AIR CONDITIONER (MULTI TYPE)
Installation manual
Outdoor Unit
Model name:
<Heat Pump Model> |
<Cooling Only Model> |
For commercial use |
|
|
|
||
MMY-MAP0804HT8-E |
MMY-MAP0804T8-E |
Not accessible to the general public |
|
Vente interdite au grand public |
|||
MMY-MAP1004HT8-E |
MMY-MAP1004T8-E |
||
Kein öffentlicher Zugang |
|||
MMY-MAP1204HT8-E |
MMY-MAP1204T8-E |
Non accessibile a clienti generici |
|
MMY-MAP1404HT8-E |
MMY-MAP1404T8-E |
No destinado al público en general |
|
Não acessível ao público em geral |
|||
MMY-MAP1604HT8-E |
MMY-MAP1604T8-E |
||
Niet geschikt voor huishoudelijk gebruik |
|||
MMY-MAP0804HT8Z-E |
MMY-MAP0804T8Z-E |
Μη προσβάσιμο από το γενικό κοινό |
|
Недоступен для посторонних |
|||
MMY-MAP1004HT8Z-E |
MMY-MAP1004T8Z-E |
Genel erişime açık değildir |
|
|
|||
MMY-MAP1204HT8Z-E |
MMY-MAP1204T8Z-E |
|
|
MMY-MAP1404HT8Z-E |
MMY-MAP1404T8Z-E |
|
|
MMY-MAP1604HT8Z-E |
MMY-MAP1604T8Z-E |
|
|
MMY-MAP0804HT8ZG-E |
MMY-MAP0804T8ZG-E |
|
|
MMY-MAP1004HT8ZG-E |
MMY-MAP1004T8ZG-E |
|
|
MMY-MAP1204HT8ZG-E |
MMY-MAP1204T8ZG-E |
|
|
MMY-MAP1404HT8ZG-E |
MMY-MAP1404T8ZG-E |
|
|
MMY-MAP1604HT8ZG-E |
MMY-MAP1604T8ZG-E |
|
Installation manual |
English |
1-EN |
– 1 – |
2-EN |
SMMS-i |
Installation Manual |
Original instruction
ADOPTION OF NEW REFRIGERANT
This Air Conditioner uses R410A an environmentally friendly refrigerant.
Contents
1 PRECAUTIONS FOR SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2 ACCESSORY PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 3 INSTALLATION OF NEW REFRIGERANT AIR CONDITIONER . . . . . . . . . . . . . . . . . 4 4 SELECTION OF INSTALLATION PLACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 5 CARRYING IN THE OUTDOOR UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 6 INSTALLATION OF THE OUTDOOR UNIT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 7 REFRIGERANT PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 8 ELECTRIC WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 9 ADDRESS SETTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 10 TEST RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 11 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 12 MACHINE CARD AND LOGBOOK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
SMMS-i |
Installation Manual |
Thank you for purchasing this Toshiba air conditioner.
This Installation Manual describes the installation method of the outdoor unit. For installation of indoor units, follow the Installation Manual supplied with the indoor unit.
Moreover, as this installation manual includes the important articles concerning the “Machinery” Directive (Directive 2006/42/ EC), please read through the manual and make sure you understand it. After installation, give this Installation Manual, the Owner’s Manual and the Installation Manual supplied with the indoor unit to the customer and tell the customer to keep them safe.
Prepare an exclusive power source for indoor units, independent to that for outdoor units.
Y-shaped branching joints or a branching header (separately purchased) are required for connecting pipes between indoor and outdoor units. Choose either of them considering the system capacity concerning piping. For installing branching pipes, refer to the installation manual of the Y-shaped branching unit or branching header (separately purchased).
Outdoor connecting branching joints are required for connecting between outdoor units.
Generic Denomination: Air Conditioner
Definition of Qualified Installer or Qualified Service Person
The air conditioner must be installed, maintained, repaired and removed by a qualified installer or qualified service person. When any of these jobs is to be done, ask a qualified installer or qualified service person to do them for you.
A qualified installer or qualified service person is an agent who has the qualifications and knowledge described in the table below.
Agent |
|
Qualifications and knowledge which the agent must have |
|
|
• |
The qualified installer is a person who installs, maintains, relocates and removes the air conditioners made by |
|
|
|
Toshiba Carrier Corporation. He or she has been trained to install, maintain, relocate and remove the air |
|
|
|
conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such |
|
|
|
operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the |
|
|
|
knowledge related to these operations. |
|
|
• |
The qualified installer who is allowed to do the electrical work involved in installation, relocation and removal has |
|
|
|
the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is |
|
|
|
a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier |
|
|
|
Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have |
|
Qualified installer |
|
been trained and is thus thoroughly acquainted with the knowledge related to this work. |
|
• |
The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation, |
||
|
|||
|
|
relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated |
|
|
|
by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant |
|
|
|
handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she |
|
|
|
has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly |
|
|
|
acquainted with the knowledge related to this work. |
|
|
• |
The qualified installer who is allowed to work at heights has been trained in matters relating to working at heights |
|
|
|
with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in |
|
|
|
such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the |
|
|
|
knowledge related to this work. |
|
|
|
||
|
• The qualified service person is a person who installs, repairs, maintains, relocates and removes the air conditioners |
||
|
|
made by Toshiba Carrier Corporation. He or she has been trained to install, repair, maintain, relocate and remove |
|
|
|
the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such |
|
|
|
operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the |
|
|
|
knowledge related to these operations. |
|
|
• |
The qualified service person who is allowed to do the electrical work involved in installation, repair, relocation and |
|
|
|
removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and |
|
|
|
he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by |
|
|
|
Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or |
|
Qualified service |
|
individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work. |
|
person |
• |
The qualified service person who is allowed to do the refrigerant handling and piping work involved in installation, |
|
|
|
repair, relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as |
|
|
|
stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to |
|
|
|
refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, |
|
|
|
he or she has been instructed in such matters by an individual or individuals who have been trained and is thus |
|
|
|
thoroughly acquainted with the knowledge related to this work. |
|
|
• |
The qualified service person who is allowed to work at heights has been trained in matters relating to working at |
|
|
|
heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been |
|
|
|
instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted |
|
|
|
with the knowledge related to this work. |
|
|
|
|
Definition of Protective Gear
When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’ work clothing.
