SK-2224 Basic Operating Instructions P/N 151064
|
|
|
|
These instructions must be framed and displayed next to the SK-2224 panel in accordance |
|||||
|
|
|
|
with NFPA 72 fire code for Local Fire Alarm System. |
|||||
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
LED (Color) |
|
|
Function |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
AC (green) |
ON = Good AC |
|
|
||
|
|
|
|
||||||
|
|
|
|
|
|
OFF = Low AC trouble condition and it was acknowledged |
|
||
|
|
|
|
|
|
FLASHING = Unacknowledged AC Low trouble condition |
|
||
|
|
|
|
GENERAL TROUBLE |
ON = System trouble |
|
|||
|
|
|
|
(yellow) |
|
OFF = System OK |
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
FLASHING = At least one serial device is in trouble |
|
||
|
|
|
|
|
|
||||
|
|
|
|
|
|
DOUBLE FLASHING = Two types of serial devices are in trouble. |
|
||
|
|
|
|
|
|
|
|
||
|
|
|
|
WALK TEST (yellow) |
ON = Walk test is in progress |
|
|||
|
|
||||||||
|
|
|
|
|
|
OFF = Walk test is off. |
|
||
|
|
|
|
|
|
FLASHING = Walk test is on and at least one zone is not ready |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
GND FAULT (yellow) |
ON = Ground fault condition exists and was acknowledged |
|
|||
|
|
|
|
|
|
OFF = No fault |
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
FLASHING = A ground fault condition detected |
|
||
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
||
|
|
|
|
LOW BATTERY (yellow) |
ON = Battery low condition that has been acknowledged |
|
|||
|
|
||||||||
|
|
|
|
|
|
OFF = Good battery condition |
|
||
|
|
|
|
|
|
||||
|
|
|
|
|
|
FLASHING = Battery low condition |
|
||
|
|
|
|
ZONE 1 |
ALARM (red) |
ON = Zone in alarm which has been acknowledged |
|
||
|
|
|
|
and |
|
OFF = No Alarm |
|
|
|
|
|
|
|
ZONE 2 |
|
FLASHING = Zone in alarm has not yet been acknowledged. |
|
||
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SUPERVISORY |
ON = Zone has a supervisory condition (self-restoring condition) |
|
||
Line |
|
|
|
|
(yellow) |
OFF = No supervisory condition exists. |
|
||
|
|
|
|
||||||
|
|
|
|
|
FLASHING = supervisory trouble detected on that zone. |
|
|||
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
Dotted |
|
|
|
|
TROUBLE |
ON = Zone has a trouble condition which has been acknowledged |
|
||
|
|
|
|
(yellow) |
OFF = No zone trouble |
|
|||
|
|
|
|
|
|
||||
|
|
|
|
|
|
FLASHING = Zone has a trouble condition |
|
||
the |
|
|
|
|
|
DOUBLE FLASHING = Zone was disabled |
|
||
|
|
|
|
|
|||||
|
|
|
|
|
CLEAN ME FLASHING = Indicates that the smoke detector needs cleaning (LED is on long and |
|
|||
|
|
|
|
|
|
||||
Along |
|
|
|
|
|
|
|||
|
|
|
|
|
Off for a short time period) |
|
|||
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
NAC 1 |
ACTIVE (yellow) |
ON = NAC is active during an alarm |
|
||
|
|
||||||||
Cut |
|
|
|
and |
|
OFF = NAC is not active during alarm |
|
||
|
|
|
NAC 2 |
|
|
|
|
||
|
|
|
TROUBLE |
ON = NAC has a trouble condition and was acknowledged |
|
||||
|
|
|
|
|
(yellow) |
OFF = No trouble condition |
|
||
|
|
|
|
|
|
FLASHING = NAC is in trouble |
|
||
|
|
|
|
|
|
||||
|
|
|
|
|
|
DOUBLE FLASHING = Circuit was disabled |
|
||
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SYSTEM SILENCED |
ON = System audible output has been silenced |
|
|||
|
|
||||||||
|
|
|
|
(yellow) |
|
OFF = Nothing silenced |
|
||
|
|
|
|||||||
|
|
|
|
|
|
FLASHING = Partially silenced |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
Operation |
|
|
Keystrokes |
||
|
|
|
|
|
|
||||
|
|
|
|
|
|
||||
|
|
|
Disable notification appliance circuit. |
|
Press the appropriate [NAC DISABLE] key. The NAC circuit will be disabled and the corresponding |
||||
|
|
||||||||
|
|
|
To re-enable the circuit, press [NAC |
|
TROUBLE LED will Double Flash. This function is not available during an alarm condition. |
||||
|
|
|
DISABLE] again. |
|
|
|
|
|
|
|
|
|
Disable a zone |
|
|
Press the appropriate [ZONE DISABLE] key. The zone will be disabled and the corresponding TROUBLE |
|||
|
|
|
To re-enable the circuit, press [ZONE |
|
LED will Double Flash. This function is not available during an alarm or supervisory condition. |
||||
|
|
||||||||
|
|
|
DISABLE] again. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|||
|
|
|
Begin Walk Test |
|
|
Press [WALK TEST]. Walk Test LED turns on. |
|||
|
|
|
|||||||
|
|
|
|
|
|
|
Note: |
Walk test will not activate if the control panel has a trouble, alarm, or supervisory condition. |
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|||
|
|
|
End Walk Test |
|
|
Press [WALK TEST]. |
|||
|
|
|
|
|
|
|
NOTE: The Walk Test feature is not operational during an alarm, supervisory or any system trouble |
||
|
|
|
|
|
|
|
condition.The test ends automatically after 10 minutes of no system activity. |
||
|
|
|
|
|
|||||
|
|
|
Acknowledge condition (alarm, supervisory, |
Press [ACK]. The corresponding LED will change from blinking to steady for the duration of the condition. |
|||||
|
|
|
trouble) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|||
|
|
|
Silence Panel |
|
|
Press [SILENCE]. This will silence the on-board PZT and all active NAC circuits that have been configured as |
|||
|
|
|
|
|
|
|
"silenceable". |
||
|
|
|
|
|
|
||||
|
|
|
Perform system reset |
|
Press [RESET]. Resets alarms, supervisories, troubles and all LEDs. |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
Manual Dialer Test. |
|
|
Press the [ACK] and [ SILENCE] buttons at the same time. |
|||
|
|
|
Dialer Reset. |
|
|
Press the [RESET] and [WALK TEST] buttons at the same time. |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
For Service Contact: