SILENT
KNIGHT
®
by Honeywell Model SD500-ARM Relay Module Installation Quick Reference
This sheet is intended to be used for quick reference only. For complete information on wiring, addressing, and programming this device, refer to the control panel installation manual.
5820 Board |
|
|
|
|
|||
|
Assembly |
|
|
|
|
||
SLC Out |
SLC In |
|
|
|
|
||
SC- S+ SC- |
S+ |
|
|
|
|
||
33 |
34 |
35 |
36 |
|
|
|
|
|
|
|
|
Supervised |
|
|
|
|
|
|
|
Power limited |
|
|
|
|
|
|
|
LED |
|
|
NO1 |
|
|
|
SLC+- |
|
|
C1 |
|
|
|
|
|
|
|
NC1 |
|
LED flashes green when |
|
|
|
NO2 |
|||
contacts are in normal state; |
|
|
|
||||
1 2 3 4 5 6 |
7 |
8 |
C2 |
||||
|
flashes red when |
Dipswitch |
|||||
|
NC2 |
||||||
contacts are activated. |
|
|
|
Electrical & Environmental Specifications
Operating Temperature |
32° – 120°F (0° – 49°C) |
|
|
|
|
Operating Voltage |
24 |
VDC |
|
|
|
SLC Current |
0.55 mA |
|
|
|
|
SLC Loop Resistance |
50Ω |
|
|
|
|
Relay Ratings |
30 |
VDC @ 2.0A Resistive |
|
30 |
VDC @ 1.0 A Inductive (.6PF) |
|
30 |
VDC @ 0.6 A (0.35PF) Pilot Duty |
120 VAC @ 0.6 A (0.35PF) Pilot Duty
For indoor use only
Relay 1
Contacts are Form C, non-supervised.
Power limited sources only. Relay 2 Programmable relays.
If power-limited circuits are installed (using types FPL, FPLR, FPLP or other permitted substitute cables), they must be separated from all other conductors by a minimum of 0.25 in. or by a nonconductive sleeve or barrier.
For device addressing. See manual for list of valid addresses.
Figure 1: Typical Wiring
SD500-ARM circuit board and mounting plate (assembled at the factory)
SLC+-
When attaching cover plate, line up screw holes as shown.
4-square electrical box
|
|
|
|
NO1 |
|
|
|
|
C1 |
|
|
|
|
NC1 |
4 |
5 |
|
7 |
NO2 |
6 |
8 |
|||
|
|
|
|
C2 |
|
|
|
|
NC2 |
Cover plate
Fit screws through notches on mounting plate. Tighten screws to secure to box.
Figure 2: Typical Mounting
P/N 151091 Rev D