Xylem Palmer Bowlus flumes User Manual

Installation Instructions
Palmer & Bowlus flumes
Note!
General
It is very important for the overall measuring accuracy to comply with the installation instructions on the next page.
The Palmer & Bowlus flume is characterized by its circular connection which makes it easy to install in pipelines.
The flume is aimed at measurement in the scale of 20 - 100 % of the nominal flow.
No simple formula can be set up for the Palmer & Bowlus flumes; the formulas are defined individually for every flume.
For the Palmer & Bowlus flumes with the dimensions as listed in the table below, the flow formulas are defined and incorporated in the flow converter and is chosen in the menu “Programming of flow calculation”.
Flume sizes
MPBGB0204
Size: Q 8” DN 200 ( 200 mm) 14 m 10” DN 250 ( 250 mm) 22 m 12” DN 315 ( 315 mm) 40 m 15” DN 400 ( 400 mm) 65 m 24” DN 600 ( 600 mm) 220 m 30” DN 800 ( 800 mm) 330 m
Material: 8”, 10”, 12”: Glass fibre reinforced polyester / PVC
pH range: pH 3 - 10 Temperature range: - 20 … +30 °C, for short periods up to 90 °C
Note: Max. height H must never exceed the measuring range for the flowmeter + deadband.
As our products are developed continuously, we reserve the right to make any changes without prior notice.
15”, 24”, 30”: PVC
min
3 3 3 3
Q /h 70 m3/h 100 mm See note 151 mm 2.8 kg /h 110 m3/h 125 mm below. 179 mm 3.5 kg /h 200 m3/h 150 mm 240 mm 4.8 kg /h 325 m3/h 200 mm 277 mm 9.8 kg
3 3
max
/h 1100 m3/h 300 mm 453 mm 15.6 kg /h 1750 m3/h 400 mm 540 mm 30.1 kg
F H Ha Weight
MJK Automation A/S
Byageren 7 DK-2850 Nærum Denmark Tel.: (+45) 45 56 06 56 Fax: (+45) 45 56 06 46 mjk@mjk.dk www.mjk.dk
Installation instructions
Mounting of the flume
Mounting of the ultrasonic sensor
1: The flume should be mounted in-line in the pipe without contractions both upstream and
downstream. 2: The flume section should be mounted in absolute level . 3: To obtain a precise measurement, it is important that both the upstream and the down-
stream pipe slopes downwards equally to ensure the water never accumulates in the
measuring section of the flume. 4: Position the flume correctly in relation to the flow direction. Observe the flow direction as
indicated with an arrow on the top edge of the flume.
1: It should be mounted firmly. 2: It should be mounted absolutely vertical.
Use a spirit level in TWO directions.Use a spirit level in TWO directions.
Use a spirit level in TWO directions.
Use a spirit level in TWO directions.Use a spirit level in TWO directions.
3: The ultrasonic sensor should be mounted so the ultrasonic signal can pass without any
obstructions from pipes, cables and other installations.
Q/h diagram for Palmer & Bowlus flumes
Q/h diagram for the MJK Palmer & Bowlus flumes, the height ha is shown as a function of the flow Q.
ha [m]
0,35
0,3
15"
0,25
0,2
0,15
0,1
0,05
0
0 50 100 150 200 250 300 350 400 450 500
10"
8"
12"
24" 30"
Q [m3/h]
2
MJK Automation A/S
Byageren 7 DK-2850 Nærum Denmark Tel.: (+45) 45 56 06 56 Fax: (+45) 45 56 06 46 mjk@mjk.dk www.mjk.dk