In addition to such normal protective gear, wear the protective gear described below when undertaking the special work detailed in the table below.
Failure to wear the proper protective gear is dangerous because you will be more susceptible to injury, burns, electric shocks and other injuries.
SMMS-i |
|
|
Installation Manual |
||
|
|
|
|
|
|
Work undertaken |
|
|
Protective gear worn |
||
|
|
|
|
|
|
All types of work |
|
Protective gloves |
|
||
|
‘Safety’ working clothing |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
Electrical-related |
|
Gloves to provide protection for electricians and from heat |
|||
|
Insulating shoes |
|
|||
work |
|
|
|||
|
Clothing to provide protection from electric shock |
||||
|
|
|
|
||
|
|
|
|
|
|
Work done at heights |
|
Helmets for use in industry |
|
||
(50 cm or more) |
|
|
|||
|
|
|
|||
|
|
|
|
|
|
Transportation of |
|
Shoes with additional protective toe cap |
|||
heavy objects |
|
||||
|
|
|
|||
|
|
|
|
|
|
Repair of outdoor unit |
Gloves to provide protection for electricians and from heat |
||||
|
|
|
|
|
|
Warning Indications on the Air Conditioner Unit |
|||||
|
|
|
|
||
|
|
Warning indication |
Description |
||
|
|
|
|
|
|
|
|
|
|
WARNING |
WARNING |
|
|
|
|
|
|
|
|
|
ELECTRICAL SHOCK HAZARD |
ELECTRICAL SHOCK HAZARD |
|
|
|
|
|
Disconnect all remote |
|
|
|
|
|
electric power supplies |
Disconnect all remote electric power supplies before servicing. |
|
|
|
|
before servicing. |
|
|
|
|
|
|
|
|
|
|
|
WARNING |
WARNING |
|
|
|
Moving parts. |
Moving parts. |
|
|
|
|
Do not operate unit with grille |
Do not operate unit with grille removed. |
|
|
|
|
removed. |
Stop the unit before the servicing. |
|
|
|
|
Stop the unit before the servicing. |
||
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
CAUTION |
CAUTION |
|
|
|
|
|
|
|
|
|
High temperature parts. |
High temperature parts. |
|
|
|
|
You might get burned |
||
|
|
|
You might get burned when removing this panel. |
||
|
|
|
when removing this panel. |
||
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
CAUTION |
CAUTION |
|
|
|
|
|
|
|
|
|
Do not touch the aluminum |
Do not touch the aluminium fins of the unit. |
|
|
|
|
fins of the unit. |
||
|
|
|
Doing so may result in injury. |
||
|
|
|
Doing so may result in injury. |
||
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
CAUTION |
CAUTION |
|
|
|
|
BURST HAZARD |
BURST HAZARD |
|
|
|
Open the service valves before |
Open the service valves before the operation, otherwise there might be the |
|
|
|
|
the operation, otherwise there |
||
|
|
|
burst. |
||
|
|
|
might be the burst. |
||
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
CAUTION |
CAUTION |
|
|
|
Do not climb onto the |
Do not climb onto the fan guard. |
|
|
|
|
fan guard. |
||
|
|
|
Doing so may result in injury. |
Doing so may result in injury. |
|
|
|
|
|
|
|
SMMS-i |
Installation Manual |
WARNING
General
•Before starting to install the air conditioner, read through the Installation Manual carefully, and follow its instructions to install the air conditioner. Otherwise, falling down of the unit may occur, or the unit may cause noise, vibration or water leakage.
•Only a qualified installer(*1) or qualified service person(*1) is allowed to do installationwork. If installation is carried out by an unqualified individual, a fire, electric shocks, injury, water leakage, noise and/or vibration may result.
•If using separately sold products, make sure to use Toshiba specified products only. Using unspecified products may cause fire, electric shock, water leak or other failure.
•Before opening the service panel of the outdoor unit, set the circuit breaker to the OFF position. Failure to set the circuit breaker to the OFF position may result in electric shocks through contact with the interior parts. Only a qualified installer(*1) or qualified service person(*1) is allowed to remove the service panel of the outdoor unit and do the work required.
•Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit breakers for both the indoor and outdoor units to the OFF position. Otherwise, electric shock may result.
•Place a “Work in progress” sign near the circuit breaker while the installation, maintenance, repair or removal work is being carried out. There is a danger of electric shocks if the circuit breaker is set to ON by mistake.
•Only a qualified installer(*1) or qualified service person(*1) is allowed to undertake work at heights using a stand of 50 cm or more or to remove the intake grille of the indoor unit to undertake work.
•Wear protective gloves and safety work clothing during installation, servicing and removal.
•Do not touch the aluminium fin of the outdoor unit. You may injure yourself if you do so. If the fin must be touched for some reason, first put on protective gloves and safety work clothing, and then proceed.
•Do not climb onto or place objects on top of the outdoor unit. You may fall or the objects may fall off of the outdoor unit and result in injury.
