Schneider Electric MK-7100 Series, MK4-7100 Series Installation Instructions

Installation Instructions

SPECIFICATIONS

Construction

Housing: Die cast aluminum.

Diaphragm: Replaceable beaded molded neoprene.

Mounting: Any position.

Dimensions of Actuator: 17-5/8 x 7-3/4 x 7-5/8 in. (448 x 197 x 194 mm).

Mechanical

Stroke: Nominal 4-1/2 in. (114 mm), adjustable 4 to 5 in. (102 to 127 mm). Nominal Damper Area: Actuator sizing should be done in accordance with damper manufacturer’s specifications.

Start Point: Adjustable, see Table-1.

Spring: Retracts actuator crank arm on loss of air pressure.

Maximum air pressure: 30 psig (207 kPa).

Environment

Ambient Temperature Limits:

Shipping, -40 to 160°F (-40 to 71°C).

Operating, -20 to 160°F (-29 to 71°C).

Air Connections: 1/8” FNPT.

Air Connections (MK4-7100 Series only): Barbed fittings for 1/4” OD poly tube.

Table-1 Model Chart for Actuators.

 

 

 

 

Maximum Forcec

 

 

Nominal Torqueb

 

 

 

 

Return

 

Power Stroke

 

Proportional Controlc

 

Nominal

Starting

Stroke

 

 

 

 

 

 

 

 

 

 

Based on

15 psi

15 psi

 

20 psi

15 psi

 

15 psi

 

20 psi

TAC

Operating

Pressure

 

 

 

Supply

 

Supply

 

Supply

 

Supply

Model No.

Range

Adjustable

1.5 psi

Supply

Single

 

Single or

Supply

 

Single

 

Single or

 

 

 

Pressure to

Dual Press.

Press.

 

Dual Press.

Dual Press.

 

Press.

 

Dual Press.

 

 

 

Actuator

System

 

System

 

 

 

 

 

Systemd

 

Systemd

 

Systemd

 

Systemd

 

 

 

 

 

 

 

 

 

 

psi

psi

lb.

lb.

lb.

 

lb.

lb. -in.

 

lb. -in.

 

lb. -in.

MK-7101

3 to 8

3 ± 0.5

30

110

140

 

240

67.5

 

 

 

 

MK4-7101a

 

 

67.5

 

67.5

 

 

 

 

 

 

 

 

 

 

MK-7121

8 to 13

8 ± 0.5

130

10

40

 

140

22.5

 

 

 

 

 

 

 

 

 

 

MK4-7121a

 

 

90

 

293

 

 

 

 

 

 

 

 

 

 

aFactory installed positive posi ioner (AK-42309-500) start point adjustable 1 to 12 psi (7 to 83 kPa) with span adjustable 2 to 13 psi (14 to 90 kPa).

bNominal torque for actuators without positioner is based on 1.5 psi (10 kPa) pressure change at the actuator.

cForce and torques based on factory set stroke and starting pressure.

dAdjust pressure reducing valve so that listed pressures are available at the actuator.

Accessories

AK-42309-500

AM-301

AM-530a

AM-532

AM-538

AM-542

AM-543

Tool-95

Positive positioner and linkage (do not use with MK2-71X1; positive positioner does not meet temperature rating of MK2-71X1)

90° angle mounting bracket

Crank arm for 1/2 in. diameter damper shaft holes for 4-1/2 in. stroke

Frame mounting kit Actuator brace kit

Rod end connector for 5/16 in. (10 mm) rodb Actuator shaft extension

Pneumatic calibration tool kit

aRequired to connect damper actuator to damper shaft.

bMaximum length of 5/16 in. (10 mm) rod which can be used wi h AM-542, 15 in. (381 mm).

August, 2017 tc

© 2017 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.

 

Document Number: F-15221-11

Schneider Electric MK-7100 Series, MK4-7100 Series Installation Instructions
Loading...