tekmar 150 User Manual

- Data Brochure
D 150
One Stage Setpoint Control 150
The tekmar One Stage Setpoint Control 150 is a microprocessor-based control that to maintain a fixed setpoint temperature by cycling a heating or cooling device using either bang-bang or Pulse Width Modulated (PWM) output control.
Setpoint
HEAT
Differential
F
This reliable and versatile control has a very wide setpoint range, an adjustable differential and time delay that makes it useable in many different applications. The control has a digital LCD window that normally shows the actual sensor temperature and can be used to view the setpoint as well as the other programmed settings.
A Universal sensor 071 is supplied with the control. The wire to the sensor may be extended up to 500 ft. (150m) by standard 18 AWG low voltage wire. The display will indicate a sensor fault whenever the sensor is either open or short circuited.

Technical Data

Technical specifications
Dimensions — 2-7/8" x 4-3/4" x 7/8”
)mm 22 x 021 x 47( Gross Weight — 1 lb (450g) Ambient — -20 to 120°F (-30 to 50°C)
gnisnednoc-non HR % 09<
Power supply — 24 V (ac) ±10%, 50/60 Hz, 1.3 VA
A 20.0 %01± )cd( V 42 Relay — 240 V (ac) 8 A 1/4 hp Sensor — 10 kΩ @77°F (25° ± 0.2°C),
rotsimreht CTN ,3 evruc
.tf 005 ot pu htiw etarucca
eriw eguag 81 fo )m051(
Control accuracy — ±0.5°F (±0.3°C) at 70°F (21°C)
Settings
Temperature display — -85 to 302°F (-65 to 150°C) Setpoint — -40 to 239°F (-40 to 115°C) Differential (Bang/Bang) — 1 to 40°F (1 to 22°C) Differential range (PWM) — 3 to 40°F (2 to 22°C) Time delay (Bang/Bang) — 0 to 19 min. 50 sec.
(10 second increments)
Cycle length (PWM) — 30 sec. to 19 min. 50 sec.
(10 second increments) Operating mode — Heating/Cooling Temperature scale — Fahrenheit/Celsius Programmed settings — Ten year memory
backup
Programming
mode indicator
Heating mode
indicator
Item
Identifiers
Item
selection
and display
button
Wiring Chamber;
Terminals for 24Vac power
supply and
control circuit
for heating/
cooling device
Hole for mounting screw
PRGM
HEAT COOL
Item
Hole for mounting screw
can be programmed
FC
12/08
Temperature, Differential and Delay/Cycle Display
°C or °F indicators
Cooling mode indicator
Programming and display buttons
Wiring Chamber; Terminals for Sensor

