Specification Sheet
MP131-24T,-24F, -24MP
Actuators for Floating and Proportional Control
Product Description
MP131 actuators are used together with automatically balanced combination valve type SmartX PIBCV for 1/2” to 1-¼”. Typical applications are temperature control and permanent automatic balancing on terminal units (fan-coils, chilled ceilings, air-handling units).
Specifications
Part Numbers |
MP131-24T |
|
MP131-24F |
|
MP131-24MP |
Power supply |
24 Vac +10… –15 % |
Power consumption |
|
running |
1, 24MP: 1.5 VA |
standby |
0, 24MP: 0.4 W |
|
|
Frequency |
50/60 Hz |
|
|
24MP: |
V 0…10 (2-10) Ri = 200 kΩ |
Control input Y |
mA 0…20 (4-20) Ri = 500 Ω |
Control output X (V) |
0…10 Ro (min) = 38 kΩ |
Close off force |
|
MP131-24T |
130 N |
MP131-24F |
|
MP131-24MP |
|
Stroke |
|
MP131-24T |
5 mm |
MP131-24F |
|
MP131-24MP |
|
Speed |
|
MP131-24T |
12 s/mm |
MP131-24F |
24 s/mm |
MP131-24MP |
|
Relative humidity |
max. 80 % |
Max. medium temperature |
240 °F (120 °C) |
|
|
Ambient temperature |
0…131 °F (0…55 °C) |
Storage and transport |
-40…158 °F (–40…70 °C) |
temperature |
|
Protection class |
IP42 |
|
|
Weight |
.66 lbs (0.3 kg) |
Agency Listings |
Underwriters Laboratory (E489326) |
|
compliance as Electric Actuators, |
|
cULus LISTED per UL60730 and CSA |
|
E60730. European Community com- |
|
pliance per EMC directive (2014/30/ |
|
EU) and LVD directive (2014/35/EU). |
|
Australian/New Zealand community |
|
RCM mark. |
Features
•Gap detection at stem up position
•3 point version
•Force switch-off at stem down position prevents overload of actuator and valve
•No tools required for mounting
•Maintenance-free lifetime
•Low-noise operation
Dimensions (inches)
5.15 |
2.08 |
4.67 |
|
<![if ! IE]> <![endif]>3.56 |
<![if ! IE]> <![endif]>2.89 |
Mounting and Installation
The actuator should be mounted with the valve stem in either horizontal position or pointing upwards. The actuator is fixed to the valve body by means of a ribbed nut which requires no tools for mounting. The ribbed nut should be tightened by hand.
1.Check the valve neck. The actuator should be in stem up position (factory setting) and mounted securely on the valve body.
2.Wire the actuator according to the wiring diagram.
3.Stem movement is indicated by the Position Indicator (a small pin riding in a channel as shown in (1) below).
(1)
© 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. |
February, 2017 tc |
Document Number: F-27961-1 |
|