•When working at height, put a sign in place so that no-one will approach the work location before proceeding with the work. Parts or other objects may fall from above, possibly injuring a person below. Also, be sure that workers put on helmets.
•When cleaning the filter or other parts of the outdoor unit, set the circuit breaker to OFF without fail, and place a “Work in progress” sign near the circuit breaker before proceeding with the work.
•When working at heights, put a sign in place so that no-one will approach the work location, before proceeding with the work. Parts and other objects may fall from above, possibly injuring a person below.
•The refrigerant used by this air conditioner is the R410A.
•You shall ensure that the air conditioner is transported in stable condition. If you find any part of the product broken, contact your dealer.
•Do not disassemble, modify, repair or move the product yourself. Doing so may cause fire, electric shock, injury or water leaks. Ask a qualified installer or qualified service person to do any repairs or to move the product.
Selection of installation location
•If you install the unit in a small room, take appropriate measures to prevent the refrigerant from exceeding the limit concentration even if it leaks. Consult the dealer from whom you purchased the air conditioner when you implement the measures. Accumulation of highly concentrated refrigerant may cause an oxygen deficiency accident.
•Do not install in a location where flammable gas may leaks are possible. If the gas should leak and accumulate around the unit, it may ignite and cause a fire.
•When transporting the air conditioner, wear shoes with protective toe caps, protective gloves and other protective clothing.
•When transporting the air conditioner, do not take hold of the bands around the packing carton. You may injure yourself if the bands should break.
•Install the indoor unit at least 2.5 m above the floor level since otherwise the users may injure themselves or receive electric shocks if they poke their fingers or other objects into the indoor unit while the air conditioner is running.
•Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner, otherwise it may cause imperfect combustion.
•Places where the operation sound of the outdoor unit may cause a disturbance. (Especially at the boundary line with a neighbour, install the air conditioner while considering the noise.)
Installation
•Follow the instructions in the Installation Manual to install the air conditioner. Failure to follow these instructions may cause the product to fall down or topple over or give rise to noise, vibration, water leakage or other failure.
•The designated bolts (M12) and nuts (M12) for securing the outdoor unit must be used when installing the unit.
•Install the outdoor unit property in a location that is durable enough to support the weight of the outdoor unit. Insufficient durability may cause the outdoor unit to fall, which may result in injury.
•Install the unit in the prescribed manner for protection against strong wind and earthquake. Incorrect installation may result in the unit falling down, or other accidents.
•Be sure to fix the screws back which have been removed for installation or other purposes.
EN
3-EN |
– 2 – |
4-EN |
|
|
5-EN |
– 3 – |
6-EN |
SMMS-i |
Installation Manual |
Refrigerant piping
•Install the refrigerant pipe securely during the installation work before operating the air conditioner. If the compressor is operated with the valve open and without refrigerant pipe, the compressor sucks air and the refrigeration cycles is over pressurized, which may cause a injury.
•Tighten the flare nut with a torque wrench in the specified manner. Excessive tighten of the flare nut may cause a crack in the flare nut after a long period, which may result in refrigerant leakage.
•Ventilate the air if the refrigerant gas leaks during installation. If the leaked refrigerant gas comes into contact with fire, toxic gas may be produced.
•After the installation work, confirm that refrigerant gas does not leak. If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas may be generated.
•When the air conditioner has been installed or relocated, follow the instructions in the Installation Manual and purge the air completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle. Failure to purge the air completely may cause the air conditioner to malfunction.
•Nitrogen gas must be used for the airtight test.
•The charge hose must be connected in such a way that it is not slack.
•If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas comes in contact with fire, noxious gas may be generated.
Electrical wiring
•Only a qualified installer(*1) or qualified service person(*1) is allowed to carry out the electrical work of the air conditioner. Under no circumstances must this work be done by an unqualified individual since failure to carry out the work properly may result in electric shocks and/or electrical leaks.
•When connecting the electrical wires, repairing the electrical parts or undertaking other electrical jobs, wear gloves to provide protection for electricians and from heat, insulating shoes and clothing to provide protection from electric shocks. Failure to wear this protective gear may result in electric shocks.
•When executing address setting, test run, or troubleshooting through the checking window on the electric parts box, put on insulated heat-proof gloves, insulated shoes and other clothing to provide protection from electric shock. Otherwise you may receive an electric shock.
•Use wiring that meets the specifications in the Installation Manual and the stipulations in the local regulations and laws. Use of wiring which does not meet the specifications may give rise to electric shocks, electrical leakage, smoking and/or a fire.
•Check that the product is properly earthed. (grounding work) Incomplete earthing may cause electric shock.
•Do not connect the earth line to a gas pipe, water pipe, lightning conductor, or a telephone earth line.
•After completing the repair or relocation work, check that the ground wires are connected properly.
•Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local regulations and laws.
•Install the circuit breaker where it can be easily accessed by the agent.
•When installing the circuit breaker outdoors, install one which is designed to be used outdoors.
•Under no circumstances must the power cable be extended. Connection trouble in the places where the cable is extended may give rise to smoking and/or a fire.
•Electrical wiring work shall be conducted according to law and regulation in the community and installation manual. Failure to do so may result in electrocution or short circuit.
•Do not supply power from the power terminal block equipped on the outdoor unit to another outdoor unit. Capacity overflow may occur on the terminal block and may result in fire.
•When carrying out electric connection, use the wire specified in the Installation Manual and connect and fix the wires securely to prevent them applying external force to the terminals. Improper connection or fixing may result in fire.
Test run
•Before operating the air conditioner after having completed the work, check that the electrical parts box cover of the indoor unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON position. You may receive an electric shock if the power is turned on without first conducting these checks.
