Schneider Electric MP131-24T, MP131-24F, MP131-24MP Specification Sheet

Specification Sheet

MP131-24T,-24F, -24MP

Actuators for Floating and Proportional Control

Product Description

MP131 actuators are used together with automatically balanced combination valve type SmartX PIBCV for 1/2” to 1-¼”. Typical applications are temperature control and permanent automatic balancing on terminal units (fan-coils, chilled ceilings, air-handling units).

Specifications

Part Numbers

MP131-24T

 

MP131-24F

 

MP131-24MP

Power supply

24 Vac +10… –15 %

Power consumption

 

running

1, 24MP: 1.5 VA

standby

0, 24MP: 0.4 W

 

 

Frequency

50/60 Hz

 

 

24MP:

V 0…10 (2-10) Ri = 200 kΩ

Control input Y

mA 0…20 (4-20) Ri = 500 Ω

Control output X (V)

0…10 Ro (min) = 38 kΩ

Close off force

 

MP131-24T

130 N

MP131-24F

 

MP131-24MP

 

Stroke

 

MP131-24T

5 mm

MP131-24F

 

MP131-24MP

 

Speed

 

MP131-24T

12 s/mm

MP131-24F

24 s/mm

MP131-24MP

 

Relative humidity

max. 80 %

Max. medium temperature

240 °F (120 °C)

 

 

Ambient temperature

0…131 °F (0…55 °C)

Storage and transport

-40…158 °F (–40…70 °C)

temperature

 

Protection class

IP42

 

 

Weight

.66 lbs (0.3 kg)

Agency Listings

Underwriters Laboratory (E489326)

 

compliance as Electric Actuators,

 

cULus LISTED per UL60730 and CSA

 

E60730. European Community com-

 

pliance per EMC directive (2014/30/

 

EU) and LVD directive (2014/35/EU).

 

Australian/New Zealand community

 

RCM mark.

Features

Gap detection at stem up position

3 point version

Force switch-off at stem down position prevents overload of actuator and valve

No tools required for mounting

Maintenance-free lifetime

Low-noise operation

Dimensions (inches)

5.15

2.08

4.67

 

<![if ! IE]>

<![endif]>3.56

<![if ! IE]>

<![endif]>2.89

Mounting and Installation

The actuator should be mounted with the valve stem in either horizontal position or pointing upwards. The actuator is fixed to the valve body by means of a ribbed nut which requires no tools for mounting. The ribbed nut should be tightened by hand.

1.Check the valve neck. The actuator should be in stem up position (factory setting) and mounted securely on the valve body.

2.Wire the actuator according to the wiring diagram.

3.Stem movement is indicated by the Position Indicator (a small pin riding in a channel as shown in (1) below).

(1)

© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.

February, 2017 tc

Document Number: F-27961-1

 

Schneider Electric MP131-24T, MP131-24F, MP131-24MP Specification Sheet