Xylem IMS SOLOQ User Manual

QUICK START GUIDE
IMS-SOLOQ-1
Aquavar SOLO – Quick Installation Guide
1. Mount Aquavar SOLO Drive (in a vertical position);
• Must have 6” minimum clearance on all sides for proper cooling.
2. Wire Input Power to SOLO Drive (Single Phase, 230V)
• Review Circuit Breaker Sizing - see IMS-SOLOQ-2 or IM229
3. Wire Motor Drop Cable to SOLO Drive (75˚C Copper Wire min.)
• 3AS Models - Use with Three Phase, 230V, ¾ to 5 HP Motors
• 1AS15 Model - Compatible w/Single Phase, 230V Motors
3-Wire - .5 - 2 HP CP / Pentek XE; .5 – 1.5 HP FE & Grundfos
2-Wire - .5 – 1.5 CentriPro, Pentek XE, Franklin Elec. & Grundfos 2-Wire
– units with R05K or newer software only.
• Review Wire Sizing (Table 4 of IM229)
4. Mount Transducer and Confirm Transducer Cable Wiring
• Transducer cable maximum length = 200 feet
• Connect Pressure Transducer to piping manifold and to ground
5. User Interface Board Adjustments
• Select proper “Current Limit Setting” (equal to motor SFA)
• 1AS15 Only - Set “Pump Stop Sensitivity” - High is Default
_ _
• 3AS
• Dry Well Sensitivity - Set on “High” position;
• Low Pressure Cut-Off and Pressure Drop setting adjusted to application /
• Optional use of Secondary Switch Connection, refer to IM229
6. Adjust Tank Pressure
• Set approximately 20 PSI below pressure set point
• Adjust as needed to optimize - see IMS-SOLOQ-2 or IM229
7. Turn Drive Power On - Adjust Pressure - Purge Air
• Purge air from system and check for leaks
• Factory default is 50 psi - push and hold Increase Pressure button if
8. Check Motor Rotation and Confirm Performance
Refer to Aquavar SOLO Installation Manual, IM229, for complete details. Check Motor Insulation Resistance on retrot jobs before replacing drive.
Only - Select maximum frequency setting (60 Hz or 80 Hz);
60 Hz = matching Liquid End HP and Motor HP
80 Hz = “over-speed” application; motor HP > Liquid End HP
If nuisance tripping occurs, switch to “Low” position
system requirements.
higher pressure is desired and also adjust tank pre-charge.
Aquavar SOLO User Interface Board
1AS Controllers 3AS Controllers
Drive
Settings /
Protection
Pressure
Adjustment
Current Limit Dial
(Motor Overload Protection)
TRANSDUCER JUMPER
Pressure
Transducer
Connection
Switch Input (Over
Pressure Protection,
Level Control)
Service Factor Amps – All Motors
230 Volt 200 Volt
HP 1Ø 2-Wire 1Ø 3-Wire
CentriPro1 Franklin Grundfos CentriPro1 Franklin Grundfos CentriPro Franklin Grundfos CentriPro Franklin
½ 4.7/4.7 6 6 6.3/6.1 6 6 N/A N/A N/A N/A N/A
¾ 6.4/6.2 8 8.4 8.3/7.8 8 8.4 3.9 3.8 N/A 4.5 4.4
1 9.1/8.1 9.8 9.8 9.7/9.4 9.8 9.8 4.7 4.7 N/A 5.5 5.4
1½ 11.0/10.4 13.12 13.12 11.1/10.9 11.5 11.6 6.1 5.9 7.3 7.2 6.8
2 N/A N/A N/A 12.2 13.22 13.22 7.6 8.1 8.7 8.8 9.3
3 N/A N/A N/A N/A N/A N/A 10.1 10.9 12.2 12 12.5
5 N/A N/A N/A N/A N/A N/A 17.5 17.8 19.82 20.22 20.5
1. CentriPro 2-Wire motors have Generation 1 and Generation 2 amp ratings, see motor nameplate or motor data sticker that was supplied with motor.
2. Amps are higher than controller overload range - use of these motors will current limit and provide reduced performance.