•When you have noticed that some kind of trouble (such as when an error display has appeared, there is a smell of burning, abnormal sounds are heard, the air conditioner fails to cool or heat or water is leaking) has occurred in the air conditioner, do not touch the air conditioner yourself but set the circuit breaker to the OFF position, and contact a qualified service person. Take steps to ensure that the power will not be turned on (by marking “out of service” near the circuit breaker, for instance) until qualified service person arrives. Continuing to use the air conditioner in the trouble status may cause mechanical problems to escalate or result in electric shocks or other failure.
•After the work has finished, be sure to use an insulation tester set (500V Megger) to check the resistance is 2 MΩ or more between the charge section and the non-charge metal section (Earth section). If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side.
•Upon completion of the installation work, check for refrigerant leaks and check the insulation resistance and water drainage. Then conduct a test run to check that the air conditioner is operating properly.
Explanations given to user
•Upon completion of the installation work, tell the user where the circuit breaker is located. If the user does not know where the circuit breaker is, he or she will not be able to turn it off in the event that trouble has occurred in the air conditioner.
•If you have discovered that the fan grille is damaged, do not approach the outdoor unit but set the circuit breaker to the OFF position, and contact a qualified service person(*1) to have the repairs done. Do not set the circuit breaker to the ON position until the repairs are completed.
•After the installation work, follow the Owner’s Manual to explain to the customer how to use and maintain the unit.
SMMS-i |
Installation Manual |
Relocation
•Only a qualified installer(*1) or qualified service person(*1) is allowed to relocate the air conditioner. It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and/or vibration may result.
•When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air or other gas to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in rupture, injury or other trouble.
•Never recover the refrigerant into the outdoor unit. Be sure to use a refrigerant recovery machine to recover the refrigerant when moving or repairing. It is impossible to recover the refrigerant into the outdoor unit. Refrigerant recovery into the outdoor unit may result in serious accidents such as explosion of the unit, injury or other accidents.
(*1) Refer to the “Definition of Qualified Installer or Qualified Service Person.”
CAUTION
New Refrigerant Air Conditioner Installation
•THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER.
•The characteristics of R410A refrigerant are; easy to absorb water, oxidizing membrane or oil, and its pressure is approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle.
•To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant.
•Accordingly the exclusive tools are required for the new refrigerant (R410A).
•For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not enter.
To Disconnect the Appliance from Main Power Supply.
• This appliance must be connected to the main power supply by means of a switch with a contact separation of at least 3 mm.
The installation fuse (all type can be used) must be used for the power supply line of this conditioner.
SMMS-i |
|
|
|
Installation Manual |
|
2 |
ACCESSORY PARTS |
||||
|
|
|
|
||
Part name |
Q’ty |
Shape |
Usage |
||
Owner’s Manual |
1 |
– |
(Be sure to hand it to the customers.) |
||
Installation Manual |
2 |
– |
(Be sure to hand it to the customers.) |
||
|
|
|
|
|
|
CD-ROM |
|
1 |
– |
For other languages that do not appear in this Installation Manual, |
|
(Owner’s manual, |
|||||
Please refer to the enclosed CD-ROM. |
|||||
Installation manual) |
|
|
|||
|
|
|
|||
Attached pipe |
1 |
|
Connecting pipe for gas side piping |
||
(for Ø22.2) |
|
(MAP080, MAP100 type) |
|||
|
|
||||
|
|
|
|
||
Attached pipe |
1 |
|
Connecting pipe for gas side piping |
||
(for Ø28.6) |
|
(MAP120, MAP140, MAP160 type) |
|||
|
|
||||
|
|
|
|
||
F-GAS label |
1 |
|
Fill the items on the label after adding refrigerant. |
||
|
|
|
|
|
SMMS-i |
Installation Manual |
This air conditioner adopts the new HFC refrigerant (R410A) which does not deplete the ozone layer.
•R410A refrigerant is vulnerable to impurities such as water, oxidizing membranes, or oils because the pressure of R410A refrigerant is higher than that of the former refrigerant by approximately 1.6 times.
As well as the adoption of the new refrigerant, the refrigerating oil has been also changed. Therefore, pay attention so that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle of the new refrigerant air conditioner during installation.
•To prevent mixing of refrigerant or refrigerating oil, the size of the charge port of the main unit or connecting section of the installation tool differs to that of an air conditioner for the former refrigerant.
Accordingly, exclusive tools are required for the new refrigerant (R410A) as shown below.
•For connecting pipes, use new and clean piping materials so that water or dust does not enter.
Explanation of symbols
Used tools |
Usage |
Proper use of tools/parts |
|
|
|
|
|
Gauge manifold |
Vacuuming, charging refrigerant |
Exclusive to R410A |
|
Charging hose |
and operation check |
Exclusive to R410A |
|
|
|||
|
|
|
|
Charging cylinder |
Charging refrigerant |
Unusable (Use the Refrigerant charging balance.) |
|
|
|
|
|
Gas leak detector |
Checking gas leak |
Exclusive to R410A |
|
|
|
|
|
Vacuum pump |
Vacuum drying |
Usable if a counter-flow preventive adapter is |
|
attached |
|||
|
|
||
Vacuum pump with counterflow |
Vacuum drying |
R22 (Existing article) |
|
Flare tool |
Flare processing of pipes |
Usable by adjusting size |
|
|
|
|
|
Bender |
Bending processing of pipes |
R22 (Existing article) |
|
|
|
|
|
Refrigerant recovery device |
Recovering refrigerant |
Exclusive to R410A |
|
|
|
|
|
Torque wrench |
Tightening flare nut |
Exclusive to Ø12.7mm and Ø15.9mm |
|
|
|
|
|
Pipe cutter |
Cutting pipes |
R22 (Existing article) |
|
Refrigerant canister |
Charging refrigerant |
Exclusive to R410A |
|
Enter the refrigerate name for identification |
|||
|
|
||
Welding machine/Nitrogen gas |
Welding of pipes |
R22 (Existing article) |
|
cylinder |
|||
|
|
||
Refrigerant charging balance |
Charging refrigerant |
R22 (Existing article) |
|
|
|
|
EN
7-EN |
– 4 – |
8-EN |
|
|
9-EN |
– 5 – |
10-EN |
SMMS-i |
Installation Manual |
Upon customer’s approval, install the air conditioner in a place which satisfies the following conditions:
•Place where it can be installed horizontally.
