SmartX Controller
W1-Sized I/O Modules
Dimensions
Installation Sheet
Installing the Module Labeling the Module
02-16006-20-en September 2016 1 of 2
Smoke Control Application Note
Terminal Base for All I/O Modules
All Universal Inputs (UI), Digital Inputs (DI), and
Analog Outputs (AO) are power-limited per UL 864
requirements. All Digital Output (DO) relays are nonpower-limited. For more information on the use of the
I/O modules for a UL 864 smoke control application,
see the latest version of the Smoke Control Design
Guide (04-16014-XX-en).
Specifications
Operation environment
Ambient temperature, operating
0 to 50 °C (32 to 122 °F)
Humidity
Maximum 95 % RH non-condensing
Mechanical
Enclosure rating
IP 20
Plastic rating
UL94-5VB
Electrical
I/O bus power
24 VDC max. 30 W per I/O bus
power supply, Class 2
Maximum addresses per I/O bus
32
Regulatory compliance
EMC, safety, and environment
FCC CFR 47 Part 15 Class B, ICES-003
Class B, RCM, CE - EMCD 2014/30/EU,
CE - LVD 2014/35/EU, WEEE
2012/19/EU, RoHS 2011/65/EU, China
RoHS SJ/T 11364-2014, UL 916 Listed
products for the United States and
Canada, Open Class Energy
Management Equipment (UL file
E80146.), UL 864 Listed products for the
United States. 10th Edition Smoke
Control System. (UL file S5527.)
AO-8 (-H) Module
DC input power
24 VDC , 4.9 W
Output rating
0 to 10 VDC , 0 to 20 mA
Channels
8 output
AO-V-8 (-H) Module
DC input power
24 VDC , 0.7 W
Output rating
0 to 10 VDC
Channels
8 output
DI-16 Module
DC input power
24 VDC , 1.6 W
Input rating
24 V, 2.4 mA
Channels
16 input
UI-16 Module
DC input power
24 VDC , 1.8 W
Input rating
24 V, 2.4 mA
Channels
16 input
RTD-DI-16 Module
DC input power
24 VDC , 1.6 W
Input rating
24 V, 2.4 mA
Channels
16 input
UI-8/DO-FC-4 (-H) Module
DC input power
24 VDC , 1.9 W
Relay contact rating
250 VAC / 30 VDC , 3 A
Pilot Duty (Power Factor 0.35)
Input rating
24 V, 2.4 mA
Device Part number
TB-IO-W1 Terminal Base SXWTBIOW110001
Channels
4 output/8 input
UI-8/AO-4 (-H) Module
DC input power
24 VDC , 3.2 W
Output rating
0 to 10 VDC , 0 to 20 mA
Input rating
24 V, 2.4 mA
Channels
4 output/8 input
UI-8/AO-V-4 (-H) Module
DC input power
24 VDC , 1.0 W
Output rating
0 to 10 VDC
Input rating
24 V, 2.4 mA
Channels
4 output/8 input
DO-FA-12(-H) Module
DC input power
24 VDC , 1.8 W
Relay contact rating
250 VAC / 30 VDC , 2 A
Pilot Duty (Power Factor 0.35)
Channels
12 output
DO-FC-8 (-H) Module
DC input power
24 VDC , 2.2 W
Relay contact rating
250 VAC / 30 VDC , 3 A
Pilot Duty (Power Factor 0.35)
Channels
8 output
02-16006-20-en September 2016 2 of 2