2
Pressure Ranges for All Available Transducers
Transducer
(Min. PSI) (Max. PSI) (Min. PSI) (Max. PSI) (Min. PSI) (Max. PSI)
100 PSI 200 PSI 300 PSI 60 255 60 255 30 150
(1) Standard on 1AS15, 3AS20 and 3AS30 (2) Standard on 3AS50
1AS15 / 3AS20 3AS30 3AS50
(1)
20 85 20 85 10 50
(2)
40 170 40 170 20 100
Xylem Inc.
www.xyleminc.com
© 2012 Xylem Inc. IMS-SOLOQ-1 January 2012
QUICK START GUIDE
IMS-SOLOQ-2
Aquavar® SOLO Controller
PRESSURE TANK SIZING and SET-UP
• Use Total Tank Volume to size tank. Total tank volume should be approximately 20% of the pump’s maximum ow rate. Ex., pump maximum ow =10 GPM = 2 gallon Total Vol. tank.
• If the User Interface Board (UIB) is set for a 5 PSI Pressure Drop adjust the tank pressure to 20 PSI below the desired system set-point. Ex., 50 PSI system set-point = 30 PSI tank pre-charge.
• If the UIB is set for a 20 PSI Pressure Drop adjust the tank pressure to 30 PSI below the de­sired system set-point. Ex., 50 PSI system set-point = 20 PSI tank pre-charge. Each system is different so this setting may require minor adjustment for optimum performance.
• Large Tanks - installations with large volume tanks may require minor tank pre-charge pressure adjustments for optimum performance - please see more details in IM229, espe­cially if the system turns On and Off too often or does not turn off.
10 2 V6P TP6P 23 4.5 V15P TP15P 41 8.2 V25P TP25P 70 13.9 V45 TP45 100 19.9 V60 TP60
Maximum
Pump GPM
Recommended Tanks
Total Volume Order No. or Order No.
CONTROLLER, BREAKER, GENERATOR SIZING
Motor Controller Model HP Voltage
1AS15 3AS20 3AS30 3AS50
½ 230 200 ¾ 230 200 1 230 200 230 200 2 230 200 230 3 40
200
8100
5 230 200
Circuit Generator
Breaker ③ (VA)
2200
15
2900
3500
20
30
4400
6100
50 13300
Supply voltage must be
196 VAC – 265 VAC.
Shaded areas indicate
which controller models can be used with which motors. Lighter shading indicates combinations where controller will limit peak performance to 85% of catalog value for pump/motor.
Circuit Breaker or Dual
Element Time Delay Fuse Size (Amps) protecting branch circuit supplying controller.
Minimum size of single
phase 240 V generator required.
FAULT CODES
No Light: Low Voltage or No Voltage to Controller
Green Light Codes:
• Constant Green - Unit in Standby: system is Off or system detected low voltage, below 190 VAC and is waiting for voltage to increase to acceptable level.
• Blinking Green - Pump is running: all is normal
Red Light Codes:
• Constant Red - Controller Error: internal controller issue, replace controller.
• 2 Blinks - Dry Well: controller will restart automatically
• 3 Blinks - Transducer Fault: controller will not run if the signal from the
transducer is disconnected or out of tolerance.
• 4 Blinks - Over Current: controller will attempt to restart three times before
displaying this fault. To clear the fault, turn power off, wait 1 minute, turn power on. Fault may be caused by setting Overload Dial on too low a setting.
• 5 Blinks - Short Circuit: controller will attempt to restart three times, to clear,
turn power off, wait 1 minute, turn power on.
• 6 Blinks - Ground Fault: controller will not restart - To clear the fault, turn
power off, wait 1 minute, turn power on.
• 7 Blinks - Temperature: controller will restart automatically when the
temperature reaches an acceptable level.
• 8 Blinks - Open Lead: controller will not restart. To clear the fault, turn power
off, wait 1 minute, turn power on.
• 9 Blinks - Low Pressure Cut-off: Controller will not restart. Pressure 20 PSI
below set point for 30 seconds. May be a broken pipe or tripped pressure relief valve.