•Place which can reserve a sufficient service space for safe maintenance or checks.
•Place where there is no problem even if the drained water overflows.
Avoid the following places:
•Salty places (seaside area) or places with much gas sulfide (hot spring area) (If selecting such a place, special maintenance is required.)
•Places where oil (including machine oil), steam, oil smoke or corrosive gas is generated.
•Places where an organic solvent is used.
•Chemical plants with a cooling system using liquid carbon dioxide.
•Places where a device generating high frequency (inverter, non-utility generator, medical apparatus, or communication equipment) is set. (Malfunction or abnormal control of the air conditioner, or interference to devices listed above may occur.)
•Places where discharged air from the outdoor unit blows against the windows of a neighbour's house.
•Places unable to bear the weight of the unit.
•Places with poor ventilation.
SMMS-i |
Installation Manual |
Leave space necessary for running, installation and servicing.
Air discharge
Air intake
Air intake
Air intake
Air intake
Installation/servicing |
|
||
|
surface |
|
|
|
Square hole for |
||
|
handling |
|
|
|
Outdoor unit top view |
||
500mm or more |
|
|
|
(Rear side) |
|
|
|
10mm or more |
|
|
|
500mm or more |
|
10mm or more |
|
(Front side) |
20mm or more |
||
20mm or more |
NOTE
•If there is an obstacle above the outdoor unit, leave a space of 2000mm or more to the top end of the outdoor unit.
•If there is a wall around the outdoor unit, make sure that its height does not exceed 800mm.
SMMS-i Installation Manual
▼ Combination of outdoor units
Model name |
|
Cooperating outdoor unit |
|
|
(Standard type) |
Unit 1 |
Unit 2 |
Unit 3 |
|
|
|
|||
|
|
|
|
|
MMY-MAP0804* |
MMY-MAP0804* |
– |
– |
|
|
|
|
|
|
MMY-MAP1004* |
MMY-MAP1004* |
– |
– |
|
|
|
|
|
|
MMY-MAP1204* |
MMY-MAP1204* |
– |
– |
|
MMY-MAP1404* |
MMY-MAP1404* |
– |
– |
|
|
|
|
|
|
MMY-MAP1604* |
MMY-MAP1604* |
– |
– |
|
|
|
|
|
|
MMY-AP1814* |
MMY-MAP1004* |
MMY-MAP0804* |
– |
|
|
|
|
|
|
MMY-AP2014* |
MMY-MAP1004* |
MMY-MAP1004* |
– |
|
MMY-AP2214* |
MMY-MAP1204* |
MMY-MAP1004* |
– |
|
|
|
|
|
|
MMY-AP2414* |
MMY-MAP1204* |
MMY-MAP1204* |
– |
|
|
|
|
|
|
MMY-AP2614* |
MMY-MAP1604* |
MMY-MAP1004* |
– |
|
|
|
|
|
|
MMY-AP2814* |
MMY-MAP1604* |
MMY-MAP1204* |
– |
|
MMY-AP3014* |
MMY-MAP1604* |
MMY-MAP1404* |
– |
|
|
|
|
|
|
MMY-AP3214* |
MMY-MAP1604* |
MMY-MAP1604* |
– |
|
|
|
|
|
|
MMY-AP3414* |
MMY-MAP1204* |
MMY-MAP1204* |
MMY-MAP1004* |
|
|
|
|
|
|
MMY-AP3614* |
MMY-MAP1204* |
MMY-MAP1204* |
MMY-MAP1204* |
|
MMY-AP3814* |
MMY-MAP1604* |
MMY-MAP1204* |
MMY-MAP1004* |
|
|
|
|
|
|
MMY-AP4014* |
MMY-MAP1604* |
MMY-MAP1204* |
MMY-MAP1204* |
|
|
|
|
|
|
MMY-AP4214* |
MMY-MAP1604* |
MMY-MAP1404* |
MMY-MAP1204* |
|
|
|
|
|
|
MMY-AP4414* |
MMY-MAP1604* |
MMY-MAP1604* |
MMY-MAP1204* |
|
|
|
|
|
|
MMY-AP4614* |
MMY-MAP1604* |
MMY-MAP1604* |
MMY-MAP1404* |
|
|
|
|
|
|
MMY-AP4814* |
MMY-MAP1604* |
MMY-MAP1604* |
MMY-MAP1604* |
|
|
|
|
|
|
|
|
|
|
|
Model name |
|
Cooperating outdoor unit |
|
|
|
|
|
|
|
(High Efficiency Model) |
Unit 1 |
Unit 2 |
Unit 3 |
Unit 4 |
|
|
|
|
|
MMY-AP1624* |
MMY-MAP0804* |
MMY-MAP0804* |
– |
– |
|
|
|
|
|
MMY-AP2424* |
MMY-MAP0804* |
MMY-MAP0804* |
MMY-MAP0804* |
– |
|
|
|
|
|
MMY-AP2624* |
MMY-MAP1004* |
MMY-MAP0804* |
MMY-MAP0804* |
– |
|
|
|
|
|
MMY-AP2824* |
MMY-MAP1004* |
MMY-MAP1004* |
MMY-MAP0804* |
– |
|
|
|
|
|
MMY-AP3024* |
MMY-MAP1004* |
MMY-MAP1004* |
MMY-MAP1004* |
– |
|
|
|
|
|
MMY-AP3224* |
MMY-MAP0804* |
MMY-MAP0804* |
MMY-MAP0804* |
MMY-MAP0804* |
MMY-AP3424* |
MMY-MAP1004* |
MMY-MAP0804* |
MMY-MAP0804* |
MMY-MAP0804* |
|
|
|
|
|
MMY-AP3624* |
MMY-MAP1004* |
MMY-MAP1004* |
MMY-MAP0804* |
MMY-MAP0804* |
|
|
|
|
|
MMY-AP3824* |
MMY-MAP1004* |
MMY-MAP1004* |
MMY-MAP1004* |
MMY-MAP0804* |
|
|
|
|
|
MMY-AP4024* |
MMY-MAP1004* |
MMY-MAP1004* |
MMY-MAP1004* |
MMY-MAP1004* |
|
|
|
|
|
MMY-AP4224* |
MMY-MAP1204* |
MMY-MAP1004* |
MMY-MAP1004* |
MMY-MAP1004* |
|
|
|
|
|
MMY-AP4424* |
MMY-MAP1204* |
MMY-MAP1204* |
