Schneider Electric MPR-5600 Series, MPR-5700 Series Data Sheet

SPECIFICATIONS
Actuator Inputs
Control Circuit:
MPR-561X and -563X Series, Two-wire.
MPR-571X and -573X Serie Input Impedance: 82.5 Ω for 4 to 20 mA input. Power Input: Refer to Table-1 and Table Connections: Color-coded 4' (1.2 m) leads.
s, Three-wire.
-2.
Actuator Outputs
Electrical:
Position Signals, Internal feedback circuitry provides positive positioning of the damper
in relation to the controller signal.
Startpoint Adjustment, Adjustable potentiometer provide
actuator startpoint.
Mechanical:
Stroke,
Damper Approximately 2" (51 mm) from fully
AM-601 linkage).
Valve Approximately 9/16" (14.3 mm) from fully retracte
Nominal Damper Area, Actuator sizing should be done in accordance with damper
manufacturer’s specifications.
Output Torque Rating, The proportional o
available throughout the entire stroke and is based on the lowest force available under
normal operation, the spring return stroke, or at minimum (-10%) supply voltage.
retracted to fully extended (includes
utput torque rating of 15 lb-in. (1.7 N-m) is
s manual adjustment of the
d to fully extended.
Environment
Ambient Temperature Limits:
Shipping & Storage, -40 to 140° F (-40 to 60° C).
Operating,
Damper -20 to
Valve Refer to Table-3. Humidity Location: NEMA Type 1, indoor only.
Agency Listings:
UL 873: Underwriters Laboratorie
Regulating Equipment). CSA: Certified for use in Canada by Und C22.2 No. 24-93. European Community: EMC Directive (8 (72/23/EEC).
: 5 to 95% RH, non-condensing.
140° F (-29 to 60° C).
s (File # E9429 Category Temperature-Indicating and
erwriters Laboratories. Canadian Standard
9/336/EEC). Low Voltage Directive
2 © Copyright 2010 Schneider Electric All Rights Reserved. F-23576-7
Table-1 Model Chart for Valve (Basic) Actuators.
Timing in Seconds
@ 72 F (22 C)
No Load Stroke Retract
on
Extend Retract
Power
Loss
Required Linkages
Val ve
Applications
Damper
Applications
Part Number
a
Actuator Power Input
AC
Voltage
+10/
Hz VA Watt
-15%
s
MPR-5610 120
MPR-5611 240
MPR-5613 24
MPR-5710
MPR-5711
d
d
120 Compatible
240
50/60 18 10 60 30 15
AV-600 AV-601
c
AM-601
MPR-5713 24
a
These MPR-5X1X series valve actuators are compatible with VB-7XXX 1/2" to 2" valve bodies.
b
The MPR-5X1X series actuators are basic models which may be equipped for damper applications wi h the installation of an AM-601 linkage.
c
May be required for steam and hot water. Refer to Table-3.
d
These actuators are obsolete. They are listed here for reference only.
Table-2 Model Chart for Damper Actuato
rs.
Actuator Power Input Timing in Seconds @ 72 F (22 C)
Part Number
a
AC
Voltage
+10/
-15%
Hz VA Wa
tts
No Load Stroke
Extend Retract
Retract on
Power
Loss
b
Input
Signal
Inpu
t
Signal
Compatible with 4 to 20 mA
with 135 ¾ Slidewire (Series 90)
MPR-5630 120
Compatible
with
MPR-5633 24
MPR-5730
b
120 Compatible
50 60 18 10 60 30 15
4 to 20 mA
with
MPR-5733
b
24
135 ¾
Slidewire
(Series 90)
a
Damper models (MPR-5X3X) are provided with factory-installed damper linkages. Only base models (MPR-5X1X) require separately-ordered linkages.
b
These actuators are obsolete. They are listed here for reference only.
Table-3 Restrictions on Maximum Ambient Temperature for Valve Actuators.
Maximum Temperature of Media
in the Valve Body
(Check Rating of the Valve)
F ( C)
366 (186)
340 (171) 93 (34)
281 (138) 103 (39)
181 (83) 120 (48)
80 (26) 140 (60)
a
Maximum ambient temperature of the actuator must never exceed 140 F (60 C).
b
Minimum allowable ambient temperature of he actuators is -20 F (-29 C).
Maximum Ambient Temperature
of MPR-563X and -573X Serie
AV-600 (Only)
F ( C)
Do Not Use
a
s
AV-600 and AV-601
F ( C)
88 (31)
140 (60)
b
a
a
a
F-23576-7 © Copyright 2010 Schneider Electric All Rights Reserved. 3
ACCESSORIES
Notes:
1. The 135 Ω controller is supplied by others.
2. The controller has setpoint and throttling range (proportional band) adjustments.
Black
24Vac Black/Blue
120Vac White
240Vac White/Black
To AC Power
Source
MPR-571X or MPR-573X
W
R B
Temp.
Drop
Controller
135 Ω Slidewire
Yellow/White
Red
Blue
Sequence of operation: As the temperature decreases at the controller, R moves toward B and the actuator shaft extends. On power loss to the actuator, the shaft retracts.
Green
Notes:
1. The 135 Ω controller is supplied by others.
2. The controller has setpoint and throttling range (proportional band) adjustments.
24Vac Black/Blue
120Vac White
240Vac White/Black
To AC Power
Source
W
R B
Temp.
Drop
Controller
135 Ω Slidewire
Blue
Red
Yellow/White
Black
MPR-571X or MPR-573X
Sequence of operation: As the temperature decreases at the controller, R moves toward B and the actuator shaft retracts. On power loss to the actuator, the shaft retracts.
Green
Common
11-1612 1/2" conduit bushing
Damper Linkages
AM-111 Crank arm for 5/16" diameter damper shaft AM-112 Crank arm for 3/8" diameter damper shaft AM-113 Crank arm for 1/2" diameter damper shaft AM-115 Crank arm for 7/16" diameter damper shaft AM-122 Linkage connector straight type AM-123 Damper clip AM-125 5/16" diameter x 20" damper rod AM-125-048 5/16" diameter x 48" damper rod AM-132 Ball joint connector AM-161-3 Damper linkage kit AM-601 Device includes mounting bracket, da
AM-602 Spacer
Valve Linkages and Valves
AV-600 Valve linkage 1/2" to 1-1/4" (obsolete VB-9XXX) AV-601 Valve linkage extension for hot water
AV-7600 Valves linkage 1/2" to 2" to be used with VB-7XXX VB-7XXX 1/2" to 2" valve bodies VB-9XXX 1/2" to 1-1/4" valve bodies (obsolete)
(factory-available)
TOOLS
TOOL-19 Spring compression tool for AV-600 TOOL-37 1-5/8" open-ended wrench TOOL-209 135 Ω and 0 to 7 mA manual positioner
straight connector. Requir (51 mm) stroke damper actuators.
AV-7600
ed to modify (MPR-5X1X series) valve actuators into 2"
mper linkage with spring, and AM-122
and steam applications; use with AV-
600 &
TYPICAL APPLICATIONS (wiring diagrams)
Figure-1 Wiring Diagram - Decrease in Temperature Causes Actuator Shaft to Extend.
4 © Copyright 2010 Schneider Electric All Rights Reserved. F-23576-7
Loading...