Note - In many instances the controller is blamed for faults caused by bad motors, tanks with incorrect or no air charge, poor wiring and/or improper grounding. Since the SOLO may be used to retrot an existing installation into a variable speed system, IM229 includes instructions on checking Motor Insulation Resistance and Winding Resistance. Before replacing a SOLO drive on a retrot installation please perform these tests to verify the motor and wire are in good condition and the tank pressure is set properly.
Xylem Inc.
www.xyleminc.com
© 2012 Xylem Inc. IMS-SOLOQ-2 January 2012
QUICK START GUIDE
IMS-SOLOQ-3
Aquavar SOLO – Quick Installation Guide
Recommended 1AS15 Overload Settings - All Motor Brands
Motor Type SFA Wires On ²
.5 CentriPro, Pentek 4.7 2 4.7
2 wire .75 CentriPro, Pentek 6.4 2 6.4
Gen 1 1 CentriPro, Pentek 9.1 2 9.1
1.5 CentriPro, Pentek 11.0 2 11.0
0.5 CentriPro, Pentek 4.7 2 4.7
2 wire 0.75 CentriPro, Pentek 6.2 2 6.3
Gen 2 ³ 1 CentriPro, Pentek 8.1 2 8.3
1.5 CentriPro, Pentek 10.4 2 11
.5 Franklin / Grundfos 6 2 6.3
1 Franklin / Grundfos 9.8 2 9.7
1.5 Franklin / Grundfos 13.1 ¹ 2 12.2
.5 CentriPro, Pentek 6.3 3 6.3
Gen 1
1.5 CentriPro, Pentek 11.1 3 11.1
2 CentriPro, Pentek 12.2 3 12.2
.5 CentriPro, Pentek 6.1 3 6.3
Gen 2 ³
1.5 CentriPro, Pentek 10.9 3 11
2 CentriPro, Pentek 12.2 3 12.2
.5 Franklin / Grundfos 6 3 6.3
.75 Franklin / Grundfos 8 / 8.4 3 8.3
3 wire 1 Franklin / Grundfos 9.8 3 9.7
1.5 Franklin / Grundfos 11.5 / 11.6 3 11.5
2 Franklin / Grundfos 13.2 ¹ 3 12.2
HP Brand
.75 Franklin / Grundfos 8 / 8.4 2 8.3
2 wire
.75 CentriPro, Pentek 8.3 3 8.3
3 wire
1 CentriPro, Pentek 9.7 3 9.7
.75 CentriPro, Pentek 7.8 3 8.3
3 wire
1 CentriPro, Pentek 9.4 3 9.7
Motor No. Set Dial
SOLO Dial Setting
Overload Current Setting Setting
1 4.7
2 6.3
3 6.4
4 8.3
5 9.1
6 9.7
7 11.0
8 11.1
9 11.5
10 12.2
Overload Setting Dial is located on the UIB (User Interface Board) inside the controller.
¹ Amps are higher than controller overload range - use of 1AS15 on these motors will limit current and reduce
performance.
² Note: It is acceptable to use a higher setting than the 2-wire motor maximum amperage because the 2-wire motor's
on winding overloads will protect the motor while the higher SOLO setting will not inhibit performance.
³ Gen 2 motors - 2-Wire were released for sale in Nov/Dec 2011, 3-Wire will be available Feb/March 2012.
VFD Accessories
9K585 Moisture
Sensor with Relay
9K585 Wiring Instructions:
White and Green Wires - Connect to
Switch Input Terminals
Black Wire to Transducer "B" Connector
Red Wire to Transducer "R" Connector
Float Switches - tested for use
with Aquavar SOLO Controllers
6K210 Gauge Guard
9K589 Over-Pressure Switch
for use with Aquavar SOLO or “S-Drive” Controllers
FLOAT SWITCH CATALOG NUMBERS
A2X13 10’ N.O. A2X33 20’ N.O. A2X53 30’ N.O. A2X23U 15’ N.C. A2X33U 20’ N.C. A2X53U 30’ N.C.
Xylem Inc.
www.xyleminc.com
© 2012 Xylem Inc. IMS-SOLOQ-3 January 2012
Connect wires to Switch Input Terminals
See BCPVFDACC for more information.
Loading...