MMY-MAP1004* |
MMY-MAP1004* |
|
|
|
|
|
MMY-AP4624* |
MMY-MAP1204* |
MMY-MAP1204* |
MMY-MAP1204* |
MMY-MAP1004* |
|
|
|
|
|
MMY-AP4824* |
MMY-MAP1204* |
MMY-MAP1204* |
MMY-MAP1204* |
MMY-MAP1204* |
SMMS-i |
Installation Manual |
CAUTION
Handle the outdoor unit carefully, observing the following items.
•When using a forklift or other machinery for loading/unloading in transportation, insert the prongs of the forklift into the rectangular holes for handling as shown below.
•When lifting up the unit, insert a rope able to bear the unit’s weight into the rectangular holes for handling, and tie the unit from 4 sides.
(Apply padding in positions where the rope comes into contact with the outdoor unit so that no damage is caused to the outer surface of the outdoor unit.)
(There are reinforcing plates on the side surfaces, so the rope cannot be passed through.)
|
|
GOOD |
NO GOOD NO GOOD |
|
|
Plaster |
|
|
|
Rope |
|
Rectangular |
Side |
Plaster |
|
holes for |
|
|
|
handling |
|
|
|
Front /Back |
NO GOOD |
|
|
|
Rectangular |
Reinforcing |
|
|
|
holes for |
plate |
|
|
lifting |
|
GOOD |
|
|
|
|
Prongs of the |
|
|
|
forklift |
|
|
EN
11-EN |
– 6 – |
12-EN |
|
|
13-EN |
– 7 – |
14-EN |
SMMS-i Installation Manual
Weight centre of an outdoor unit
(A) |
|
|
(B) |
|
|
|
Anchor bolt position |
Anchor bolt position |
|
|
920 |
700 |
|
|
|
bolt position 755 |
|
bolt position |
755 |
Anchor |
Y |
Anchor |
Y |
X X
Z |
Z |
No. |
Model type |
X (mm) |
Y (mm) |
Z (mm) |
Weight (kg) |
||
Heat pump model |
Cooling only model |
||||||
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
MAP080 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(A) |
MAP100 |
500 |
390 |
645 |
242 |
241 |
|
|
|
|
|
|
|
|
|
|
MAP120 |
|
|
|
|
|
|
(B) |
MAP140 |
605 |
350 |
700 |
330 |
330 |
|
|
|||||||
MAP160 |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
|
|
SMMS-i |
Installation Manual |
WARNING
•Be sure to install the outdoor unit in a place able to bear its weight.
If strength is insufficient, the unit may fall down resulting in human injury.
•Perform specified installation work to protect against strong wind and earthquakes.
If the outdoor unit is imperfectly installed, an accident by falling or dropping may be caused.
CAUTION
•Drain water is discharged from the outdoor unit. (Especially while heating) Install the outdoor unit in a place with good drainage.
•For installation, be careful of the strength and level of the foundation so that abnormal sounds (vibration or noise) are not generated.
REQUIREMENT
Installation in a snowfall area
•Set up a stand higher than the snowfall.
•Apply an angled structure to the stand so that drainage will not be prevented. (Avoid using a stand with a flat surface.)
2.Mount a snowfall-hood onto the air inlet and the air outlet.
•Leave enough space for the snowfall-hood so that it will not be an obstacle for the air inlet and the air outlet.
Snowfall-hood for air outlet (locally procured)
Snowfall-hood for air outlet
(4 faces)
(locally procured)
Stand
(locally procured)
1.To install multiple outdoor units, arrange them with 20mm or more spaces in between.
Fix each outdoor unit with M12 anchor bolts at 4 positions. 20mm projection is appropriate for an anchor bolt.
20mm or more |
20mm or more |
20
M12 anchor bolt
4 positions/unit
SMMS-i |
Installation Manual |
• Anchor bolt positions are as shown below:
Continuous hole |
|
|
310 or |
|
|
310 or |
|
|
|
|||||
|
|
more |
|
|
more |
|
|
|
||||||
(15 x 20 long hole) |
|
A |
|
A |
|
|
|
A |
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
755 |
790 |
|
|
|
|
|
|
|
B |
(Unit: mm)
Model type |
A |
B |
MAP080*, MAP1000*, MAP120* |
700 |
990 |
|
|
|
MAP1404*, 1604* |
920 |
1210 |
|
|
|
500mm or more
NO GOOD |
|
GOOD |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
GOOD |
|
GOOD |
|
Install the vibration-proof |
|
|
rubber so that the bent part |
|
Anchor bolt |
of the fixing leg is |
|
grounded. |
|
|
|
|
|
Vibration-proof rubber |
|
|
NO GOOD |
NO GOOD |
NO GOOD |
The bent part of the fixing leg is not grounded.