Sequence of Operation

• When the One Stage Setpoint Control 150 is powered-up
will then monitor the sensor temperature and display it in the digital display. (See diagram)
Bang - Bang Operating Mode
PWM
Dip Switch Down
Bang-Bang control outputs turn equipment on when there is a demand for heating or cooling, and then shut it completely off when the demand is satisfied.
• If the control is programmed for “Heat”
in this mode, it turns on its relay and the “HEAT” display element when the sensor temperature is (a) — 1/2 the differential setting below the setpoint, When the sensor
temperature rises 1/2 the differential setting above the
(b) — the delay has timed out.
and
setpoint, the relay switches off , the “HEAT” display element turns off and the delay starts to time out.
During the time out period, the Delay/Cycle pointer
will flash if heating is needed.
the digital display will show all of the display elements. The control
Desired temperature this example 160°F(71°C)
WarmerCooler
Temperature
CONTROL RELAY (HEATING)
OFF ON
e
s
i
r
e
r
u
t
a
r
e
p
m
e
T
155°F(68°C)
Time
Differential
this example
165°F(74°C)
T
e
m
p
e
r
a
t
u
r
e
f
a
1 0 °F ( 5 °C )
l
l
• If the control is programmed for “Cool”
in this mode, it turns on its relay and shows the “COOL” display element when the sensor temperature is (a) — 1/ 2 the differential setting above the setpoint, When the sensor
temperature drops 1/2 the differential setting below the
(b) — the delay has timed out.
and
setpoint, the relay switches off, the “COOL” display element turns off and the delay starts to time out.
During the time out period, the Delay/Cycle pointer will
flash if cooling is needed.
PWM Operating Mode
PWM
Dip Switch Up
The Pulse Width Modulation (PWM) control output is an on/off action, but differs from the simple bang-bang by changing the length of the “on” time based on how much the actual temperature differs from the desired temperature. With the advance to PWM output, overshoot and undershoot is reduced by adding a quantity based function. The heating device is not simply operated “when” heat is needed but the operation is varied depending on “how much” heat is needed.
• If the control is programmed for “Heat”
in this mode, the relay is off as long as the sensor temperature is 1/2 the differential setting
WarmerCooler
Temperature
Desired temperature;
(Setting, this example 68° F) 19°C
WarmerCooler
Heating
Temperature
RELAY ON
CONTROL RELAY (COOLING)
Desired temperature this example 40°F(4°C)
RELAY OFF
ON OFF
m
p
e
e
T
r
a
t
u
Cycle length
Time
e
T
r
e
p
m
Pulse Width
i
r
e
r
u
t
a
r
e
35°F(2°C)
Time
e
s
T
e
m
above the setpoint. The relay is continually on when the sensor temperature is 1/2 the differential below the setpoint. If the sensor temperature is between these two points, PWM action occurs. As more heat is required, the relay “on” time is increased and the “off” time is decreased within each cycle. As less heat is required, the relay “on” time is decreased and the “off” time is increased within each cycle.
• If the control is programmed for “Cool”
in this mode, the relay is continually on when the sensor temperature is 1/2 the differential setting above the setpoint. The relay is off when the sensor temperature is 1/2 the differential below the setpoint. If the sensor temperature is between these two points, PWM action occurs. As more cooling is required, the relay “on” time is increased and the “off” time is decreased within each cycle. As less cooling is required, the relay “on” time is decreased and the “off” time is increased within each cycle .
Caution— If PWM is selected, the minimum time delay is disabled.
Differential
this example
10°F(5°C)
45°F(7°C)
p
e
r
a t
u
r
e
f
a
l
l
PWM Zone;
(Differential Setting, this example 4° F (2°C)

Installation

Caution
Improper installation and operation of this control could result in damage to equipment and possibly even personal injury. It is your responsibility to ensure that this control is safely installed according to all applicable codes and standards.
Step One Getting ready
Check the contents of this package. If any of the contents listed are missing or damaged, please refer to the Limited Warranty and Product Return Procedure on the back of this brochure and contact your wholesaler or tekmar sales agent for assistance.
Type 150 includes:
Other information available:
Note: Carefully read the Sequence of Operation section in this brochure to ensure that you have chosen the proper control and
understand its functions within the operational requirements of your system.
Step Two
Mounting
The control is mounted in accordance with the instructions in the Data Brochure D 001.
Step Three
Rough-in wiring
All electrical wiring terminates in the two wiring chambers at the bottom front of the control. If the control is to be mounted on an electrical box, the wiring can be roughed-in at the electrical box prior to installation of the control (see Brochure D 001). Standard 18 AWG solid wire is recommended for all low voltage wiring to this control.
Caution: Power should not be applied to any of the wires during this rough-in wiring stage.
• Install the Universal Sensor 071, according to the instructions in Data Brochure D 070 and run the wiring back to the control
but don’t connect.
• Install a 24 V (ac) Class 2 transformer with a minimum 5 VA rating close to the control, and run the wiring from the transformer
to the control.
A Class 2 transformer must be used. Do not connect any of the transformer terminals to ground.
• Install the wiring from the heating/cooling device control circuit to the control.
One Control 150 • One Universal Sensor 071
• One Data Brochure D 150 • One Data Brochure D 001 • One Data Brochure D 070
• Essay E 001
Step Four
Testing and connecting the wiring
Caution
These tests are to be performed using standard testing practices and procedures and should only be carried out by a properly trained and experienced technician. A good quality electrical test meter, capable of reading from at least 0 — 200 Volts AC, and at least 0 — 2,000,000 Ohms, is essential to properly test this control. At no time should voltages in excess of 28 V (ac) be measured at any of the wires connected to this control.
2
Loading...
+ 2 hidden pages