (K1) or circuit breaker (Q1).
English
Start push-button.
4
Stop push-button.
5
Start/Stop switch. Bear in mind that when using two-wire digital
6
input command (normally open switch with retention), in case
of a power interruption, upon return of power, the motor will be
started immediately if the switch remains closed.
In case of maintenance of the Soft-Starter SSW-07 or the motor
7
it is necessary to remove the input fuses or disconnect the power
supply to ensure the complete equipment disconnection from
the power supply.
The emergency stop can be used by disconnecting the
8
electronics power supply.
Undervoltage release for the Q1 power isolation circuit breaker.
9
23
CHAPTER 3 - INSTALLATION AND CONNECTION
3.3.1 Recommended
Set-up with
Command
via Two-wire
Digital Inputs
and Isolation
Contactor
English
Refer to notes in item 3.3.
R
S
T
PE
K1
R S T
U V W
M
3~
T1
K1
RL1
23
14
24
RL2
DI1A2A1
DI2
DI3
13
Figure 3.10 - Recommended set-up with commands via two-wire digital inputs
and isolation contactor
3.3.2 Recommended
Set-up with
Command
via Threewire Digital
Inputs and
Circuit- Breaker
Refer to notes in item 3.3.
R
S
T
PE
Q1
R S T
U V W
M
3~
T1
Q1
DI1A2A1
DI2
DI3
13
14
23
RL1RL2
24
24
Figure 3.11 - Recommended set-up with commands via three-wire digital
inputs and a circuit-breaker
NOTE!
It’s necessary to program the digital input DI2 for the three-wire
command function. Refer to item 4.10.
NOTE!
The RL1 shall be set to the “No fault” function. Refer to item 4.12.
3.3.3 Recommended
Set-up with
Command
via Two-wire
Digital Inputs
and Direction of
Rotation
To program the parameters shown above, is necessary the use of
keypad or serial communication. See the Programming Manual for
more information.
K2
R S T
U V W
M
3~
DI1A2A1
DI2
DI3
13
RL1
23
14
24
RL2
Figure 3.13 - Recommended Set-up with Command via Two-wires Digital
Inputs and DC-Braking
26
3.3.5 Symbols
CHAPTER 3 - INSTALLATION AND CONNECTION
Electrical connection between
two signals
Connection terminalsThyristor/SCR
Relay or contactor coil
M
3~
Normally open contact (NO)Transformer
Indicator lightN.O Contact (with retention)
Circuit-breaker
(opens under load)
ResistorNormally open (NO)
Fuse
Three-phase motor
Normally closed (NC)
push-button
push-button
English
CapacitorCircuit-breaker with
undervoltage release
27
CHAPTER 4
SETTING THE SSW-07
This chapter describes how to make the necessary settings for the
correct functioning of the SSW-07.
4.1 CONTROL
TYPE SETTING
English
DIP Switch Control
Type Setting
Figure 4.1 - Control type setting
Select the type of starting control that best adapts to the application.
Voltage Ramp Starting:
This is the most commonly used method. Very easy to program
and set.
The Soft-Starter SSW-07 imposes the voltage applied to the motor.
Generally applied to loads with a lower initial torque or a square
torque.
This kind of control can be used as an initial working test.
Current Limit Starting:
The maximum current level is maintained during the start, being set
according to the application necessities.
Generally applied to loads with a higher initial torque or a constant
torque.
This kind of control is used to adapt the start to the capacity limits
of the supply network.
NOTES!
1. The Current Ramp control type, is only programmed using keypad
or serial communication. See the Programming Manual for more
details.
2. To program the control type in Pump control, see the Programming
Manual or item 5.1.4.
28
CHAPTER 4 - SETTING THE SSW-07
4.2 KICK START
Kick Start Enabling
DIP Switch
English
Figure 4.2 - Kick Start enabling
Soft-Starter SSW-07 offers a Kick Start function for loads that
present a large initial resistance to movement.
This function is enabled through the Kick Start DIP Switch. The
duration of the voltage pulse is set through the trimpot Kick Start
Time.
The voltage pulse applied is of 80 % Un during the programmed
trimpot Kick Start Time.
4.3 INITIAL
VOLTAGE
SETTING
NOTE!
Use this function only for specic applications and where necessary.
Set the initial voltage to a value that the motor starts to run as soon
as the start command is given to the SSW-07.
Initial Voltage
Setting Trimpot
The dot indicates
the factory default
setting
Figure 4.3 - Initial voltage setting
29
Loading...
+ 131 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.