SMMS-i |
Installation Manual |
5.Be careful of the connecting arrangement of the header unit and follower units. Set the outdoor units in order of capacity from the one with the largest capacity. (A (Header unit) ≥ B ≥ C ≥ D)
•Be sure to use a header unit for the leading outdoor unit to be connected to the main pipe. (Figure 1 and 3)
•Be sure to use a T-shaped branch joint (RBM-BT14E/RBM-BT24E: separately purchased) to connect each outdoor unit.
•Be careful of the direction of the Outdoor unit connection piping kit for the liquid side. (As shown in Figure 2, a Outdoor unit connection piping kit cannot be attached so that the refrigerant of the main pipe flows directly into the header unit.)
Liquid piping
▼ Figure 1 |
|
|
▼ Figure 2 |
|
|
GOOD |
|
|
NO GOOD |
|
|
Header unit |
Follower unit |
Follower unit |
Header unit |
Follower unit |
Follower unit |
A |
B |
C |
A |
B |
C |
Main pipe
NO GOOD
To the indoor unit |
Main pipe |
|
|
|
To the indoor unit |
Gas piping
▼Figure 3
GOOD
Header unit |
Follower unit |
Follower unit |
A |
B |
C |
Main pipe
To the indoor unit
Extension valve
[Inverse connection of a gas-side branch unit]
▼ Figure 4
NO GOOD
Header unit |
Follower unit |
Follower unit |
A |
B |
C |
Main pipe
To the indoor unit
To gas-side branch unit
•When attaching a Y-shaped branch unit for the gas side, attach it level with the ground (Be sure not to exceed ±15 degrees.). Regarding a T-shape branch joints for the liquid side, there is no restriction for its angle.
|
(Horizontal line) |
(Horizontal line) |
|
|
|
|
Within ±15 degrees |
|
Within ±15 |
Do not connect |
|
|
|
a branch unit |
|||
|
|
|
degrees |
||
A |
(A arrow view) |
(B arrow view) |
vertically. |
||
|
|||||
|
|
|
B
At a level position
EN
15-EN |
– 8 – |
16-EN |
|
|
17-EN |
– 9 – |
18-EN |
SMMS-i Installation Manual
When drawing pipes downward
|
|
[Vertical connection of branch units] |
▼ Figure 5 |
|
▼ Figure 6 |
GOOD |
|
NO GOOD |
Header unit |
Follower unit |
Follower unit |
A |
B |
C |
L-shaped |
|
|
pipe |
|
|
|
To gas-side |
To gas-side |
To gas-side branch |
branch unit |
branch unit |
To gas-side branch |
|
|
unit |
|
|
|
unit |
|
•Adding only one follower unit is possible. Install the additional unit so that its position is opposite to the header unit. Use an extension valve for installation (See the figure above.).
Specify the pipe diameter in advance to allow for adding another unit.
SMMS-i |
Installation Manual |
WARNING
•If the refrigerant gas leaks during installation, ventilate the room.
If the leaked refrigerant gas comes into contact with fire, noxious gas may be generated.
•After installation, check that the refrigerant gas does not leak.
If the refrigerant gas leaks into the room and comes into contact with fire such as a fan heater, stove, or kitchen range, noxious gas may be generated.
• The refrigerant pipe connecting section is set in the |
|
outdoor unit. Remove the front panel and the piping/ |
Hook |
wiring panel. (M5: 9 pcs.) |
|
• As shown in the illustration on the right, the hooks are |
|
at the right and left sides of the front panel. Lift up and |
|
remove the front panel. |
|
• |
Pipes can be drawn out forward or downward from the |
|
|
|
outdoor unit. |
|
|
• When drawing out the pipe forward, draw it out to the |
|
|
|
|
outside via the piping/wiring panel, and leave a space |
|
0 |
|
of 500mm or more from the main pipe connecting the |
5 |
|
|
|
||
|
outdoor unit with the indoor unit, considering service |
|
|
|
work or other work on the unit. (For replacing the |
|
|
|
compressor, 500mm or more space is required.) |
|
|
• |
When drawing out the pipe downward, remove the |
|
|
|
knockouts on the base plate of the outdoor unit, draw |
|
|
|
the pipes out of the outdoor unit, and perform piping on |
|
|
|
the right/left or rear side. Downward length of the balance |
|
|
|
|
|
|
|
|
Front panel |
|
|
|
|
|
o |
r |
Piping/wiring panel |
|
|
|
m |
|
|
||
|
|
|
|
|
(Rear piping) |
||
0 |
m |
|
e |
|
|
||
o |
r |
|
|
|
|||
m |
|
(Left |
|
||||
|
|
|
|
(Right |
|||
|
|
|
|
|
piping) |
||
Drawing out |
piping) |
||||||
|
|||||||
|
|
|
|
|
|
forward |
(Left piping) |
Drawing out |
(Right piping) |
|
||
|
|
|
|
downward |
|
pipe should be 5m or less.
|
Ball valve of gas |
|
Ball valve of gas |
side |
|
side |
|
|
Packed valve of liquid |
Ball valve of liquid |
|
side |
||
side |
||
|
||
|
Packed valve of |
|
Packed valve of |
balance pipe |
|
balance pipe |
|
(MAP080, MAP100, MAP120) |
(MAP140, MAP160) |
SMMS-i |
Installation Manual |
REQUIREMENT
•For a welding work of the refrigerant pipes, be sure to use nitrogen gas in order to prevent oxidation of the inside of the pipes; otherwise clogging of the refrigerating cycle due to oxidized scale may occur.
•Use clean and new pipes for the refrigerant pipes and perform piping work so that water or dust does not contaminate the refrigerant.
•Be sure to use a double spanner to loosen or tighten the flare nut. If a single spanner is used, the required level of tightening cannot be obtained. Tighten the flare nut with the specified torque. (If it is hard to loosen or tighten the flare nut of the balance pipe or packed valve of the liquid side with a double spanner, loosen or tighten the flare nut while holding the valve mounting plate with a spanner.)
Outer dia. of |
|
Packed valve of |
Tightening torque (N•m) |
balance pipe |
|
copper pipe |
|
|
|
|
|
6.4 mm |
14 to 18 (1.4 to 1.8 kgf•m) |
Ball valve of gas side |
9.5 mm |
33 to 42 (3.3 to 4.2 kgf•m) |
|
12.7 mm |
50 to 62 (5.0 to 6.2 kgf•m) |
Packed valve of liquid |
15.9 mm |
63 to 77 (6.3 to 7.7 kgf•m) |
side |
|
Pipe connection method of valve at the gas side (Example)
Type |
Pipe |
|
Draw-out forward |
|
|
Draw-out downward |
|
diameter |
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
Cut the L-shaped pipe at the horizontal straight |
Cut the L-shaped pipe at the vertical straight |
||||
|
|
section, then braze the supplied attachment |
section, then braze the supplied attachment |
||||
|
|
pipe and the socket and pipe procured locally. |
pipe and the socket and pipe procured locally. |
||||
|
|
|
|
Gas |
|
|
|
MAP080 |
Ø22.2 |
Liquid |
Gas pipe |
pipe |
Liquid |
Gas pipe |
Gas |
MAP100 |
pipe |
Attachment |
|
pipe |
|
||
|
|
|
Attachment |
pipe |
|||
|
|
Balance |
pipe |
|
Balance |
|
|
|
|
Socket |
|
pipe |
|
||
|
|
pipe |
|
pipe |
Socket |
|
|
|
|
|
|
|
|
|
|
|
|
|
Pipe |
|
|
Pipe |
Section |
|
|
|
|
|
|
to be cut |
|
|
|
|
|
|
|
|
|
|
|
|
|
Section to be |
|
|
|
|
|
|
|
cut |
|
|
|
Cut the L-shaped pipe at the horizontal straight |
Cut the L-shaped pipe at the vertical straight |
section, then braze the supplied attachment |
section, then braze the supplied attachment |
pipe and the socket and pipe procured locally. |
pipe and the socket and pipe procured locally. |
|
|
Liquid |
Gas |
Liquid |
|
|
MAP120 |
Ø28.6 |
pipe |
Gas pipe |
Gas |
||
pipe |
Gas pipe |
pipe |
||||
|
|
|
|
|
|
|
|
|
Balance |
Attachment pipe |
Balance |
Attachment |
pipe |
|
|
pipe |
|
pipe |
|
|
|
|
Socket |
pipe |
|
||
|
|
|
|
|
||
|
|
|
|
Socket |
Section |
|
|
|
|
Pipe |
|
||
|
|
|
|
Pipe |
to be cut |
|
|
|
|
|
|
||
|
|
|
Section to be |
|
|
|
|
|
|
|
|
|
|
|
|
|
cut |
|
|
|
SMMS-i |
|
|
Installation Manual |
|
|
|
|
|
|
Type |
Pipe |
Draw-out forward |
Draw-out downward |
|
diameter |
||||
|
|
|
||
|
|
Cut the L-shaped pipe at the horizontal straight |
Cut the L-shape pipe at the vertical straight |
|
|
|
section, then braze the supplied attachment |
section, then braze the supplied attachment |
|
|
|
pipe, and the socket and pipe procured locally. |
pipe, and the socket and pipe procured locally. |
|
|
|
|
Gas |
|
|
|
MAP140 |
Ø28.6 |
Liquid |
Gas pipe |
pipe |
Liquid |
Gas pipe |
Gas |
|
|||||||
MAP160 |
pipe |
|
pipe |
|
|||
|
Attachment pipe |
|
Balance |
Attachment |
pipe |
||
|
|
Balance |
|
|
|||
|
|
Socket |
|
pipe |
pipe |
|
|
|
|
pipe |
|
|
Socket |
|
|
|
|
Pipe |
|
|
Section |
||
|
|
|
|
|
Pipe |
||
|
|
|
|
Section |
|
to be cut |
|
|
|
|
|
|
|
|
|
|
|
|
|
to be cut |
|
|
|
Extruding margin of copper pipe with flare machining: B (Unit: mm)
Copper pipe outer |
When using R410A |
When using |
B |
dia. |
tool |
conventional tool |
|
9.5 |
|
|
|
12.7 |
0 to 0.5 |
1.0 to 1.5 |
|
15.9 |
|
|
|
Extruding margin of copper pipe with flare tools: A (Unit: mm)
Copper pipe outer dia. |
A-+00.4 |
|
|
|
A |
|
|
9.5 |
13.2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
12.7 |
16.6 |
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
15.9 |
19.7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*When using the conventional flare tool, to connect R410A pipes with flaring, make a margin approx. 0.5mm longer than that of an R22 pipe so that the flare size matches the one specified. It is convenient to use a copper pipe gauge for size adjustment of the extruding margin.
EN
19-EN |
– 10 – |
20-EN |
|
|